Boiler controller · BACnet points list

AERCO Benchmark E / Edge X BACnet points list

Updated 28 October 2026

Short answer

The Edge X controller on AERCO's Benchmark E boilers talks BACnet IP on its Ethernet port or BACnet MS/TP on its RS-485 port. Standalone and client units expose their own setpoints and readings, while a BST cascade manager also exposes plant-level values and a block of read-only points for every unit in the cascade (up to 16). Only analog inputs (read only) and analog values (read/write) are used.

This page lists 390 BACnet objects for the AERCO Benchmark E / Edge X — 38 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.

Manufacturer
AERCO
Model
Benchmark E / Edge X
Equipment
Boiler controller
Equipment type
Boilers & water heaters
BACnet objects
390 (38 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Application software 1.0 (PICS dated October 2024)
Also known as
BMK E, BMKE, Benchmark, Edge X, Edge controller, OMM-0173
Source document
Edge X Communication Guide for Systems Integrators (Edge X Communication Manual) · OMM-0173E · rev. 2025-06-17
Download CSV 390 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: AERCO Benchmark E / Edge X

Integration in brief

Enable the BAS port in the Edge X Comm & Failsafe menu (BACnet IP on the J5 Ethernet jack or MS/TP on the RS-485 terminals), choose the comm-loss behaviour, then have the BAS write the setpoint. For a cascade, connect the BAS to the BST manager only; it exposes plant values plus a read-only block for each unit. A technician-level password is needed before BAS points are available.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 12Operating ModeSelects constant, remote or outdoor-reset setpointWrite
AV 13Remote SignalSet to BAS so the remote setpoint comes from BACnetWrite
AV 4SetpointUnit temperature setpoint, 35-220 °FWrite
AV 200SetpointPlant setpoint on a BST managerWrite
AI 1Unit StatusStandby / manual / auto / fault stateRead
AI 2Outlet TempOutlet water temperatureRead
AI 0Active Event IDActive event / fault codeRead
AI 108Units FaultedUnits faulted in the cascadeRead

Enable & remote start

On the controller go to Settings > Advanced Setup > Comm & Failsafe and enable BAS; for IP turn on the "BAS (J6)" toggle, which actually uses the J5 jack. The object list has no separate start/stop object: the BAS controls the unit through AV 12 Operating Mode, AV 13 Remote Signal (0 = BAS) and the setpoint in AV 4, or AV 200 on a BST manager. Firing-rate control (Direct Drive) is listed only for legacy BMK units.

Heartbeat & communication loss

The BAS Comm Failsafe setting chooses whether the unit shuts down or runs at a constant setpoint when it loses the BAS (AV 24 Unit Failsafe Mode: 0 = Standby, 1 = Constant Setpt). The BACnet IP screen also has a delay-before-communication-fault setting; its range and default are not given.

Sensors & values from the BMS

AV 85 / AV 213 Supply Header Temp Source and AV 215 return header source can be set to BAS (2), but the object list has no writable header or outdoor temperature value. On BMK E the outdoor sensor source (AV 81 / AV 217) is listed as Direct only.

Network setup

Watch out for

AERCO Benchmark E / Edge X BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

