Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet points list

Updated 28 October 2026

Short answer

The ModSync SE sequences up to eight hydronic boilers, and Fulton's N54 ProtoNode publishes its data as one flat list of 164 objects. Plant points cover enable, setpoint source and value, supply/return temperatures and the alarm code; each boiler then has a 12-point block of status, temperature and firing rate, followed by optional valve, pump and pressure points.

This page lists 164 BACnet objects for the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.

Manufacturer
Fulton
Model
Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
Equipment
Boiler plant sequencer
Equipment type
Boilers & water heaters
BACnet objects
164 (11 writable)
Transport
—
Firmware
ModSync SE 6.6.1.X
Also known as
ModSync, ModSync SE, Fulton ModSync, ModSync sequencer, N54 ProtoNode
Source document
Hydronic ModSync SE Version 6.6.1.X - Fulton N54 ProtoNode BACnet Network Addressing
Download CSV 164 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)

Integration in brief

Enable the plant with Remote Enable/Disable, set ModSync Setpoint Mode to BMS and write the supply setpoint to BMS Setpoint Input. Read back the active ModSync setpoint, supply temperature, each boiler's run and alarm status and the ModSync alarm code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 7Remote Enable/DisablePlant enable (1 = enable)Write
AV 9BMS Setpoint Input (Note 2)Supply setpoint from the BMS, °FWrite
AV 10ModSync Setpoint ModeMust be 2 = BMS to use the BMS setpointWrite
BI 16Boiler 1 Run StatusBoiler 1 running (repeat per boiler)Read
AI 11ModSync SetpointActive plant setpoint, °FRead
AV 3Supply TemperatureSystem supply water temperature, °FWrite
AI 22Boiler 1 Firing RateBoiler 1 firing rate, % (repeat per boiler)Read
BI 17Boiler 1 Alarm StatusBoiler 1 alarm (repeat per boiler)Read
AI 12ModSync Alarm CodePlant alarm code from Fulton's alarm chartRead

Enable & remote start

BV 7 Remote Enable/Disable enables the plant from the BMS. For a BMS setpoint, set AV 10 ModSync Setpoint Mode = 2 (BMS) and write AV 9 BMS Setpoint Input; AV 9 is an optional point that has to be enabled at the ModSync.

Sensors & values from the BMS

Outdoor air (AV 2), return (AV 4), differential (AV 5) and the system pressures (AV 149-151) are read/write analog values, available when the matching option is enabled at the ModSync. The sheet does not say when the BMS must write them.

