Boiler burner control gateway · BACnet points list
Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet points list
Updated 6 November 2026
Fulton's N54 ProtoNode reads the boiler's Siemens LMV3 burner control and its Yokogawa UT32A temperature controller over Modbus and publishes 30 objects per boiler. Objects 1-28 are the same burner data as the LMV3-only sheet; 29-30 add the outlet temperature and a writable setpoint from the UT32A.
This page lists 30 BACnet objects for the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Fulton’s own free documentation, linked below.
- Manufacturer
- Fulton
- Model
- Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)
- Equipment
- Boiler burner control gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 30 (4 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- LMV3, Siemens LMV3, Yokogawa UT32A, UT32A, N54 ProtoNode
Reference only, provided as-is: verify against Fulton’s current documentation and the live device before use. Not official Fulton information. Terms of use.
BMS integration notes: Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)
Put the boiler in remote with the Modbus Mode BV, then run it with Operating Mode In Remote (Auto/On/Off) and the Remote Firing Rate, or write the temperature setpoint to the Yokogawa controller. Monitor burner phase, firing rate, outlet temperature, the alarm output and the LMV error code.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 1027 | Boiler 1 Operating Mode In Remote | Run command in remote: 0 = Auto, 1 = On, 2 = Off | Write |
| BV 1026 | Boiler 1 Modbus Mode | Set 1 = Remote so network commands take effect | Write |
| AV 1028 | Boiler 1 Remote Firing Rate | Firing rate command, %; 20 % minimum to enable | Write |
| AV 1030 | Boiler 1 Current Setpoint | Temperature setpoint, 0-250 °F | Write |
| BI 1014 | Boiler 1 Controller On/Off Status | Burner controller on/off state | Read |
| AI 1001 | Boiler 1 Burner Control Phase | Burner sequence phase; 60 = operation, 0 = lockout | Read |
| AI 1029 | Boiler 1 Outlet Temperature | Outlet water temperature, °F | Read |
| AI 1005 | Boiler 1 Firing Rate | Actual firing rate, % | Read |
| BI 1020 | Boiler 1 Alarm Status | Boiler alarm active | Read |
| AI 1010 | Boiler 1 Current Error: Error Code | Active LMV error code | Read |
Enable & remote start
Write BV (X)026 Modbus Mode = 1 (Remote). In remote, AV (X)027 Operating Mode In Remote selects 0 = Auto, 1 = On or 2 = Off, and AV (X)028 Remote Firing Rate sets the rate; the boiler is only enabled at 20 % or more. AV (X)030 Current Setpoint is the writable temperature setpoint.
Network setup
- Object ID = boiler Modbus address followed by the three-digit point number: (X)001-(X)030. Boiler 1 = 1001-1030.
- The LMV3 sits at Modbus address X and the Yokogawa UT32A at X+10 on the ProtoNode.
- The sheet gives no device instance, MAC address or baud rate; those are set on the ProtoNode gateway.
Watch out for
- A remote firing rate below 20 % does not enable the boiler.
- Error code points need the Siemens LMV manual to decode.
Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1001 | Boiler 1 Burner Control Phase | Read | 0=Lockout Phase, 2=Safety Phase, 10=Home Run, 12=Standby, 22=Fan Motor On, 30=Pre-Purge, 36=Driving to Ignition, 38=Ignition, 40=Fuel Valve On, 44=Flame Stabilization, 50=Safety Time 2, 52=Flame Stabilization 2, 60=Operation, 70=Post- Purge | ||
| AI | 1002 | Boiler 1 Position of Fuel Actuator | Range -50 to 150 | Read | ||
| AI | 1003 | Boiler 1 Position of Air Actuator | Range -50 to 150 | Read | ||
| AI | 1004 | Boiler 1 Current Type of Fuel | Read | 0=Fuel 0 (Gas), 1=Fuel 1 (Oil) | ||
| AImin | 1005 | Boiler 1 Firing Rate | Range 0 to 100 | % | Read | |
| AI | 1006 | Boiler 1 Flame Signal | Range 0 to 100 | % | Read | |
| AI | 1007 | Boiler 1 Startup Counter Total | Range 0 to 999999 | Read | ||
| AI | 1008 | Boiler 1 Hours Run Fuel 0 | Range 0 to 999999 | Read | ||
| AI | 1009 | Boiler 1 Hours Run Fuel 1 | Range 0 to 999999 | Read | ||
| AImin | 1010 | Boiler 1 Current Error: Error Code | *See LMV Manual | Read | ||
| AI | 1011 | Boiler 1 Current Error: Error Diagnostic | *See LMV Manual | Read | ||
| AI | 1012 | Boiler 1 Current Error: Error Class | *See LMV Manual | Read | ||
| AI | 1013 | Boiler 1 Current Error: Error Phase | *See LMV Manual | Read | ||
| BImin | 1014 | Boiler 1 Controller On/Off Status | Read | 0=Off, 1=On | ||