390 of 390 shown
Type
Access
Show
AERCO Benchmark E / Edge X BACnet Points List
DescriptionStates
AV2BAS PasswordPassword for BAS write accessWrite
AVmin4SetpointUnit temperature setpoint (35-220 °F)°FWrite
AV5LanguageDisplay languageWrite0=English (BMK also 1=Spanish, 2=French)
AV6TimeController time (legacy BMK only)Write
AV7DateController date (legacy BMK only)Write
AV8Unit of Measurement BASUnits used on the BAS interfaceWriteEnglish / Metric
AV9Cascade Baud RateCascade (BST/IST/WHM) Modbus baud rateWrite0=9600, 1=19200, 2=38400, 3=57600, 4=115200
AV10Unit TypeAppliance type (legacy BMK only)Write0=KC Boiler, 1=KC Boiler LN, 2=BMK Boiler Std, 3=BMK Blr Std Dual, 4=BMK Boiler LN, 5=BMK Blr LN Dual, 6=KC Water Heater, 7=KC Water Heater LN, 8=Innovation, 9=Innovation N
AV11Unit SizeAppliance size (legacy BMK only)Write0=Spare, 1=600 MBH, 2=800 MBH, 3=1060 MBH, 4=1350 MBH, 5=500 MBH, 6=750 MBH, 7=1000 MBH, 8=1.5 MBTU, 9=1500 MBH, 10=2.0 MBTU, 11=2000 MBH, 12=2500 MBH, 13=3.0 MBTU, 14=3000 MBH, 15=4000 MBH, 16=5000 MBH, 17=6000 MBH
AVmin12Operating ModeHow the unit gets its setpointWrite0=Constant Setpt, 1=Rmt Setpt, 2=Outdoor Reset (BMK: 0=Constant, 1=Remote, 2=Direct Drive, 3=Combination, 4=Outdoor Reset)
AVmin13Remote SignalSource of the remote setpoint signalWrite0=BAS, 1=Analog Input (BMK: 0=4-20mA/1-5V, 1=0-20mA/0-5V, 2=Network, 3=BAS, 4=BST PWM)
AV16Outdoor Sensor On/OffEnables the outdoor air sensorWriteDisable / Enable
AV17Warm Weather Standby TemperatureOutdoor temperature for warm weather standby (BMK: Warm Weather Shtdwn)°FWrite
AV18SH Temperature Control Setpoint Low LimitLowest allowed setpoint (BMK: Setpoint Low Limit)°FWrite
AV19SH Temperature Control Setpoint Hi LimitHighest allowed setpoint (BMK: Setpoint High Limit)°FWrite
AV20Temperature High LimitOutlet temperature high limit°FWrite
AV23Interlocks Aux Delay 2Auxiliary interlock delay (BMK: Auxiliary Delay)sWrite
AV24Unit Failsafe ModeBehaviour when the BAS signal is lostWrite0=Standby, 1=Constant Setpt (BMK: 0=Shutdown, 1=Constant Setpt)
AV26Proportional BandPID proportional band°FWrite
AV27Integral BandPID integral gainWrite
AV28Derivative BandPID derivative time (legacy BMK only)minWrite
AV70BASBAS protocol selection (legacy BMK only)Write0=Off, 1=BACnet MSTP, 2=BACnet IP, 3=Modbus RTU, 4=Modbus TCP
AV71BAS Baud RateBAS serial baud rate (legacy BMK only)Write0=9600, 1=19200, 2=38400, 3=57600
AV81Outdoor Air Temp SensorOutdoor temperature source (BMK: Outdoor Temp Source)WriteDirect (BMK: 0=Network, 1=Direct, 2=BAS)
AV83PLM EnabledEnables power limit management (BMK E only)Write0=Disable, 1=Enable
AV84PLM Power LimitPower limit for PLM (BMK E only)%Write
AV85Supply Header Temp SourceSupply header sensor source (BMK E only)Write0=Off, 1=Direct, 2=BAS
AImin0Active Event IDActive event code (BMK: Message Code)Read
AImin1Unit StatusCurrent unit stateRead0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Direct Drive, 5=Fault, 6=Unit in Demand Delay, 7=Unit Starting (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AImin2Outlet TempOutlet water temperature°FRead
AI3Inlet TempInlet water temperature°FRead
AI5Outdoor Air TempOutdoor air temperature (BMK: Outside Temp)°FRead
AI11Run CyclesTotal burner run cyclesRead
AI13Run HoursTotal run hourshRead
AI16Active Setpoint TempSetpoint currently in use°FRead
AI17PID OutputPID output (legacy BMK only)%Read
AI19BAS Communication AddressBAS network address of the unitRead
AI45Valve Control ModeIsolation valve control mode (BMK: Control Mode)Read0=On/Off (BMK: 0=On/Off, 1=Linear Modulation, 2=Delta T Modulation)
AI46Isolation Feedback ModeIsolation valve feedback enabledReadDisable / Enable
AI47Minimum Signal LevelValve signal minimum (BMK: Open Vlv Control Signal)ReadBMK E: 0-10 V / 0-20 mA (BMK: 0=0mA, 1=4mA, 2=20mA)
AI48Maximum Signal LevelValve signal maximum (BMK: Close Vlv Control Signal)ReadBMK E: 0-10 V / 0-20 mA (BMK: 0=0mA, 1=4mA, 2=20mA)
AI148Serial AlphaSerial number letter (BMK: Unit Alpha)Read0=E, 1=G, 2=H, 3=R, 4=N, 5=A, 6=Z
AI149Serial YearSerial number year (BMK: Unit Year)Read
AI150Serial NumberSerial number digits (BMK: Unit Serial #)Read
AI152Unit ModeStandalone or cascade roleRead0=Standalone, 1=Cascade (BMK: 0=Off/Standalone, 1=Client, 2=Manager)
AI153Unit SizeBenchmark E size (BMK E only)Read0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI154Unit TypeAppliance type (BMK E only)Read0=KC Boiler, 1=KC Boiler LN, 2=BMK Boiler Std, 3=BMK Blr Std Dual, 4=BMK Boiler LN, 5=BMK Blr LN Dual, 6=BMK Inlet Natural Gas, 7=BMK Inlet Dual Fuel, 8=BMK Dual Inlet NGas, 9=BMK Dual Inlet Dual Fuel, 10=SmartPlate, 11=Benchmark E, 12=Other
AI155BAS EnableActive BAS protocol (BMK E only)Read0=Off, 1=BACnet MSTP, 2=BACnet IP
AI156BAS Baud RateBAS MS/TP baud rate (BMK E only)Read0=9600, 1=19200, 2=38400, 4=115200
AI157Power OutputCurrent power output (BMK E only)%Read
AI158Header TempHeader temperature (BMK E only)°FRead
AVmin200SetpointPlant setpoint°FWrite
