Boiler controller gateway · BACnet points list

Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet points list

Updated 6 November 2026

Short answer

Fulton's N54 ProtoNode publishes 41 objects for each hydronic boiler with the SOLA control. They cover water temperatures, active setpoints and operating points, firing rate, fan speed, flame signal, alarm and lockout data, safety input states and pump outputs. The BMS can enable central heat, DHW and lead/lag, send their setpoints, and force the burner on or off with a remote firing rate.

This page lists 41 BACnet objects for the Fulton Hydronic SOLA Boiler (N54 ProtoNode) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.

Manufacturer
Fulton
Model
Hydronic SOLA Boiler (N54 ProtoNode)
Equipment
Boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
41 (8 writable)
Transport
—
Firmware
Not stated
Also known as
SOLA, Fulton SOLA, Honeywell SOLA, N54 ProtoNode
Source document
Hydronic SOLA - Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date)
Download CSV 41 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.

BMS integration notes: Fulton Hydronic SOLA Boiler (N54 ProtoNode)

Integration in brief

Turn central heat on with CH Enable and write the CH setpoint, or let the BMS hold the boiler with Remote Operating Mode and a Remote Firing Rate. Read burner status, outlet temperature, firing rate, the alarm status and the lockout code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1032Boiler 1 CH EnableCentral heat enable (1 = enable)Write
AV 1033Boiler 1 CH Setpoint InputCentral heat setpoint, °FWrite
AV 1040Boiler 1 Remote Operating Mode0 = Auto, 1 = Remote Off, 2 = Remote OnWrite
AV 1041Boiler 1 Remote Firing RateFiring rate in remote, 0-100 %Write
AI 1039Boiler 1 Burner StatusBurner state code; see statesRead
AI 1001Boiler 1 Outlet TemperatureOutlet water temperature, °FRead
AI 1013Boiler 1 Firing RateActual firing rate, %Read
BI 1016Boiler 1 Alarm StatusAlarm active (1 = active)Read
AI 1017Boiler 1 Lockout CodeLockout code; 0 = no lockoutRead

Enable & remote start

BV (X)032 CH Enable turns central heat on; AV (X)033 CH Setpoint Input sets the CH target. AV (X)040 Remote Operating Mode (0 Auto, 1 Remote Off, 2 Remote On) and AV (X)041 Remote Firing Rate let the BMS force the burner. DHW and lead/lag have their own enable and setpoint objects.

