Boiler controller and plant sequencer via ProtoNode gateway · BACnet points list

AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet points list

Updated 28 October 2026

Short answer

The AERCO ProtoNode RER reads C-More boiler controllers and an ACS or BMS II sequencer over Modbus RTU and serves them as one BACnet IP or BACnet MS/TP device, using a DIP-selected profile for 4, 8 or 12 C-Mores. This file follows the 12-boiler profile: 11 values per boiler plus 30 plant values from the ACS/BMS II. All objects are analog values; only the network setpoints are writable.

This page lists 162 BACnet objects for the AERCO C-More boilers with ACS / BMS II (ProtoNode RER) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.

Manufacturer
AERCO
Model
C-More boilers with ACS / BMS II (ProtoNode RER)
Equipment
Boiler controller and plant sequencer via ProtoNode gateway
Equipment type
Boilers & water heaters
BACnet objects
162 (13 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
Node_Offset + A-bank DIP switch value (MAC); the manual's example uses Node_Offset 50,000
Also known as
C-More, C-More controller, ACS, BMS II, BMS, ProtoNode RER, ProtoNode-RER, 64084, FPC-N34, GF-129, OMM-0080
Source document
AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 · OMM-0080_0H · rev. 2014-11-06
Download CSV 162 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: AERCO C-More boilers with ACS / BMS II (ProtoNode RER)

Integration in brief

Set the ProtoNode S-bank DIP switches to the BACnet profile for the number of C-Mores, give each C-More a Comm Address (1-12) and the ACS/BMS II Modbus address 128, then write the setpoint: 03-Net Header Set Temp on the ACS/BMS II for plant control, or each boiler's 03-Net Remote Setpt. The BAS must keep rewriting the setpoint, at least three times per network timeout.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 3303-Net Header Set TempPlant header setpoint via ACS/BMS II, 40-220 °FWrite
AV 2403-Net Remote SetptBoiler 1 network setpoint, 40-220 °FWrite
AV 2308-Unit StatusBoiler 1 status; 5 = FaultRead
AV 3404-Header TempHeader water temperature, °FRead
AV 2906-Outlet TempBoiler 1 outlet water temperature, °FRead
AV 2601-Fire Rate OutBoiler 1 fire rate, %Read
AV 2207-Display CodeBoiler 1 status/fault message codeRead
AV 3606-Display CodeACS/BMS II fault bit fieldRead

Enable & remote start

No start/stop object. For plant control set the ACS/BMS II to Header Set Mode = Remote Setpt and Remote Signal = Network, then write AV 33. For a single C-More set Boiler Mode = Remote Setpt and Remote Signal = Network, then write its 03-Net Remote Setpt. Monitor-only needs just the Modbus address and 9600 baud.

Heartbeat & communication loss

The BAS must write the setpoint at least three times within the unit's Network Timeout or the unit stops using it. Defaults are 30 s on C-More (5-999 s, Configuration menu), ACS (5-240 s) and BMS II (5-240 s, RS-232 menu).

