Boiler plant sequencer · BACnet points list
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet points list
Updated 28 October 2026
The ModSync SE sequences up to eight hydronic boilers, and Fulton's N54 ProtoNode publishes its data as one flat list of 164 objects. Plant points cover enable, setpoint source and value, supply/return temperatures and the alarm code; each boiler then has a 12-point block of status, temperature and firing rate, followed by optional valve, pump and pressure points.
This page lists 164 BACnet objects for the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.
- Manufacturer
- Fulton
- Model
- Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
- Equipment
- Boiler plant sequencer
- Equipment type
- Boilers & water heaters
- BACnet objects
- 164 (11 writable)
- Transport
- —
- Firmware
- ModSync SE 6.6.1.X
- Also known as
- ModSync, ModSync SE, Fulton ModSync, ModSync sequencer, N54 ProtoNode
BMS integration notes: Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
Enable the plant with Remote Enable/Disable, set ModSync Setpoint Mode to BMS and write the supply setpoint to BMS Setpoint Input. Read back the active ModSync setpoint, supply temperature, each boiler's run and alarm status and the ModSync alarm code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 7 | Remote Enable/Disable | Plant enable (1 = enable) | Write |
| AV 9 | BMS Setpoint Input (Note 2) | Supply setpoint from the BMS, °F | Write |
| AV 10 | ModSync Setpoint Mode | Must be 2 = BMS to use the BMS setpoint | Write |
| BI 16 | Boiler 1 Run Status | Boiler 1 running (repeat per boiler) | Read |
| AI 11 | ModSync Setpoint | Active plant setpoint, °F | Read |
| AV 3 | Supply Temperature | System supply water temperature, °F | Write |
| AI 22 | Boiler 1 Firing Rate | Boiler 1 firing rate, % (repeat per boiler) | Read |
| BI 17 | Boiler 1 Alarm Status | Boiler 1 alarm (repeat per boiler) | Read |
| AI 12 | ModSync Alarm Code | Plant alarm code from Fulton's alarm chart | Read |
Enable & remote start
BV 7 Remote Enable/Disable enables the plant from the BMS. For a BMS setpoint, set AV 10 ModSync Setpoint Mode = 2 (BMS) and write AV 9 BMS Setpoint Input; AV 9 is an optional point that has to be enabled at the ModSync.
Sensors & values from the BMS
Outdoor air (AV 2), return (AV 4), differential (AV 5) and the system pressures (AV 149-151) are read/write analog values, available when the matching option is enabled at the ModSync. The sheet does not say when the BMS must write them.
Network setup
- Object IDs 1-164 are fixed; boiler 1 data is 13-24, each further boiler adds 12 (boiler 8 = 97-108).
- The sheet gives no device instance, MAC address or baud rate; those are set on the ProtoNode gateway.
Watch out for
- Points marked (Note 2) stay inactive unless the option is enabled at the ModSync.
- Status, Lead Lag Position and alarm codes are analog values carrying a code; see the states.