AV201Setback SetpointPlant setback setpoint°FWrite
AV202Setback Start TimeSetback schedule start timeWrite
AV203Setback Stop TimeSetback schedule stop timeWrite
AV204SH Temperature Control Setback ScheduleEnables the setback scheduleWriteDisable / Enable
AV213Supply Header Temp SourceSupply header sensor sourceWrite0=Off, 1=Direct, 2=BAS
AV215Rtn Hdr Temp SensorReturn header sensor sourceWrite0=Off, 1=Direct, 2=BAS
AV217Outdoor Air Temp SensOutdoor air sensor sourceWriteDirect
AV219BACnet Communication ProtocolBACnet data link in useWrite0=BACnet IP, 1=BACnet MSTP (also printed as 0=Off, 1=BACnet MSTP, 2=BACnet IP)
AV230PLM EnabledEnables plant power limit managementWrite0=Disable, 1=Enable
AV231PLM Power LimitPlant power limit%Write
AI100Unit RoleCascade role of this unitRead0=BST Manager, 1=BST Client
AI101SetpointPlant setpoint°FRead
AI102Setback SetpointPlant setback setpoint°FRead
AI103Setback Start TimeSetback schedule start timeRead
AI104Setback Stop TimeSetback schedule stop timeRead
AI106Average Outlet TempAverage outlet temperature of the plant (BMK: Outlet Temp)°FRead
AI107Units AvailableUnits available to the cascadeRead
AImin108Units FaultedUnits in faultRead
AI109BAS Communication AddressBAS network addressRead
AI110Header TempHeader temperature°FRead
AI111Outdoor Air TemperatureOutdoor air temperature°FRead
AI112Average Power OutputAverage plant power output%Read
AI113Units ActiveUnits currently firingRead
AI114Active SetpointPlant setpoint currently in use°FRead
AI115Gas Next On ThresholdFiring rate that brings on the next gas unit%Read
AI116SH Temperature Control Setpoint Hi LimitHighest allowed plant setpoint°FRead
AI117SH Temperature Control Setpoint Low LimitLowest allowed plant setpoint°FRead
AI118Temperature High LimitPlant temperature high limit°FRead
AI119Operating ModePlant setpoint modeRead0=Constant Setpoint, 1=Rmt Setpt, 2=Outdoor Air Reset
AI120Next Off Valve Pos GasValve position that stages off the next gas unit%Read
AI122Casc Next On Valve Pos ElecValve position that stages on the next electric unit%Read
AI123Power OutputPlant power output%Read
AI124Next Off Valve Pos ElecValve position that stages off the next electric unit%Read
AI126BAS Baud RateBAS MS/TP baud rateRead0=9600, 1=19200, 2=38400, 3=57600, 4=115200
AI300Cascade Unit AddressCascade unit 1: cascade address (BMK: Communication Address)Read
AI301Cascade Client StateCascade unit 1: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI302Active Event IDCascade unit 1: active event code (BMK: Fault Code)Read
AI303Outlet TempCascade unit 1: outlet temperature°FRead
AI305Inlet TempCascade unit 1: inlet temperature°FRead
AI306Exhaust TempCascade unit 1: exhaust temperature (legacy BMK only)°FRead
AI307Inlet Air TempCascade unit 1: inlet air temperature (legacy BMK only)°FRead
AI308Flame StrengthCascade unit 1: flame strength (legacy BMK only)%Read
AI309Fire Rate InCascade unit 1: fire rate in (legacy BMK only)%Read
AI310Fire Rate OutCascade unit 1: fire rate out (legacy BMK only)%Read
AI311Unit TypeCascade unit 1: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI312Unit SizeCascade unit 1: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI313Valve StatusCascade unit 1: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI314Plant SetpointCascade unit 1: plant setpoint seen by the unit°FRead
AI315Run CyclesCascade unit 1: run cycles (BMK: Run Cycle Upper)Read
AI316Run Cycle LowerCascade unit 1: run cycles low word (legacy BMK only)Read
AI317Run HoursCascade unit 1: run hourshRead
AI319Oxygen LevelCascade unit 1: flue oxygen (legacy BMK only)%Read
AI320Power OutputCascade unit 1: power output%Read
AI400Cascade Unit AddressCascade unit 2: cascade address (BMK: Communication Address)Read
AI401Cascade Client StateCascade unit 2: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI402Active Event IDCascade unit 2: active event code (BMK: Fault Code)Read
AI403Outlet TempCascade unit 2: outlet temperature°FRead
AI405Inlet TempCascade unit 2: inlet temperature°FRead
AI406Exhaust TempCascade unit 2: exhaust temperature (legacy BMK only)°FRead
AI407Inlet Air TempCascade unit 2: inlet air temperature (legacy BMK only)°FRead
AI408Flame StrengthCascade unit 2: flame strength (legacy BMK only)%Read
AI409Fire Rate InCascade unit 2: fire rate in (legacy BMK only)%Read
AI410Fire Rate OutCascade unit 2: fire rate out (legacy BMK only)%Read
AI411Unit TypeCascade unit 2: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI412Unit SizeCascade unit 2: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI413Valve StatusCascade unit 2: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI414Plant SetpointCascade unit 2: plant setpoint seen by the unit°FRead
AI415Run CyclesCascade unit 2: run cycles (BMK: Run Cycle Upper)Read
AI416Run Cycle LowerCascade unit 2: run cycles low word (legacy BMK only)Read
AI417Run HoursCascade unit 2: run hourshRead
AI419Oxygen LevelCascade unit 2: flue oxygen (legacy BMK only)%Read
AI420Power OutputCascade unit 2: power output%Read
