Steam boiler controller gateway · BACnet points list

Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) BACnet points list

Updated 11 November 2026

Short answer

Fulton's N54 ProtoNode publishes 47 objects for each boiler (one block of objects per boiler), for VSRT steam boilers with the PURE control. It covers burner state, modulation, steam pressures, safety switch states and alarms. The BMS can enable the boiler, send a pressure setpoint and a heartbeat, and supply outdoor and header values when the boiler is set up for them.

This page lists 47 BACnet objects for the Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.

Manufacturer
Fulton
Model
PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)
Equipment
Steam boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
47 (5 writable)
Transport
—
Firmware
Not stated
Also known as
VSRT, Fulton VSRT, Steam PURE, Fulton PURE, N54 ProtoNode
Source document
Steam PURE Per Boiler - Fulton N54 ProtoNode BACnet Network Addressing (VSRT) · rev. 2021-08-02 (file date)
Download CSV 47 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.

BMS integration notes: Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)

Integration in brief

Remove the BMS enable jumper at the boiler, write BMS Enable = 1, send the pressure setpoint to BMS Network Setpoint and keep writing 1 to BMS Heartbeat at least every 10 s. Check that Current Setpoint Mode reads BMS Network (3), then read status, outlet pressure, modulation rate and the alarm points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1057Boiler 1 BMS EnableNetwork enable; jumper must be removed firstWrite
AV 1052Boiler 1 BMS Network SetpointSteam pressure setpoint, 0-200 psiWrite
AV 1058Boiler 1 BMS HeartbeatWrite 1 at least every 10 s for remote operationWrite
AI 1051Boiler 1 Current Setpoint ModeSetpoint source; 3 = BMS NetworkRead
AI 1001Boiler 1 LMV StatusBurner phase; 60 = modulating, 0 = lockoutRead
AI 1017Boiler 1 Outlet PressureOutlet steam pressure, psiRead
AI 1005Boiler 1 Modulation RateActual modulation rate, %Read
AI 1044Boiler 1 Active AlarmAny alarm active (1 = alarm)Read
AI 1043Boiler 1 Current Alarm IndexAlarm number from Fulton's alarm chartRead

Enable & remote start

Remove the physical jumper at the boiler, then write BV (X)057 BMS Enable = 1. The setpoint comes from AV (X)052 BMS Network Setpoint (0-200 psi); AI (X)051 Current Setpoint Mode reads 3 when the network setpoint is in use.

Heartbeat & communication loss

AV (X)058 BMS Heartbeat: the BMS must write 1 at least once every 10 seconds for remote operation. What the boiler does when the heartbeat stops is not stated on this sheet.

Sensors & values from the BMS

AV (X)025 outdoor air temperature (°F) and AV (X)026 common header supply pressure (psi) are writable only when the boiler program is set to take that value from the BMS.