Network setup

Watch out for

Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

164 of 164 shown
Type
Access
Show
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet Points List
DescriptionStates
AI1Lead Boiler PositionWhich boiler is lead, 0-8Read
AV2Outdoor Air Temperature (Note 2)Outdoor air temperature (optional)°FWrite
AVmin3Supply TemperatureSystem supply temperature°FWrite
AV4Return Temperature (Note 2)System return temperature (optional)°FWrite
AV5Differential Temperature (Note 2)Supply/return differential (optional)°FWrite
BI6Building ModeOccupied or unoccupiedRead0=Unoccupied, 1=Occupied
BVmin7Remote Enable/DisablePlant enable from the BMSWrite0=Disable, 1=Enable
BI8Domestic Hot Water PriorityDHW priority activeRead0=Disabled, 1=Enabled
AVmin9BMS Setpoint Input (Note 2)Supply setpoint written by the BMS°FWrite
AVmin10ModSync Setpoint ModeSetpoint source selectionWrite0=ModSync, 1=Remote SP, 2=BMS, 3=Manual
AImin11ModSync SetpointActive plant setpoint°FRead
AImin12ModSync Alarm CodePlant alarm code (see Fulton alarm chart)Read
BI13Boiler 1 Local/Remote StatusBoiler in local or remoteRead0=Local, 1=Remote
BI14Boiler 1 ModSync Enable/DisableBoiler enabled by the sequencerRead0=Disable, 1=Enable
BI15Boiler 1 Heat DemandSequencer heat demand to this boilerRead0=Off, 1=On
BImin16Boiler 1 Run StatusBoiler runningRead0=Off, 1=On
BImin17Boiler 1 Alarm StatusBoiler alarmRead0=Off, 1=On
BI18Boiler 1 Current Fuel (Note 3)Fuel in use; LMV boilers onlyRead0=Gas, 1=Oil
AI19Boiler 1 StatusBoiler state codeRead0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water
AI20Boiler 1 Lead Lag PositionLead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7
AI21Boiler 1 Outlet TemperatureBoiler outlet temperature°FRead
AImin22Boiler 1 Firing RateBoiler firing rate%Read
AI23Boiler 1 ModSync CyclesCycle count seen by the sequencerRead
AI24Boiler 1 ModSync Run HoursRun hours seen by the sequencerRead
BI25Boiler 2 Local/Remote StatusBoiler in local or remoteRead0=Local, 1=Remote
BI26Boiler 2 ModSync Enable/DisableBoiler enabled by the sequencerRead0=Disable, 1=Enable
BI27Boiler 2 Heat DemandSequencer heat demand to this boilerRead0=Off, 1=On
BI28Boiler 2 Run StatusBoiler runningRead0=Off, 1=On
BI29Boiler 2 Alarm StatusBoiler alarmRead0=Off, 1=On
BI30Boiler 2 Current Fuel (Note 3)Fuel in use; LMV boilers onlyRead0=Gas, 1=Oil
AI31Boiler 2 StatusBoiler state codeRead0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water
AI32Boiler 2 Lead Lag PositionLead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7
AI33Boiler 2 Outlet TemperatureBoiler outlet temperature°FRead
AI34Boiler 2 Firing RateBoiler firing rate%Read
AI35Boiler 2 ModSync CyclesCycle count seen by the sequencerRead
AI36Boiler 2 ModSync Run HoursRun hours seen by the sequencerRead
BI37Boiler 3 Local/Remote StatusBoiler in local or remoteRead0=Local, 1=Remote
BI38Boiler 3 ModSync Enable/DisableBoiler enabled by the sequencerRead0=Disable, 1=Enable
BI39Boiler 3 Heat DemandSequencer heat demand to this boilerRead0=Off, 1=On
BI40Boiler 3 Run StatusBoiler runningRead0=Off, 1=On
BI41Boiler 3 Alarm StatusBoiler alarmRead0=Off, 1=On
BI42Boiler 3 Current Fuel (Note 3)Fuel in use; LMV boilers onlyRead0=Gas, 1=Oil
AI43Boiler 3 StatusBoiler state codeRead0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water
AI44Boiler 3 Lead Lag PositionLead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7
AI45Boiler 3 Outlet TemperatureBoiler outlet temperature°FRead
AI46Boiler 3 Firing RateBoiler firing rate%Read
AI47Boiler 3 ModSync CyclesCycle count seen by the sequencerRead
AI48Boiler 3 ModSync Run HoursRun hours seen by the sequencerRead
BI49Boiler 4 Local/Remote StatusBoiler in local or remoteRead0=Local, 1=Remote
BI50Boiler 4 ModSync Enable/DisableBoiler enabled by the sequencerRead0=Disable, 1=Enable
BI51Boiler 4 Heat DemandSequencer heat demand to this boilerRead0=Off, 1=On
BI52Boiler 4 Run StatusBoiler runningRead0=Off, 1=On
BI53Boiler 4 Alarm StatusBoiler alarmRead0=Off, 1=On
BI54Boiler 4 Current Fuel (Note 3)Fuel in use; LMV boilers onlyRead0=Gas, 1=Oil
AI55Boiler 4 StatusBoiler state codeRead0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water
AI56Boiler 4 Lead Lag PositionLead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7
AI57Boiler 4 Outlet TemperatureBoiler outlet temperature°FRead
