- Benchmark / Innovation Edge controller - BST Manager plant objects
Boiler plant manager (sequencing controller) · BACnet points list
AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet points list
Updated 12 November 2026Unofficial source
When an Edge controller is the BST (Boiler Sequencing Technology) Manager it serves extra BACnet objects for the whole plant on top of its own unit objects: plant status and setpoints as Analog Inputs, plant settings as writable Analog Values, a read-only block for each of up to 16 BST units, and readings from up to 6 SmartPlate water heaters. BACnet IP runs on the Ethernet port and BACnet MS/TP on the RS-485 BAS port.
This page lists 100 BACnet objects for the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of AERCO’s documentation hosted by Watts staging media server, not by AERCO itself, so treat it as unofficial.
- Manufacturer
- AERCO
- Model
- Benchmark / Innovation Edge controller - BST Manager plant objects
- Equipment
- Boiler plant manager (sequencing controller)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 100 (37 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- BST Manager, Boiler Sequencing Technology, Edge [i], Edge [ii], Benchmark Edge, BMK Edge, Innovation Edge, OMM-0140, SmartPlate via Edge
- Source document
- Edge Communication Manual for Systems Integrators · OMM-0140J · rev. 2025-11-04 (unofficial copy, hosted by Watts staging media server)
Reference only, provided as-is: verify against AERCO’s current documentation and the live device before use. Not official AERCO information. Terms of use.
BMS integration notes: AERCO Benchmark / Innovation Edge controller - BST Manager plant objects
Connect the BAS to the BST Manager only. Check Allow BAS to Write (AV 51), then drive the plant with Remote Disable Code (AV 229) and the plant remote setpoint (AV 200); read plant status, header temperature, firing rate and the per-unit blocks.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 229 | Remote Disable Code | 0 = enable plant, 85 = disable plant | Write |
| AV 200 | Plant Remote Setpoint | Plant remote setpoint, 20-245 °F | Write |
| AV 51 | Allow BAS to Write | BAS write permission (0-1) | Write |
| AI 114 | Act Setpt | Active plant setpoint | Read |
| AI 110 | Header Temp | Header temperature | Read |
| AI 112 | BST Fire Rate | Plant firing rate, % | Read |
| AI 113 | Units Ignited | Units firing | Read |
| AI 108 | Units Faulted | Number of units in fault | Read |
| AI 301 | unit Status | Unit 1 status (5 = fault) | Read |
Enable & remote start
Allow BAS to Write (AV 51, 0-1) controls BAS write access. The plant is disabled by writing 85 to Remote Disable Code (AV 229) and enabled with 0; this needs Allow System Disable = Yes under Advanced Setup > Comm & Network > BAS.
Heartbeat & communication loss
Network Timeout (AV 53) is 5-999 s; the manual lists it but these tables do not describe the fallback action.
Sensors & values from the BMS
Header, return header, DHW header and outdoor temperatures can be written by the BAS (AV 214, AV 216, AV 206, AV 218) when their sensor source (AV 213, AV 215, AV 205, AV 217) is set to BAS.
Network setup
- Choose the BAS protocol (AV 219 or the BAS menu): BACnet IP on the Ethernet port or BACnet MS/TP on RS-485; MS/TP baud 9600-57600 (AV 220).
Watch out for
- Read the per-unit blocks for unit faults; AI 108 only counts faulted units.
- Run cycles and run hours are split into upper and lower words.
AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 100 | Unit Mode | Unit role | Read | 0=Off, 1=BST Client, 2=BST Manager | |
| AI | 101 | Plant Constant Setpoint | Plant constant setpoint, 20-245 °F | °F | Read | |
| AI | 102 | Setback Setpoint | Setback setpoint, 20-245 °F | °F | Read | |
| AI | 103 | Setback Start Time | Setback start time | Read | ||
| AI | 104 | Setback Stop Time | Setback stop time | Read | ||
| AI | 105 | Auto-Manager Transfer | Automatic manager transfer | Read | Disabled / Enabled | |
| AI | 106 | OutletTemp | Plant outlet temperature | °F | Read | |
| AI | 107 | UEnabled | Units enabled, 0-16 | Read | ||
| AImin | 108 | Units Faulted | Units in fault, 0-16 | Read | ||
| AI | 109 | Unit Address | Unit address, 0-16 | Read | ||
| AImin | 110 | Header Temp | Header temperature | °F | Read | |
| AI | 111 | BST Outdoor Temp | Outdoor temperature, -70 to 130 °F | °F | Read | |
| AImin | 112 | BST Fire Rate | Plant firing rate | % | Read | |
| AImin | 113 | Units Ignited | Units firing, 0-16 | Read | ||
| AImin | 114 | Act Setpt | Active plant setpoint | °F | Read | |
| AI | 115 | SH Next On Valve Pos | Valve position to start the next unit, 16-100 % | % | Read | |
| AI | 116 | BST Setpt Hi Lim | Plant setpoint high limit | °F | Read | |
| AI | 117 | BST Setpt Low Limit | Plant setpoint low limit | °F | Read | |
| AI | 118 | Cascade Temp Hi Limit | Cascade temperature high limit | °F | Read | |
| AI | 119 | SH Operating Mode | Space-heating setpoint mode | Read | 0=Constant Setpoint, 1=Rmt Stpt, 2=Outdoor Air Reset | |
| AI | 120 | DHW Header Temp | DHW header temperature | °F | Read | |
| AI | 121 | DHW Setpoint | DHW setpoint, 40-245 °F | °F | Read | |
| AI | 122 | Fuel Type | Fuel type | Read | 0=Natural Gas, 1=Propane | |
| AI | 123 | VSP Pump Output | Variable-speed pump signal, 0-10 V | V | Read | |
| AI | 124 | VSP Pump Relay | Variable-speed pump relay | Read | Off / On | |
| AI | 125 | Loop Return Temp | Loop return temperature | °F | Read | |
| AI | 126 | DHW Header Temp | DHW header temperature (second object) | °F | Read | |
| AI | 127 | SmartPlate Outlet | SmartPlate outlet temperature | °F | Read | |
| AI | 128 | SmartPlate Valve Pos | SmartPlate valve position | % | Read | |
| AI | 129 | SmartPlate Setpoint | SmartPlate setpoint, 0-140 °F | °F | Read | |
| AI | 130 | SmartPlate Error Number | SmartPlate error number, 0-10 | Read | ||
| AI | 131 | SmartPlate Pmp Unit Addr | SmartPlate pump unit address, 0-16 | Read | ||
| AI | 132 | SmartPlate Start Address | SmartPlate start address, 50-54 | Read | ||
| AI | 133 | Number of SmartPlates | Number of SmartPlates, 0-6 | Read | ||
| AI | 152 | Unit Mode | Unit role | Read | 0=OFF, 1=Client, 2=Manager | |
| AVmin | 51 | Allow BAS to Write | Enable BAS writes, 0-1 | Write | ||
| AV | 53 | Network Timeout | Network timeout, 5-999 s | s | Write | |
| AVmin | 200 | Plant Remote Setpoint | Plant remote setpoint from the BAS, 20-245 °F | °F | Write | |
| AV | 201 | Setback Setpoint | Setback setpoint | °F | Write | |
| AV | 202 | Setback Start Time | Setback start time | Write | ||
| AV | 203 | Setback Stop Time | Setback stop time | Write | ||
| AV | 204 | Setback Schedule | Setback schedule | Write | Disable / Enable | |
| AV | 205 | DHW Temp Sensor | DHW header sensor source | Write | 0=OFF, 1=Network, 2=Direct, 3=BAS | |
| AV | 206 | DHW Header Temp | DHW header temperature written by the BAS | °F | Write | |
| AV | 207 | DHW Operating Mode | DHW setpoint mode | Write | 0=Constant Setpoint, 1=Remote Setpoint | |
