- Home
- BACnet points lists
- Fulton
- Hydronic SOLA Boiler (N54 ProtoNode)
Boiler controller gateway · BACnet points list
Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet points list
Updated 6 November 2026
Fulton's N54 ProtoNode publishes 41 objects for each hydronic boiler with the SOLA control. They cover water temperatures, active setpoints and operating points, firing rate, fan speed, flame signal, alarm and lockout data, safety input states and pump outputs. The BMS can enable central heat, DHW and lead/lag, send their setpoints, and force the burner on or off with a remote firing rate.
This page lists 41 BACnet objects for the Fulton Hydronic SOLA Boiler (N54 ProtoNode) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.
- Manufacturer
- Fulton
- Model
- Hydronic SOLA Boiler (N54 ProtoNode)
- Equipment
- Boiler controller gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 41 (8 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- SOLA, Fulton SOLA, Honeywell SOLA, N54 ProtoNode
Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.
BMS integration notes: Fulton Hydronic SOLA Boiler (N54 ProtoNode)
Turn central heat on with CH Enable and write the CH setpoint, or let the BMS hold the boiler with Remote Operating Mode and a Remote Firing Rate. Read burner status, outlet temperature, firing rate, the alarm status and the lockout code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1032 | Boiler 1 CH Enable | Central heat enable (1 = enable) | Write |
| AV 1033 | Boiler 1 CH Setpoint Input | Central heat setpoint, °F | Write |
| AV 1040 | Boiler 1 Remote Operating Mode | 0 = Auto, 1 = Remote Off, 2 = Remote On | Write |
| AV 1041 | Boiler 1 Remote Firing Rate | Firing rate in remote, 0-100 % | Write |
| AI 1039 | Boiler 1 Burner Status | Burner state code; see states | Read |
| AI 1001 | Boiler 1 Outlet Temperature | Outlet water temperature, °F | Read |
| AI 1013 | Boiler 1 Firing Rate | Actual firing rate, % | Read |
| BI 1016 | Boiler 1 Alarm Status | Alarm active (1 = active) | Read |
| AI 1017 | Boiler 1 Lockout Code | Lockout code; 0 = no lockout | Read |
Enable & remote start
BV (X)032 CH Enable turns central heat on; AV (X)033 CH Setpoint Input sets the CH target. AV (X)040 Remote Operating Mode (0 Auto, 1 Remote Off, 2 Remote On) and AV (X)041 Remote Firing Rate let the BMS force the burner. DHW and lead/lag have their own enable and setpoint objects.
Network setup
- Object ID = boiler Modbus address followed by the three-digit point number: (X)001-(X)041. Boiler 1 = 1001-1041, boiler 2 = 2001-2041.
- The sheet gives no device instance, MAC address or baud rate; those are set on the ProtoNode gateway.
Watch out for
- Lockout codes (1-4096) are decoded with the SOLA control manual.
- The safety input BIs report the circuit (0 = open, 1 = made), not a fault flag; check which way each switch fails.
Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1001 | Boiler 1 Outlet Temperature | Range -40 to 266 | °F | Read | |
| AI | 1002 | Boiler 1 Inlet Temperature | Range -40 to 266 | °F | Read | |
| AI | 1003 | Boiler 1 DHW Temperature | Range -40 to 266 | °F | Read | |
| AI | 1004 | Boiler 1 Outdoor Air Temperature | Range -40 to 266 | °F | Read | |
| AI | 1005 | Boiler 1 Header Temperature | Range -40 to 266 | °F | Read | |
| AI | 1006 | Boiler 1 Stack Temperature | Range -40 to 266 | °F | Read | |
| AI | 1007 | Boiler 1 Active CH Setpoint | Range -40 to 266 | °F | Read | |
| AI | 1008 | Boiler 1 Active DHW Setpoint | Range -40 to 266 | °F | Read | |
| AI | 1009 | Boiler 1 Active LL Setpoint | Range -40 to 266 | °F | Read | |
| AI | 1010 | Boiler 1 CH Operating Point | Range -40 to 266 | °F | Read | |
| AI | 1011 | Boiler 1 CH DHW Operating Point | Range -40 to 266 | °F | Read | |
| AI | 1012 | Boiler 1 LL Operating Point | Range -40 to 266 | °F | Read | |
| AImin | 1013 | Boiler 1 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 1014 | Boiler 1 Fan Speed | Range based on user settings. | Read | ||
| AI | 1015 | Boiler 1 Flame Signal | Read | |||
| BImin | 1016 | Boiler 1 Alarm Status | Read | 0=Inactive, 1=Active | ||
| AImin | 1017 | Boiler 1 Lockout Code | Range 1 to 4096 (see manual) | Read | 0=No Lockout | |
| AI | 1018 | Boiler 1 Alarm Reason | Read | 0=None, 1=Lockout (See Manal), 2=Alert (See Manual), 3=Other | ||
| BI | 1019 | Boiler 1 Low Water Input Status | Read | 0=Circuit Open, 1=Circuit Made | ||
| BI | 1020 | Boiler 1 Air Switch Input Status | Read | 0=Circuit Open, 1=Circuit Made | ||
| BI | 1021 | Boiler 1 Low Gas Pressure Input Status | Read | 0=Circuit Open, 1=Circuit Made | ||
| BI | 1022 | Boiler 1 High Gas Pressure Input Status | Read | 0=Circuit Open, 1=Circuit Made | ||
| BI | 1023 | Boiler 1 High Back Pressure Input Status | Read | 0=Circuit Open, 1=Circuit Made | ||
| BI | 1024 | Boiler 1 High Condensate Input Status | Read | 0=Circuit Open, 1=Circuit Made | ||
| BI | 1025 | Boiler 1 High Temp Input Status | Read | 0=Circuit Open, 1=Circuit Made | ||
| BI | 1026 | Boiler 1 Auxiliary Annunciator Input Status | Read | 0=Circuit Open, 1=Circuit Made | ||
| BI | 1027 | Boiler 1 Pump A Status | Read | 0=Inactive, 1=Active | ||
| BI | 1028 | Boiler 1 Pump B Status | Read | 0=Inactive, 1=Active | ||
| BI | 1029 | Boiler 1 Pump C Status | Read | 0=Inactive, 1=Active | ||
| AI | 1030 | Boiler 1 Burner Cycle Count | Range 0 - 999,999 | Read | ||
| AI | 1031 | Boiler 1 Burner Run Hours | Range 0 - 999,999 | Read | ||
| BVmin | 1032 | Boiler 1 CH Enable | Write | 0=Disable Central Heat, 1=Enable Central Heat | ||
| AVmin | 1033 | Boiler 1 CH Setpoint Input | Range -40 to 266 | °F | Write | |
| BV | 1034 | Boiler 1 DHW Enable | Write | 0=Disable DHW, 1=Enable DHW | ||
| AV | 1035 | Boiler 1 DHW Setpoint Input | Range -40 to 266 | °F | Write | |
| BV | 1036 | Boiler 1 LL Enable | Write | 0=Disable Lead Lag, 1=Enable Lead Lag | ||
| AV | 1037 | Boiler 1 LL Setpoint Input | Range -40 to 266 | °F | Write | |
| AI | 1038 | Boiler 1 Burner Demand Source | Read | 0=Unknown, 1=No Source Demand, 2=CH, 3=DHW, 4=Lead Lag Slave, 5=Lead Lag Master, 6=CH Frost Protection, 7=DHW Frost Protection, 8=No demand due to burner switch turned off, 9=DHW Storage, 11=Warm Weather Shutdown, 12=Hot Standby | ||
| AImin | 1039 | Boiler 1 Burner Status | Read | 0=Disabled, 1=Locked out, 2-3=Reserved, 4=Anti Short Cycle, 5=Unconfigured Safety Data, 6-33=Reserved, 34=Standby Hold, 35=Standby Delay, 36-47=Reserved, 48=Normal Standby, 49=Preparing, 50=Ignition, 51=Firing, 52=Postpurge | ||
| AVmin | 1040 | Boiler 1 Remote Operating Mode | Write | 0=Auto, 1=Remote Off, 2=Remote On | ||
| AVmin | 1041 | Boiler 1 Remote Firing Rate | Range 0 to 100 | % | Write |
No points match these filters.