AI500Cascade Unit AddressCascade unit 3: cascade address (BMK: Communication Address)Read
AI501Cascade Client StateCascade unit 3: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI502Active Event IDCascade unit 3: active event code (BMK: Fault Code)Read
AI503Outlet TempCascade unit 3: outlet temperature°FRead
AI505Inlet TempCascade unit 3: inlet temperature°FRead
AI506Exhaust TempCascade unit 3: exhaust temperature (legacy BMK only)°FRead
AI507Inlet Air TempCascade unit 3: inlet air temperature (legacy BMK only)°FRead
AI508Flame StrengthCascade unit 3: flame strength (legacy BMK only)%Read
AI509Fire Rate InCascade unit 3: fire rate in (legacy BMK only)%Read
AI510Fire Rate OutCascade unit 3: fire rate out (legacy BMK only)%Read
AI511Unit TypeCascade unit 3: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI512Unit SizeCascade unit 3: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI513Valve StatusCascade unit 3: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI514Plant SetpointCascade unit 3: plant setpoint seen by the unit°FRead
AI515Run CyclesCascade unit 3: run cycles (BMK: Run Cycle Upper)Read
AI516Run Cycle LowerCascade unit 3: run cycles low word (legacy BMK only)Read
AI517Run HoursCascade unit 3: run hourshRead
AI519Oxygen LevelCascade unit 3: flue oxygen (legacy BMK only)%Read
AI520Power OutputCascade unit 3: power output%Read
AI600Cascade Unit AddressCascade unit 4: cascade address (BMK: Communication Address)Read
AI601Cascade Client StateCascade unit 4: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI602Active Event IDCascade unit 4: active event code (BMK: Fault Code)Read
AI603Outlet TempCascade unit 4: outlet temperature°FRead
AI605Inlet TempCascade unit 4: inlet temperature°FRead
AI606Exhaust TempCascade unit 4: exhaust temperature (legacy BMK only)°FRead
AI607Inlet Air TempCascade unit 4: inlet air temperature (legacy BMK only)°FRead
AI608Flame StrengthCascade unit 4: flame strength (legacy BMK only)%Read
AI609Fire Rate InCascade unit 4: fire rate in (legacy BMK only)%Read
AI610Fire Rate OutCascade unit 4: fire rate out (legacy BMK only)%Read
AI611Unit TypeCascade unit 4: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI612Unit SizeCascade unit 4: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI613Valve StatusCascade unit 4: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI614Plant SetpointCascade unit 4: plant setpoint seen by the unit°FRead
AI615Run CyclesCascade unit 4: run cycles (BMK: Run Cycle Upper)Read
AI616Run Cycle LowerCascade unit 4: run cycles low word (legacy BMK only)Read
AI617Run HoursCascade unit 4: run hourshRead
AI619Oxygen LevelCascade unit 4: flue oxygen (legacy BMK only)%Read
AI620Power OutputCascade unit 4: power output%Read
AI700Cascade Unit AddressCascade unit 5: cascade address (BMK: Communication Address)Read
AI701Cascade Client StateCascade unit 5: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI702Active Event IDCascade unit 5: active event code (BMK: Fault Code)Read
AI703Outlet TempCascade unit 5: outlet temperature°FRead
AI705Inlet TempCascade unit 5: inlet temperature°FRead
AI706Exhaust TempCascade unit 5: exhaust temperature (legacy BMK only)°FRead
AI707Inlet Air TempCascade unit 5: inlet air temperature (legacy BMK only)°FRead
AI708Flame StrengthCascade unit 5: flame strength (legacy BMK only)%Read
AI709Fire Rate InCascade unit 5: fire rate in (legacy BMK only)%Read
AI710Fire Rate OutCascade unit 5: fire rate out (legacy BMK only)%Read
AI711Unit TypeCascade unit 5: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI712Unit SizeCascade unit 5: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI713Valve StatusCascade unit 5: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI714Plant SetpointCascade unit 5: plant setpoint seen by the unit°FRead
AI715Run CyclesCascade unit 5: run cycles (BMK: Run Cycle Upper)Read
AI716Run Cycle LowerCascade unit 5: run cycles low word (legacy BMK only)Read
AI717Run HoursCascade unit 5: run hourshRead
AI719Oxygen LevelCascade unit 5: flue oxygen (legacy BMK only)%Read
AI720Power OutputCascade unit 5: power output%Read
AI800Cascade Unit AddressCascade unit 6: cascade address (BMK: Communication Address)Read
AI801Cascade Client StateCascade unit 6: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI802Active Event IDCascade unit 6: active event code (BMK: Fault Code)Read
AI803Outlet TempCascade unit 6: outlet temperature°FRead
AI805Inlet TempCascade unit 6: inlet temperature°FRead
AI806Exhaust TempCascade unit 6: exhaust temperature (legacy BMK only)°FRead
AI807Inlet Air TempCascade unit 6: inlet air temperature (legacy BMK only)°FRead
AI808Flame StrengthCascade unit 6: flame strength (legacy BMK only)%Read
AI809Fire Rate InCascade unit 6: fire rate in (legacy BMK only)%Read
AI810Fire Rate OutCascade unit 6: fire rate out (legacy BMK only)%Read