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Lead Boiler Position | Which boiler is lead, 0-8 | Read | ||
| AV | 2 | Outdoor Air Temperature (Note 2) | Outdoor air temperature (optional) | °F | Write | |
| AVmin | 3 | Supply Temperature | System supply temperature | °F | Write | |
| AV | 4 | Return Temperature (Note 2) | System return temperature (optional) | °F | Write | |
| AV | 5 | Differential Temperature (Note 2) | Supply/return differential (optional) | °F | Write | |
| BI | 6 | Building Mode | Occupied or unoccupied | Read | 0=Unoccupied, 1=Occupied | |
| BVmin | 7 | Remote Enable/Disable | Plant enable from the BMS | Write | 0=Disable, 1=Enable | |
| BI | 8 | Domestic Hot Water Priority | DHW priority active | Read | 0=Disabled, 1=Enabled | |
| AVmin | 9 | BMS Setpoint Input (Note 2) | Supply setpoint written by the BMS | °F | Write | |
| AVmin | 10 | ModSync Setpoint Mode | Setpoint source selection | Write | 0=ModSync, 1=Remote SP, 2=BMS, 3=Manual | |
| AImin | 11 | ModSync Setpoint | Active plant setpoint | °F | Read | |
| AImin | 12 | ModSync Alarm Code | Plant alarm code (see Fulton alarm chart) | Read | ||
| BI | 13 | Boiler 1 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 14 | Boiler 1 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 15 | Boiler 1 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BImin | 16 | Boiler 1 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BImin | 17 | Boiler 1 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 18 | Boiler 1 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 19 | Boiler 1 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 20 | Boiler 1 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 21 | Boiler 1 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AImin | 22 | Boiler 1 Firing Rate | Boiler firing rate | % | Read | |
| AI | 23 | Boiler 1 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 24 | Boiler 1 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 25 | Boiler 2 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 26 | Boiler 2 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 27 | Boiler 2 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 28 | Boiler 2 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 29 | Boiler 2 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 30 | Boiler 2 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 31 | Boiler 2 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 32 | Boiler 2 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 33 | Boiler 2 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 34 | Boiler 2 Firing Rate | Boiler firing rate | % | Read | |
| AI | 35 | Boiler 2 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 36 | Boiler 2 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 37 | Boiler 3 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 38 | Boiler 3 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 39 | Boiler 3 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 40 | Boiler 3 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 41 | Boiler 3 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 42 | Boiler 3 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 43 | Boiler 3 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 44 | Boiler 3 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 45 | Boiler 3 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 46 | Boiler 3 Firing Rate | Boiler firing rate | % | Read | |
| AI | 47 | Boiler 3 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 48 | Boiler 3 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 49 | Boiler 4 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 50 | Boiler 4 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 51 | Boiler 4 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 52 | Boiler 4 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 53 | Boiler 4 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 54 | Boiler 4 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 55 | Boiler 4 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 56 | Boiler 4 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 57 | Boiler 4 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 58 | Boiler 4 Firing Rate | Boiler firing rate | % | Read | |
| AI | 59 | Boiler 4 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 60 | Boiler 4 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 61 | Boiler 5 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 62 | Boiler 5 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 63 | Boiler 5 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 64 | Boiler 5 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 65 | Boiler 5 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 66 | Boiler 5 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 67 | Boiler 5 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 68 | Boiler 5 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 69 | Boiler 5 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 70 | Boiler 5 Firing Rate | Boiler firing rate | % | Read | |
| AI | 71 | Boiler 5 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 72 | Boiler 5 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 73 | Boiler 6 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 74 | Boiler 6 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 75 | Boiler 6 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 76 | Boiler 6 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 77 | Boiler 6 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 78 | Boiler 6 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 79 | Boiler 6 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 80 | Boiler 6 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 81 | Boiler 6 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 82 | Boiler 6 Firing Rate | Boiler firing rate | % | Read | |
| AI | 83 | Boiler 6 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 84 | Boiler 6 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 85 | Boiler 7 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 86 | Boiler 7 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 87 | Boiler 7 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 88 | Boiler 7 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 89 | Boiler 7 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 90 | Boiler 7 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 91 | Boiler 7 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 92 | Boiler 7 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 93 | Boiler 7 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 94 | Boiler 7 Firing Rate | Boiler firing rate | % | Read | |