| AV | 208 | DHW Rmt Setpt Signal | DHW remote setpoint signal | Write | 0=1-5V, 1=0-5V, 2=Network, 3=BAS | |
| AV | 209 | DHW BAS Remote Setpoint | DHW remote setpoint from the BAS, 40-245 °F | °F | Write | |
| AV | 210 | Other SH PRI Setpt Mode | Other space-heating priority setpoint mode | Write | 0=Constant Setpoint, 1=Remote Setpoint | |
| AV | 211 | Other SH PRI Remote Signl | Other space-heating priority remote signal | Write | 0=1-5V, 1=0-5V, 2=Network, 3=BAS | |
| AV | 212 | Other SH PRI Setpoint | Other space-heating priority setpoint | °F | Write | |
| AV | 213 | Hdr Temp Sensor | Header sensor source | Write | 0=Network, 1=FFWD Temp, 2=Direct, 3=BAS, 4=OFF | |
| AV | 214 | BAS Header Temp | Header temperature written by the BAS | °F | Write | |
| AV | 215 | Rtn Hdr Temp Sensor | Return header sensor source | Write | 0=OFF, 1=Network, 2=Direct, 3=BAS | |
| AV | 216 | Rtn Hdr Temp Sensor | Return header temperature, 0-250 °F (second object) | °F | Write | |
| AV | 217 | Outdoor Air Temp Sens | Outdoor air sensor source | Write | 0=Network, 1=Direct, 2=BAS, 3=OFF | |
| AV | 218 | OAT BAS Temp | Outdoor temperature written by the BAS | °F | Write | |
| AV | 219 | BAS | BAS protocol | Write | 0=OFF, 1=BACnet MSTP, 2=BACnet IP, 3=Modbus RTU, 4=Modbus TCP | |
| AV | 220 | Baud Rate | BAS baud rate | Write | 0=9600, 1=19200, 2=38400, 3=57600 | |
| AV | 221 | INTL Communication | Internal (unit-to-unit) communication | Write | 0=Disabled, 1=Enabled | |
| AV | 222 | Intl Baud Rate | Internal baud rate | Write | 0=9600, 1=19200, 2=38400, 3=57600 | |
| AV | 223 | onAER Mode | onAER connection | Write | 0=Disabled, 1=Ethernet, 2=Wi-Fi, 3=Wiznet | |
| AV | 224 | AERtrim | AERtrim | Write | 0=Disabled, 1=Enabled | |
| AV | 225 | O2 Monitoring | O2 monitoring | Write | 0=No, 1=Yes | |
| AV | 226 | SmartPlate Setpoint | SmartPlate setpoint | Write | ||
| AV | 227 | SP Pump Out Signal | SmartPlate pump output signal | Write | ||
| AV | 228 | SmartPlate Pmp Unit Addr | SmartPlate pump unit address | Write | ||
| AVmin | 229 | Remote Disable Code | Plant enable / disable code (needs Allow System Disable = Yes) | Write | 0=Enable Plant, 85=Disable Plant | |
| AV | 230 | VSP Pump Mode | Variable-speed pump mode, 0-10 | Write | ||
| AV | 231 | VSP Pump Adjust Time | Variable-speed pump adjust time, 1-600 | Write | ||
| AV | 233 | VSP Pump Adjust Value | Variable-speed pump adjust value | % | Write | |
| AV | 245 | SH Setpoint | Space-heating setpoint, 60-180 | °F | Write | |
| AV | 246 | Remote Manager Disable | Same setting as AV 229 | Write | ||
| AI | 300 | Communication Address | Unit communication address, 0-255 | Read | ||
| AImin | 301 | unit Status | Unit status | Read | 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault | |
| AI | 302 | Fault Code | Fault code (manual section 6) | Read | ||
| AI | 303 | Outlet Temperature | Unit outlet temperature | °F | Read | |
| AI | 304 | FFWD Temperature | Unit feed-forward temperature | °F | Read | |
| AI | 305 | Inlet Temperature | Unit inlet temperature | °F | Read | |
| AI | 306 | Exhaust Temperature | Exhaust temperature, 50-450 °F | °F | Read | |
| AI | 307 | Inlet Air Temperature | Inlet air temperature, -70 to 130 °F | °F | Read | |
| AI | 308 | Flame Strength | Flame strength | % | Read | |
| AI | 309 | Fire Rate In | Firing rate command | % | Read | |
| AI | 310 | Fire Rate Out | Actual firing rate | % | Read | |
