Boiler burner control gateway · BACnet points list

Fulton Boiler with Siemens LMV3 (N54 ProtoNode) BACnet points list

Updated 28 October 2026

Short answer

Fulton's N54 ProtoNode gateway reads each boiler's Siemens LMV3 burner control over Modbus and publishes a block of 28 objects per boiler. Most points are burner phase, actuator positions, counters, error codes and switch states; three writable objects let the BMS take the boiler into remote, pick Auto/On/Off and send a firing rate.

This page lists 28 BACnet objects for the Fulton Boiler with Siemens LMV3 (N54 ProtoNode) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.

Manufacturer
Fulton
Model
Boiler with Siemens LMV3 (N54 ProtoNode)
Equipment
Boiler burner control gateway
Equipment type
Boilers & water heaters
BACnet objects
28 (3 writable)
Transport
—
Firmware
Not stated
Also known as
LMV3, LMV 3, Siemens LMV3, N54 ProtoNode, Fulton ProtoNode
Source document
LMV 3 Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date)
Download CSV 28 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Fulton Boiler with Siemens LMV3 (N54 ProtoNode)

Integration in brief

Put the boiler in remote with the Modbus Mode BV, then run it with Operating Mode In Remote (Auto/On/Off) and the Remote Firing Rate. Monitor burner phase, firing rate, the alarm output and the LMV error code. Every boiler on the ProtoNode has its own block of object IDs based on its Modbus address.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1027Boiler 1 Operating Mode In RemoteRun command in remote: 0 = Auto, 1 = On, 2 = OffWrite
BV 1026Boiler 1 Modbus ModeSet 1 = Remote so network commands take effectWrite
AV 1028Boiler 1 Remote Firing RateFiring rate command, %; 20 % minimum to enableWrite
BI 1014Boiler 1 Controller On/Off StatusBurner controller on/off stateRead
AI 1001Boiler 1 Burner Control PhaseBurner sequence phase; 60 = operation, 0 = lockoutRead
AI 1005Boiler 1 Firing RateActual firing rate, %Read
BI 1020Boiler 1 Alarm StatusBoiler alarm activeRead
AI 1010Boiler 1 Current Error: Error CodeActive LMV error codeRead

Enable & remote start

Write BV (X)026 Modbus Mode = 1 (Remote). In remote, AV (X)027 Operating Mode In Remote selects 0 = Auto, 1 = On or 2 = Off, and AV (X)028 Remote Firing Rate sets the rate; the boiler is only enabled at 20 % or more.

Network setup

Watch out for

Fulton Boiler with Siemens LMV3 (N54 ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