| AI | 95 | Boiler 7 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 96 | Boiler 7 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 97 | Boiler 8 Local/Remote Status | Boiler in local or remote | Read | 0=Local, 1=Remote | |
| BI | 98 | Boiler 8 ModSync Enable/Disable | Boiler enabled by the sequencer | Read | 0=Disable, 1=Enable | |
| BI | 99 | Boiler 8 Heat Demand | Sequencer heat demand to this boiler | Read | 0=Off, 1=On | |
| BI | 100 | Boiler 8 Run Status | Boiler running | Read | 0=Off, 1=On | |
| BI | 101 | Boiler 8 Alarm Status | Boiler alarm | Read | 0=Off, 1=On | |
| BI | 102 | Boiler 8 Current Fuel (Note 3) | Fuel in use; LMV boilers only | Read | 0=Gas, 1=Oil | |
| AI | 103 | Boiler 8 Status | Boiler state code | Read | 0=Disabled By ModSync, 1=Temp Override, 2=Remote Disable, 3=Outside Temp Cutoff, 4=Standby, 5=Purging, 6=Gas Valve Energized, 7=Modulating, 8=Air Switch Alarm, 10=Heat Demand, 11=Low Gas Pressure, 13=Safety Loop Alarm, 14=LMV Error, 15=Disabled By BMS, 16=Modbus Com Error, 17=Post Purge, 18=Boiler Alarm, 19=Limit String Open, 20=Communication Disabled, 21=Warming Active, 22=Primary Low Water, 23=Secondary Low Water, 24=High Water | |
| AI | 104 | Boiler 8 Lead Lag Position | Lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3, 6=Lag 4, 7=Lag 5, 8=Lag 6, 9=Lag 7 | |
| AI | 105 | Boiler 8 Outlet Temperature | Boiler outlet temperature | °F | Read | |
| AI | 106 | Boiler 8 Firing Rate | Boiler firing rate | % | Read | |
| AI | 107 | Boiler 8 ModSync Cycles | Cycle count seen by the sequencer | Read | ||
| AI | 108 | Boiler 8 ModSync Run Hours | Run hours seen by the sequencer | Read | ||
| BI | 109 | Boiler 1 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 110 | Boiler 2 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 111 | Boiler 3 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 112 | Boiler 4 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 113 | Boiler 5 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 114 | Boiler 6 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 115 | Boiler 7 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 116 | Boiler 8 Isolation Valve Command (Note 2) | Isolation valve command (optional) | Read | 0=Close, 1=Open | |
| BI | 117 | Boiler 1 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 118 | Boiler 2 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 119 | Boiler 3 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 120 | Boiler 4 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 121 | Boiler 5 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 122 | Boiler 6 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 123 | Boiler 7 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 124 | Boiler 8 Isolation Valve Status Input (Note 2) | Isolation valve proof input (optional) | Read | 0=Off, 1=On | |
| BI | 125 | Boiler 1 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 126 | Boiler 2 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 127 | Boiler 3 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 128 | Boiler 4 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 129 | Boiler 5 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 130 | Boiler 6 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 131 | Boiler 7 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 132 | Boiler 8 Pump Command (Note 2) | Boiler pump command (optional) | Read | 0=Off, 1=On | |
| BI | 133 | Boiler 1 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 134 | Boiler 2 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 135 | Boiler 3 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 136 | Boiler 4 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 137 | Boiler 5 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 138 | Boiler 6 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 139 | Boiler 7 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| BI | 140 | Boiler 8 Pump Status Input (Note 2) | Boiler pump proof input (optional) | Read | 0=Off, 1=On | |
| AI | 141 | Boiler 1 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 142 | Boiler 2 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 143 | Boiler 3 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 144 | Boiler 4 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 145 | Boiler 5 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 146 | Boiler 6 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 147 | Boiler 7 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AI | 148 | Boiler 8 Pump Speed (Note 2) | Boiler pump speed (optional) | % | Read | |
| AV | 149 | Supply Pressure (Note 2) | System supply pressure, 0-200 | psi | Write | |
| AV | 150 | Return Pressure (Note 2) | System return pressure, 0-200 | psi | Write | |
| AV | 151 | Differential Pressure (Note 2) | System differential pressure, 0-200 | psi | Write | |
| AV | 152 | Differential Setpoint (Note 2) | Differential setpoint; temperature or pressure per ModSync | Write | ||
| AI | 153 | System Pump 1 Status (Note 2) | System pump state | Read | 0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm | |
| AI | 154 | System Pump 2 Status (Note 2) | System pump state | Read | 0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm | |
| AI | 155 | System Pump 3 Status (Note 2) | System pump state | Read | 0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm | |
| AI | 156 | System Pump 4 Status (Note 2) | System pump state | Read | 0=Disabled, 1=Standby, 2=Command, 3=Running, 4=Alarm | |
| AI | 157 | System Pump 1 Speed (Note 2) | System pump speed | % | Read | |
| AI | 158 | System Pump 2 Speed (Note 2) | System pump speed | % | Read | |
| AI | 159 | System Pump 3 Speed (Note 2) | System pump speed | % | Read | |
| AI | 160 | System Pump 4 Speed (Note 2) | System pump speed | % | Read | |
| AI | 161 | System Pump 1 Lead Lag Position (Note 2) | System pump lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3 | |
| AI | 162 | System Pump 2 Lead Lag Position (Note 2) | System pump lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3 | |
| AI | 163 | System Pump 3 Lead Lag Position (Note 2) | System pump lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3 | |
| AI | 164 | System Pump 4 Lead Lag Position (Note 2) | System pump lead/lag position | Read | 0=Manual, 1=Disabled, 2=Lead, 3=Lag 1, 4=Lag 2, 5=Lag 3 |
No points match these filters.
