Boiler controller and plant sequencer via ProtoNode gateway · BACnet points list

AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) BACnet points list

Updated 28 October 2026

Short answer

The AERCO ProtoNode RER profile for four Modulex boilers with BCM controllers and one ACS or BMS II serves 54 analog values on BACnet IP or BACnet MS/TP. Each Modulex has modulation, setpoint, temperature, status and error values plus a writable requested outlet temperature and direct-drive modulation; the ACS/BMS II adds plant header values and a writable network header setpoint.

This page lists 54 BACnet objects for the AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.

Manufacturer
AERCO
Model
Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)
Equipment
Boiler controller and plant sequencer via ProtoNode gateway
Equipment type
Boilers & water heaters
BACnet objects
54 (9 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
Node_Offset + A-bank DIP switch value (MAC); the manual's example uses Node_Offset 50,000
Also known as
Modulex, MLX, Modulex E8, BCM, ACS, BMS II, ProtoNode RER, 64084, GF-129, OMM-0080
Source document
AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 · OMM-0080_0H · rev. 2014-11-06
Download CSV 54 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)

Integration in brief

Set S0 and S1 On (S2, S3, A1 Off) for the BACnet profile with 4 Modulex and 1 ACS/BMS II, set each BCM's address DIP switches to 1-4 and the ACS/BMS II to Modbus address 128. Plant setpoint goes to AV 33 on the ACS/BMS II; each Modulex also has a writable requested outlet temperature and a direct-drive modulation value.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 3303-Net Header Set TempPlant header setpoint via ACS/BMS II, 40-220 °FWrite
AV 13603-Req Outlet TempModulex 1 requested outlet temperatureWrite
AV 13704-Net Direct DriveModulex 1 modulation command, 0-100 %Write
AV 14108-Unit StatusModulex 1 status: 1 standby, 3 fired, 5 faultRead
AV 3404-Header TempHeader water temperature, °FRead
AV 13906-Flow Sens TempModulex 1 flow (outlet) temperatureRead
AV 13401-Act Mod LevModulex 1 actual modulation, %Read
AV 111-Error CodeModulex 1 error code and faulted deviceRead
AV 3606-Display CodeACS/BMS II fault bit fieldRead

Enable & remote start

No start/stop object. The ACS/BMS II takes the plant setpoint from AV 33 when Header Set Mode = Remote Setpt and Remote Signal = Network. Each Modulex has writable 03-Req Outlet Temp and 04-Net Direct Drive values; the manual lists the BCM setup as the same as monitor-only.

Heartbeat & communication loss

The BAS must write the setpoint at least three times within the ACS/BMS II Network Timeout (default 30 s, 5-240 s).