28 of 28 shown
Type
Access
Show
Fulton Boiler with Siemens LMV3 (N54 ProtoNode) BACnet Points List
DescriptionStates
AImin1001Boiler 1 Burner Control PhaseLMV3 burner sequence phase codeRead0=Lockout Phase, 2=Safety Phase, 10=Home Run, 12=Standby, 22=Fan Motor On, 30=Pre-Purge, 36=Driving to Ignition, 38=Ignition, 40=Fuel Valve On, 44=Flame Stabilization, 50=Safety Time 2, 52=Flame Stabilization 2, 60=Operation, 70=Post- Purge
AI1002Boiler 1 Position of Fuel ActuatorFuel actuator position, -50 to 150Read
AI1003Boiler 1 Position of Air ActuatorAir actuator position, -50 to 150Read
AI1004Boiler 1 Current Type of FuelFuel in useRead0=Fuel 0 (Gas), 1=Fuel 1 (Oil)
AImin1005Boiler 1 Firing RateBurner firing rate, 0-100 %%Read
AI1006Boiler 1 Flame SignalFlame signal strength, 0-100 %%Read
AI1007Boiler 1 Startup Counter TotalTotal burner start countRead
AI1008Boiler 1 Hours Run Fuel 0Run hours on fuel 0 (gas)Read
AI1009Boiler 1 Hours Run Fuel 1Run hours on fuel 1 (oil)Read
AImin1010Boiler 1 Current Error: Error CodeActive LMV error code (see LMV manual)Read
AI1011Boiler 1 Current Error: Error DiagnosticDiagnostic code for the active errorRead
AI1012Boiler 1 Current Error: Error ClassClass of the active errorRead
AI1013Boiler 1 Current Error: Error PhaseBurner phase when the error occurredRead
BImin1014Boiler 1 Controller On/Off StatusBurner controller on/off stateRead0=Off, 1=On
BI1015Boiler 1 Pressure Switch Valve ProvingValve proving pressure switch inputRead0=Off, 1=On
BI1016Boiler 1 Safety Loop StatusSafety loop inputRead0=Off, 1=On
BI1017Boiler 1 Pressure Switch Min StatusMinimum pressure switch inputRead0=Off, 1=On
BI1018Boiler 1 Pressure Switch Mas StatusMaximum pressure switch inputRead0=Off, 1=On
BI1019Boiler 1 Air Pressure Switch StatusCombustion air pressure switch inputRead0=Off, 1=On
BImin1020Boiler 1 Alarm StatusBoiler alarm outputRead0=Off, 1=On
BI1021Boiler 1 Ignition StatusIgnition outputRead0=Off, 1=On
BI1022Boiler 1 Fan StatusCombustion fan outputRead0=Off, 1=On
BI1023Boiler 1 Fuel Valve V1 StatusFuel valve V1 outputRead0=Off, 1=On
BI1024Boiler 1 Fuel Valve V2 StatusFuel valve V2 outputRead0=Off, 1=On
BI1025Boiler 1 Fuel Valve V3 StatusFuel valve V3 outputRead0=Off, 1=On
BVmin1026Boiler 1 Modbus ModeLocal or remote (network) controlWrite0=Local, 1=Remote
AVmin1027Boiler 1 Operating Mode In RemoteRun command used while in remoteWrite0=Auto, 1=On, 2=Off
AVmin1028Boiler 1 Remote Firing RateFiring rate command, 0-100 %; 20 % minimum enables%Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Boiler with Siemens LMV3 (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fulton Boiler with Siemens LMV3 (N54 ProtoNode)

How many BACnet points does the Fulton Boiler with Siemens LMV3 (N54 ProtoNode) have?

This list has 28 BACnet objects: 13 analog inputs, 2 analog values, 12 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fulton Boiler with Siemens LMV3 (N54 ProtoNode) BACnet points are writable?

3 of the 28 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fulton Boiler with Siemens LMV3 (N54 ProtoNode) BACnet documentation?

The source is LMV 3 Fulton N54 ProtoNode BACnet Network Addressing, revision 2020-04-08 (file date), published free by Fulton at https://fulton.com/app/uploads/2021/02/N54-LMV3-BACnet-list_2020-0408.pdf.

What are the minimum BACnet points to integrate the Fulton Boiler with Siemens LMV3 (N54 ProtoNode)?

Start with AV 1027 Boiler 1 Operating Mode In Remote (Run command in remote: 0 = Auto, 1 = On, 2 = Off); BV 1026 Boiler 1 Modbus Mode (Set 1 = Remote so network commands take effect); AV 1028 Boiler 1 Remote Firing Rate (Firing rate command, %; 20 % minimum to enable); BI 1014 Boiler 1 Controller On/Off Status (Burner controller on/off state); AI 1001 Boiler 1 Burner Control Phase (Burner sequence phase; 60 = operation, 0 = lockout); AI 1005 Boiler 1 Firing Rate (Actual firing rate, %); BI 1020 Boiler 1 Alarm Status (Boiler alarm active); AI 1010 Boiler 1 Current Error: Error Code (Active LMV error code).

How do I enable BMS control of the Fulton Boiler with Siemens LMV3 (N54 ProtoNode)?

Write BV (X)026 Modbus Mode = 1 (Remote). In remote, AV (X)027 Operating Mode In Remote selects 0 = Auto, 1 = On or 2 = Off, and AV (X)028 Remote Firing Rate sets the rate; the boiler is only enabled at 20 % or more.

How do I check these points on the real Boiler with Siemens LMV3 (N54 ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Fulton BACnet points lists

Source: LMV 3 Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date). Object names, instances and units are reproduced as published; descriptions are our own.