| AI | 311 | Unit Type | Unit type code | Read | 0=KC Boiler, 1=KC Boiler LN, 2=BMK Boiler Std, 3=BMK Blr Std Dual, 4=BMK Boiler LN, 5=BMK Blr LN Dual, 6=KC Water Heater, 7=KC Water Heater LN, 8=Innovation, 9=Innovation N | |
| AI | 312 | Unit Size | Unit size code | Read | 0=SPARE, 1=600 MBH, 2=800 MBH, 3=1060 MBH, 4=1350 MBH, 5=500 MBH, 6=750 MBH, 7=1000 MBH, 8=1.5 MBTU, 9=1500 MBH, 10=2.0 MBTU, 11=2000 MBH, 12=2500 MBH, 13=3.0 MBTU, 14=3000 MBH, 15=4000 MBH, 16=5000 MBH, 17=6000 MBH | |
| AI | 313 | Valve State | Isolation valve state | Read | close / open | |
| AI | 314 | Net Remote Setpoint | Network remote setpoint, 0-9999 | Read | ||
| AI | 315 | Run Cycle Upper | Run cycles, upper word | Read | ||
| AI | 316 | Run Cycle Lower | Run cycles, lower word | Read | ||
| AI | 317 | Run Hours Upper | Run hours, upper word | Read | ||
| AI | 318 | Run Hours Lower | Run hours, lower word | Read | ||
| AI | 319 | Oxygen Lvel | Flue O2, 0-24 % | % | Read | |
| AI | 3500 | SP Outlet | SmartPlate 1 outlet temperature, 30-245 °F | °F | Read | |
| AI | 3501 | SP Valve Position | SmartPlate 1 valve position | % | Read | |
| AI | 3502 | SP Setpoint | SmartPlate 1 setpoint | °F | Read | |
| AI | 3503 | SP Error # | SmartPlate 1 error number, 0-20 | Read | ||
| AI | 3504 | SP Delta Pres | SmartPlate EV 1 differential pressure, 0-100 psi | psi | Read | |
| AI | 3505 | SP DHW Inlet | SmartPlate EV 1 DHW inlet temperature | °F | Read | |
| AI | 3506 | SP Flow | SmartPlate EV 1 flow, 0-200 gpm | gpm | Read | |
| AI | 3507 | SP Boiler Inlet | SmartPlate 1 boiler inlet temperature | °F | Read |
No points match these filters.
Object ID lookup: AERCO Benchmark / Innovation Edge controller point IDs by name
AI100Unit ModeAI101Plant Constant SetpointAI102Setback SetpointAI103Setback Start TimeAI104Setback Stop TimeAI105Auto-Manager TransferAI106OutletTempAI107UEnabledAI108Units FaultedAI109Unit AddressAI110Header TempAI111BST Outdoor TempAI112BST Fire RateAI113Units IgnitedAI114Act SetptAI115SH Next On Valve PosAI116BST Setpt Hi LimAI117BST Setpt Low LimitAI118Cascade Temp Hi LimitAI119SH Operating ModeAI120DHW Header TempAI121DHW SetpointAI122Fuel TypeAI123VSP Pump OutputAI124VSP Pump RelayAI125Loop Return TempAI126DHW Header TempAI127SmartPlate OutletAI128SmartPlate Valve PosAI129SmartPlate SetpointAI130SmartPlate Error NumberAI131SmartPlate Pmp Unit AddrAI132SmartPlate Start AddressAI133Number of SmartPlatesAI152Unit ModeAV51Allow BAS to WriteAV53Network TimeoutAV200Plant Remote SetpointAV201Setback SetpointAV202Setback Start TimeAV203Setback Stop TimeAV204Setback ScheduleAV205DHW Temp SensorAV206DHW Header TempAV207DHW Operating ModeAV208DHW Rmt Setpt SignalAV209DHW BAS Remote SetpointAV210Other SH PRI Setpt ModeAV211Other SH PRI Remote SignlAV212Other SH PRI SetpointAV213Hdr Temp SensorAV214BAS Header TempAV215Rtn Hdr Temp SensorAV216Rtn Hdr Temp SensorAV217Outdoor Air Temp SensAV218OAT BAS TempAV219BASAV220Baud RateAV221INTL CommunicationAV222Intl Baud RateAV223onAER ModeAV224AERtrimAV225O2 MonitoringAV226SmartPlate SetpointAV227SP Pump Out SignalAV228SmartPlate Pmp Unit AddrAV229Remote Disable CodeAV230VSP Pump ModeAV231VSP Pump Adjust TimeAV233VSP Pump Adjust ValueAV245SH SetpointAV246Remote Manager DisableAI300Communication AddressAI301unit StatusAI302Fault CodeAI303Outlet TemperatureAI304FFWD TemperatureAI305Inlet TemperatureAI306Exhaust TemperatureAI307Inlet Air TemperatureAI308Flame StrengthAI309Fire Rate InAI310Fire Rate OutAI311Unit TypeAI312Unit SizeAI313Valve StateAI314Net Remote SetpointAI315Run Cycle UpperAI316Run Cycle LowerAI317Run Hours UpperAI318Run Hours LowerAI319Oxygen LvelAI3500SP OutletAI3501SP Valve PositionAI3502SP SetpointAI3503SP Error #AI3504SP Delta PresAI3505SP DHW InletAI3506SP FlowAI3507SP Boiler Inlet
