Boiler plant controller gateway · BACnet points list

Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode) BACnet points list

Updated 6 November 2026

Short answer

Fulton's N54 ProtoNode publishes 65 objects for the SOLA lead/lag master boiler. The first 41 mirror the per-boiler SOLA list for the master itself; the rest give status, stage and firing rate for slaves 1-8. The BMS can enable central heat, DHW and lead/lag and send their setpoints.

This page lists 65 BACnet objects for the Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.

Manufacturer
Fulton
Model
Hydronic SOLA Master (lead/lag) (N54 ProtoNode)
Equipment
Boiler plant controller gateway
Equipment type
Boilers & water heaters
BACnet objects
65 (8 writable)
Transport
—
Firmware
Not stated
Also known as
SOLA Master, Fulton SOLA lead lag, N54 ProtoNode
Source document
Hydronic SOLA Master - Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date)
Download CSV 65 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.

BMS integration notes: Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)

Integration in brief

On the lead/lag master, enable lead/lag with LL Enable and write the LL setpoint (or use CH Enable and the CH setpoint for a single boiler). Read the master burner status, outlet temperature, firing rate and alarms, plus the status, stage and firing rate of each of up to 8 slaves.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 36Master Boiler LL EnableLead/lag enable (1 = enable)Write
AV 37Master Boiler LL Setpoint InputLead/lag setpoint, °FWrite
BV 32Master Boiler CH EnableCentral heat enable (1 = enable)Write
AV 33Master Boiler CH Setpoint InputCentral heat setpoint, °FWrite
AI 39Master Boiler Burner StatusMaster burner state code; see statesRead
AI 1Master Boiler Outlet TemperatureMaster outlet water temperature, °FRead
AI 13Master Boiler Firing RateMaster firing rate, %Read
AI 42Slave 1 StatusSlave 1 state (repeat per slave)Read
BI 16Master Boiler Alarm StatusMaster alarm active (1 = active)Read
AI 17Master Boiler Lockout CodeLockout code; 0 = no lockoutRead

Enable & remote start

BV 36 LL Enable and AV 37 LL Setpoint Input run the lead/lag group from the master. BV 32/AV 33 (central heat) and BV 34/AV 35 (DHW) enable and set the master itself; AV 40 Remote Operating Mode and AV 41 Remote Firing Rate force its burner.

