Boiler plant manager (sequencing controller) · BACnet points list

AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet points list

Updated 12 November 2026Unofficial source

Short answer

When an Edge controller is the BST (Boiler Sequencing Technology) Manager it serves extra BACnet objects for the whole plant on top of its own unit objects: plant status and setpoints as Analog Inputs, plant settings as writable Analog Values, a read-only block for each of up to 16 BST units, and readings from up to 6 SmartPlate water heaters. BACnet IP runs on the Ethernet port and BACnet MS/TP on the RS-485 BAS port.

This page lists 100 BACnet objects for the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of AERCO’s documentation hosted by Watts staging media server, not by AERCO itself, so treat it as unofficial.

Manufacturer
AERCO
Model
Benchmark / Innovation Edge controller - BST Manager plant objects
Equipment
Boiler plant manager (sequencing controller)
Equipment type
Boilers & water heaters
BACnet objects
100 (37 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
BST Manager, Boiler Sequencing Technology, Edge [i], Edge [ii], Benchmark Edge, BMK Edge, Innovation Edge, OMM-0140, SmartPlate via Edge
Source document
Edge Communication Manual for Systems Integrators · OMM-0140J · rev. 2025-11-04 (unofficial copy, hosted by Watts staging media server)
Download CSV 100 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AERCO’s current documentation and the live device before use. Not official AERCO information. Terms of use.

BMS integration notes: AERCO Benchmark / Innovation Edge controller - BST Manager plant objects

Integration in brief

Connect the BAS to the BST Manager only. Check Allow BAS to Write (AV 51), then drive the plant with Remote Disable Code (AV 229) and the plant remote setpoint (AV 200); read plant status, header temperature, firing rate and the per-unit blocks.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 229Remote Disable Code0 = enable plant, 85 = disable plantWrite
AV 200Plant Remote SetpointPlant remote setpoint, 20-245 °FWrite
AV 51Allow BAS to WriteBAS write permission (0-1)Write
AI 114Act SetptActive plant setpointRead
AI 110Header TempHeader temperatureRead
AI 112BST Fire RatePlant firing rate, %Read
AI 113Units IgnitedUnits firingRead
AI 108Units FaultedNumber of units in faultRead
AI 301unit StatusUnit 1 status (5 = fault)Read

Enable & remote start

Allow BAS to Write (AV 51, 0-1) controls BAS write access. The plant is disabled by writing 85 to Remote Disable Code (AV 229) and enabled with 0; this needs Allow System Disable = Yes under Advanced Setup > Comm & Network > BAS.

Heartbeat & communication loss

Network Timeout (AV 53) is 5-999 s; the manual lists it but these tables do not describe the fallback action.

Sensors & values from the BMS

Header, return header, DHW header and outdoor temperatures can be written by the BAS (AV 214, AV 216, AV 206, AV 218) when their sensor source (AV 213, AV 215, AV 205, AV 217) is set to BAS.