AI811Unit TypeCascade unit 6: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI812Unit SizeCascade unit 6: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI813Valve StatusCascade unit 6: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI814Plant SetpointCascade unit 6: plant setpoint seen by the unit°FRead
AI815Run CyclesCascade unit 6: run cycles (BMK: Run Cycle Upper)Read
AI816Run Cycle LowerCascade unit 6: run cycles low word (legacy BMK only)Read
AI817Run HoursCascade unit 6: run hourshRead
AI819Oxygen LevelCascade unit 6: flue oxygen (legacy BMK only)%Read
AI820Power OutputCascade unit 6: power output%Read
AI900Cascade Unit AddressCascade unit 7: cascade address (BMK: Communication Address)Read
AI901Cascade Client StateCascade unit 7: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI902Active Event IDCascade unit 7: active event code (BMK: Fault Code)Read
AI903Outlet TempCascade unit 7: outlet temperature°FRead
AI905Inlet TempCascade unit 7: inlet temperature°FRead
AI906Exhaust TempCascade unit 7: exhaust temperature (legacy BMK only)°FRead
AI907Inlet Air TempCascade unit 7: inlet air temperature (legacy BMK only)°FRead
AI908Flame StrengthCascade unit 7: flame strength (legacy BMK only)%Read
AI909Fire Rate InCascade unit 7: fire rate in (legacy BMK only)%Read
AI910Fire Rate OutCascade unit 7: fire rate out (legacy BMK only)%Read
AI911Unit TypeCascade unit 7: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI912Unit SizeCascade unit 7: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI913Valve StatusCascade unit 7: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI914Plant SetpointCascade unit 7: plant setpoint seen by the unit°FRead
AI915Run CyclesCascade unit 7: run cycles (BMK: Run Cycle Upper)Read
AI916Run Cycle LowerCascade unit 7: run cycles low word (legacy BMK only)Read
AI917Run HoursCascade unit 7: run hourshRead
AI919Oxygen LevelCascade unit 7: flue oxygen (legacy BMK only)%Read
AI920Power OutputCascade unit 7: power output%Read
AI1000Cascade Unit AddressCascade unit 8: cascade address (BMK: Communication Address)Read
AI1001Cascade Client StateCascade unit 8: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1002Active Event IDCascade unit 8: active event code (BMK: Fault Code)Read
AI1003Outlet TempCascade unit 8: outlet temperature°FRead
AI1005Inlet TempCascade unit 8: inlet temperature°FRead
AI1006Exhaust TempCascade unit 8: exhaust temperature (legacy BMK only)°FRead
AI1007Inlet Air TempCascade unit 8: inlet air temperature (legacy BMK only)°FRead
AI1008Flame StrengthCascade unit 8: flame strength (legacy BMK only)%Read
AI1009Fire Rate InCascade unit 8: fire rate in (legacy BMK only)%Read
AI1010Fire Rate OutCascade unit 8: fire rate out (legacy BMK only)%Read
AI1011Unit TypeCascade unit 8: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1012Unit SizeCascade unit 8: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1013Valve StatusCascade unit 8: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1014Plant SetpointCascade unit 8: plant setpoint seen by the unit°FRead
AI1015Run CyclesCascade unit 8: run cycles (BMK: Run Cycle Upper)Read
AI1016Run Cycle LowerCascade unit 8: run cycles low word (legacy BMK only)Read
AI1017Run HoursCascade unit 8: run hourshRead
AI1019Oxygen LevelCascade unit 8: flue oxygen (legacy BMK only)%Read
AI1020Power OutputCascade unit 8: power output%Read
AI1100Cascade Unit AddressCascade unit 9: cascade address (BMK: Communication Address)Read
AI1101Cascade Client StateCascade unit 9: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1102Active Event IDCascade unit 9: active event code (BMK: Fault Code)Read
AI1103Outlet TempCascade unit 9: outlet temperature°FRead
AI1105Inlet TempCascade unit 9: inlet temperature°FRead
AI1106Exhaust TempCascade unit 9: exhaust temperature (legacy BMK only)°FRead
AI1107Inlet Air TempCascade unit 9: inlet air temperature (legacy BMK only)°FRead
AI1108Flame StrengthCascade unit 9: flame strength (legacy BMK only)%Read
AI1109Fire Rate InCascade unit 9: fire rate in (legacy BMK only)%Read
AI1110Fire Rate OutCascade unit 9: fire rate out (legacy BMK only)%Read
AI1111Unit TypeCascade unit 9: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1112Unit SizeCascade unit 9: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1113Valve StatusCascade unit 9: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1114Plant SetpointCascade unit 9: plant setpoint seen by the unit°FRead
AI1115Run CyclesCascade unit 9: run cycles (BMK: Run Cycle Upper)Read
AI1116Run Cycle LowerCascade unit 9: run cycles low word (legacy BMK only)Read
AI1117Run HoursCascade unit 9: run hourshRead
AI1119Oxygen LevelCascade unit 9: flue oxygen (legacy BMK only)%Read
AI1120Power OutputCascade unit 9: power output%Read
AI1200Cascade Unit AddressCascade unit 10: cascade address (BMK: Communication Address)Read
AI1201Cascade Client StateCascade unit 10: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1202Active Event IDCascade unit 10: active event code (BMK: Fault Code)Read
AI1203Outlet TempCascade unit 10: outlet temperature°FRead
