Steam boiler burner control · BACnet points list

Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet points list

Updated 6 November 2026

Short answer

Fulton lists 26 Analog Value objects (integer values) for a steam boiler with a Siemens LMV5 burner control on a BACnet interface. Objects 1-19 are read-only: fuel, output, setpoint, actual pressure, flame signal, units, error code and modes. Objects 20-26 are the writable copies of the mode, output and setpoint values.

This page lists 26 BACnet objects for the Fulton Siemens LMV5 Steam Boiler with BACnet Interface — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.

Manufacturer
Fulton
Model
Siemens LMV5 Steam Boiler with BACnet Interface
Equipment
Steam boiler burner control
Equipment type
Boilers & water heaters
BACnet objects
26 (7 writable)
Transport
—
Firmware
Not stated
Also known as
LMV5, Siemens LMV5, LMV52, Fulton LMV5
Source document
Network Addressing For Standard Configurations - LMV5 Steam with A BACnet Interface
Download CSV 26 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.

BMS integration notes: Fulton Siemens LMV5 Steam Boiler with BACnet Interface

Integration in brief

Write Modbus Mode = Remote (AV 21), then use Operating Mode in Remote (AV 22: Auto, Remote On, Remote Off) and the setpoint or output objects. Read current output, actual pressure, flame signal and the error code. AV 1-19 are read-only copies; the writable versions are AV 20-26.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 22Operating Mode in Remote0 = Auto, 1 = Remote On, 2 = Remote OffWrite
AV 21Modbus ModeSet 1 = Remote so network commands take effectWrite
AV 25Setpoint W1Steam pressure setpoint W1, psiWrite
AV 23Predefined Output Modulation (Modulation Rate)Output in remote, 200-1000Write
AV 2Current OutputCurrent burner output, %Read
AV 4Actual Value / Current TemperatureActual steam pressure, psiRead
AV 5Flame SignalFlame signal, %Read
AV 9Current Error: Error CodeActive LMV error codeRead

Enable & remote start

AV 21 Modbus Mode = 1 (Remote) hands control to the network; AV 22 Operating Mode in Remote then selects 0 = Auto, 1 = Remote On or 2 = Remote Off. AV 23 Predefined Output Modulation sets the output (200-1000) and AV 24-26 are the writable setpoints W3, W1 and W2.

Network setup

Watch out for

Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

26 of 26 shown
Type
Analog
Access
Show
Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet Points List
DescriptionStates
AV1Current Fuel TypeRead0=Gas, 1=Oil
AVmin2Current OutputRange 0 - 100%Read
AV3Current SetpointRange 0 - 200psiRead
AVmin4Actual Value / Current TemperatureRange 0 - 200psiRead
AVmin5Flame SignalRange 0 - 100%Read
AV6Volume Unit of oilRead0=L, 1=gal
AV7Unit of TempRead0=C, 1=F
AV8Unit of PressureRead0=barr, 1=psi
AVmin9Current Error: Error CodeActive LMV error codeRead
AV1035Name printed as a bare number; meaning not givenRead
AV1137Name printed as a bare number; meaning not givenRead
AV12Selection of Manual or Automatic OperationRead0=Auto, 1=Burner On, 2=Burner Off
AV13Operating ModeRead0=ExtLR X5-03, 1=IntLR, 2=IntLR Bus, 3=IntLR x62, 4=ExtLR x62, 5=ExtLR Bus
AV14Modbus ModeRead0=Local, 1=Remote
AV15Operating Mode in RemoteRead0=Auto, 1=Remote On, 2=Remote Off
AV16Predefined Output Modulation (Modulation Rate)Range 200 - 1000Read
AV17External Setpoint W3Range 0 - 200psiRead
AV18Setpoint W1Range 0 - 200psiRead
AV19Setpoint W2Range 0 - 200psiRead
AV20Operating ModeWrite0=ExtLR X5-03, 1=IntLR, 2=IntLR Bus, 3=IntLR x62, 4=ExtLR x62, 5=ExtLR Bus
AVmin21Modbus ModeWrite0=Local, 1=Remote
AVmin22Operating Mode in RemoteWrite0=Auto, 1=Remote On, 2=Remote Off
AVmin23Predefined Output Modulation (Modulation Rate)Range 200 - 1000Write
AV24External Setpoint W3Range 0 - 200psiWrite
AVmin25Setpoint W1Range 0 - 200psiWrite
AV26Setpoint W2Range 0 - 200psiWrite
Object ID lookup: Fulton Siemens LMV5 Steam Boiler with BACnet Interface point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens LMV5 Steam Boiler with BACnet Interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fulton Siemens LMV5 Steam Boiler with BACnet Interface

How many BACnet points does the Fulton Siemens LMV5 Steam Boiler with BACnet Interface have?

This list has 26 BACnet objects: 26 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet points are writable?

7 of the 26 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet documentation?

The source is Network Addressing For Standard Configurations - LMV5 Steam with A BACnet Interface, published free by Fulton at https://fulton.com/app/uploads/2021/03/BACnet_PointsList_LMV5-1.pdf.

What are the minimum BACnet points to integrate the Fulton Siemens LMV5 Steam Boiler with BACnet Interface?

Start with AV 22 Operating Mode in Remote (0 = Auto, 1 = Remote On, 2 = Remote Off); AV 21 Modbus Mode (Set 1 = Remote so network commands take effect); AV 25 Setpoint W1 (Steam pressure setpoint W1, psi); AV 23 Predefined Output Modulation (Modulation Rate) (Output in remote, 200-1000); AV 2 Current Output (Current burner output, %); AV 4 Actual Value / Current Temperature (Actual steam pressure, psi); AV 5 Flame Signal (Flame signal, %); AV 9 Current Error: Error Code (Active LMV error code).

How do I enable BMS control of the Fulton Siemens LMV5 Steam Boiler with BACnet Interface?

AV 21 Modbus Mode = 1 (Remote) hands control to the network; AV 22 Operating Mode in Remote then selects 0 = Auto, 1 = Remote On or 2 = Remote Off. AV 23 Predefined Output Modulation sets the output (200-1000) and AV 24-26 are the writable setpoints W3, W1 and W2.