- Steam ModSync SE v6.6.1.0 (ProtoNode)
Steam boiler plant sequencer · BACnet points list
Fulton Steam ModSync SE v6.6.1.0 (ProtoNode) BACnet points list
Updated 6 November 2026
The steam version of the ModSync SE sequences up to eight steam boilers, and a Sierra Monitor ProtoNode publishes its data as 104 objects (IDs 1-108). Plant objects cover lead boiler, header pressure, building mode, remote enable, setpoint source and value and the alarm code; each boiler then has a 12-object block of local/remote, enable, demand, run, alarm, status, lead/lag position, outlet pressure, firing rate, cycles and run hours.
This page lists 104 BACnet objects for the Fulton Steam ModSync SE v6.6.1.0 (ProtoNode) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.
- Manufacturer
- Fulton
- Model
- Steam ModSync SE v6.6.1.0 (ProtoNode)
- Equipment
- Steam boiler plant sequencer
- Equipment type
- Boilers & water heaters
- BACnet objects
- 104 (4 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- ModSync SE, ModSync, Fulton ModSync steam, ProtoNode
- Source document
- ModSync SE BACnet Interface Manual, Version 6.6.1.0
Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.
BMS integration notes: Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)
Enable the plant with Remote Enable/Disable, set ModSync Setpoint Mode to BMS and write the steam pressure setpoint to BMS Setpoint Input. Read back the active ModSync setpoint, header pressure, each boiler's run and alarm status and the ModSync alarm code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 7 | Remote Enable/Disable | Plant enable (1 = enable) | Write |
| AV 9 | BMS Setpoint Input (Note 2) | Steam pressure setpoint from the BMS, psi | Write |
| AV 10 | ModSync Setpoint Mode | Must be 2 = BMS to use the BMS setpoint | Write |
| BI 16 | Boiler 1 Run Status | Boiler 1 running (repeat per boiler) | Read |
| AI 11 | ModSync Setpoint | Active plant setpoint, psi | Read |
| AV 3 | Supply Header Pressure | Supply header steam pressure, psi | Write |
| AI 22 | Boiler 1 Firing Rate | Boiler 1 firing rate, % (repeat per boiler) | Read |
| BI 17 | Boiler 1 Alarm Status | Boiler 1 alarm (repeat per boiler) | Read |
| AI 12 | ModSync Alarm Code | Plant alarm code from Fulton's alarm chart | Read |
Enable & remote start
BV 7 Remote Enable/Disable enables the plant from the BMS. For a BMS setpoint, set AV 10 ModSync Setpoint Mode = 2 (BMS) and write AV 9 BMS Setpoint Input; AV 9 only works if that option is enabled at the ModSync.
Sensors & values from the BMS
AV 3 Supply Header Pressure is a read/write analog value (0-200 psi, range depends on the sensor). The manual does not say when the BMS must write it.
Network setup
- The ProtoNode offers BACnet MS/TP on its RS-485 terminals (+, -, G) and BACnet IP on its Ethernet port; the port you connect to picks the protocol.
- Object IDs 1-108 are fixed; boiler 1 data is 13-24, each further boiler adds 12 (boiler 8 = 97-108).
- The manual gives no device instance, MAC address or baud rate.
Watch out for
- Points marked Note 2 stay inactive unless the option is enabled at the ModSync.
- Current Fuel applies only to Fulton Vantage boilers.
- Status, Lead Lag Position and alarm codes are analog inputs carrying a code; see the states.