AI1205Inlet TempCascade unit 10: inlet temperature°FRead
AI1206Exhaust TempCascade unit 10: exhaust temperature (legacy BMK only)°FRead
AI1207Inlet Air TempCascade unit 10: inlet air temperature (legacy BMK only)°FRead
AI1208Flame StrengthCascade unit 10: flame strength (legacy BMK only)%Read
AI1209Fire Rate InCascade unit 10: fire rate in (legacy BMK only)%Read
AI1210Fire Rate OutCascade unit 10: fire rate out (legacy BMK only)%Read
AI1211Unit TypeCascade unit 10: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1212Unit SizeCascade unit 10: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1213Valve StatusCascade unit 10: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1214Plant SetpointCascade unit 10: plant setpoint seen by the unit°FRead
AI1215Run CyclesCascade unit 10: run cycles (BMK: Run Cycle Upper)Read
AI1216Run Cycle LowerCascade unit 10: run cycles low word (legacy BMK only)Read
AI1217Run HoursCascade unit 10: run hourshRead
AI1219Oxygen LevelCascade unit 10: flue oxygen (legacy BMK only)%Read
AI1220Power OutputCascade unit 10: power output%Read
AI1300Cascade Unit AddressCascade unit 11: cascade address (BMK: Communication Address)Read
AI1301Cascade Client StateCascade unit 11: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1302Active Event IDCascade unit 11: active event code (BMK: Fault Code)Read
AI1303Outlet TempCascade unit 11: outlet temperature°FRead
AI1305Inlet TempCascade unit 11: inlet temperature°FRead
AI1306Exhaust TempCascade unit 11: exhaust temperature (legacy BMK only)°FRead
AI1307Inlet Air TempCascade unit 11: inlet air temperature (legacy BMK only)°FRead
AI1308Flame StrengthCascade unit 11: flame strength (legacy BMK only)%Read
AI1309Fire Rate InCascade unit 11: fire rate in (legacy BMK only)%Read
AI1310Fire Rate OutCascade unit 11: fire rate out (legacy BMK only)%Read
AI1311Unit TypeCascade unit 11: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1312Unit SizeCascade unit 11: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1313Valve StatusCascade unit 11: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1314Plant SetpointCascade unit 11: plant setpoint seen by the unit°FRead
AI1315Run CyclesCascade unit 11: run cycles (BMK: Run Cycle Upper)Read
AI1316Run Cycle LowerCascade unit 11: run cycles low word (legacy BMK only)Read
AI1317Run HoursCascade unit 11: run hourshRead
AI1319Oxygen LevelCascade unit 11: flue oxygen (legacy BMK only)%Read
AI1320Power OutputCascade unit 11: power output%Read
AI1400Cascade Unit AddressCascade unit 12: cascade address (BMK: Communication Address)Read
AI1401Cascade Client StateCascade unit 12: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1402Active Event IDCascade unit 12: active event code (BMK: Fault Code)Read
AI1403Outlet TempCascade unit 12: outlet temperature°FRead
AI1405Inlet TempCascade unit 12: inlet temperature°FRead
AI1406Exhaust TempCascade unit 12: exhaust temperature (legacy BMK only)°FRead
AI1407Inlet Air TempCascade unit 12: inlet air temperature (legacy BMK only)°FRead
AI1408Flame StrengthCascade unit 12: flame strength (legacy BMK only)%Read
AI1409Fire Rate InCascade unit 12: fire rate in (legacy BMK only)%Read
AI1410Fire Rate OutCascade unit 12: fire rate out (legacy BMK only)%Read
AI1411Unit TypeCascade unit 12: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1412Unit SizeCascade unit 12: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1413Valve StatusCascade unit 12: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1414Plant SetpointCascade unit 12: plant setpoint seen by the unit°FRead
AI1415Run CyclesCascade unit 12: run cycles (BMK: Run Cycle Upper)Read
AI1416Run Cycle LowerCascade unit 12: run cycles low word (legacy BMK only)Read
AI1417Run HoursCascade unit 12: run hourshRead
AI1419Oxygen LevelCascade unit 12: flue oxygen (legacy BMK only)%Read
AI1420Power OutputCascade unit 12: power output%Read
AI1500Cascade Unit AddressCascade unit 13: cascade address (BMK: Communication Address)Read
AI1501Cascade Client StateCascade unit 13: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1502Active Event IDCascade unit 13: active event code (BMK: Fault Code)Read
AI1503Outlet TempCascade unit 13: outlet temperature°FRead
AI1505Inlet TempCascade unit 13: inlet temperature°FRead
AI1506Exhaust TempCascade unit 13: exhaust temperature (legacy BMK only)°FRead
AI1507Inlet Air TempCascade unit 13: inlet air temperature (legacy BMK only)°FRead
AI1508Flame StrengthCascade unit 13: flame strength (legacy BMK only)%Read
AI1509Fire Rate InCascade unit 13: fire rate in (legacy BMK only)%Read
AI1510Fire Rate OutCascade unit 13: fire rate out (legacy BMK only)%Read
AI1511Unit TypeCascade unit 13: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1512Unit SizeCascade unit 13: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1513Valve StatusCascade unit 13: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1514Plant SetpointCascade unit 13: plant setpoint seen by the unit°FRead
AI1515Run CyclesCascade unit 13: run cycles (BMK: Run Cycle Upper)Read
