Boiler and water heater plant controller via ProtoNode gateway · BACnet points list

AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD) BACnet points list

Updated 28 October 2026

Short answer

With the SSD (Slave/Slave Device) profile the AERCO ProtoNode RER sits on the BST or WHM Modbus network at fixed address 247 and serves the master's operating values and a 20-value block for each of up to 8 units on BACnet IP or BACnet MS/TP. The BMS changes the plant setpoint and setback values by writing them and then writing 1 to a send command. This file lists the master points and unit 1.

This page lists 46 BACnet objects for the AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.

Manufacturer
AERCO
Model
C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)
Equipment
Boiler and water heater plant controller via ProtoNode gateway
Equipment type
Boilers & water heaters
BACnet objects
46 (5 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
Node_Offset + A-bank DIP switch value (MAC); the manual's example uses Node_Offset 50,000
Also known as
C-More, BST, Boiler Sequencing Technology, WHM, Water Heater Management, SSD, Slave/Slave Device, Innovation, KC, Benchmark, ProtoNode RER, 64084, GF-129, OMM-0080
Source document
AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 · OMM-0080_0H · rev. 2014-11-06
Download CSV 46 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)

Integration in brief

Select the SSD BACnet profile on the ProtoNode (S1 and A3 On, all other S and A1 Off); the gateway then talks to the BST/WHM master at address 247. To change the plant setpoint write AV 200 (and setback values AV 201-203 if used), then write 1 to AV 51 to send them. Read plant values from AV 100-119 and each unit's block from AV 300 onwards.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 200SetptPlant setpoint to send, 40-200 °FWrite
AV 51Write Cntrl Val to BST/WHMWrite 1 to send AV 200-203 to the masterWrite
AV 107Units ActiveUnits active, 0-8Read
AV 301Unit StatusUnit 1 status; 5 = FaultRead
AV 101SetpointPlant setpoint in use, °FRead
AV 110Header TempHeader temperature, °FRead
AV 106Avg Outlet TempAverage outlet temperature, °FRead
AV 108Units FaultedNumber of faulted units, 0-8Read
AV 302Fault CodeUnit 1 fault code (C-More codes)Read

Enable & remote start

No start/stop object. Write the new setpoint (AV 200) and, if used, setback setpoint and times (AV 201-203), then write 1 to AV 51 Write Cntrl Val to BST/WHM to pass them to the master.