Fulton Steam ModSync SE v6.6.1.0 (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Lead Boiler Position | Range 0 to 8 | Read | ||
| AVmin | 3 | Supply Header Pressure | Range 0 to 200; range depends on sensor | psi | Write | |
| BI | 6 | Building Mode | Read | 0=Unoccupied, 1=Occupied | ||
| BVmin | 7 | Remote Enable/Disable | Write | 0=Disable, 1=Enable | ||
| AVmin | 9 | BMS Setpoint Input (Note 2) | Range 0 to 200; range depends on sensor | psi | Write | |
| AVmin | 10 | ModSync Setpoint Mode | Write | 0=ModSync, 1=Remote SP, 2=BMS, 3=Manual | ||
| AImin | 11 | ModSync Setpoint | Range 0 to 200; range depends on sensor | psi | Read | |
| AImin | 12 | ModSync Alarm Code | Plant alarm code; see the alarm chart in the manual | Read | ||
| BI | 13 | Boiler 1 Local/Remote Status | Read | 0=Local, 1=Remote | ||
| BI | 14 | Boiler 1 ModSync Enable/Disable | Read | 0=Disable, 1=Enable | ||
| BI | 15 | Boiler 1 Heat Demand | Read | 0=Off, 1=On | ||
| BImin | 16 | Boiler 1 Run Status | Read | 0=Off, 1=On | ||
| BImin | 17 | Boiler 1 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 18 | Boiler 1 Current Fuel (Note 3) | Read | 0=Gas, 1=Oil | ||
| AI | 19 | Boiler 1 Status | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open BACnet Object ID | ||
| AI | 20 | Boiler 1 Lead Lag Position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | ||
| AI | 21 | Boiler 1 Outlet Pressure | Range 0 to 200; range depends on sensor | psi | Read | |
| AImin | 22 | Boiler 1 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 23 | Boiler 1 ModSync Cycles | Range 0 to 999999999 | Read | ||
| AI | 24 | Boiler 1 ModSync Run Hours | Range 0 to 999999999 | Read | ||
| BI | 25 | Boiler 2 Local/Remote Status | Read | 0=Local, 1=Remote | ||
| BI | 26 | Boiler 2 ModSync Enable/Disable | Read | 0=Disable, 1=Enable | ||
| BI | 27 | Boiler 2 Heat Demand | Read | 0=Off, 1=On | ||
| BI | 28 | Boiler 2 Run Status | Read | 0=Off, 1=On | ||
| BI | 29 | Boiler 2 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 30 | Boiler 2 Current Fuel (Note 3) | Read | 0=Gas, 1=Oil | ||
| AI | 31 | Boiler 2 Status | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open | ||
| AI | 32 | Boiler 2 Lead Lag Position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | ||
| AI | 33 | Boiler 2 Outlet Pressure | Range 0 to 200; range depends on sensor | psi | Read | |
| AI | 34 | Boiler 2 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 35 | Boiler 2 ModSync Cycles | Range 0 to 999999999 | Read | ||
| AI | 36 | Boiler 2 ModSync Run Hours | Range 0 to 999999999 | Read | ||
| BI | 37 | Boiler 3 Local/Remote Status | Read | 0=Local, 1=Remote | ||
| BI | 38 | Boiler 3 ModSync Enable/Disable | Read | 0=Disable, 1=Enable | ||
| BI | 39 | Boiler 3 Heat Demand | Read | 0=Off, 1=On | ||
| BI | 40 | Boiler 3 Run Status | Read | 0=Off, 1=On | ||
| BI | 41 | Boiler 3 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 42 | Boiler 3 Current Fuel (Note 3) | Read | 0=Gas, 1=Oil | ||
| AI | 43 | Boiler 3 Status | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open | ||
| AI | 44 | Boiler 3 Lead Lag Position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | ||
| AI | 45 | Boiler 3 Outlet Pressure | Range 0 to 200; range depends on sensor | psi | Read | |
