Boiler burner control gateway · BACnet points list

Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet points list

Updated 6 November 2026

Short answer

Fulton's N54 ProtoNode reads the boiler's Siemens LMV3 burner control and its Yokogawa UT32A temperature controller over Modbus and publishes 30 objects per boiler. Objects 1-28 are the same burner data as the LMV3-only sheet; 29-30 add the outlet temperature and a writable setpoint from the UT32A.

This page lists 30 BACnet objects for the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.

Manufacturer
Fulton
Model
Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)
Equipment
Boiler burner control gateway
Equipment type
Boilers & water heaters
BACnet objects
30 (4 writable)
Transport
—
Firmware
Not stated
Also known as
LMV3, Siemens LMV3, Yokogawa UT32A, UT32A, N54 ProtoNode
Source document
Hydronic LMV 3 and Yokogawa - Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date)
Download CSV 30 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.

BMS integration notes: Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)

Integration in brief

Put the boiler in remote with the Modbus Mode BV, then run it with Operating Mode In Remote (Auto/On/Off) and the Remote Firing Rate, or write the temperature setpoint to the Yokogawa controller. Monitor burner phase, firing rate, outlet temperature, the alarm output and the LMV error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1027Boiler 1 Operating Mode In RemoteRun command in remote: 0 = Auto, 1 = On, 2 = OffWrite
BV 1026Boiler 1 Modbus ModeSet 1 = Remote so network commands take effectWrite
AV 1028Boiler 1 Remote Firing RateFiring rate command, %; 20 % minimum to enableWrite
AV 1030Boiler 1 Current SetpointTemperature setpoint, 0-250 °FWrite
BI 1014Boiler 1 Controller On/Off StatusBurner controller on/off stateRead
AI 1001Boiler 1 Burner Control PhaseBurner sequence phase; 60 = operation, 0 = lockoutRead
AI 1029Boiler 1 Outlet TemperatureOutlet water temperature, °FRead
AI 1005Boiler 1 Firing RateActual firing rate, %Read
BI 1020Boiler 1 Alarm StatusBoiler alarm activeRead
AI 1010Boiler 1 Current Error: Error CodeActive LMV error codeRead

Enable & remote start

Write BV (X)026 Modbus Mode = 1 (Remote). In remote, AV (X)027 Operating Mode In Remote selects 0 = Auto, 1 = On or 2 = Off, and AV (X)028 Remote Firing Rate sets the rate; the boiler is only enabled at 20 % or more. AV (X)030 Current Setpoint is the writable temperature setpoint.

Network setup

Watch out for

Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

30 of 30 shown
Type
Access
Show
Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet Points List
DescriptionStates
AImin1001Boiler 1 Burner Control PhaseRead0=Lockout Phase, 2=Safety Phase, 10=Home Run, 12=Standby, 22=Fan Motor On, 30=Pre-Purge, 36=Driving to Ignition, 38=Ignition, 40=Fuel Valve On, 44=Flame Stabilization, 50=Safety Time 2, 52=Flame Stabilization 2, 60=Operation, 70=Post- Purge
AI1002Boiler 1 Position of Fuel ActuatorRange -50 to 150Read
AI1003Boiler 1 Position of Air ActuatorRange -50 to 150Read
AI1004Boiler 1 Current Type of FuelRead0=Fuel 0 (Gas), 1=Fuel 1 (Oil)
AImin1005Boiler 1 Firing RateRange 0 to 100%Read
AI1006Boiler 1 Flame SignalRange 0 to 100%Read
AI1007Boiler 1 Startup Counter TotalRange 0 to 999999Read
AI1008Boiler 1 Hours Run Fuel 0Range 0 to 999999Read
AI1009Boiler 1 Hours Run Fuel 1Range 0 to 999999Read
AImin1010Boiler 1 Current Error: Error Code*See LMV ManualRead
AI1011Boiler 1 Current Error: Error Diagnostic*See LMV ManualRead
AI1012Boiler 1 Current Error: Error Class*See LMV ManualRead
AI1013Boiler 1 Current Error: Error Phase*See LMV ManualRead
BImin1014Boiler 1 Controller On/Off StatusRead0=Off, 1=On
BI1015Boiler 1 Pressure Switch Valve ProvingRead0=Off, 1=On
BI1016Boiler 1 Safety Loop StatusRead0=Off, 1=On
BI1017Boiler 1 Pressure Switch Min StatusRead0=Off, 1=On
BI1018Boiler 1 Pressure Switch Mas StatusRead0=Off, 1=On
BI1019Boiler 1 Air Pressure Switch StatusRead0=Off, 1=On
BImin1020Boiler 1 Alarm StatusRead0=Off, 1=On
BI1021Boiler 1 Ignition StatusRead0=Off, 1=On
BI1022Boiler 1 Fan StatusRead0=Off, 1=On
BI1023Boiler 1 Fuel Valve V1 StatusRead0=Off, 1=On
BI1024Boiler 1 Fuel Valve V2 StatusRead0=Off, 1=On
BI1025Boiler 1 Fuel Valve V3 StatusRead0=Off, 1=On
BVmin1026Boiler 1 Modbus ModeWrite0=Local, 1=Remote
AVmin1027Boiler 1 Operating Mode In RemoteWrite0=Auto, 1=On, 2=Off
AVmin1028Boiler 1 Remote Firing RateRange 0 to 100 (Minimum 20% required for boiler enable)%Write
AImin1029Boiler 1 Outlet TemperatureRange 0 to 250°FRead
AVmin1030Boiler 1 Current SetpointRange 0 to 250°FWrite
Object ID lookup: Fulton Boiler with Siemens LMV3 and Yokogawa UT32A point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)

How many BACnet points does the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) have?

This list has 30 BACnet objects: 14 analog inputs, 3 analog values, 12 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet points are writable?

4 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet documentation?

The source is Hydronic LMV 3 and Yokogawa - Fulton N54 ProtoNode BACnet Network Addressing, revision 2020-04-08 (file date), published free by Fulton at https://fulton.com/app/uploads/2021/02/N54-LMV3-UT32A-BACnet-list_2020-0408.pdf.

What are the minimum BACnet points to integrate the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)?

Start with AV 1027 Boiler 1 Operating Mode In Remote (Run command in remote: 0 = Auto, 1 = On, 2 = Off); BV 1026 Boiler 1 Modbus Mode (Set 1 = Remote so network commands take effect); AV 1028 Boiler 1 Remote Firing Rate (Firing rate command, %; 20 % minimum to enable); AV 1030 Boiler 1 Current Setpoint (Temperature setpoint, 0-250 °F); BI 1014 Boiler 1 Controller On/Off Status (Burner controller on/off state); AI 1001 Boiler 1 Burner Control Phase (Burner sequence phase; 60 = operation, 0 = lockout); AI 1029 Boiler 1 Outlet Temperature (Outlet water temperature, °F); AI 1005 Boiler 1 Firing Rate (Actual firing rate, %); BI 1020 Boiler 1 Alarm Status (Boiler alarm active); AI 1010 Boiler 1 Current Error: Error Code (Active LMV error code).

How do I enable BMS control of the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)?

Write BV (X)026 Modbus Mode = 1 (Remote). In remote, AV (X)027 Operating Mode In Remote selects 0 = Auto, 1 = On or 2 = Off, and AV (X)028 Remote Firing Rate sets the rate; the boiler is only enabled at 20 % or more. AV (X)030 Current Setpoint is the writable temperature setpoint.

How do I check these points on the real Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Fulton BACnet points lists

Source: Hydronic LMV 3 and Yokogawa - Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date). Object names, instances and units are reproduced as published; descriptions are our own.