AI1516Run Cycle LowerCascade unit 13: run cycles low word (legacy BMK only)Read
AI1517Run HoursCascade unit 13: run hourshRead
AI1519Oxygen LevelCascade unit 13: flue oxygen (legacy BMK only)%Read
AI1520Power OutputCascade unit 13: power output%Read
AI1600Cascade Unit AddressCascade unit 14: cascade address (BMK: Communication Address)Read
AI1601Cascade Client StateCascade unit 14: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1602Active Event IDCascade unit 14: active event code (BMK: Fault Code)Read
AI1603Outlet TempCascade unit 14: outlet temperature°FRead
AI1605Inlet TempCascade unit 14: inlet temperature°FRead
AI1606Exhaust TempCascade unit 14: exhaust temperature (legacy BMK only)°FRead
AI1607Inlet Air TempCascade unit 14: inlet air temperature (legacy BMK only)°FRead
AI1608Flame StrengthCascade unit 14: flame strength (legacy BMK only)%Read
AI1609Fire Rate InCascade unit 14: fire rate in (legacy BMK only)%Read
AI1610Fire Rate OutCascade unit 14: fire rate out (legacy BMK only)%Read
AI1611Unit TypeCascade unit 14: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1612Unit SizeCascade unit 14: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1613Valve StatusCascade unit 14: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1614Plant SetpointCascade unit 14: plant setpoint seen by the unit°FRead
AI1615Run CyclesCascade unit 14: run cycles (BMK: Run Cycle Upper)Read
AI1616Run Cycle LowerCascade unit 14: run cycles low word (legacy BMK only)Read
AI1617Run HoursCascade unit 14: run hourshRead
AI1619Oxygen LevelCascade unit 14: flue oxygen (legacy BMK only)%Read
AI1620Power OutputCascade unit 14: power output%Read
AI1700Cascade Unit AddressCascade unit 15: cascade address (BMK: Communication Address)Read
AI1701Cascade Client StateCascade unit 15: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1702Active Event IDCascade unit 15: active event code (BMK: Fault Code)Read
AI1703Outlet TempCascade unit 15: outlet temperature°FRead
AI1705Inlet TempCascade unit 15: inlet temperature°FRead
AI1706Exhaust TempCascade unit 15: exhaust temperature (legacy BMK only)°FRead
AI1707Inlet Air TempCascade unit 15: inlet air temperature (legacy BMK only)°FRead
AI1708Flame StrengthCascade unit 15: flame strength (legacy BMK only)%Read
AI1709Fire Rate InCascade unit 15: fire rate in (legacy BMK only)%Read
AI1710Fire Rate OutCascade unit 15: fire rate out (legacy BMK only)%Read
AI1711Unit TypeCascade unit 15: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1712Unit SizeCascade unit 15: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1713Valve StatusCascade unit 15: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1714Plant SetpointCascade unit 15: plant setpoint seen by the unit°FRead
AI1715Run CyclesCascade unit 15: run cycles (BMK: Run Cycle Upper)Read
AI1716Run Cycle LowerCascade unit 15: run cycles low word (legacy BMK only)Read
AI1717Run HoursCascade unit 15: run hourshRead
AI1719Oxygen LevelCascade unit 15: flue oxygen (legacy BMK only)%Read
AI1720Power OutputCascade unit 15: power output%Read
AI1800Cascade Unit AddressCascade unit 16: cascade address (BMK: Communication Address)Read
AI1801Cascade Client StateCascade unit 16: unit state (BMK: Unit Status)Read0=Disabled, 1=Standby, 2=Manual Mode, 3=Automatic Mode, 4=Unit Fault, 5=Unit In Demand Delay, 6=Unit Starting, 8=Comm Error (BMK: 0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault)
AI1802Active Event IDCascade unit 16: active event code (BMK: Fault Code)Read
AI1803Outlet TempCascade unit 16: outlet temperature°FRead
AI1805Inlet TempCascade unit 16: inlet temperature°FRead
AI1806Exhaust TempCascade unit 16: exhaust temperature (legacy BMK only)°FRead
AI1807Inlet Air TempCascade unit 16: inlet air temperature (legacy BMK only)°FRead
AI1808Flame StrengthCascade unit 16: flame strength (legacy BMK only)%Read
AI1809Fire Rate InCascade unit 16: fire rate in (legacy BMK only)%Read
AI1810Fire Rate OutCascade unit 16: fire rate out (legacy BMK only)%Read
AI1811Unit TypeCascade unit 16: appliance type codeReadBMK E: 0=KC Boiler ... 11=Benchmark E, 12=Other (same list as AI 154)
AI1812Unit SizeCascade unit 16: appliance size codeReadBMK E: 0=216kW, 1=360kW, 2=432kW, 3=576kW, 4=684kW
AI1813Valve StatusCascade unit 16: isolation valve statusRead0=Off, 1=Closed, 2=Open, 3=Partial Open/Closed, 4=Closing, 5=Opening, 6=Failed to Close, 7=Failed to Open, 8=Defaulted Closed
AI1814Plant SetpointCascade unit 16: plant setpoint seen by the unit°FRead
AI1815Run CyclesCascade unit 16: run cycles (BMK: Run Cycle Upper)Read
AI1816Run Cycle LowerCascade unit 16: run cycles low word (legacy BMK only)Read
AI1817Run HoursCascade unit 16: run hourshRead
AI1819Oxygen LevelCascade unit 16: flue oxygen (legacy BMK only)%Read
AI1820Power OutputCascade unit 16: power output%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Benchmark E / Edge X and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AERCO Benchmark E / Edge X