| AI | 46 | Boiler 3 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 47 | Boiler 3 ModSync Cycles | Range 0 to 999999999 | Read | ||
| AI | 48 | Boiler 3 ModSync Run Hours | Range 0 to 999999999 | Read | ||
| BI | 49 | Boiler 4 Local/Remote Status | Read | 0=Local, 1=Remote | ||
| BI | 50 | Boiler 4 ModSync Enable/Disable | Read | 0=Disable, 1=Enable | ||
| BI | 51 | Boiler 4 Heat Demand | Read | 0=Off, 1=On | ||
| BI | 52 | Boiler 4 Run Status | Read | 0=Off, 1=On | ||
| BI | 53 | Boiler 4 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 54 | Boiler 4 Current Fuel (Note 3) | Read | 0=Gas, 1=Oil | ||
| AI | 55 | Boiler 4 Status | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open | ||
| AI | 56 | Boiler 4 Lead Lag Position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | ||
| AI | 57 | Boiler 4 Outlet Pressure | Range 0 to 200; range depends on sensor | psi | Read | |
| AI | 58 | Boiler 4 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 59 | Boiler 4 ModSync Cycles | Range 0 to 999999999 | Read | ||
| AI | 60 | Boiler 4 ModSync Run Hours | Range 0 to 999999999 | Read | ||
| BI | 61 | Boiler 5 Local/Remote Status | Read | 0=Local, 1=Remote | ||
| BI | 62 | Boiler 5 ModSync Enable/Disable | Read | 0=Disable, 1=Enable | ||
| BI | 63 | Boiler 5 Heat Demand | Read | 0=Off, 1=On | ||
| BI | 64 | Boiler 5 Run Status | Read | 0=Off, 1=On | ||
| BI | 65 | Boiler 5 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 66 | Boiler 5 Current Fuel (Note 3) | Read | 0=Gas, 1=Oil | ||
| AI | 67 | Boiler 5 Status | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open | ||
| AI | 68 | Boiler 5 Lead Lag Position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | ||
| AI | 69 | Boiler 5 Outlet Pressure | Range 0 to 200; range depends on sensor | psi | Read | |
| AI | 70 | Boiler 5 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 71 | Boiler 5 ModSync Cycles | Range 0 to 999999999 | Read | ||
| AI | 72 | Boiler 5 ModSync Run Hours | Range 0 to 999999999 | Read | ||
| BI | 73 | Boiler 6 Local/Remote Status | Read | 0=Local, 1=Remote | ||
| BI | 74 | Boiler 6 ModSync Enable/Disable | Read | 0=Disable, 1=Enable | ||
| BI | 75 | Boiler 6 Heat Demand | Read | 0=Off, 1=On | ||
| BI | 76 | Boiler 6 Run Status | Read | 0=Off, 1=On | ||
| BI | 77 | Boiler 6 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 78 | Boiler 6 Current Fuel (Note 3) | Read | 0=Gas, 1=Oil | ||
| AI | 79 | Boiler 6 Status | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open | ||
| AI | 80 | Boiler 6 Lead Lag Position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | ||
| AI | 81 | Boiler 6 Outlet Pressure | Range 0 to 200; range depends on sensor | psi | Read | |
| AI | 82 | Boiler 6 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 83 | Boiler 6 ModSync Cycles | Range 0 to 999999999 | Read | ||
| AI | 84 | Boiler 6 ModSync Run Hours | Range 0 to 999999999 | Read | ||
| BI | 85 | Boiler 7 Local/Remote Status | Read | 0=Local, 1=Remote | ||
| BI | 86 | Boiler 7 ModSync Enable/Disable | Read | 0=Disable, 1=Enable | ||
| BI | 87 | Boiler 7 Heat Demand | Read | 0=Off, 1=On | ||
| BI | 88 | Boiler 7 Run Status | Read | 0=Off, 1=On | ||