Network setup

Watch out for

AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

162 of 162 shown
Type
Analog
Access
Show
AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet Points List
DescriptionStates
AVmin2601-Fire Rate OutBoiler 1: fire rate output (0-100)%Read
AV2702-Active SetpointBoiler 1: setpoint in use (40-220)°FRead
AVmin2403-Net Remote SetptBoiler 1: network remote setpoint (40-220)°FWrite
AV2805-Fire Rate InBoiler 1: fire rate input (0-100)%Read
AVmin2906-Outlet TempBoiler 1: outlet water temperature (30-245)°FRead
AVmin2207-Display CodeBoiler 1: status/fault message code (1-48, see manual)Read
AVmin2308-Unit StatusBoiler 1: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV4209-Run CyclesBoiler 1: run cycle count (0-999,999)Read
AV4310-Run HoursBoiler 1: run hours (0-999,999)hRead
AV16111-OxygenBoiler 1: flue O2 level (0-25)%Read
AV18112-Exhaust TempBoiler 1: exhaust temperature (50-550)°FRead
AV3001-Fire Rate OutBoiler 2: fire rate output (0-100)%Read
AV4602-Active SetpointBoiler 2: setpoint in use (40-220)°FRead
AV4703-Net Remote SetptBoiler 2: network remote setpoint (40-220)°FWrite
AV5005-Fire Rate InBoiler 2: fire rate input (0-100)%Read
AV5106-Outlet TempBoiler 2: outlet water temperature (30-245)°FRead
AV5207-Display CodeBoiler 2: status/fault message code (1-48, see manual)Read
AV5308-Unit StatusBoiler 2: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV4409-Run CyclesBoiler 2: run cycle count (0-999,999)Read
AV4510-Run HoursBoiler 2: run hours (0-999,999)hRead
AV16211-OxygenBoiler 2: flue O2 level (0-25)%Read
AV18212-Exhaust TempBoiler 2: exhaust temperature (50-550)°FRead
AV5401-Fire Rate OutBoiler 3: fire rate output (0-100)%Read
AV5502-Active SetpointBoiler 3: setpoint in use (40-220)°FRead
AV5603-Net Remote SetptBoiler 3: network remote setpoint (40-220)°FWrite
AV6005-Fire Rate InBoiler 3: fire rate input (0-100)%Read
AV6106-Outlet TempBoiler 3: outlet water temperature (30-245)°FRead
AV6207-Display CodeBoiler 3: status/fault message code (1-48, see manual)Read
AV6308-Unit StatusBoiler 3: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV5809-Run CyclesBoiler 3: run cycle count (0-999,999)Read
AV5910-Run HoursBoiler 3: run hours (0-999,999)hRead
AV16311-OxygenBoiler 3: flue O2 level (0-25)%Read
AV18312-Exhaust TempBoiler 3: exhaust temperature (50-550)°FRead
AV7001-Fire Rate OutBoiler 4: fire rate output (0-100)%Read
AV7102-Active SetpointBoiler 4: setpoint in use (40-220)°FRead
AV7203-Net Remote SetptBoiler 4: network remote setpoint (40-220)°FWrite
AV7305-Fire Rate InBoiler 4: fire rate input (0-100)%Read
AV6506-Outlet TempBoiler 4: outlet water temperature (30-245)°FRead
AV6607-Display CodeBoiler 4: status/fault message code (1-48, see manual)Read
AV6708-Unit StatusBoiler 4: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV6809-Run CyclesBoiler 4: run cycle count (0-999,999)Read
AV6910-Run HoursBoiler 4: run hours (0-999,999)hRead
AV16411-OxygenBoiler 4: flue O2 level (0-25)%Read
AV18412-Exhaust TempBoiler 4: exhaust temperature (50-550)°FRead
AV8001-Fire Rate OutBoiler 5: fire rate output (0-100)%Read
AV8102-Active SetpointBoiler 5: setpoint in use (40-220)°FRead
AV8203-Net Remote SetptBoiler 5: network remote setpoint (40-220)°FWrite
AV7405-Fire Rate InBoiler 5: fire rate input (0-100)%Read
AV7506-Outlet TempBoiler 5: outlet water temperature (30-245)°FRead
AV7607-Display CodeBoiler 5: status/fault message code (1-48, see manual)Read
AV7708-Unit StatusBoiler 5: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV7809-Run CyclesBoiler 5: run cycle count (0-999,999)Read
AV7910-Run HoursBoiler 5: run hours (0-999,999)hRead
AV16511-OxygenBoiler 5: flue O2 level (0-25)%Read
AV18512-Exhaust TempBoiler 5: exhaust temperature (50-550)°FRead
AV9001-Fire Rate OutBoiler 6: fire rate output (0-100)%Read
AV9102-Active SetpointBoiler 6: setpoint in use (40-220)°FRead
AV9203-Net Remote SetptBoiler 6: network remote setpoint (40-220)°FWrite
AV8405-Fire Rate InBoiler 6: fire rate input (0-100)%Read
AV8506-Outlet TempBoiler 6: outlet water temperature (30-245)°FRead
