- Siemens LMV5 Steam Boiler with BACnet Interface
Steam boiler burner control · BACnet points list
Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet points list
Updated 6 November 2026
Fulton lists 26 Analog Value objects (integer values) for a steam boiler with a Siemens LMV5 burner control on a BACnet interface. Objects 1-19 are read-only: fuel, output, setpoint, actual pressure, flame signal, units, error code and modes. Objects 20-26 are the writable copies of the mode, output and setpoint values.
This page lists 26 BACnet objects for the Fulton Siemens LMV5 Steam Boiler with BACnet Interface — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.
- Manufacturer
- Fulton
- Model
- Siemens LMV5 Steam Boiler with BACnet Interface
- Equipment
- Steam boiler burner control
- Equipment type
- Boilers & water heaters
- BACnet objects
- 26 (7 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- LMV5, Siemens LMV5, LMV52, Fulton LMV5
Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.
BMS integration notes: Fulton Siemens LMV5 Steam Boiler with BACnet Interface
Write Modbus Mode = Remote (AV 21), then use Operating Mode in Remote (AV 22: Auto, Remote On, Remote Off) and the setpoint or output objects. Read current output, actual pressure, flame signal and the error code. AV 1-19 are read-only copies; the writable versions are AV 20-26.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 22 | Operating Mode in Remote | 0 = Auto, 1 = Remote On, 2 = Remote Off | Write |
| AV 21 | Modbus Mode | Set 1 = Remote so network commands take effect | Write |
| AV 25 | Setpoint W1 | Steam pressure setpoint W1, psi | Write |
| AV 23 | Predefined Output Modulation (Modulation Rate) | Output in remote, 200-1000 | Write |
| AV 2 | Current Output | Current burner output, % | Read |
| AV 4 | Actual Value / Current Temperature | Actual steam pressure, psi | Read |
| AV 5 | Flame Signal | Flame signal, % | Read |
| AV 9 | Current Error: Error Code | Active LMV error code | Read |
Enable & remote start
AV 21 Modbus Mode = 1 (Remote) hands control to the network; AV 22 Operating Mode in Remote then selects 0 = Auto, 1 = Remote On or 2 = Remote Off. AV 23 Predefined Output Modulation sets the output (200-1000) and AV 24-26 are the writable setpoints W3, W1 and W2.
Network setup
- Object IDs 1-26 are fixed.
- The sheet gives no device instance, MAC address or baud rate.
Watch out for
- Every object is an Analog Value carrying integers, including on/off and mode codes.
- AV 1-19 are read-only; write to AV 20-26 instead.
- Pressure units on the setpoints follow AV 8 Unit of Pressure (0 = bar, 1 = psi); the sheet labels them psi.
Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | Current Fuel Type | Read | 0=Gas, 1=Oil | ||
| AVmin | 2 | Current Output | Range 0 - 100% | Read | ||
| AV | 3 | Current Setpoint | Range 0 - 200 | psi | Read | |
| AVmin | 4 | Actual Value / Current Temperature | Range 0 - 200 | psi | Read | |
| AVmin | 5 | Flame Signal | Range 0 - 100% | Read | ||
| AV | 6 | Volume Unit of oil | Read | 0=L, 1=gal | ||
| AV | 7 | Unit of Temp | Read | 0=C, 1=F | ||
| AV | 8 | Unit of Pressure | Read | 0=barr, 1=psi | ||
| AVmin | 9 | Current Error: Error Code | Active LMV error code | Read | ||
| AV | 10 | 35 | Name printed as a bare number; meaning not given | Read | ||
| AV | 11 | 37 | Name printed as a bare number; meaning not given | Read | ||
| AV | 12 | Selection of Manual or Automatic Operation | Read | 0=Auto, 1=Burner On, 2=Burner Off | ||
| AV | 13 | Operating Mode | Read | 0=ExtLR X5-03, 1=IntLR, 2=IntLR Bus, 3=IntLR x62, 4=ExtLR x62, 5=ExtLR Bus | ||
| AV | 14 | Modbus Mode | Read | 0=Local, 1=Remote | ||
| AV | 15 | Operating Mode in Remote | Read | 0=Auto, 1=Remote On, 2=Remote Off | ||
| AV | 16 | Predefined Output Modulation (Modulation Rate) | Range 200 - 1000 | Read | ||
| AV | 17 | External Setpoint W3 | Range 0 - 200 | psi | Read | |
| AV | 18 | Setpoint W1 | Range 0 - 200 | psi | Read | |
| AV | 19 | Setpoint W2 | Range 0 - 200 | psi | Read | |
| AV | 20 | Operating Mode | Write | 0=ExtLR X5-03, 1=IntLR, 2=IntLR Bus, 3=IntLR x62, 4=ExtLR x62, 5=ExtLR Bus | ||
| AVmin | 21 | Modbus Mode | Write | 0=Local, 1=Remote | ||
| AVmin | 22 | Operating Mode in Remote | Write | 0=Auto, 1=Remote On, 2=Remote Off | ||
| AVmin | 23 | Predefined Output Modulation (Modulation Rate) | Range 200 - 1000 | Write | ||
| AV | 24 | External Setpoint W3 | Range 0 - 200 | psi | Write | |
| AVmin | 25 | Setpoint W1 | Range 0 - 200 | psi | Write | |
| AV | 26 | Setpoint W2 | Range 0 - 200 | psi | Write |
No points match these filters.