Integration notes
- From tables 4-3 to 4-6 of the manual (pages 19-22). The manager also serves the stand-alone / client objects of tables 4-1 and 4-2, which match the AERCO Edge [ii] list; they are not repeated here.
- Access follows the table type: AI tables are read only, AV tables read/write.
- BST unit blocks: unit 1 is AI 300-319 (listed); unit n uses the same names at AI 300 + 100 x (n - 1), up to unit 16 = AI 1800-1819.
- SmartPlate blocks: SmartPlate 1 is AI 3500-3507 (listed); SmartPlate n uses AI 3500 + 100 x (n - 1), up to 4000-4007. SP Delta Pres, SP DHW Inlet and SP Flow apply to SmartPlate EV only.
- The manual prints DHW Header Temp twice (AI 120 and AI 126) and Rtn Hdr Temp Sensor twice (AV 215 selector, AV 216 temperature); both are kept. AI 134-151 are not used.
- Columns mark some objects NA for BMK Edge[ii], BMK Edge[i] or Innovation Edge[i] (mostly DHW, VSP pump and SmartPlate objects); check the manual for your model. Trailing colons on names are dropped.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Benchmark / Innovation Edge controller - BST Manager plant objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects
How many BACnet points does the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects have?
This list has 100 BACnet objects: 63 analog inputs, 37 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet points are writable?
37 of the 100 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official AERCO Benchmark / Innovation Edge controller - BST Manager plant objects BACnet documentation?
AERCO does not publish it on its own website. This list comes from Edge Communication Manual for Systems Integrators (OMM-0140J), revision 2025-11-04, a copy hosted by Watts staging media server at https://stagesc10.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/650538-source. Ask AERCO or its representative for the current revision.
What are the minimum BACnet points to integrate the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects?
Start with AV 229 Remote Disable Code (0 = enable plant, 85 = disable plant); AV 200 Plant Remote Setpoint (Plant remote setpoint, 20-245 °F); AV 51 Allow BAS to Write (BAS write permission (0-1)); AI 114 Act Setpt (Active plant setpoint); AI 110 Header Temp (Header temperature); AI 112 BST Fire Rate (Plant firing rate, %); AI 113 Units Ignited (Units firing); AI 108 Units Faulted (Number of units in fault); AI 301 unit Status (Unit 1 status (5 = fault)).
How do I enable BMS control of the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects?
Allow BAS to Write (AV 51, 0-1) controls BAS write access. The plant is disabled by writing 85 to Remote Disable Code (AV 229) and enabled with 0; this needs Allow System Disable = Yes under Advanced Setup > Comm & Network > BAS.
Does the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects need a BACnet heartbeat or have a communication timeout?
Network Timeout (AV 53) is 5-999 s; the manual lists it but these tables do not describe the fallback action.
Can the BMS supply sensor values to the AERCO Benchmark / Innovation Edge controller - BST Manager plant objects?
Header, return header, DHW header and outdoor temperatures can be written by the BAS (AV 214, AV 216, AV 206, AV 218) when their sensor source (AV 213, AV 215, AV 205, AV 217) is set to BAS.