AV8607-Display CodeBoiler 6: status/fault message code (1-48, see manual)Read
AV8708-Unit StatusBoiler 6: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV8809-Run CyclesBoiler 6: run cycle count (0-999,999)Read
AV8910-Run HoursBoiler 6: run hours (0-999,999)hRead
AV16611-OxygenBoiler 6: flue O2 level (0-25)%Read
AV18612-Exhaust TempBoiler 6: exhaust temperature (50-550)°FRead
AV10001-Fire Rate OutBoiler 7: fire rate output (0-100)%Read
AV10102-Active SetpointBoiler 7: setpoint in use (40-220)°FRead
AV10203-Net Remote SetptBoiler 7: network remote setpoint (40-220)°FWrite
AV9405-Fire Rate InBoiler 7: fire rate input (0-100)%Read
AV9506-Outlet TempBoiler 7: outlet water temperature (30-245)°FRead
AV9607-Display CodeBoiler 7: status/fault message code (1-48, see manual)Read
AV9708-Unit StatusBoiler 7: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV9809-Run CyclesBoiler 7: run cycle count (0-999,999)Read
AV9910-Run HoursBoiler 7: run hours (0-999,999)hRead
AV16711-OxygenBoiler 7: flue O2 level (0-25)%Read
AV18712-Exhaust TempBoiler 7: exhaust temperature (50-550)°FRead
AV11001-Fire Rate OutBoiler 8: fire rate output (0-100)%Read
AV11102-Active SetpointBoiler 8: setpoint in use (40-220)°FRead
AV11203-Net Remote SetptBoiler 8: network remote setpoint (40-220)°FWrite
AV10405-Fire Rate InBoiler 8: fire rate input (0-100)%Read
AV10506-Outlet TempBoiler 8: outlet water temperature (30-245)°FRead
AV10607-Display CodeBoiler 8: status/fault message code (1-48, see manual)Read
AV10708-Unit StatusBoiler 8: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV10809-Run CyclesBoiler 8: run cycle count (0-999,999)Read
AV10910-Run HoursBoiler 8: run hours (0-999,999)hRead
AV16811-OxygenBoiler 8: flue O2 level (0-25)%Read
AV18812-Exhaust TempBoiler 8: exhaust temperature (50-550)°FRead
AV12001-Fire Rate OutBoiler 9: fire rate output (0-100)%Read
AV12102-Active SetpointBoiler 9: setpoint in use (40-220)°FRead
AV12203-Net Remote SetptBoiler 9: network remote setpoint (40-220)°FWrite
AV11405-Fire Rate InBoiler 9: fire rate input (0-100)%Read
AV11506-Outlet TempBoiler 9: outlet water temperature (30-245)°FRead
AV11607-Display CodeBoiler 9: status/fault message code (1-48, see manual)Read
AV11708-Unit StatusBoiler 9: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV11809-Run CyclesBoiler 9: run cycle count (0-999,999)Read
AV11910-Run HoursBoiler 9: run hours (0-999,999)hRead
AV16911-OxygenBoiler 9: flue O2 level (0-25)%Read
AV18912-Exhaust TempBoiler 9: exhaust temperature (50-550)°FRead
AV13001-Fire Rate OutBoiler 10: fire rate output (0-100)%Read
AV13102-Active SetpointBoiler 10: setpoint in use (40-220)°FRead
AV13203-Net Remote SetptBoiler 10: network remote setpoint (40-220)°FWrite
AV12405-Fire Rate InBoiler 10: fire rate input (0-100)%Read
AV12506-Outlet TempBoiler 10: outlet water temperature (30-245)°FRead
AV12607-Display CodeBoiler 10: status/fault message code (1-48, see manual)Read
AV12708-Unit StatusBoiler 10: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV12809-Run CyclesBoiler 10: run cycle count (0-999,999)Read
AV12910-Run HoursBoiler 10: run hours (0-999,999)hRead
AV17011-OxygenBoiler 10: flue O2 level (0-25)%Read
AV19012-Exhaust TempBoiler 10: exhaust temperature (50-550)°FRead
AV14001-Fire Rate OutBoiler 11: fire rate output (0-100)%Read
AV14102-Active SetpointBoiler 11: setpoint in use (40-220)°FRead
AV14203-Net Remote SetptBoiler 11: network remote setpoint (40-220)°FWrite
AV13405-Fire Rate InBoiler 11: fire rate input (0-100)%Read
AV13506-Outlet TempBoiler 11: outlet water temperature (30-245)°FRead
AV13607-Display CodeBoiler 11: status/fault message code (1-48, see manual)Read
AV13708-Unit StatusBoiler 11: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV13809-Run CyclesBoiler 11: run cycle count (0-999,999)Read
AV13910-Run HoursBoiler 11: run hours (0-999,999)hRead
AV17111-OxygenBoiler 11: flue O2 level (0-25)%Read
AV19112-Exhaust TempBoiler 11: exhaust temperature (50-550)°FRead
AV15001-Fire Rate OutBoiler 12: fire rate output (0-100)%Read
AV15102-Active SetpointBoiler 12: setpoint in use (40-220)°FRead