Object ID lookup: Fulton Hydronic SOLA Boiler point IDs by name
AI1001Boiler 1 Outlet TemperatureAI1002Boiler 1 Inlet TemperatureAI1003Boiler 1 DHW TemperatureAI1004Boiler 1 Outdoor Air TemperatureAI1005Boiler 1 Header TemperatureAI1006Boiler 1 Stack TemperatureAI1007Boiler 1 Active CH SetpointAI1008Boiler 1 Active DHW SetpointAI1009Boiler 1 Active LL SetpointAI1010Boiler 1 CH Operating PointAI1011Boiler 1 CH DHW Operating PointAI1012Boiler 1 LL Operating PointAI1013Boiler 1 Firing RateAI1014Boiler 1 Fan SpeedAI1015Boiler 1 Flame SignalBI1016Boiler 1 Alarm StatusAI1017Boiler 1 Lockout CodeAI1018Boiler 1 Alarm ReasonBI1019Boiler 1 Low Water Input StatusBI1020Boiler 1 Air Switch Input StatusBI1021Boiler 1 Low Gas Pressure Input StatusBI1022Boiler 1 High Gas Pressure Input StatusBI1023Boiler 1 High Back Pressure Input StatusBI1024Boiler 1 High Condensate Input StatusBI1025Boiler 1 High Temp Input StatusBI1026Boiler 1 Auxiliary Annunciator Input StatusBI1027Boiler 1 Pump A StatusBI1028Boiler 1 Pump B StatusBI1029Boiler 1 Pump C StatusAI1030Boiler 1 Burner Cycle CountAI1031Boiler 1 Burner Run HoursBV1032Boiler 1 CH EnableAV1033Boiler 1 CH Setpoint InputBV1034Boiler 1 DHW EnableAV1035Boiler 1 DHW Setpoint InputBV1036Boiler 1 LL EnableAV1037Boiler 1 LL Setpoint InputAI1038Boiler 1 Burner Demand SourceAI1039Boiler 1 Burner StatusAV1040Boiler 1 Remote Operating ModeAV1041Boiler 1 Remote Firing Rate
Integration notes
- Object IDs are written (X)001-(X)041, where (X) is the boiler's Modbus address on the ProtoNode. This list shows boiler address 1 (1001-1041).
- The sheet does not say which BACnet transport the gateway is set to; ProtoNode gateways are normally configured for BACnet IP or BACnet MS/TP.
- Fan Speed range depends on user settings.
- Burner Demand Source and Burner Status are analog inputs carrying a code; the codes are in the states.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hydronic SOLA Boiler (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Fulton Hydronic SOLA Boiler (N54 ProtoNode)
How many BACnet points does the Fulton Hydronic SOLA Boiler (N54 ProtoNode) have?
This list has 41 BACnet objects: 21 analog inputs, 5 analog values, 12 binary inputs, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet points are writable?
8 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet documentation?
The source is Hydronic SOLA - Fulton N54 ProtoNode BACnet Network Addressing, revision 2020-04-08 (file date), published free by Fulton at https://fulton.com/app/uploads/2021/02/N54-sola-BACnet-list_2020-0408.pdf.
What are the minimum BACnet points to integrate the Fulton Hydronic SOLA Boiler (N54 ProtoNode)?