Network setup

Watch out for

Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

41 of 41 shown
Type
Access
Show
Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet Points List
DescriptionStates
AImin1001Boiler 1 Outlet TemperatureRange -40 to 266°FRead
AI1002Boiler 1 Inlet TemperatureRange -40 to 266°FRead
AI1003Boiler 1 DHW TemperatureRange -40 to 266°FRead
AI1004Boiler 1 Outdoor Air TemperatureRange -40 to 266°FRead
AI1005Boiler 1 Header TemperatureRange -40 to 266°FRead
AI1006Boiler 1 Stack TemperatureRange -40 to 266°FRead
AI1007Boiler 1 Active CH SetpointRange -40 to 266°FRead
AI1008Boiler 1 Active DHW SetpointRange -40 to 266°FRead
AI1009Boiler 1 Active LL SetpointRange -40 to 266°FRead
AI1010Boiler 1 CH Operating PointRange -40 to 266°FRead
AI1011Boiler 1 CH DHW Operating PointRange -40 to 266°FRead
AI1012Boiler 1 LL Operating PointRange -40 to 266°FRead
AImin1013Boiler 1 Firing RateRange 0 to 100%Read
AI1014Boiler 1 Fan SpeedRange based on user settings.Read
AI1015Boiler 1 Flame SignalRead
BImin1016Boiler 1 Alarm StatusRead0=Inactive, 1=Active
AImin1017Boiler 1 Lockout CodeRange 1 to 4096 (see manual)Read0=No Lockout
AI1018Boiler 1 Alarm ReasonRead0=None, 1=Lockout (See Manal), 2=Alert (See Manual), 3=Other
BI1019Boiler 1 Low Water Input StatusRead0=Circuit Open, 1=Circuit Made
BI1020Boiler 1 Air Switch Input StatusRead0=Circuit Open, 1=Circuit Made
BI1021Boiler 1 Low Gas Pressure Input StatusRead0=Circuit Open, 1=Circuit Made
BI1022Boiler 1 High Gas Pressure Input StatusRead0=Circuit Open, 1=Circuit Made
BI1023Boiler 1 High Back Pressure Input StatusRead0=Circuit Open, 1=Circuit Made
BI1024Boiler 1 High Condensate Input StatusRead0=Circuit Open, 1=Circuit Made
BI1025Boiler 1 High Temp Input StatusRead0=Circuit Open, 1=Circuit Made
BI1026Boiler 1 Auxiliary Annunciator Input StatusRead0=Circuit Open, 1=Circuit Made
BI1027Boiler 1 Pump A StatusRead0=Inactive, 1=Active
BI1028Boiler 1 Pump B StatusRead0=Inactive, 1=Active
BI1029Boiler 1 Pump C StatusRead0=Inactive, 1=Active
AI1030Boiler 1 Burner Cycle CountRange 0 - 999,999Read
AI1031Boiler 1 Burner Run HoursRange 0 - 999,999Read
BVmin1032Boiler 1 CH EnableWrite0=Disable Central Heat, 1=Enable Central Heat
AVmin1033Boiler 1 CH Setpoint InputRange -40 to 266°FWrite
BV1034Boiler 1 DHW EnableWrite0=Disable DHW, 1=Enable DHW
AV1035Boiler 1 DHW Setpoint InputRange -40 to 266°FWrite
BV1036Boiler 1 LL EnableWrite0=Disable Lead Lag, 1=Enable Lead Lag
AV1037Boiler 1 LL Setpoint InputRange -40 to 266°FWrite
AI1038Boiler 1 Burner Demand SourceRead0=Unknown, 1=No Source Demand, 2=CH, 3=DHW, 4=Lead Lag Slave, 5=Lead Lag Master, 6=CH Frost Protection, 7=DHW Frost Protection, 8=No demand due to burner switch turned off, 9=DHW Storage, 11=Warm Weather Shutdown, 12=Hot Standby
AImin1039Boiler 1 Burner StatusRead0=Disabled, 1=Locked out, 2-3=Reserved, 4=Anti Short Cycle, 5=Unconfigured Safety Data, 6-33=Reserved, 34=Standby Hold, 35=Standby Delay, 36-47=Reserved, 48=Normal Standby, 49=Preparing, 50=Ignition, 51=Firing, 52=Postpurge
AVmin1040Boiler 1 Remote Operating ModeWrite0=Auto, 1=Remote Off, 2=Remote On
AVmin1041Boiler 1 Remote Firing RateRange 0 to 100%Write
Object ID lookup: Fulton Hydronic SOLA Boiler point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hydronic SOLA Boiler (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fulton Hydronic SOLA Boiler (N54 ProtoNode)

How many BACnet points does the Fulton Hydronic SOLA Boiler (N54 ProtoNode) have?

This list has 41 BACnet objects: 21 analog inputs, 5 analog values, 12 binary inputs, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet points are writable?

8 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fulton Hydronic SOLA Boiler (N54 ProtoNode) BACnet documentation?

The source is Hydronic SOLA - Fulton N54 ProtoNode BACnet Network Addressing, revision 2020-04-08 (file date), published free by Fulton at https://fulton.com/app/uploads/2021/02/N54-sola-BACnet-list_2020-0408.pdf.

What are the minimum BACnet points to integrate the Fulton Hydronic SOLA Boiler (N54 ProtoNode)?

Start with BV 1032 Boiler 1 CH Enable (Central heat enable (1 = enable)); AV 1033 Boiler 1 CH Setpoint Input (Central heat setpoint, °F); AV 1040 Boiler 1 Remote Operating Mode (0 = Auto, 1 = Remote Off, 2 = Remote On); AV 1041 Boiler 1 Remote Firing Rate (Firing rate in remote, 0-100 %); AI 1039 Boiler 1 Burner Status (Burner state code; see states); AI 1001 Boiler 1 Outlet Temperature (Outlet water temperature, °F); AI 1013 Boiler 1 Firing Rate (Actual firing rate, %); BI 1016 Boiler 1 Alarm Status (Alarm active (1 = active)); AI 1017 Boiler 1 Lockout Code (Lockout code; 0 = no lockout).

How do I enable BMS control of the Fulton Hydronic SOLA Boiler (N54 ProtoNode)?

BV (X)032 CH Enable turns central heat on; AV (X)033 CH Setpoint Input sets the CH target. AV (X)040 Remote Operating Mode (0 Auto, 1 Remote Off, 2 Remote On) and AV (X)041 Remote Firing Rate let the BMS force the burner. DHW and lead/lag have their own enable and setpoint objects.

How do I check these points on the real Hydronic SOLA Boiler (N54 ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Fulton BACnet points lists

Source: Hydronic SOLA - Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date). Object names, instances and units are reproduced as published; descriptions are our own.