AV15203-Net Remote SetptBoiler 12: network remote setpoint (40-220)°FWrite
AV14405-Fire Rate InBoiler 12: fire rate input (0-100)%Read
AV14506-Outlet TempBoiler 12: outlet water temperature (30-245)°FRead
AV14607-Display CodeBoiler 12: status/fault message code (1-48, see manual)Read
AV14708-Unit StatusBoiler 12: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AV14809-Run CyclesBoiler 12: run cycle count (0-999,999)Read
AV14910-Run HoursBoiler 12: run hours (0-999,999)hRead
AV17211-OxygenBoiler 12: flue O2 level (0-25)%Read
AV19212-Exhaust TempBoiler 12: exhaust temperature (50-550)°FRead
AV3101-Fire Rate OutACS/BMS II: plant fire rate output (0-100)%Read
AV3202-Header Set TempACS/BMS II: header setpoint in use (40-220)°FRead
AVmin3303-Net Header Set TempACS/BMS II: network header setpoint (40-220)°FWrite
AVmin3404-Header TempACS/BMS II: header temperature (40-220)°FRead
AV3505-Outside Air TempACS/BMS II: outdoor air temperature (-60 to 120)°FRead
AVmin3606-Display CodeACS/BMS II: fault/message bit fieldReadBit 0=Outside air sensor error, Bit 1=Header sensor error, Bit 2=Interlock 1 error, Bit 3=Interlock 2 error, Bit 4=Indoor air/return sensor error, Bit 5=4-20 mA input error
AV3707-Num Boilers FiredACS/BMS II: number of boilers firingRead
AV3808-Num Boilers OnlineACS/BMS II: number of boilers on lineRead
AV3909-Last Blr FiredACS/BMS II: last boiler firedRead
AV4010-Boiler 1 StatusACS/BMS II: status of PWM-controlled boiler 1Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired
AV4111-Boiler 2 StatusACS/BMS II: status of PWM-controlled boiler 2Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired
AV4812-Boiler 3 StatusACS/BMS II: status of PWM-controlled boiler 3Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired
AV113-Boiler 4 StatusACS/BMS II: status of PWM-controlled boiler 4Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired
AV214-Boiler 5 StatusACS/BMS II: status of PWM-controlled boiler 5Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired
AV315-Boiler 6 StatusACS/BMS II: status of PWM-controlled boiler 6Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired
AV416-Boiler 7 StatusACS/BMS II: status of PWM-controlled boiler 7Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired
AV517-Boiler 8 StatusACS/BMS II: status of PWM-controlled boiler 8Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired
AV618-Net Blr 1 StatusACS/BMS II: status of network boiler 1Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV719-Net Blr 2 StatusACS/BMS II: status of network boiler 2Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV820-Net Blr 3 StatusACS/BMS II: status of network boiler 3Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV921-Net Blr 4 StatusACS/BMS II: status of network boiler 4Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV1022-Net Blr 5 StatusACS/BMS II: status of network boiler 5Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV1123-Net Blr 6 StatusACS/BMS II: status of network boiler 6Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV1224-Net Blr 7 StatusACS/BMS II: status of network boiler 7Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV1325-Net Blr 8 StatusACS/BMS II: status of network boiler 8Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV1426-Net Blr 9 StatusACS/BMS II: status of network boiler 9Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV1527-Net Blr 10 StatusACS/BMS II: status of network boiler 10Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV1628-Net Blr 11 StatusACS/BMS II: status of network boiler 11Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV1729-Net Blr 12 StatusACS/BMS II: status of network boiler 12Read1-40=Fired and sequence number, 119=Not on line, 120=On line but not fired, 121=On line but disabled, 122=On line but faulted
AV17330-Return TempACS/BMS II: return temperature°FRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the C-More boilers with ACS / BMS II (ProtoNode RER) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AERCO C-More boilers with ACS / BMS II (ProtoNode RER)