| BI | 89 | Boiler 7 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 90 | Boiler 7 Current Fuel (Note 3) | Read | 0=Gas, 1=Oil | ||
| AI | 91 | Boiler 7 Status | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open | ||
| AI | 92 | Boiler 7 Lead Lag Position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | ||
| AI | 93 | Boiler 7 Outlet Pressure | Range 0 to 200; range depends on sensor | psi | Read | |
| AI | 94 | Boiler 7 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 95 | Boiler 7 ModSync Cycles | Range 0 to 999999999 | Read | ||
| AI | 96 | Boiler 7 ModSync Run Hours | Range 0 to 999999999 | Read | ||
| BI | 97 | Boiler 8 Local/Remote Status | Read | 0=Local, 1=Remote | ||
| BI | 98 | Boiler 8 ModSync Enable/Disable | Read | 0=Disable, 1=Enable | ||
| BI | 99 | Boiler 8 Heat Demand | Read | 0=Off, 1=On | ||
| BI | 100 | Boiler 8 Run Status | Read | 0=Off, 1=On | ||
| BI | 101 | Boiler 8 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 102 | Boiler 8 Current Fuel (Note 2) | Read | 0=Gas, 1=Oil | ||
| AI | 103 | Boiler 8 Status | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open | ||
| AI | 104 | Boiler 8 Lead Lag Position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | ||
| AI | 105 | Boiler 8 Outlet Pressure | Range 0 to 200; range depends on sensor | psi | Read | |
| AI | 106 | Boiler 8 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 107 | Boiler 8 ModSync Cycles | Range 0 to 999999999 | Read | ||
| AI | 108 | Boiler 8 ModSync Run Hours | Range 0 to 999999999 | Read |
No points match these filters.
Object ID lookup: Fulton Steam ModSync SE v6.6.1.0 point IDs by name
AI1Lead Boiler PositionAV3Supply Header PressureBI6Building ModeBV7Remote Enable/DisableAV9BMS Setpoint Input (Note 2)AV10ModSync Setpoint ModeAI11ModSync SetpointAI12ModSync Alarm CodeBI13Boiler 1 Local/Remote StatusBI14Boiler 1 ModSync Enable/DisableBI15Boiler 1 Heat DemandBI16Boiler 1 Run StatusBI17Boiler 1 Alarm StatusBI18Boiler 1 Current Fuel (Note 3)AI19Boiler 1 StatusAI20Boiler 1 Lead Lag PositionAI21Boiler 1 Outlet PressureAI22Boiler 1 Firing RateAI23Boiler 1 ModSync CyclesAI24Boiler 1 ModSync Run HoursBI25Boiler 2 Local/Remote StatusBI26Boiler 2 ModSync Enable/DisableBI27Boiler 2 Heat DemandBI28Boiler 2 Run StatusBI29Boiler 2 Alarm StatusBI30Boiler 2 Current Fuel (Note 3)AI31Boiler 2 StatusAI32Boiler 2 Lead Lag PositionAI33Boiler 2 Outlet PressureAI34Boiler 2 Firing RateAI35Boiler 2 ModSync CyclesAI36Boiler 2 ModSync Run HoursBI37Boiler 3 Local/Remote StatusBI38Boiler 3 ModSync Enable/DisableBI39Boiler 3 Heat DemandBI40Boiler 3 Run StatusBI41Boiler 3 Alarm StatusBI42Boiler 3 Current Fuel (Note 3)AI43Boiler 3 StatusAI44Boiler 3 Lead Lag PositionAI45Boiler 3 Outlet PressureAI46Boiler 3 Firing RateAI47Boiler 3 ModSync CyclesAI48Boiler 3 ModSync Run HoursBI49Boiler 4 Local/Remote StatusBI50Boiler 4 ModSync Enable/DisableBI51Boiler 4 Heat DemandBI52Boiler 4 Run StatusBI53Boiler 4 Alarm StatusBI54Boiler 4 Current Fuel (Note 3)AI55Boiler 4 StatusAI56Boiler 4 Lead Lag PositionAI57Boiler 4 Outlet PressureAI58Boiler 4 Firing RateAI59Boiler 4 ModSync CyclesAI60Boiler 4 ModSync Run HoursBI61Boiler 5 Local/Remote StatusBI62Boiler 5 ModSync Enable/DisableBI63Boiler 5 Heat DemandBI64Boiler 