| BI | 1015 | Boiler 1 Pressure Switch Valve Proving | Read | 0=Off, 1=On | ||
| BI | 1016 | Boiler 1 Safety Loop Status | Read | 0=Off, 1=On | ||
| BI | 1017 | Boiler 1 Pressure Switch Min Status | Read | 0=Off, 1=On | ||
| BI | 1018 | Boiler 1 Pressure Switch Mas Status | Read | 0=Off, 1=On | ||
| BI | 1019 | Boiler 1 Air Pressure Switch Status | Read | 0=Off, 1=On | ||
| BImin | 1020 | Boiler 1 Alarm Status | Read | 0=Off, 1=On | ||
| BI | 1021 | Boiler 1 Ignition Status | Read | 0=Off, 1=On | ||
| BI | 1022 | Boiler 1 Fan Status | Read | 0=Off, 1=On | ||
| BI | 1023 | Boiler 1 Fuel Valve V1 Status | Read | 0=Off, 1=On | ||
| BI | 1024 | Boiler 1 Fuel Valve V2 Status | Read | 0=Off, 1=On | ||
| BI | 1025 | Boiler 1 Fuel Valve V3 Status | Read | 0=Off, 1=On | ||
| BVmin | 1026 | Boiler 1 Modbus Mode | Write | 0=Local, 1=Remote | ||
| AVmin | 1027 | Boiler 1 Operating Mode In Remote | Write | 0=Auto, 1=On, 2=Off | ||
| AVmin | 1028 | Boiler 1 Remote Firing Rate | Range 0 to 100 (Minimum 20% required for boiler enable) | % | Write | |
| AImin | 1029 | Boiler 1 Outlet Temperature | Range 0 to 250 | °F | Read | |
| AVmin | 1030 | Boiler 1 Current Setpoint | Range 0 to 250 | °F | Write |
No points match these filters.
Object ID lookup: Fulton Boiler with Siemens LMV3 and Yokogawa UT32A point IDs by name
AI1001Boiler 1 Burner Control PhaseAI1002Boiler 1 Position of Fuel ActuatorAI1003Boiler 1 Position of Air ActuatorAI1004Boiler 1 Current Type of FuelAI1005Boiler 1 Firing RateAI1006Boiler 1 Flame SignalAI1007Boiler 1 Startup Counter TotalAI1008Boiler 1 Hours Run Fuel 0AI1009Boiler 1 Hours Run Fuel 1AI1010Boiler 1 Current Error: Error CodeAI1011Boiler 1 Current Error: Error DiagnosticAI1012Boiler 1 Current Error: Error ClassAI1013Boiler 1 Current Error: Error PhaseBI1014Boiler 1 Controller On/Off StatusBI1015Boiler 1 Pressure Switch Valve ProvingBI1016Boiler 1 Safety Loop StatusBI1017Boiler 1 Pressure Switch Min StatusBI1018Boiler 1 Pressure Switch Mas StatusBI1019Boiler 1 Air Pressure Switch StatusBI1020Boiler 1 Alarm StatusBI1021Boiler 1 Ignition StatusBI1022Boiler 1 Fan StatusBI1023Boiler 1 Fuel Valve V1 StatusBI1024Boiler 1 Fuel Valve V2 StatusBI1025Boiler 1 Fuel Valve V3 StatusBV1026Boiler 1 Modbus ModeAV1027Boiler 1 Operating Mode In RemoteAV1028Boiler 1 Remote Firing RateAI1029Boiler 1 Outlet TemperatureAV1030Boiler 1 Current Setpoint
Integration notes
- Object IDs are written (X)001-(X)030, where (X) is the LMV3's Modbus address. This list shows address 1 (1001-1030).
- The sheet says the Yokogawa control sits at Modbus address X+10 but still prints its two objects as (X)029 and (X)030.
- The sheet does not say which BACnet transport the gateway is set to; ProtoNode gateways are normally configured for BACnet IP or BACnet MS/TP.
- Objects (X)001-(X)028 match the LMV3-only N54 sheet already in the library (fulton/lmv3-protonode-n54).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)
How many BACnet points does the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) have?
This list has 30 BACnet objects: 14 analog inputs, 3 analog values, 12 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet points are writable?
4 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode) BACnet documentation?
The source is Hydronic LMV 3 and Yokogawa - Fulton N54 ProtoNode BACnet Network Addressing, revision 2020-04-08 (file date), published free by Fulton at https://fulton.com/app/uploads/2021/02/N54-LMV3-UT32A-BACnet-list_2020-0408.pdf.
What are the minimum BACnet points to integrate the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)?
Start with AV 1027 Boiler 1 Operating Mode In Remote (Run command in remote: 0 = Auto, 1 = On, 2 = Off); BV 1026 Boiler 1 Modbus Mode (Set 1 = Remote so network commands take effect); AV 1028 Boiler 1 Remote Firing Rate (Firing rate command, %; 20 % minimum to enable); AV 1030 Boiler 1 Current Setpoint (Temperature setpoint, 0-250 °F); BI 1014 Boiler 1 Controller On/Off Status (Burner controller on/off state); AI 1001 Boiler 1 Burner Control Phase (Burner sequence phase; 60 = operation, 0 = lockout); AI 1029 Boiler 1 Outlet Temperature (Outlet water temperature, °F); AI 1005 Boiler 1 Firing Rate (Actual firing rate, %); BI 1020 Boiler 1 Alarm Status (Boiler alarm active); AI 1010 Boiler 1 Current Error: Error Code (Active LMV error code).