AI58Boiler 4 Firing RateBoiler firing rate%Read
AI59Boiler 4 ModSync CyclesCycle count seen by the sequencerRead
AI60Boiler 4 ModSync Run HoursRun hours seen by the sequencerRead
BI61Boiler 5 Local/Remote StatusBoiler in local or remoteRead0=Local, 1=Remote
BI62Boiler 5 ModSync Enable/DisableBoiler enabled by the sequencerRead0=Disable, 1=Enable
BI63Boiler 5 Heat DemandSequencer heat demand to this boilerRead0=Off, 1=On
BI64Boiler 5 Run StatusBoiler runningRead0=Off, 1=On
BI65Boiler 5 Alarm StatusBoiler alarmRead0=Off, 1=On
BI66Boiler 5 Current Fuel (Note 3)Fuel in use; LMV boilers onlyRead0=Gas, 1=Oil
AI67Boiler 5 StatusBoiler state codeRead0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water
AI68Boiler 5 Lead Lag PositionLead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7
AI69Boiler 5 Outlet TemperatureBoiler outlet temperature°FRead
AI70Boiler 5 Firing RateBoiler firing rate%Read
AI71Boiler 5 ModSync CyclesCycle count seen by the sequencerRead
AI72Boiler 5 ModSync Run HoursRun hours seen by the sequencerRead
BI73Boiler 6 Local/Remote StatusBoiler in local or remoteRead0=Local, 1=Remote
BI74Boiler 6 ModSync Enable/DisableBoiler enabled by the sequencerRead0=Disable, 1=Enable
BI75Boiler 6 Heat DemandSequencer heat demand to this boilerRead0=Off, 1=On
BI76Boiler 6 Run StatusBoiler runningRead0=Off, 1=On
BI77Boiler 6 Alarm StatusBoiler alarmRead0=Off, 1=On
BI78Boiler 6 Current Fuel (Note 3)Fuel in use; LMV boilers onlyRead0=Gas, 1=Oil
AI79Boiler 6 StatusBoiler state codeRead0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water
AI80Boiler 6 Lead Lag PositionLead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7
AI81Boiler 6 Outlet TemperatureBoiler outlet temperature°FRead
AI82Boiler 6 Firing RateBoiler firing rate%Read
AI83Boiler 6 ModSync CyclesCycle count seen by the sequencerRead
AI84Boiler 6 ModSync Run HoursRun hours seen by the sequencerRead
BI85Boiler 7 Local/Remote StatusBoiler in local or remoteRead0=Local, 1=Remote
BI86Boiler 7 ModSync Enable/DisableBoiler enabled by the sequencerRead0=Disable, 1=Enable
BI87Boiler 7 Heat DemandSequencer heat demand to this boilerRead0=Off, 1=On
BI88Boiler 7 Run StatusBoiler runningRead0=Off, 1=On
BI89Boiler 7 Alarm StatusBoiler alarmRead0=Off, 1=On
BI90Boiler 7 Current Fuel (Note 3)Fuel in use; LMV boilers onlyRead0=Gas, 1=Oil
AI91Boiler 7 StatusBoiler state codeRead0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water
AI92Boiler 7 Lead Lag PositionLead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7
AI93Boiler 7 Outlet TemperatureBoiler outlet temperature°FRead
AI94Boiler 7 Firing RateBoiler firing rate%Read
AI95Boiler 7 ModSync CyclesCycle count seen by the sequencerRead
AI96Boiler 7 ModSync Run HoursRun hours seen by the sequencerRead
BI97Boiler 8 Local/Remote StatusBoiler in local or remoteRead0=Local, 1=Remote
BI98Boiler 8 ModSync Enable/DisableBoiler enabled by the sequencerRead0=Disable, 1=Enable
BI99Boiler 8 Heat DemandSequencer heat demand to this boilerRead0=Off, 1=On
BI100Boiler 8 Run StatusBoiler runningRead0=Off, 1=On
BI101Boiler 8 Alarm StatusBoiler alarmRead0=Off, 1=On
BI102Boiler 8 Current Fuel (Note 3)Fuel in use; LMV boilers onlyRead0=Gas, 1=Oil
AI103Boiler 8 StatusBoiler state codeRead0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water
AI104Boiler 8 Lead Lag PositionLead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7
AI105Boiler 8 Outlet TemperatureBoiler outlet temperature°FRead
AI106Boiler 8 Firing RateBoiler firing rate%Read
AI107Boiler 8 ModSync CyclesCycle count seen by the sequencerRead
AI108Boiler 8 ModSync Run HoursRun hours seen by the sequencerRead
BI109Boiler 1 Isolation Valve Command (Note 2)Isolation valve command (optional)Read0=Close, 1=Open
BI110Boiler 2 Isolation Valve Command (Note 2)Isolation valve command (optional)Read0=Close, 1=Open
BI111Boiler 3 Isolation Valve Command (Note 2)Isolation valve command (optional)Read0=Close, 1=Open
BI112Boiler 4 Isolation Valve Command (Note 2)Isolation valve command (optional)Read0=Close, 1=Open
BI113Boiler 5 Isolation Valve Command (Note 2)Isolation valve command (optional)Read0=Close, 1=Open
BI114Boiler 6 Isolation Valve Command (Note 2)Isolation valve command (optional)Read0=Close, 1=Open
BI115Boiler 7 Isolation Valve Command (Note 2)Isolation valve command (optional)Read0=Close, 1=Open