Start with BV 1032 Boiler 1 CH Enable (Central heat enable (1 = enable)); AV 1033 Boiler 1 CH Setpoint Input (Central heat setpoint, °F); AV 1040 Boiler 1 Remote Operating Mode (0 = Auto, 1 = Remote Off, 2 = Remote On); AV 1041 Boiler 1 Remote Firing Rate (Firing rate in remote, 0-100 %); AI 1039 Boiler 1 Burner Status (Burner state code; see states); AI 1001 Boiler 1 Outlet Temperature (Outlet water temperature, °F); AI 1013 Boiler 1 Firing Rate (Actual firing rate, %); BI 1016 Boiler 1 Alarm Status (Alarm active (1 = active)); AI 1017 Boiler 1 Lockout Code (Lockout code; 0 = no lockout).
How do I enable BMS control of the Fulton Hydronic SOLA Boiler (N54 ProtoNode)?
BV (X)032 CH Enable turns central heat on; AV (X)033 CH Setpoint Input sets the CH target. AV (X)040 Remote Operating Mode (0 Auto, 1 Remote Off, 2 Remote On) and AV (X)041 Remote Firing Rate let the BMS force the burner. DHW and lead/lag have their own enable and setpoint objects.
How do I check these points on the real Hydronic SOLA Boiler (N54 ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Fulton BACnet points lists
- Boiler burner control gateway
Fulton Boiler with Siemens LMV3 (N54 ProtoNode)
Fulton boilers with a Siemens LMV3 burner management control, read through Fulton's N54 ProtoNode gateway.
Also known as: LMV3, LMV 3, Siemens LMV3, N54 ProtoNode, Fulton ProtoNode - Boiler burner control gateway
Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)
Fulton hydronic boilers with a Siemens LMV3 burner control and a Yokogawa UT32A temperature controller, read through the N54 ProtoNode.
Also known as: LMV3, Siemens LMV3, Yokogawa UT32A, UT32A, N54 ProtoNode - Boiler plant sequencer
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
Fulton ModSync SE hydronic boiler sequencer (software 6.6.1.X) managing up to 8 boilers, read through the N54 ProtoNode.
Also known as: ModSync, ModSync SE, Fulton ModSync, ModSync sequencer, N54 ProtoNode - Boiler plant controller gateway
Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)
The SOLA lead/lag master of a group of Fulton hydronic boilers (up to 8 slaves), read through the N54 ProtoNode.
Also known as: SOLA Master, Fulton SOLA lead lag, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) 750-2000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Single (N54 ProtoNode)
Fulton Endura (EDR) 750-2000 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura XE (EXE) 399-750 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Single (N54 ProtoNode)
Fulton Endura XE (EXE) 399-750 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) ZE lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Single (N54 ProtoNode)
Fulton Endura (EDR) ZE boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 (N54 ProtoNode)
Fulton hydronic boilers run by the PURE control (the file name points to Endura+ EDR+ 2500-6000 MBH sizes), read through the N54 ProtoNode.
Also known as: PURE, Fulton PURE, Endura+, EDR+, Endura Plus, Hydronic PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura+ (EDR+) 2500-6000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura+, EDR+, Endura Plus, EDR+ 2500, EDR+ 6000, Fulton PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton VSRT steam boiler lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)
Fulton VSRT steam boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE, Fulton PURE, N54 ProtoNode - Boiler burner control
Fulton Siemens LMV36 with BACnet Interface
Fulton boilers with a Siemens LMV36 burner control on a BACnet interface.
Also known as: LMV36, Siemens LMV36, LMV3, Fulton LMV36 - Steam boiler burner control
Fulton Siemens LMV5 Steam Boiler with BACnet Interface
Fulton steam boilers whose Siemens LMV5 burner management is given a BACnet interface (standard configurations).
Also known as: LMV5, Siemens LMV5, LMV52, Fulton LMV5 - Steam boiler plant sequencer
Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)
Fulton ModSync SE steam boiler sequencer (version 6.6.1.0) managing up to 8 steam boilers, read through a Sierra Monitor ProtoNode.
Also known as: ModSync SE, ModSync, Fulton ModSync steam, ProtoNode
Source: Hydronic SOLA - Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date). Object names, instances and units are reproduced as published; descriptions are our own.