How do I enable BMS control of the Fulton Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)?
Write BV (X)026 Modbus Mode = 1 (Remote). In remote, AV (X)027 Operating Mode In Remote selects 0 = Auto, 1 = On or 2 = Off, and AV (X)028 Remote Firing Rate sets the rate; the boiler is only enabled at 20 % or more. AV (X)030 Current Setpoint is the writable temperature setpoint.
How do I check these points on the real Boiler with Siemens LMV3 and Yokogawa UT32A (N54 ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Fulton BACnet points lists
- Boiler burner control gateway
Fulton Boiler with Siemens LMV3 (N54 ProtoNode)
Fulton boilers with a Siemens LMV3 burner management control, read through Fulton's N54 ProtoNode gateway.
Also known as: LMV3, LMV 3, Siemens LMV3, N54 ProtoNode, Fulton ProtoNode - Boiler plant sequencer
Fulton Hydronic ModSync SE v6.6.1.X (N54 ProtoNode)
Fulton ModSync SE hydronic boiler sequencer (software 6.6.1.X) managing up to 8 boilers, read through the N54 ProtoNode.
Also known as: ModSync, ModSync SE, Fulton ModSync, ModSync sequencer, N54 ProtoNode - Boiler controller gateway
Fulton Hydronic SOLA Boiler (N54 ProtoNode)
Fulton hydronic boilers with the SOLA burner control, one block of objects per boiler on the N54 ProtoNode.
Also known as: SOLA, Fulton SOLA, Honeywell SOLA, N54 ProtoNode - Boiler plant controller gateway
Fulton Hydronic SOLA Master (lead/lag) (N54 ProtoNode)
The SOLA lead/lag master of a group of Fulton hydronic boilers (up to 8 slaves), read through the N54 ProtoNode.
Also known as: SOLA Master, Fulton SOLA lead lag, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) 750-2000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura EDR 750-2000 Single (N54 ProtoNode)
Fulton Endura (EDR) 750-2000 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura, EDR 750, EDR 2000, EDR 2MM, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura XE (EXE) 399-750 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura XE EXE 399-750 Single (N54 ProtoNode)
Fulton Endura XE (EXE) 399-750 hydronic boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura XE, EXE 399, EXE 750, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura (EDR) ZE lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE Provider, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura ZE Single (N54 ProtoNode)
Fulton Endura (EDR) ZE boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: Endura ZE, EDR ZE, Fulton PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 (N54 ProtoNode)
Fulton hydronic boilers run by the PURE control (the file name points to Endura+ EDR+ 2500-6000 MBH sizes), read through the N54 ProtoNode.
Also known as: PURE, Fulton PURE, Endura+, EDR+, Endura Plus, Hydronic PURE, N54 ProtoNode - Boiler controller gateway
Fulton PURE Control - Endura+ EDR+ 2500-6000 Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton Endura+ (EDR+) 2500-6000 hydronic lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: Endura+, EDR+, Endura Plus, EDR+ 2500, EDR+ 6000, Fulton PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Provider (N54 ProtoNode)
The Provider (lead) boiler of a Fulton VSRT steam boiler lead/lag group with the PURE control, read through the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE Provider, N54 ProtoNode - Steam boiler controller gateway
Fulton PURE Control - VSRT Steam Boiler Single (N54 ProtoNode)
Fulton VSRT steam boilers with the PURE control, one boiler per address block on the N54 ProtoNode.
Also known as: VSRT, Fulton VSRT, Steam PURE, Fulton PURE, N54 ProtoNode - Boiler burner control
Fulton Siemens LMV36 with BACnet Interface
Fulton boilers with a Siemens LMV36 burner control on a BACnet interface.
Also known as: LMV36, Siemens LMV36, LMV3, Fulton LMV36 - Steam boiler burner control
Fulton Siemens LMV5 Steam Boiler with BACnet Interface
Fulton steam boilers whose Siemens LMV5 burner management is given a BACnet interface (standard configurations).
Also known as: LMV5, Siemens LMV5, LMV52, Fulton LMV5 - Steam boiler plant sequencer
Fulton Steam ModSync SE v6.6.1.0 (ProtoNode)
Fulton ModSync SE steam boiler sequencer (version 6.6.1.0) managing up to 8 steam boilers, read through a Sierra Monitor ProtoNode.
Also known as: ModSync SE, ModSync, Fulton ModSync steam, ProtoNode
Source: Hydronic LMV 3 and Yokogawa - Fulton N54 ProtoNode BACnet Network Addressing · rev. 2020-04-08 (file date). Object names, instances and units are reproduced as published; descriptions are our own.