Boiler burner control · BACnet points list

Fulton Siemens LMV36 with BACnet Interface BACnet points list

Updated 6 November 2026

Short answer

Fulton lists 21 objects for a boiler with a Siemens LMV36 burner control on a BACnet interface. Analog Inputs 1-18 report output, flame signal and the state of the controller, safety loop, gas pressure switches, alarm, ignition, fan and fuel valves (as 0/1 integers), plus remote mode and fuel. Analog Values 19-21 let the BMS take remote control and set an output.

This page lists 21 BACnet objects for the Fulton Siemens LMV36 with BACnet Interface — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.

Manufacturer
Fulton
Model
Siemens LMV36 with BACnet Interface
Equipment
Boiler burner control
Equipment type
Boilers & water heaters
BACnet objects
21 (3 writable)
Transport
—
Firmware
Not stated
Also known as
LMV36, Siemens LMV36, LMV3, Fulton LMV36
Source document
Network Addressing - LMV36 with A BACnet Interface
Download CSV 21 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.

BMS integration notes: Fulton Siemens LMV36 with BACnet Interface

Integration in brief

Write Modbus Mode = Remote (AV 19), then Operating Mode in Remote (AV 20: Auto, Remote On, Remote Off) and the Predefined Output (AV 21). Read current output, flame signal, the alarm input and the switch states.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 20Operating Mode in Remote0 = Auto, 1 = Remote On, 2 = Remote OffWrite
AV 19Modbus ModeSet 1 = Remote so network commands take effectWrite
AV 21Predefined Output Modulation (Modulation Rate)Output in remote, 200-1000Write
AI 3Controller On/OffController on/off; 0 = On, 1 = OffRead
AI 1Current OutputCurrent burner output, %Read
AI 2Flame SignalFlame signal, %Read
AI 9AlarmAlarm; 0 = On, 1 = OffRead

Enable & remote start

AV 19 Modbus Mode = 1 (Remote) hands control to the network; AV 20 Operating Mode in Remote selects 0 = Auto, 1 = Remote On or 2 = Remote Off, and AV 21 Predefined Output Modulation sets the output (200-1000).

Network setup

Watch out for

Fulton Siemens LMV36 with BACnet Interface BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

21 of 21 shown
Type
Access
Show
Fulton Siemens LMV36 with BACnet Interface BACnet Points List
DescriptionStates
AImin1Current OutputRange 0 - 100%Read
AImin2Flame SignalRange 0 - 100%Read
AImin3Controller On/OffRead0=On, 1=Off
AI4Pressure Valve ProveRead0=On, 1=Off
AI5Safety LoopRead0=On, 1=Off
AI6DW MinRead0=On, 1=Off
AI7DW MaxRead0=On, 1=Off
AI8Air Pressure SwitchRead0=On, 1=Off
AImin9AlarmRead0=On, 1=Off
AI10IgnitionRead0=On, 1=Off
AI11FanRead0=On, 1=Off
AI12Fuel V1Read0=On, 1=Off
AI13Fuel V2Read0=On, 1=Off
AI14Fuel V3Read0=On, 1=Off
AI15Modbus ModeRead0=Local, 1=Remote
AI16Operating Mode in RemoteRead0=Auto, 1=Remote On, 2=Remote Off
AI17Predefined Output Modulation (Modulation Rate)Range 200 - 1000Read
AI18Current Fuel ModeRead0=Gas, 1=Oil
AVmin19Modbus ModeWrite0=Local, 1=Remote
AVmin20Operating Mode in RemoteWrite0=Auto, 1=Remote On, 2=Remote Off
AVmin21Predefined Output Modulation (Modulation Rate)Range 200 - 1000Write
Object ID lookup: Fulton Siemens LMV36 with BACnet Interface point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens LMV36 with BACnet Interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fulton Siemens LMV36 with BACnet Interface

How many BACnet points does the Fulton Siemens LMV36 with BACnet Interface have?

This list has 21 BACnet objects: 18 analog inputs, 3 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fulton Siemens LMV36 with BACnet Interface BACnet points are writable?

3 of the 21 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fulton Siemens LMV36 with BACnet Interface BACnet documentation?

The source is Network Addressing - LMV36 with A BACnet Interface, published free by Fulton at https://fulton.com/app/uploads/2021/02/BACnet_PointsList_LMV36.pdf.

What are the minimum BACnet points to integrate the Fulton Siemens LMV36 with BACnet Interface?

Start with AV 20 Operating Mode in Remote (0 = Auto, 1 = Remote On, 2 = Remote Off); AV 19 Modbus Mode (Set 1 = Remote so network commands take effect); AV 21 Predefined Output Modulation (Modulation Rate) (Output in remote, 200-1000); AI 3 Controller On/Off (Controller on/off; 0 = On, 1 = Off); AI 1 Current Output (Current burner output, %); AI 2 Flame Signal (Flame signal, %); AI 9 Alarm (Alarm; 0 = On, 1 = Off).

How do I enable BMS control of the Fulton Siemens LMV36 with BACnet Interface?

AV 19 Modbus Mode = 1 (Remote) hands control to the network; AV 20 Operating Mode in Remote selects 0 = Auto, 1 = Remote On or 2 = Remote Off, and AV 21 Predefined Output Modulation sets the output (200-1000).

How do I check these points on the real Siemens LMV36 with BACnet Interface?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Fulton BACnet points lists

Source: Network Addressing - LMV36 with A BACnet Interface. Object names, instances and units are reproduced as published; descriptions are our own.