Network setup

Watch out for

AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

46 of 46 shown
Type
Analog
Access
Show
AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD) BACnet Points List
DescriptionStates
AVmin51Write Cntrl Val to BST/WHMBST/WHM master: write 1 to send the written values to BST/WHMWrite
AV53BST/WHM TimeoutBST/WHM master: master presence flag (read only)Read0=WHM present, 1=WHM absent
AV100ModeBST/WHM master: master modeRead0=Off, 1=Slave, 2=Master
AVmin101SetpointBST/WHM master: setpoint in use (40-200)°FRead
AV102Setback SetptBST/WHM master: setback setpoint (40-200)°FRead
AV103Setback StartBST/WHM master: setback start, minutes after midnightminRead
AV104Setback EndBST/WHM master: setback end, minutes after midnightminRead
AV105Auto MasterBST/WHM master: auto master statusRead0=No, 1=Yes
AVmin106Avg Outlet TempBST/WHM master: average outlet temperature (30-245)°FRead
AVmin107Units ActiveBST/WHM master: units active (0-8)Read
AVmin108Units FaultedBST/WHM master: units faulted (0-8)Read
AV109Master AddrBST/WHM master: BST/WHM master address (0, 10-255)Read
AVmin110Header TempBST/WHM master: header temperature°FRead
AV111Outdoor TempBST/WHM master: outdoor temperature°FRead
AV112Percent OutputBST/WHM master: plant percent output%Read
AV113Number of Units FiringBST/WHM master: number of units firingRead
AV114Master Active SetpointBST/WHM master: master active setpoint°FRead
AV115Next Turn-On PercentBST/WHM master: next turn-on percent%Read
AV116Header High LimitBST/WHM master: header high limit°FRead
AV117Header Low LimitBST/WHM master: header low limit°FRead
AV118Header Temp High LimitBST/WHM master: header temperature high limit°FRead
AV119Header Setpoint ModeBST/WHM master: header setpoint modeRead
AVmin200SetptBST/WHM master: setpoint to write (40-200)°FWrite
AV201Setback SetptBST/WHM master: setback setpoint to write (40-200)°FWrite
AV202Setback StartBST/WHM master: setback start to write, minutes after midnightminWrite
AV203Setback EndBST/WHM master: setback end to write, minutes after midnightminWrite
AV300Comm AddressUnit 1: unit Modbus communication address (0-127)Read
AVmin301Unit StatusUnit 1: unit operating statusRead0=Disabled, 1=Standby, 2=Manual Operation, 3=Remote Operation, 4=Auto Operation, 5=Fault
AVmin302Fault CodeUnit 1: fault code (0-74, C-More fault codes)Read
AV303Outlet TempUnit 1: outlet temperature (30-245)°FRead
AV304FFWD TempUnit 1: feed-forward temperature (30-245)°FRead
AV305Inlet TempUnit 1: inlet temperature (30-245)°FRead
AV306Exhaust TempUnit 1: exhaust temperature (50-550)°FRead
AV307Air TempUnit 1: inlet air temperature (-70 to 245)°FRead
AV308Flame StrengthUnit 1: flame strength (0-100)%Read
AV309Fire Rate InUnit 1: fire rate input (0-100)%Read
AV310Fire Rate OutUnit 1: fire rate output (0-100)%Read
AV311Unit TypeUnit 1: unit type codeRead1=KC Boiler LN, 2=BMK Boiler Std, 3=BMK Blr Std Dual, 4=BMK Boiler LN, 5=BMK Blr LN Dual, 6=KC Water Heater, 7=KC Wtr Heater LN, 8=Innovation WH
AV312Unit SizeUnit 1: unit size code (0-21)Read1=600 MBH, 2=800 MBH, 3=1060 MBH, 4=1350 MBH, 5=600 MBH, 6=800 MBH, 7=1060 MBH, 8=1350 MBH, 9=500 MBH, 10=750 MBH, 11=1000 MBH, 12=1.5 MBTU, 13=1500 MBH, 14=2.0 MBTU, 15=2000 MBH, 16=2500 MBH, 17=3.0 MBTU, 18=3000 MBH, 19=4000 MBH, 20=5000 MBH, 21=6000 MBH
AV313Value StateUnit 1: valve stateRead0=Closed, 1=Open
AV314Net Remote SetptUnit 1: network remote setpoint readback (40-200)°FRead
AV315Run Cycles UpperUnit 1: run cycles, upper 16 bitsRead
AV316Run Cycles LowerUnit 1: run cycles, lower 16 bitsRead
AV317Run Hours UpperUnit 1: run hours, upper 16 bitsRead
AV318Run Hours LowerUnit 1: run hours, lower 16 bitsRead
AV319Oxygen LevelUnit 1: flue O2 level (0-25)%Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)

How many BACnet points does the AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD) have?

This list has 46 BACnet objects: 46 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD) BACnet points are writable?

5 of the 46 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD) BACnet documentation?

The source is AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 (OMM-0080_0H), revision 2014-11-06, published free by AERCO at https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/58249-source/637395359810000000/omm-0080-0h-gf-129-protonode-ler-rer-11-06-14.pdf.

What are the minimum BACnet points to integrate the AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)?

Start with AV 200 Setpt (Plant setpoint to send, 40-200 °F); AV 51 Write Cntrl Val to BST/WHM (Write 1 to send AV 200-203 to the master); AV 107 Units Active (Units active, 0-8); AV 301 Unit Status (Unit 1 status; 5 = Fault); AV 101 Setpoint (Plant setpoint in use, °F); AV 110 Header Temp (Header temperature, °F); AV 106 Avg Outlet Temp (Average outlet temperature, °F); AV 108 Units Faulted (Number of faulted units, 0-8); AV 302 Fault Code (Unit 1 fault code (C-More codes)).

How do I enable BMS control of the AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)?

No start/stop object. Write the new setpoint (AV 200) and, if used, setback setpoint and times (AV 201-203), then write 1 to AV 51 Write Cntrl Val to BST/WHM to pass them to the master.

How do I check these points on the real C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AERCO BACnet points lists

Source: AERCO ProtoNode Gateway User Manual (ProtoNode-RER / ProtoNode-LER), GF-129 · OMM-0080_0H · rev. 2014-11-06. Object names, instances and units are reproduced as published; descriptions are our own.