BI116Boiler 8 Isolation Valve Command (Note 2)Isolation valve command (optional)Read0=Close, 1=Open
BI117Boiler 1 Isolation Valve Status Input (Note 2)Isolation valve proof input (optional)Read0=Off, 1=On
BI118Boiler 2 Isolation Valve Status Input (Note 2)Isolation valve proof input (optional)Read0=Off, 1=On
BI119Boiler 3 Isolation Valve Status Input (Note 2)Isolation valve proof input (optional)Read0=Off, 1=On
BI120Boiler 4 Isolation Valve Status Input (Note 2)Isolation valve proof input (optional)Read0=Off, 1=On
BI121Boiler 5 Isolation Valve Status Input (Note 2)Isolation valve proof input (optional)Read0=Off, 1=On
BI122Boiler 6 Isolation Valve Status Input (Note 2)Isolation valve proof input (optional)Read0=Off, 1=On
BI123Boiler 7 Isolation Valve Status Input (Note 2)Isolation valve proof input (optional)Read0=Off, 1=On
BI124Boiler 8 Isolation Valve Status Input (Note 2)Isolation valve proof input (optional)Read0=Off, 1=On
BI125Boiler 1 Pump Command (Note 2)Boiler pump command (optional)Read0=Off, 1=On
BI126Boiler 2 Pump Command (Note 2)Boiler pump command (optional)Read0=Off, 1=On
BI127Boiler 3 Pump Command (Note 2)Boiler pump command (optional)Read0=Off, 1=On
BI128Boiler 4 Pump Command (Note 2)Boiler pump command (optional)Read0=Off, 1=On
BI129Boiler 5 Pump Command (Note 2)Boiler pump command (optional)Read0=Off, 1=On
BI130Boiler 6 Pump Command (Note 2)Boiler pump command (optional)Read0=Off, 1=On
BI131Boiler 7 Pump Command (Note 2)Boiler pump command (optional)Read0=Off, 1=On
BI132Boiler 8 Pump Command (Note 2)Boiler pump command (optional)Read0=Off, 1=On
BI133Boiler 1 Pump Status Input (Note 2)Boiler pump proof input (optional)Read0=Off, 1=On
BI134Boiler 2 Pump Status Input (Note 2)Boiler pump proof input (optional)Read0=Off, 1=On
BI135Boiler 3 Pump Status Input (Note 2)Boiler pump proof input (optional)Read0=Off, 1=On
BI136Boiler 4 Pump Status Input (Note 2)Boiler pump proof input (optional)Read0=Off, 1=On
BI137Boiler 5 Pump Status Input (Note 2)Boiler pump proof input (optional)Read0=Off, 1=On
BI138Boiler 6 Pump Status Input (Note 2)Boiler pump proof input (optional)Read0=Off, 1=On
BI139Boiler 7 Pump Status Input (Note 2)Boiler pump proof input (optional)Read0=Off, 1=On
BI140Boiler 8 Pump Status Input (Note 2)Boiler pump proof input (optional)Read0=Off, 1=On
AI141Boiler 1 Pump Speed (Note 2)Boiler pump speed (optional)%Read
AI142Boiler 2 Pump Speed (Note 2)Boiler pump speed (optional)%Read
AI143Boiler 3 Pump Speed (Note 2)Boiler pump speed (optional)%Read
AI144Boiler 4 Pump Speed (Note 2)Boiler pump speed (optional)%Read
AI145Boiler 5 Pump Speed (Note 2)Boiler pump speed (optional)%Read
AI146Boiler 6 Pump Speed (Note 2)Boiler pump speed (optional)%Read
AI147Boiler 7 Pump Speed (Note 2)Boiler pump speed (optional)%Read
AI148Boiler 8 Pump Speed (Note 2)Boiler pump speed (optional)%Read
AV149Supply Pressure (Note 2)System supply pressure, 0-200psiWrite
AV150Return Pressure (Note 2)System return pressure, 0-200psiWrite
AV151Differential Pressure (Note 2)System differential pressure, 0-200psiWrite
AV152Differential Setpoint (Note 2)Differential setpoint; temperature or pressure per ModSyncWrite
AI153System Pump 1 Status (Note 2)System pump stateRead0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm
AI154System Pump 2 Status (Note 2)System pump stateRead0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm
AI155System Pump 3 Status (Note 2)System pump stateRead0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm
AI156System Pump 4 Status (Note 2)System pump stateRead0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm
AI157System Pump 1 Speed (Note 2)System pump speed%Read
AI158System Pump 2 Speed (Note 2)System pump speed%Read
AI159System Pump 3 Speed (Note 2)System pump speed%Read
AI160System Pump 4 Speed (Note 2)System pump speed%Read
AI161System Pump 1 Lead Lag Position (Note 2)System pump lead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3
AI162System Pump 2 Lead Lag Position (Note 2)System pump lead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3
AI163System Pump 3 Lead Lag Position (Note 2)System pump lead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3
AI164System Pump 4 Lead Lag Position (Note 2)System pump lead/lag positionRead0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)