Network setup

Watch out for

Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

47 of 47 shown
Type
Access
Show
Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) BACnet Points List
DescriptionStates
AImin1001Boiler 1 LMV StatusRead0=LMV Safety Lockout, 2=LMV Safety Phase, 10=LMV Home Run, 12=LMV Standby, 22=Fan Motor, 24=Air Damper, 30=Prepurging, 36=Air Damper, 38=Preignition, 39=Testing Pressure Switch, 40=Fuel Valve, 42=Ignition, 44=Interval 1, 50=Safety Time 2, 52=Interval 2, 60=Modulating, 70=Afterburn Time, 72=Afterburn Time, 74=Postpurge Time, 78=Postpurge Time, 80=Evacuation of Test Space, 81=Atmospheric Pressure Test, 83=Gas Pressure Test, 90=Gas Shortage Waiting Time, 91=Limit String Open
AI1002Boiler 1 Control StatusRead0=Waiting, 1=Disabled, 2=Not Available, 3=Lead, 4=Lag 1, 5=Lag 2, 6=Lag 3, 7=Lag 4, 8=Lag 5, 9=Lag 6, 10=Lag 7, 11=Lag 8, 12=Lag 9, 14=Lag 1 (T), 15=Lag 2 (T), 16=Lag 3 (T), 17=Lag 4 (T), 18=Lag 5 (T), 19=Lag 6 (T), 20=Lag 7 (T), 21=Lag 8 (T), 22=Lag 9 (T), 23=Not Used, 24=Local, 25=Manual
AI1003Boiler 1 Modulation StatusRead0=Normal Rate, 1=Low Fire Hold, 2=Cold Start, 3=Freeze Protection, 4=Delta T Protection, 5=Outlet Soft Limit, 6=Venting Limitation
AI1004Boiler 1 Modulation TargetRange 0.0 to 100.0%Read
AImin1005Boiler 1 Modulation RateRange 0.0 to 100.0%Read
AI1006Boiler 1 Flame SignalRange 0.0 to 100.0%Read
AI1007Boiler 1 Air Actuator PositionRange -50.0 to 100.0Read
AI1008Boiler 1 Fuel Actuator PositionRange -50.0 to 100.0Read
AI1009Boiler 1 VFD StatusRead0=No Fault, 2=Auxiliary Input, 3=Power Loss, 4=Undervoltage, 5=Motor Overload, 8=Heatsink Over Temperature, 12=Hardware Overcurrent 300%, 13=Analog Input Loss, 14=Auto Restart Tried, 38=Phase U to Ground Short, 39=Phase V to Ground Short, 40=Phase W to Ground Short, 41=Phase U / V Short, 42=Phase U / W Short, 63=Software Overcurrent, 70=Power Unit Failure, 80=Autotune Failure, 122=I/O Board Failure
AI1010Boiler 1 O2 Sensor StatusRead0=Normal Operation, 1=E1: Internal Communication Error, 2=E2: Internal Register Error, 3=E3: Short to Power, 4=E4: Short to Ground, 5=E5: Short to Power, 6=E6: Short to Ground, 7=E7: Short to Power, 8=E8: Short to Ground, 9=E9: Operating Voltage Too Low, 10=E10: Check Sensor Connection, 11=E11: Heater Circuit Short, 12=E12: Heater Circuit Short
AI1011Boiler 1 VFD CommandRange 0.0 to 95.0Read
AI1012Boiler 1 VFD FeedbackRange 0.0 to 95.0Read
AI1013Boiler 1 Fan Calculated RPMRange 0.0 to 5500.0Read
AI1014Boiler 1 VFD Output CurrentRange 0.00 to 15.00Read
AI1015Boiler 1 VFD Output VoltageRange 0.0 to 461.0Read
AI1016Boiler 1 Current O2%Range 000 to 21.00%Read
AImin1017Boiler 1 Outlet PressureRange 0.0 to 200.0psiRead
AI10200.0 to 200.0Range 0.0 to 200.0; start pressure per the Provider sheetpsiRead
AI1021Boiler 1 Stop PressureRange 0.0 to 200.0psiRead
AI1022Boiler 1 Stack TemperatureRange -50.0 to 250.0°FRead
AI1023Boiler 1 Combustion Air TemperatureRange -50.0 to 250.0°FRead
AI1024Boiler 1 Current SetpointRange 0.0 to 200.0psiRead
AV1025Boiler 1 Outdoor Air TemperatureRange 0.0 to 200.0; writable when BMS-sourced°FWrite
AV1026Boiler 1 Common Header Supply PressureRange 0.0 to 200.0; writable when BMS-sourcedpsiWrite
BI1030Boiler 1 Call For HeatRead0=No Call, 1=Call For Heat
BI1031Boiler 1 On/Off SwitchRead0=Off, 1=On
BI1032Boiler 1 Primary Low WaterRead0=No Fault, 1=Fault
BI1033Boiler 1 High Pressure LimitRead0=Fault, 1=No Fault
BI1034Boiler 1 Operating Pressure LimitRead0=Fault, 1=No Fault
BI1035Boiler 1 Low Gas PressureRead0=Fault, 1=No Fault
BI1036Boiler 1 Blocked FlueRead0=Fault, 1=No Fault
BI1037Boiler 1 Customer Interlock 1Read0=Fault, 1=No Fault
BI1038Boiler 1 Customer Interlock 2Read0=Fault, 1=No Fault
BI1039Boiler 1 Secondary Low WaterRead0=No Fault, 1=Fault
AI1040Boiler 1 Run HoursRead
AI1041Boiler 1 CyclesRead
AI1042Boiler 1 Powered HoursRead
AImin1043Boiler 1 Current Alarm IndexSee Fulton alarm chartRead
AImin1044Boiler 1 Active AlarmSee Fulton alarm chartRead0=No Alarm, 1=Alarm
AImin1051Boiler 1 Current Setpoint ModeRead0=Outdoor Reset Curve, 1=BMS Analog 4-20mA, 2=BMS Analog 0-10VDC, 3=BMS Network, 4=Manual
AVmin1052Boiler 1 BMS Network SetpointRange 0.0 to 200.0psiWrite
AI1053Boiler 1 Maximum SetpointRange 0.0 to 200.0psiRead
AI1054Boiler 1 Minimum SetpointRange 0.0 to 200.0psiRead
AI1055Boiler 1 Outdoor Air CutoffRange 40.0 to 185.0°FRead
AI1056Boiler 1 Outdoor Air Cutoff ResetRange 40.0 to 185.0°FRead
BVmin1057Boiler 1 BMS EnableNeeds the enable jumper removedWrite0=Not Enabled, 1=Enabled
AVmin1058Boiler 1 BMS HeartbeatWrite 1 at least every 10 s for remote operationWrite
Object ID lookup: Fulton PURE VSRT Steam Single point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)