Integration notes
- Object IDs are fixed (1-164) and do not depend on boiler addresses.
- The sheet does not say which BACnet transport the gateway is set to; ProtoNode gateways are normally configured for BACnet IP or BACnet MS/TP.
- Points marked (Note 2) only work if the matching option is enabled at the ModSync.
- Current Fuel points apply only to boilers with LMV burner controls.
- Differential Setpoint is a temperature or a pressure, depending on the selection at the ModSync.
- Per-boiler blocks: boiler 1 = 13-24, boiler 2 = 25-36 ... boiler 8 = 97-108.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
How many BACnet points does the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) have?
This list has 164 BACnet objects: 71 analog inputs, 10 analog values, 82 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet points are writable?
11 of the 164 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode) BACnet documentation?
The source is Hydronic ModSync SE Version 6.6.1.X - Fulton N54 ProtoNode BACnet Network Addressing, published free by Fulton at https://fulton.com/app/uploads/2021/02/ModSync-SE-V661X-BACnet.pdf.
What are the minimum BACnet points to integrate the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?
Start with BV 7 Remote Enable/Disable (Plant enable (1 = enable)); AV 9 BMS Setpoint Input (Note 2) (Supply setpoint from the BMS, °F); AV 10 ModSync Setpoint Mode (Must be 2 = BMS to use the BMS setpoint); BI 16 Boiler 1 Run Status (Boiler 1 running (repeat per boiler)); AI 11 ModSync Setpoint (Active plant setpoint, °F); AV 3 Supply Temperature (System supply water temperature, °F); AI 22 Boiler 1 Firing Rate (Boiler 1 firing rate, % (repeat per boiler)); BI 17 Boiler 1 Alarm Status (Boiler 1 alarm (repeat per boiler)); AI 12 ModSync Alarm Code (Plant alarm code from Fulton's alarm chart).
How do I enable BMS control of the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?
BV 7 Remote Enable/Disable enables the plant from the BMS. For a BMS setpoint, set AV 10 ModSync Setpoint Mode = 2 (BMS) and write AV 9 BMS Setpoint Input; AV 9 is an optional point that has to be enabled at the ModSync.
Can the BMS supply sensor values to the Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?
Outdoor air (AV 2), return (AV 4), differential (AV 5) and the system pressures (AV 149-151) are read/write analog values, available when the matching option is enabled at the ModSync. The sheet does not say when the BMS must write them.
How do I check these points on the real Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Fulton BACnet points lists
- Boiler burner control gateway
Fulton Boiler with Siemens LMV3 (N54 ProtoNode)
Fulton boilers with a Siemens LMV3 burner management control, read through Fulton's N54 ProtoNode gateway.
Also known as: LMV3, LMV 3, Siemens LMV3, N54 ProtoNode, Fulton ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 (N54 ProtoNode)
Fulton hydronic boilers run by the PURE control (the file name points to Endura+ EDR+ 2500-6000 MBH sizes), read through the N54 ProtoNode.
Also known as: PURE, Fulton PURE, Endura+, EDR+, Endura Plus, Hydronic PURE, N54 ProtoNode
Source: Hydronic ModSync SE Version 6.6.1.X - Fulton N54 ProtoNode BACnet Network Addressing. Object names, instances and units are reproduced as published; descriptions are our own.