Network setup

Watch out for

AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

100 of 100 shown
Type
Access
Show
AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet Points List
DescriptionStates
AI100Unit ModeUnit roleRead0=Off, 1=BST Client, 2=BST Manager
AI101Plant Constant SetpointPlant constant setpoint, 20-245 °F°FRead
AI102Setback SetpointSetback setpoint, 20-245 °F°FRead
AI103Setback Start TimeSetback start timeRead
AI104Setback Stop TimeSetback stop timeRead
AI105Auto-Manager TransferAutomatic manager transferReadDisabled / Enabled
AI106OutletTempPlant outlet temperature°FRead
AI107UEnabledUnits enabled, 0-16Read
AImin108Units FaultedUnits in fault, 0-16Read
AI109Unit AddressUnit address, 0-16Read
AImin110Header TempHeader temperature°FRead
AI111BST Outdoor TempOutdoor temperature, -70 to 130 °F°FRead
AImin112BST Fire RatePlant firing rate%Read
AImin113Units IgnitedUnits firing, 0-16Read
AImin114Act SetptActive plant setpoint°FRead
AI115SH Next On Valve PosValve position to start the next unit, 16-100 %%Read
AI116BST Setpt Hi LimPlant setpoint high limit°FRead
AI117BST Setpt Low LimitPlant setpoint low limit°FRead
AI118Cascade Temp Hi LimitCascade temperature high limit°FRead
AI119SH Operating ModeSpace-heating setpoint modeRead0=Constant Setpoint, 1=Rmt Stpt, 2=Outdoor Air Reset
AI120DHW Header TempDHW header temperature°FRead
AI121DHW SetpointDHW setpoint, 40-245 °F°FRead
AI122Fuel TypeFuel typeRead0=Natural Gas, 1=Propane
AI123VSP Pump OutputVariable-speed pump signal, 0-10 VVRead
AI124VSP Pump RelayVariable-speed pump relayReadOff / On
AI125Loop Return TempLoop return temperature°FRead
AI126DHW Header TempDHW header temperature (second object)°FRead
AI127SmartPlate OutletSmartPlate outlet temperature°FRead
AI128SmartPlate Valve PosSmartPlate valve position%Read
AI129SmartPlate SetpointSmartPlate setpoint, 0-140 °F°FRead
AI130SmartPlate Error NumberSmartPlate error number, 0-10Read
AI131SmartPlate Pmp Unit AddrSmartPlate pump unit address, 0-16Read
AI132SmartPlate Start AddressSmartPlate start address, 50-54Read
AI133Number of SmartPlatesNumber of SmartPlates, 0-6Read
AI152Unit ModeUnit roleRead0=OFF, 1=Client, 2=Manager
AVmin51Allow BAS to WriteEnable BAS writes, 0-1Write
AV53Network TimeoutNetwork timeout, 5-999 ssWrite
AVmin200Plant Remote SetpointPlant remote setpoint from the BAS, 20-245 °F°FWrite
AV201Setback SetpointSetback setpoint°FWrite
AV202Setback Start TimeSetback start timeWrite
AV203Setback Stop TimeSetback stop timeWrite
AV204Setback ScheduleSetback scheduleWriteDisable / Enable
AV205DHW Temp SensorDHW header sensor sourceWrite0=OFF, 1=Network, 2=Direct, 3=BAS
AV206DHW Header TempDHW header temperature written by the BAS°FWrite
AV207DHW Operating ModeDHW setpoint modeWrite0=Constant Setpoint, 1=Remote Setpoint
AV208DHW Rmt Setpt SignalDHW remote setpoint signalWrite0=1-5V, 1=0-5V, 2=Network, 3=BAS
AV209DHW BAS Remote SetpointDHW remote setpoint from the BAS, 40-245 °F°FWrite
AV210Other SH PRI Setpt ModeOther space-heating priority setpoint modeWrite0=Constant Setpoint, 1=Remote Setpoint
AV211Other SH PRI Remote SignlOther space-heating priority remote signalWrite0=1-5V, 1=0-5V, 2=Network, 3=BAS
AV212Other SH PRI SetpointOther space-heating priority setpoint°FWrite
AV213Hdr Temp SensorHeader sensor sourceWrite0=Network, 1=FFWD Temp, 2=Direct, 3=BAS, 4=OFF
AV214BAS Header TempHeader temperature written by the BAS°FWrite
AV215Rtn Hdr Temp SensorReturn header sensor sourceWrite0=OFF, 1=Network, 2=Direct, 3=BAS
AV216Rtn Hdr Temp SensorReturn header temperature, 0-250 °F (second object)°FWrite
AV217Outdoor Air Temp SensOutdoor air sensor sourceWrite0=Network, 1=Direct, 2=BAS, 3=OFF
AV218OAT BAS TempOutdoor temperature written by the BAS°FWrite
AV219BASBAS protocolWrite0=OFF, 1=BACnet MSTP, 2=BACnet IP, 3=Modbus RTU, 4=Modbus TCP
AV220Baud RateBAS baud rateWrite0=9600, 1=19200, 2=38400, 3=57600
AV221INTL CommunicationInternal (unit-to-unit) communicationWrite0=Disabled, 1=Enabled
AV222Intl Baud RateInternal baud rateWrite0=9600, 1=19200, 2=38400, 3=57600
AV223onAER ModeonAER connectionWrite0=Disabled, 1=Ethernet, 2=Wi-Fi, 3=Wiznet
AV224AERtrimAERtrimWrite0=Disabled, 1=Enabled
AV225O2 MonitoringO2 monitoringWrite0=No, 1=Yes
AV226SmartPlate SetpointSmartPlate setpointWrite
AV227SP Pump Out SignalSmartPlate pump output signalWrite
AV228SmartPlate Pmp Unit AddrSmartPlate pump unit addressWrite
AVmin229Remote Disable CodePlant enable / disable code (needs Allow System Disable = Yes)Write0=Enable Plant, 85=Disable Plant
AV230VSP Pump ModeVariable-speed pump mode, 0-10Write
AV231VSP Pump Adjust TimeVariable-speed pump adjust time, 1-600Write
AV233VSP Pump Adjust ValueVariable-speed pump adjust value%Write
AV245SH SetpointSpace-heating setpoint, 60-180°FWrite
AV246Remote Manager DisableSame setting as AV 229Write
AI300Communication AddressUnit communication address, 0-255Read
AImin301unit StatusUnit statusRead0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault
AI302Fault CodeFault code (manual section 6)Read
AI303Outlet TemperatureUnit outlet temperature°FRead
AI304FFWD TemperatureUnit feed-forward temperature°FRead
AI305Inlet TemperatureUnit inlet temperature°FRead
AI306Exhaust TemperatureExhaust temperature, 50-450 °F°FRead
AI307Inlet Air TemperatureInlet air temperature, -70 to 130 °F°FRead
AI308Flame StrengthFlame strength%Read
AI309Fire Rate InFiring rate command%Read
AI310Fire Rate OutActual firing rate%Read
AI311Unit TypeUnit type codeRead0=KC Boiler, 1=KC Boiler LN, 2=BMK Boiler Std, 3=BMK Blr Std Dual, 4=BMK Boiler LN, 5=BMK Blr LN Dual, 6=KC Water Heater, 7=KC Water Heater LN, 8=Innovation, 9=Innovation N
AI312Unit SizeUnit size codeRead0=SPARE, 1=600 MBH, 2=800 MBH, 3=1060 MBH, 4=1350 MBH, 5=500 MBH, 6=750 MBH, 7=1000 MBH, 8=1.5 MBTU, 9=1500 MBH, 10=2.0 MBTU, 11=2000 MBH, 12=2500 MBH, 13=3.0 MBTU, 14=3000 MBH, 15=4000 MBH, 16=5000 MBH, 17=6000 MBH
AI313Valve StateIsolation valve stateReadclose / open
AI314Net Remote SetpointNetwork remote setpoint, 0-9999Read
AI315Run Cycle UpperRun cycles, upper wordRead
AI316Run Cycle LowerRun cycles, lower wordRead
AI317Run Hours UpperRun hours, upper wordRead
AI318Run Hours LowerRun hours, lower wordRead
AI319Oxygen LvelFlue O2, 0-24 %%Read
AI3500SP OutletSmartPlate 1 outlet temperature, 30-245 °F°FRead
AI3501SP Valve PositionSmartPlate 1 valve position%Read
AI3502SP SetpointSmartPlate 1 setpoint°FRead
AI3503SP Error #SmartPlate 1 error number, 0-20Read
AI3504SP Delta PresSmartPlate EV 1 differential pressure, 0-100 psipsiRead
AI3505SP DHW InletSmartPlate EV 1 DHW inlet temperature°FRead
AI3506SP FlowSmartPlate EV 1 flow, 0-200 gpmgpmRead
AI3507SP Boiler InletSmartPlate 1 boiler inlet temperature°FRead
Object ID lookup: AERCO Benchmark / Innovation Edge controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Benchmark / Innovation Edge controller - BST Manager plant objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects

How many BACnet points does the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects have?

This list has 100 BACnet objects: 63 analog inputs, 37 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet points are writable?

37 of the 100 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet documentation?

AERCO does not publish it on its own website. This list comes from Edge Communication Manual for Systems Integrators (OMM-0140J), revision 2025-11-04, a copy hosted by Watts staging media server at https://stagesc10.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/650538-source. Ask AERCO or its representative for the current revision.

What are the minimum BACnet points to integrate the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects?

Start with AV 229 Remote Disable Code (0 = enable plant, 85 = disable plant); AV 200 Plant Remote Setpoint (Plant remote setpoint, 20-245 °F); AV 51 Allow BAS to Write (BAS write permission (0-1)); AI 114 Act Setpt (Active plant setpoint); AI 110 Header Temp (Header temperature); AI 112 BST Fire Rate (Plant firing rate, %); AI 113 Units Ignited (Units firing); AI 108 Units Faulted (Number of units in fault); AI 301 unit Status (Unit 1 status (5 = fault)).

How do I enable BMS control of the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects?

Allow BAS to Write (AV 51, 0-1) controls BAS write access. The plant is disabled by writing 85 to Remote Disable Code (AV 229) and enabled with 0; this needs Allow System Disable = Yes under Advanced Setup > Comm & Network > BAS.

Does the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects need a BACnet heartbeat or have a communication timeout?

Network Timeout (AV 53) is 5-999 s; the manual lists it but these tables do not describe the fallback action.

Can the BMS supply sensor values to the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects?

Header, return header, DHW header and outdoor temperatures can be written by the BAS (AV 214, AV 216, AV 206, AV 218) when their sensor source (AV 213, AV 215, AV 205, AV 217) is set to BAS.

How do I check these points on the real Benchmark / Innovation Edge controller - BST Manager plant objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AERCO BACnet points lists

Source: Edge Communication Manual for Systems Integrators · OMM-0140J · rev. 2025-11-04. Object names, instances and units are reproduced as published; descriptions are our own.