How many BACnet points does the Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) have?

This list has 47 BACnet objects: 32 analog inputs, 4 analog values, 10 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) BACnet points are writable?

5 of the 47 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) BACnet documentation?

The source is Steam PURE Per Boiler - Fulton N54 ProtoNode BACnet Network Addressing (VSRT), revision 2021-08-02 (file date), published free by Fulton at https://fulton.com/app/uploads/2021/08/N54-PURE-VSRT-Single-BACnet-list_2021-0802.pdf.

What are the minimum BACnet points to integrate the Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)?

Start with BV 1057 Boiler 1 BMS Enable (Network enable; jumper must be removed first); AV 1052 Boiler 1 BMS Network Setpoint (Steam pressure setpoint, 0-200 psi); AV 1058 Boiler 1 BMS Heartbeat (Write 1 at least every 10 s for remote operation); AI 1051 Boiler 1 Current Setpoint Mode (Setpoint source; 3 = BMS Network); AI 1001 Boiler 1 LMV Status (Burner phase; 60 = modulating, 0 = lockout); AI 1017 Boiler 1 Outlet Pressure (Outlet steam pressure, psi); AI 1005 Boiler 1 Modulation Rate (Actual modulation rate, %); AI 1044 Boiler 1 Active Alarm (Any alarm active (1 = alarm)); AI 1043 Boiler 1 Current Alarm Index (Alarm number from Fulton's alarm chart).

How do I enable BMS control of the Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)?

Remove the physical jumper at the boiler, then write BV (X)057 BMS Enable = 1. The setpoint comes from AV (X)052 BMS Network Setpoint (0-200 psi); AI (X)051 Current Setpoint Mode reads 3 when the network setpoint is in use.

Does the Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode) need a BACnet heartbeat or have a communication timeout?

AV (X)058 BMS Heartbeat: the BMS must write 1 at least once every 10 seconds for remote operation. What the boiler does when the heartbeat stops is not stated on this sheet.

Can the BMS supply sensor values to the Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)?

AV (X)025 outdoor air temperature (°F) and AV (X)026 common header supply pressure (psi) are writable only when the boiler program is set to take that value from the BMS.

How do I check these points on the real PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Fulton BACnet points lists

Source: Steam PURE Per Boiler - Fulton N54 ProtoNode BACnet Network Addressing (VSRT) · rev. 2021-08-02 (file date). Object names, instances and units are reproduced as published; descriptions are our own.