How many BACnet points does the AERCO Benchmark E / Edge X have?

This list has 390 BACnet objects: 352 analog inputs, 38 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AERCO Benchmark E / Edge X BACnet points are writable?

38 of the 390 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AERCO Benchmark E / Edge X BACnet documentation?

The source is Edge X Communication Guide for Systems Integrators (Edge X Communication Manual) (OMM-0173E), revision 2025-06-17, published free by AERCO at https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/664721-source/638954248340000000/omm-0173-edge-x-communication-manual-6-17-25.pdf.

What are the minimum BACnet points to integrate the AERCO Benchmark E / Edge X?

Start with AV 12 Operating Mode (Selects constant, remote or outdoor-reset setpoint); AV 13 Remote Signal (Set to BAS so the remote setpoint comes from BACnet); AV 4 Setpoint (Unit temperature setpoint, 35-220 °F); AV 200 Setpoint (Plant setpoint on a BST manager); AI 1 Unit Status (Standby / manual / auto / fault state); AI 2 Outlet Temp (Outlet water temperature); AI 0 Active Event ID (Active event / fault code); AI 108 Units Faulted (Units faulted in the cascade).

How do I enable BMS control of the AERCO Benchmark E / Edge X?

On the controller go to Settings > Advanced Setup > Comm & Failsafe and enable BAS; for IP turn on the "BAS (J6)" toggle, which actually uses the J5 jack. The object list has no separate start/stop object: the BAS controls the unit through AV 12 Operating Mode, AV 13 Remote Signal (0 = BAS) and the setpoint in AV 4, or AV 200 on a BST manager. Firing-rate control (Direct Drive) is listed only for legacy BMK units.

Does the AERCO Benchmark E / Edge X need a BACnet heartbeat or have a communication timeout?

The BAS Comm Failsafe setting chooses whether the unit shuts down or runs at a constant setpoint when it loses the BAS (AV 24 Unit Failsafe Mode: 0 = Standby, 1 = Constant Setpt). The BACnet IP screen also has a delay-before-communication-fault setting; its range and default are not given.

Can the BMS supply sensor values to the AERCO Benchmark E / Edge X?

AV 85 / AV 213 Supply Header Temp Source and AV 215 return header source can be set to BAS (2), but the object list has no writable header or outdoor temperature value. On BMK E the outdoor sensor source (AV 81 / AV 217) is listed as Direct only.

How do I check these points on the real Benchmark E / Edge X?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AERCO BACnet points lists

Source: Edge X Communication Guide for Systems Integrators (Edge X Communication Manual) · OMM-0173E · rev. 2025-06-17. Object names, instances and units are reproduced as published; descriptions are our own.