Object ID lookup: Fulton Siemens LMV5 Steam Boiler with BACnet Interface point IDs by name
AV1Current Fuel TypeAV2Current OutputAV3Current SetpointAV4Actual Value / Current TemperatureAV5Flame SignalAV6Volume Unit of oilAV7Unit of TempAV8Unit of PressureAV9Current Error: Error CodeAV1035AV1137AV12Selection of Manual or Automatic OperationAV13Operating ModeAV14Modbus ModeAV15Operating Mode in RemoteAV16Predefined Output Modulation (Modulation Rate)AV17External Setpoint W3AV18Setpoint W1AV19Setpoint W2AV20Operating ModeAV21Modbus ModeAV22Operating Mode in RemoteAV23Predefined Output Modulation (Modulation Rate)AV24External Setpoint W3AV25Setpoint W1AV26Setpoint W2
Integration notes
- All objects are Analog Values with integer values; on/off and mode values are codes.
- Objects 10 and 11 are printed with the names "35" and "37" and no range; object 11 has no read/write mark (listed here as read-only).
- The sheet does not say which gateway or transport is used.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens LMV5 Steam Boiler with BACnet Interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Fulton Siemens LMV5 Steam Boiler with BACnet Interface
How many BACnet points does the Fulton Siemens LMV5 Steam Boiler with BACnet Interface have?
This list has 26 BACnet objects: 26 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet points are writable?
7 of the 26 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Fulton Siemens LMV5 Steam Boiler with BACnet Interface BACnet documentation?
The source is Network Addressing For Standard Configurations - LMV5 Steam with A BACnet Interface, published free by Fulton at https://fulton.com/app/uploads/2021/03/BACnet_PointsList_LMV5-1.pdf.
What are the minimum BACnet points to integrate the Fulton Siemens LMV5 Steam Boiler with BACnet Interface?
Start with AV 22 Operating Mode in Remote (0 = Auto, 1 = Remote On, 2 = Remote Off); AV 21 Modbus Mode (Set 1 = Remote so network commands take effect); AV 25 Setpoint W1 (Steam pressure setpoint W1, psi); AV 23 Predefined Output Modulation (Modulation Rate) (Output in remote, 200-1000); AV 2 Current Output (Current burner output, %); AV 4 Actual Value / Current Temperature (Actual steam pressure, psi); AV 5 Flame Signal (Flame signal, %); AV 9 Current Error: Error Code (Active LMV error code).
How do I enable BMS control of the Fulton Siemens LMV5 Steam Boiler with BACnet Interface?
AV 21 Modbus Mode = 1 (Remote) hands control to the network; AV 22 Operating Mode in Remote then selects 0 = Auto, 1 = Remote On or 2 = Remote Off. AV 23 Predefined Output Modulation sets the output (200-1000) and AV 24-26 are the writable setpoints W3, W1 and W2.
How do I check these points on the real Siemens LMV5 Steam Boiler with BACnet Interface?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Fulton BACnet points lists
- Boiler burner control gateway
Fulton Boiler with Siemens LMV3 (N54 ProtoNode)
Fulton boilers with a Siemens LMV3 burner management control, read through Fulton's N54 ProtoNode gateway.
Also known as: LMV3, LMV 3, Siemens LMV3, N54 ProtoNode, Fulton ProtoNode - Boiler burner control gateway
Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)
Fulton hydronic boilers with a Siemens LMV3 burner control and a Yokogawa UT32A temperature controller, read through the N54 ProtoNode.
Also known as: LMV3, Siemens LMV3, Yokogawa UT32A, UT32A, N54 ProtoNode - Boiler plant sequencer
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
Fulton ModSync SE hydronic boiler sequencer (software 6.6.1.X) managing up to 8 boilers, read through the N54 ProtoNode.
Also known as: ModSync, ModSync SE, Fulton ModSync, ModSync sequencer, N54 ProtoNode - Boiler controller gateway
Fulton Hydronic SOLA Boiler (N54 ProtoNode)
Fulton hydronic boilers with the SOLA burner control, one block of objects per boiler on the N54 ProtoNode.
Also known as: SOLA, Fulton SOLA, Honeywell SOLA, N54 ProtoNode - Boiler plant controller gateway
Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)
The SOLA lead/lag master of a group of Fulton hydronic boilers (up to 8 slaves), read through the N54 ProtoNode.
Also known as: SOLA Master, Fulton SOLA lead lag, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) 750-2000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Single (N54 ProtoNode)
Fulton Endura (EDR) 750-2000 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura XE (EXE) 399-750 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Single (N54 ProtoNode)
Fulton Endura XE (EXE) 399-750 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) ZE lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Single (N54 ProtoNode)
Fulton Endura (EDR) ZE boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 (N54 ProtoNode)
Fulton hydronic boilers run by the PURE control (the file name points to Endura+ EDR+ 2500-6000 MBH sizes), read through the N54 ProtoNode.
Also known as: PURE, Fulton PURE, Endura+, EDR+, Endura Plus, Hydronic PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura+ (EDR+) 2500-6000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura+, EDR+, Endura Plus, EDR+ 2500, EDR+ 6000, Fulton PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton VSRT steam boiler lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)
Fulton VSRT steam boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE, Fulton PURE, N54 ProtoNode - Boiler burner control
Fulton Siemens LMV36 with BACnet Interface
Fulton boilers with a Siemens LMV36 burner control on a BACnet interface.
Also known as: LMV36, Siemens LMV36, LMV3, Fulton LMV36 - Steam boiler plant sequencer
Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)
Fulton ModSync SE steam boiler sequencer (version 6.6.1.0) managing up to 8 steam boilers, read through a Sierra Monitor ProtoNode.
Also known as: ModSync SE, ModSync, Fulton ModSync steam, ProtoNode
Source: Network Addressing For Standard Configurations - LMV5 Steam with A BACnet Interface. Object names, instances and units are reproduced as published; descriptions are our own.