How do I check these points on the real Benchmark / Innovation Edge controller - BST Manager plant objects?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AERCO BACnet points lists
- Digital DHW mixing valve system (water tempering)
AERCO ADMS Smart Water Tempering System
AERCO ADMS digital mixing (water tempering) systems for domestic hot water.
Also known as: ADMS, AERCO ADMS, Smart Water Tempering System, 106902, OMM-0126 - Boiler / water heater controller gateway
AERCO AM Series Dependent boiler / water heater (ProtoNode FPC-N34/N35)
AERCO AM Series boilers or water heaters set up as dependent units of a cascade, read through the AERCO ProtoNode FPC-N34 / FPC-N35.
Also known as: AM Series, AM Dependent, AM Dep, AERCO AM, ProtoNode FPC-N34, FPC-N35 - Boiler / water heater cascade controller gateway
AERCO AM Series Managing boiler / water heater (ProtoNode FPC-N34/N35)
AERCO AM Series boilers or water heaters set up as the managing (or stand-alone) unit of a cascade, read through the AERCO ProtoNode FPC-N34 / FPC-N35.
Also known as: AM Series, AM Manager, AM Mngr, AERCO AM, ProtoNode FPC-N34, FPC-N35 - Boiler controller
AERCO Benchmark E / Edge X
AERCO Benchmark E (BMK E) condensing boilers with the Edge X controller, including BST cascade plants; the table also lists the legacy Benchmark (BMK) Edge equivalents.
Also known as: BMK E, BMKE, Benchmark, Edge X, Edge controller, OMM-0173 - Boiler and water heater plant controller via ProtoNode gateway
AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)
AERCO C-More boilers running on-board BST sequencing and C-More water heaters (KC, Innovation) running WHM, up to 8 units, through the ProtoNode RER SSD profile.
Also known as: C-More, BST, Boiler Sequencing Technology, WHM, Water Heater Management, SSD, Slave/Slave Device, Innovation, KC, Benchmark, ProtoNode RER, 64084, GF-129, OMM-0080 - Boiler controller and plant sequencer via ProtoNode gateway
AERCO C-More boilers with ACS / BMS II (ProtoNode RER)
AERCO boilers with the C-More controller plus an ACS or BMS II plant sequencer, read through the AERCO ProtoNode RER.
Also known as: C-More, C-More controller, ACS, BMS II, BMS, ProtoNode RER, ProtoNode-RER, 64084, FPC-N34, GF-129, OMM-0080 - Boiler and water heater plant gateway (multi-unit)
AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)
A combined AERCO plant of 12 C-More boilers, 4 Modulex boilers, 6 ECS/SmartPlate water heater valves and two BMS II boiler managers on one gateway.
Also known as: AERCO ProtoNode, C-More, Modulex, ECS, SmartPlate, BMS II, AERCO-ProtoNode-Control-Points - Water heater controller via ProtoNode gateway
AERCO ECS and SmartPlate water heaters (ProtoNode RER)
AERCO SmartPlate and ECS (Electric Valve) water heaters, up to four, read through the AERCO ProtoNode RER.
Also known as: ECS, Electronic Control System, SmartPlate, SmartPlate water heater, E Valve, ProtoNode RER, 64084, GF-129, OMM-0080 - Commercial water heater controller
AERCO Edge [ii] water heater controller (standalone / WHM)
AERCO Innovation 1600-2000 water heaters with the Edge [ii] controller, run standalone or as a WHM (Water Heater Management) manager or client.
Also known as: Edge [ii], Edge ii, Edge 2, WHM, Water Heater Management, Centurion, OMM-0176, Innovation 1600-2000 - Boiler controller and plant sequencer via ProtoNode gateway
AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)
AERCO Modulex boilers with a BCM, up to four, plus an ACS or BMS II sequencer, read through the AERCO ProtoNode RER.
Also known as: Modulex, MLX, Modulex E8, BCM, ACS, BMS II, ProtoNode RER, 64084, GF-129, OMM-0080
Source: Edge Communication Manual for Systems Integrators · OMM-0140J · rev. 2025-11-04. Object names, instances and units are reproduced as published; descriptions are our own.