5 Run StatusBI65Boiler 5 Alarm StatusBI66Boiler 5 Current Fuel (Note 3)AI67Boiler 5 StatusAI68Boiler 5 Lead Lag PositionAI69Boiler 5 Outlet PressureAI70Boiler 5 Firing RateAI71Boiler 5 ModSync CyclesAI72Boiler 5 ModSync Run HoursBI73Boiler 6 Local/Remote StatusBI74Boiler 6 ModSync Enable/DisableBI75Boiler 6 Heat DemandBI76Boiler 6 Run StatusBI77Boiler 6 Alarm StatusBI78Boiler 6 Current Fuel (Note 3)AI79Boiler 6 StatusAI80Boiler 6 Lead Lag PositionAI81Boiler 6 Outlet PressureAI82Boiler 6 Firing RateAI83Boiler 6 ModSync CyclesAI84Boiler 6 ModSync Run HoursBI85Boiler 7 Local/Remote StatusBI86Boiler 7 ModSync Enable/DisableBI87Boiler 7 Heat DemandBI88Boiler 7 Run StatusBI89Boiler 7 Alarm StatusBI90Boiler 7 Current Fuel (Note 3)AI91Boiler 7 StatusAI92Boiler 7 Lead Lag PositionAI93Boiler 7 Outlet PressureAI94Boiler 7 Firing RateAI95Boiler 7 ModSync CyclesAI96Boiler 7 ModSync Run HoursBI97Boiler 8 Local/Remote StatusBI98Boiler 8 ModSync Enable/DisableBI99Boiler 8 Heat DemandBI100Boiler 8 Run StatusBI101Boiler 8 Alarm StatusBI102Boiler 8 Current Fuel (Note 2)AI103Boiler 8 StatusAI104Boiler 8 Lead Lag PositionAI105Boiler 8 Outlet PressureAI106Boiler 8 Firing RateAI107Boiler 8 ModSync CyclesAI108Boiler 8 ModSync Run Hours
Integration notes
- Fulton's file name marks this as the steam version of the manual; the manual itself shows pressures in psi and does not repeat the word steam.
- Object IDs 1-108 are fixed and do not depend on boiler addresses; IDs 2, 4, 5 and 8 are not used on the steam version.
- Per-boiler blocks: boiler 1 = 13-24, boiler 2 = 25-36 ... boiler 8 = 97-108.
- The manual's alarm chart (pages 11-14) decodes the ModSync Alarm Code.
- Pressure ranges depend on the sensor selected at the ModSync.
- Hydronic sister product: fulton/modsync-se-hydronic.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Steam ModSync SE v6.6.1.0 (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)
How many BACnet points does the Fulton Steam ModSync SE v6.6.1.0 (ProtoNode) have?
This list has 104 BACnet objects: 51 analog inputs, 3 analog values, 49 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Fulton Steam ModSync SE v6.6.1.0 (ProtoNode) BACnet points are writable?
4 of the 104 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Fulton Steam ModSync SE v6.6.1.0 (ProtoNode) BACnet documentation?
The source is ModSync SE BACnet Interface Manual, Version 6.6.1.0, published free by Fulton at https://fulton.com/app/uploads/2021/07/ModSync-SE-Steam-v6610-BACnet-260611.pdf.
What are the minimum BACnet points to integrate the Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)?
Start with BV 7 Remote Enable/Disable (Plant enable (1 = enable)); AV 9 BMS Setpoint Input (Note 2) (Steam pressure setpoint from the BMS, psi); AV 10 ModSync Setpoint Mode (Must be 2 = BMS to use the BMS setpoint); BI 16 Boiler 1 Run Status (Boiler 1 running (repeat per boiler)); AI 11 ModSync Setpoint (Active plant setpoint, psi); AV 3 Supply Header Pressure (Supply header steam pressure, psi); AI 22 Boiler 1 Firing Rate (Boiler 1 firing rate, % (repeat per boiler)); BI 17 Boiler 1 Alarm Status (Boiler 1 alarm (repeat per boiler)); AI 12 ModSync Alarm Code (Plant alarm code from Fulton's alarm chart).