Network setup

Watch out for

AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

54 of 54 shown
Type
Analog
Access
Show
AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) BACnet Points List
DescriptionStates
AV3101-Fire Rate OutACS/BMS II: plant fire rate output (0-100)%Read
AV3202-Header Set TempACS/BMS II: header setpoint in use (40-220)°FRead
AVmin3303-Net Header Set TempACS/BMS II: network header setpoint (40-220)°FWrite
AVmin3404-Header TempACS/BMS II: header temperature (40-220)°FRead
AV3505-Outside Air TempACS/BMS II: outdoor air temperature (-60 to 120)°FRead
AVmin3606-Display CodeACS/BMS II: fault/message bit fieldReadBit 0=Outside air sensor error, Bit 1=Header sensor error, Bit 2=Interlock 1 error, Bit 3=Interlock 2 error, Bit 4=Indoor air/return sensor error, Bit 5=4-20 mA input error
AV3707-Num Boilers FiredACS/BMS II: number of boilers firingRead
AV3808-Num Boilers OnlineACS/BMS II: number of boilers on lineRead
AV3909-Last Blr FiredACS/BMS II: last boiler firedRead
AV2618-Net Blr 1 StatusACS/BMS II: status of network boiler 1Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV2719-Net Blr 2 StatusACS/BMS II: status of network boiler 2Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV4720-Net Blr 3 StatusACS/BMS II: status of network boiler 3Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV4921-Net Blr 4 StatusACS/BMS II: status of network boiler 4Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV17322-Return TempACS/BMS II: return temperature°FRead
AVmin13401-Act Mod LevModulex 1: actual modulation level (0-100)%Read
AV13502-Target SetpointModulex 1: target setpoint (32-185)°FRead
AVmin13603-Req Outlet TempModulex 1: requested outlet temperature setpoint (32-185)°FWrite
AVmin13704-Net Direct DriveModulex 1: direct drive modulation level command (0-100)%Write
AV13805-Mod Lev InModulex 1: modulation level from cascade manager (0-100)%Read
AVmin13906-Flow Sens TempModulex 1: flow sensor temperature (14-212)°FRead
AV14007-Display CodeModulex 1: status and error codeRead2=Standby, 8=High temp switch open, 10=Low gas pressure switch open, 18=Air flow switch open during ignition, 23=Flame loss during run, 32=Residual flame, 38=Other conditions, 42=Outlet (flow) temp sensor fault
AVmin111-Error CodeModulex 1: error code; low byte code, high byte deviceRead
AVmin14108-Unit StatusModulex 1: unit statusRead1=Standby, 3=Fired, 5=Fault
AV209-Ret Flow TempModulex 1: return flow temperature (32-212)°FRead
AV14401-Act Mod LevModulex 2: actual modulation level (0-100)%Read
AV14502-Target SetpointModulex 2: target setpoint (32-185)°FRead
AV14603-Req Outlet TempModulex 2: requested outlet temperature setpoint (32-185)°FWrite
AV14704-Net Direct DriveModulex 2: direct drive modulation level command (0-100)%Write
AV14805-Mod Lev InModulex 2: modulation level from cascade manager (0-100)%Read
AV14906-Flow Sens TempModulex 2: flow sensor temperature (14-212)°FRead
AV15007-Display CodeModulex 2: status and error codeRead2=Standby, 8=High temp switch open, 10=Low gas pressure switch open, 18=Air flow switch open during ignition, 23=Flame loss during run, 32=Residual flame, 38=Other conditions, 42=Outlet (flow) temp sensor fault
AV411-Error CodeModulex 2: error code; low byte code, high byte deviceRead
AV15108-Unit StatusModulex 2: unit statusRead1=Standby, 3=Fired, 5=Fault
AV509-Ret Flow TempModulex 2: return flow temperature (32-212)°FRead
AV1801-Act Mod LevModulex 3: actual modulation level (0-100)%Read
AV1902-Target SetpointModulex 3: target setpoint (32-185)°FRead
AV2003-Req Outlet TempModulex 3: requested outlet temperature setpoint (32-185)°FWrite
AV2104-Net Direct DriveModulex 3: direct drive modulation level command (0-100)%Write
AV2205-Mod Lev InModulex 3: modulation level from cascade manager (0-100)%Read
AV2306-Flow Sens TempModulex 3: flow sensor temperature (14-212)°FRead
AV2407-Display CodeModulex 3: status and error codeRead2=Standby, 8=High temp switch open, 10=Low gas pressure switch open, 18=Air flow switch open during ignition, 23=Flame loss during run, 32=Residual flame, 38=Other conditions, 42=Outlet (flow) temp sensor fault
AV711-Error CodeModulex 3: error code; low byte code, high byte deviceRead
AV2508-Unit StatusModulex 3: unit statusRead1=Standby, 3=Fired, 5=Fault
AV809-Ret Flow TempModulex 3: return flow temperature (32-212)°FRead
AV2801-Act Mod LevModulex 4: actual modulation level (0-100)%Read
AV2902-Target SetpointModulex 4: target setpoint (32-185)°FRead
AV3003-Req Outlet TempModulex 4: requested outlet temperature setpoint (32-185)°FWrite
AV4204-Net Direct DriveModulex 4: direct drive modulation level command (0-100)%Write
AV4305-Mod Lev InModulex 4: modulation level from cascade manager (0-100)%Read
AV4406-Flow Sens TempModulex 4: flow sensor temperature (14-212)°FRead
AV4507-Display CodeModulex 4: status and error codeRead2=Standby, 8=High temp switch open, 10=Low gas pressure switch open, 18=Air flow switch open during ignition, 23=Flame loss during run, 32=Residual flame, 38=Other conditions, 42=Outlet (flow) temp sensor fault
AV1011-Error CodeModulex 4: error code; low byte code, high byte deviceRead
AV4608-Unit StatusModulex 4: unit statusRead1=Standby, 3=Fired, 5=Fault
AV1109-Ret Flow TempModulex 4: return flow temperature (32-212)°FRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)

How many BACnet points does the AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) have?

This list has 54 BACnet objects: 54 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) BACnet points are writable?

9 of the 54 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) BACnet documentation?

The source is AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 (OMM-0080_0H), revision 2014-11-06, published free by AERCO at https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/58249-source/637395359810000000/omm-0080-0h-gf-129-protonode-ler-rer-11-06-14.pdf.

What are the minimum BACnet points to integrate the AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)?

Start with AV 33 03-Net Header Set Temp (Plant header setpoint via ACS/BMS II, 40-220 °F); AV 136 03-Req Outlet Temp (Modulex 1 requested outlet temperature); AV 137 04-Net Direct Drive (Modulex 1 modulation command, 0-100 %); AV 141 08-Unit Status (Modulex 1 status: 1 standby, 3 fired, 5 fault); AV 34 04-Header Temp (Header water temperature, °F); AV 139 06-Flow Sens Temp (Modulex 1 flow (outlet) temperature); AV 134 01-Act Mod Lev (Modulex 1 actual modulation, %); AV 1 11-Error Code (Modulex 1 error code and faulted device); AV 36 06-Display Code (ACS/BMS II fault bit field).

How do I enable BMS control of the AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)?

No start/stop object. The ACS/BMS II takes the plant setpoint from AV 33 when Header Set Mode = Remote Setpt and Remote Signal = Network. Each Modulex has writable 03-Req Outlet Temp and 04-Net Direct Drive values; the manual lists the BCM setup as the same as monitor-only.

Does the AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER) need a BACnet heartbeat or have a communication timeout?

The BAS must write the setpoint at least three times within the ACS/BMS II Network Timeout (default 30 s, 5-240 s).

How do I check these points on the real Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AERCO BACnet points lists