Network setup

Watch out for

Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

65 of 65 shown
Type
Access
Show
Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode) BACnet Points List
DescriptionStates
AImin1Master Boiler Outlet TemperatureRange -40 to 266°FRead
AI2Master Boiler Inlet TemperatureRange -40 to 266°FRead
AI3Master Boiler DHW TemperatureRange -40 to 266°FRead
AI4Master Boiler Outdoor Air TemperatureRange -40 to 266°FRead
AI5Master Boiler Header TemperatureRange -40 to 266°FRead
AI6Master Boiler Stack TemperatureRange -40 to 266°FRead
AI7Master Boiler Active CH SetpointRange -40 to 266°FRead
AI8Master Boiler Active DHW SetpointRange -40 to 266°FRead
AI9Master Boiler Active LL SetpointRange -40 to 266°FRead
AI10Master Boiler CH Operating PointRange -40 to 266°FRead
AI11Master Boiler CH DHW Operating PointRange -40 to 266°FRead
AI12Master Boiler LL Operating PointRange -40 to 266°FRead
AImin13Master Boiler Firing RateRange 0 to 100%Read
AI14Master Boiler Fan SpeedRange based on user settings.Read
AI15Master Boiler Flame SignalRead
BImin16Master Boiler Alarm StatusRead0=Inactive, 1=Active
AImin17Master Boiler Lockout CodeRange 1 to 4096 (see manual)Read0=No Lockout
AI18Master Boiler Alarm ReasonRead0=None, 1=Lockout (See Manal), 2=Alert (See Manual), 3=Other
BI19Master Boiler Low Water Input StatusRead0=Circuit Open, 1=Circuit Made
BI20Master Boiler Air Switch Input StatusRead0=Circuit Open, 1=Circuit Made
BI21Master Boiler Low Gas Pressure Input StatusRead0=Circuit Open, 1=Circuit Made
BI22Master Boiler High Gas Pressure Input StatusRead0=Circuit Open, 1=Circuit Made
BI23Master Boiler High Back Pressure Input StatusRead0=Circuit Open, 1=Circuit Made
BI24Master Boiler High Condensate Input StatusRead0=Circuit Open, 1=Circuit Made
BI25Master Boiler High Temp Input StatusRead0=Circuit Open, 1=Circuit Made
BI26Master Boiler Auxiliary Annunciator Input StatusRead0=Circuit Open, 1=Circuit Made
BI27Master Boiler Pump A StatusRead0=Inactive, 1=Active
BI28Master Boiler Pump B StatusRead0=Inactive, 1=Active
BI29Master Boiler Pump C StatusRead0=Inactive, 1=Active
AI30Master Boiler Burner Cycle CountRange 0 - 999,999Read
AI31Master Boiler Burner Run HoursRange 0 - 999,999Read
BVmin32Master Boiler CH EnableWrite0=Disable Central Heat, 1=Enable Central Heat
AVmin33Master Boiler CH Setpoint InputRange -40 to 266°FWrite
BV34Master Boiler DHW EnableWrite0=Disable DHW, 1=Enable DHW
AV35Master Boiler DHW Setpoint InputRange -40 to 266°FWrite
BVmin36Master Boiler LL EnableWrite0=Disable Lead Lag, 1=Enable Lead Lag
AVmin37Master Boiler LL Setpoint InputRange -40 to 266°FWrite
AI38Master Boiler Burner Demand SourceRead0=Unknown, 1=No Source Demand, 2=CH, 3=DHW, 4=Lead Lag Slave, 5=Lead Lag Master, 6=CH Frost Protection, 7=DHW Frost Protection, 8=No demand due to burner switch turned off, 9=DHW Storage, 11=Warm Weather Shutdown, 12=Hot Standby
AImin39Master Boiler Burner StatusRead0=Disabled, 1=Locked out, 2-3=Reserved, 4=Anti Short Cycle, 5=Unconfigured Safety Data, 6-33=Reserved, 34=Standby Hold, 35=Standby Delay, 36-47=Reserved, 48=Normal Standby, 49=Preparing, 50=Ignition, 51=Firing, 52=Postpurge
AV40Master Boiler Remote Operating ModeWrite0=Auto, 1=Remote Off, 2=Remote On
AV41Master Boiler Remote Firing RateRange 0 to 100%Write
AImin42Slave 1 StatusRead0=Unknown, 1=Available, 2=Add Stage, 3=Suspend Stage, 4=Firing, 5=On Leave, 6=Disabled, 7=Recovering
AI43Slave 1 StageRead0=Not Staged
AI44Slave 1 Firing RateRange 0 to 100%Read
AI45Slave 2 StatusRead0=Unknown, 1=Available, 2=Add Stage, 3=Suspend Stage, 4=Firing, 5=On Leave, 6=Disabled, 7=Recovering
AI46Slave 2 StageRead0=Not Staged
AI47Slave 2 Firing RateRange 0 to 100%Read
AI48Slave 3 StatusRead0=Unknown, 1=Available, 2=Add Stage, 3=Suspend Stage, 4=Firing, 5=On Leave, 6=Disabled, 7=Recovering
AI49Slave 3 StageRead0=Not Staged
AI50Slave 3 Firing RateRange 0 to 100%Read
AI51Slave 4 StatusRead0=Unknown, 1=Available, 2=Add Stage, 3=Suspend Stage, 4=Firing, 5=On Leave, 6=Disabled, 7=Recovering
AI52Slave 4 StageRead0=Not Staged
AI53Slave 4 Firing RateRange 0 to 100%Read
AI54Slave 5 StatusRead0=Unknown, 1=Available, 2=Add Stage, 3=Suspend Stage, 4=Firing, 5=On Leave, 6=Disabled, 7=Recovering
AI55Slave 5 StageRead0=Not Staged
AI56Slave 5 Firing RateRange 0 to 100%Read
AI57Slave 6 StatusRead0=Unknown, 1=Available, 2=Add Stage, 3=Suspend Stage, 4=Firing, 5=On Leave, 6=Disabled, 7=Recovering
AI58Slave 6 StageRead0=Not Staged
AI59Slave 6 Firing RateRange 0 to 100%Read
AI60Slave 7 StatusRead0=Unknown, 1=Available, 2=Add Stage, 3=Suspend Stage, 4=Firing, 5=On Leaved, 6=Disabled, 7=Recovering
AI61Slave 7 StageRead0=Not Staged
AI62Slave 7 Firing RateRange 0 to 100%Read
AI63Slave 8 StatusRead0=Unknown, 1=Available, 2=Add Stage, 3=Suspend Stage, 4=Firing Rate, 5=On Leave, 6=Disabled, 7=Recovering
AI64Slave 8 StageRead0=Not Staged
AI65Slave 8 Firing RateRange 0 to 100%Read
Object ID lookup: Fulton Hydronic SOLA Master point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hydronic SOLA Master (lead/lag) (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)

How many BACnet points does the Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode) have?

This list has 65 BACnet objects: 45 analog inputs, 5 analog values, 12 binary inputs, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode) BACnet points are writable?

8 of the 65 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode) BACnet documentation?

The source is Hydronic SOLA Master - Fulton N54 ProtoNode BACnet Network Addressing, revision 2020-04-08 (file date), published free by Fulton at https://fulton.com/app/uploads/2021/02/N54-sola-master-BACnet-list_2020-0408.pdf.

What are the minimum BACnet points to integrate the Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)?

Start with BV 36 Master Boiler LL Enable (Lead/lag enable (1 = enable)); AV 37 Master Boiler LL Setpoint Input (Lead/lag setpoint, °F); BV 32 Master Boiler CH Enable (Central heat enable (1 = enable)); AV 33 Master Boiler CH Setpoint Input (Central heat setpoint, °F); AI 39 Master Boiler Burner Status (Master burner state code; see states); AI 1 Master Boiler Outlet Temperature (Master outlet water temperature, °F); AI 13 Master Boiler Firing Rate (Master firing rate, %); AI 42 Slave 1 Status (Slave 1 state (repeat per slave)); BI 16 Master Boiler Alarm Status (Master alarm active (1 = active)); AI 17 Master Boiler Lockout Code (Lockout code; 0 = no lockout).

How do I enable BMS control of the Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)?

BV 36 LL Enable and AV 37 LL Setpoint Input run the lead/lag group from the master. BV 32/AV 33 (central heat) and BV 34/AV 35 (DHW) enable and set the master itself; AV 40 Remote Operating Mode and AV 41 Remote Firing Rate force its burner.

How do I check these points on the real Hydronic SOLA Master (lead/lag) (N54 ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Fulton BACnet points lists

Source: Hydronic SOLA Master - Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date). Object names, instances and units are reproduced as published; descriptions are our own.