How do I enable BMS control of the Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)?
BV 7 Remote Enable/Disable enables the plant from the BMS. For a BMS setpoint, set AV 10 ModSync Setpoint Mode = 2 (BMS) and write AV 9 BMS Setpoint Input; AV 9 only works if that option is enabled at the ModSync.
Can the BMS supply sensor values to the Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)?
AV 3 Supply Header Pressure is a read/write analog value (0-200 psi, range depends on the sensor). The manual does not say when the BMS must write it.
How do I check these points on the real Steam ModSync SE v6.6.1.0 (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Fulton BACnet points lists
- Boiler burner control gateway
Fulton Boiler with Siemens LMV3 (N54 ProtoNode)
Fulton boilers with a Siemens LMV3 burner management control, read through Fulton's N54 ProtoNode gateway.
Also known as: LMV3, LMV 3, Siemens LMV3, N54 ProtoNode, Fulton ProtoNode - Boiler burner control gateway
Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)
Fulton hydronic boilers with a Siemens LMV3 burner control and a Yokogawa UT32A temperature controller, read through the N54 ProtoNode.
Also known as: LMV3, Siemens LMV3, Yokogawa UT32A, UT32A, N54 ProtoNode - Boiler plant sequencer
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
Fulton ModSync SE hydronic boiler sequencer (software 6.6.1.X) managing up to 8 boilers, read through the N54 ProtoNode.
Also known as: ModSync, ModSync SE, Fulton ModSync, ModSync sequencer, N54 ProtoNode - Boiler controller gateway
Fulton Hydronic SOLA Boiler (N54 ProtoNode)
Fulton hydronic boilers with the SOLA burner control, one block of objects per boiler on the N54 ProtoNode.
Also known as: SOLA, Fulton SOLA, Honeywell SOLA, N54 ProtoNode - Boiler plant controller gateway
Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)
The SOLA lead/lag master of a group of Fulton hydronic boilers (up to 8 slaves), read through the N54 ProtoNode.
Also known as: SOLA Master, Fulton SOLA lead lag, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) 750-2000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Single (N54 ProtoNode)
Fulton Endura (EDR) 750-2000 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura XE (EXE) 399-750 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Single (N54 ProtoNode)
Fulton Endura XE (EXE) 399-750 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) ZE lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Single (N54 ProtoNode)
Fulton Endura (EDR) ZE boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 (N54 ProtoNode)
Fulton hydronic boilers run by the PURE control (the file name points to Endura+ EDR+ 2500-6000 MBH sizes), read through the N54 ProtoNode.
Also known as: PURE, Fulton PURE, Endura+, EDR+, Endura Plus, Hydronic PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura+ (EDR+) 2500-6000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura+, EDR+, Endura Plus, EDR+ 2500, EDR+ 6000, Fulton PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton VSRT steam boiler lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)
Fulton VSRT steam boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE, Fulton PURE, N54 ProtoNode - Boiler burner control
Fulton Siemens LMV36 with BACnet Interface
Fulton boilers with a Siemens LMV36 burner control on a BACnet interface.
Also known as: LMV36, Siemens LMV36, LMV3, Fulton LMV36 - Steam boiler burner control
Fulton Siemens LMV5 Steam Boiler with BACnet Interface
Fulton steam boilers whose Siemens LMV5 burner management is given a BACnet interface (standard configurations).
Also known as: LMV5, Siemens LMV5, LMV52, Fulton LMV5
Source: ModSync SE BACnet Interface Manual, Version 6.6.1.0. Object names, instances and units are reproduced as published; descriptions are our own.