How many BACnet points does the AERCO C-More boilers with ACS / BMS II (ProtoNode RER) have?

This list has 162 BACnet objects: 162 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet points are writable?

13 of the 162 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AERCO C-More boilers with ACS / BMS II (ProtoNode RER) BACnet documentation?

The source is AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 (OMM-0080_0H), revision 2014-11-06, published free by AERCO at https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/58249-source/637395359810000000/omm-0080-0h-gf-129-protonode-ler-rer-11-06-14.pdf.

What are the minimum BACnet points to integrate the AERCO C-More boilers with ACS / BMS II (ProtoNode RER)?

Start with AV 33 03-Net Header Set Temp (Plant header setpoint via ACS/BMS II, 40-220 °F); AV 24 03-Net Remote Setpt (Boiler 1 network setpoint, 40-220 °F); AV 23 08-Unit Status (Boiler 1 status; 5 = Fault); AV 34 04-Header Temp (Header water temperature, °F); AV 29 06-Outlet Temp (Boiler 1 outlet water temperature, °F); AV 26 01-Fire Rate Out (Boiler 1 fire rate, %); AV 22 07-Display Code (Boiler 1 status/fault message code); AV 36 06-Display Code (ACS/BMS II fault bit field).

How do I enable BMS control of the AERCO C-More boilers with ACS / BMS II (ProtoNode RER)?

No start/stop object. For plant control set the ACS/BMS II to Header Set Mode = Remote Setpt and Remote Signal = Network, then write AV 33. For a single C-More set Boiler Mode = Remote Setpt and Remote Signal = Network, then write its 03-Net Remote Setpt. Monitor-only needs just the Modbus address and 9600 baud.

Does the AERCO C-More boilers with ACS / BMS II (ProtoNode RER) need a BACnet heartbeat or have a communication timeout?

The BAS must write the setpoint at least three times within the unit's Network Timeout or the unit stops using it. Defaults are 30 s on C-More (5-999 s, Configuration menu), ACS (5-240 s) and BMS II (5-240 s, RS-232 menu).

How do I check these points on the real C-More boilers with ACS / BMS II (ProtoNode RER)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AERCO BACnet points lists

Source: AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 · OMM-0080_0H · rev. 2014-11-06. Object names, instances and units are reproduced as published; descriptions are our own.