How many BACnet points does the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) have?

This list has 164 BACnet objects: 71 analog inputs, 10 analog values, 82 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet points are writable?

11 of the 164 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet documentation?

The source is Hydronic ModSync SE Version 6.6.1.X - Fulton N54 ProtoNode BACnet Network Addressing, published free by Fulton at https://fulton.com/app/uploads/2021/02/ModSync-SE-V661X-BACnet.pdf.

What are the minimum BACnet points to integrate the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?

Start with BV 7 Remote Enable/Disable (Plant enable (1 = enable)); AV 9 BMS Setpoint Input (Note 2) (Supply setpoint from the BMS, °F); AV 10 ModSync Setpoint Mode (Must be 2 = BMS to use the BMS setpoint); BI 16 Boiler 1 Run Status (Boiler 1 running (repeat per boiler)); AI 11 ModSync Setpoint (Active plant setpoint, °F); AV 3 Supply Temperature (System supply water temperature, °F); AI 22 Boiler 1 Firing Rate (Boiler 1 firing rate, % (repeat per boiler)); BI 17 Boiler 1 Alarm Status (Boiler 1 alarm (repeat per boiler)); AI 12 ModSync Alarm Code (Plant alarm code from Fulton's alarm chart).

How do I enable BMS control of the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?

BV 7 Remote Enable/Disable enables the plant from the BMS. For a BMS setpoint, set AV 10 ModSync Setpoint Mode = 2 (BMS) and write AV 9 BMS Setpoint Input; AV 9 is an optional point that has to be enabled at the ModSync.

Can the BMS supply sensor values to the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?

Outdoor air (AV 2), return (AV 4), differential (AV 5) and the system pressures (AV 149-151) are read/write analog values, available when the matching option is enabled at the ModSync. The sheet does not say when the BMS must write them.

How do I check these points on the real Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Fulton BACnet points lists

Source: Hydronic ModSync SE Version 6.6.1.X - Fulton N54 ProtoNode BACnet Network Addressing. Object names, instances and units are reproduced as published; descriptions are our own.