Commercial water heater controller · BACnet points list

AERCO Edge [ii] water heater controller (standalone / WHM) BACnet points list

Updated 28 October 2026

Short answer

The Edge [ii] controller on AERCO water heaters talks BACnet IP on its Ethernet port or BACnet MS/TP on the J14 RS-485 terminals. Standalone and client units expose analog inputs for status, temperatures, valve position, O2 and combustion-calibration data plus analog values for setpoints and setup. A WHM manager adds plant values and a read-only block for each of up to 16 units. Only analog inputs and analog values are used.

This page lists 206 BACnet objects for the AERCO Edge [ii] water heater controller (standalone / WHM) — 73 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.

Manufacturer
AERCO
Model
Edge [ii] water heater controller (standalone / WHM)
Equipment
Commercial water heater controller
Equipment type
Boilers & water heaters
BACnet objects
206 (73 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Application software 1.0 (PICS dated 2018-09-27)
Also known as
Edge [ii], Edge ii, Edge 2, WHM, Water Heater Management, Centurion, OMM-0176, Innovation 1600-2000
Source document
Edge [ii] Controller Communication Manual · OMM-0162C · rev. 2025-10-15
Download CSV 206 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: AERCO Edge [ii] water heater controller (standalone / WHM)

Integration in brief

Enable the BAS port under Advanced Setup > Comm & Network > BAS (BACnet IP on the Ethernet port or BACnet MS/TP on J14), set the communication address and node offset, then have the BAS write the setpoint. For a WHM plant connect the BAS to the manager (or backup manager) only; it exposes plant values and a read-only block per unit.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 80Remote Disable Code85 = disable unit, 0 = enableWrite
AV 12Operating ModeSelects constant or remote setpointWrite
AV 13Remote SignalSet to BAS so the remote setpoint comes from BACnetWrite
AV 4SetpointUnit temperature setpoint, 20-245 °FWrite
AV 245WHM SetpointPlant setpoint on a WHM managerWrite
AI 1Unit StatusStandby / manual / remote / auto / fault stateRead
AI 2OutletOutlet water temperatureRead
AI 8Current Valve PositionFiring (valve) position, %Read
AI 0Message CodeActive event / fault codeRead
AI 108Units FaultedUnits faulted in the WHM plantRead

Enable & remote start

Under Advanced Setup > Comm & Network > BAS pick BACnet IP or BACnet MSTP (default Off). The BAS controls the unit through AV 12 Operating Mode (1 = Remote Setpt), AV 13 Remote Signal (3 = BAS) and the setpoint (AV 4, or AV 245 on a WHM manager). AV 80 Remote Disable Code (AV 229 for the plant) disables with 85 and enables with 0, but only when Allow System Disable = Yes in the BAS menu.

Heartbeat & communication loss

The BAS screen has a BAS Comm Timeout setting (range and default not given). On a WHM manager, AV 53 Network Timeout is listed as 5-999 s. AV 24 Unit Failsafe Mode sets what a unit does on lost communication: 0 = Shutdown, 1 = Constant Setpt.

Sensors & values from the BMS

On a WHM manager AV 213 Hdr Temp Sensor can be set to 3 = BAS, after which the BAS writes the header temperature to AV 214. AV 215 selects the return header sensor source.

Network setup

Watch out for

AERCO Edge [ii] water heater controller (standalone / WHM) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

206 of 206 shown
Type
Access
Show
AERCO Edge [ii] water heater controller (standalone / WHM) BACnet Points List
DescriptionStates
AImin0Message CodeActive message / fault codeRead
AImin1Unit StatusUnit operating statusRead0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault
AImin2OutletOutlet water temperature°FRead
AI3Lower InletLower inlet water temperature°FRead
AI4Air InletCombustion air inlet temperature°FRead
AI5Outside TempOutdoor temperature°FRead
AI6ExhaustExhaust temperature°FRead
AI7Feed ForwardFeed-forward temperature°FRead
AImin8Current Valve PositionAir/fuel valve position now%Read
AI9O2Flue O2%Read
AI11Run CyclesBurner run cyclesRead
AI13Run HoursBurner run hourshRead
AI15Flame StrengthFlame strength%Read
AI16Active Setpoint TempActive setpoint°FRead
AI17PID OutputPID output%Read
AI18SET Valve PositionValve position setpoint%Read
AI19Communication AddressUnit communication addressRead
AI44Select OutputRead0=Standard Setup, 1=Cascade Valve, 2=Aout 2
AI45Control ModeRead0=On/Off, 1=Linear Modulation, 2=Delta T Modulation
AI46Isolation FeedbackReadValues: disable / enable
AI47Open Vlv Control SignalRead0=0mA, 1=4mA, 2=20mA
AI48Close Vlv Control SignalRead0=0mA, 1=4mA, 2=20mA
AI49Blower SpeedBlower speedRead
AI50Blower Pulses/Revrange 0 to 100Read
AI51O2 Target 1O2 target for calibration point 1%Read
AI52O2 Target 2O2 target for calibration point 2%Read
AI53O2 Target 3O2 target for calibration point 3%Read
AI54O2 Target 4O2 target for calibration point 4%Read
AI55O2 Target 5O2 target for calibration point 5%Read
AI56O2 Target 6O2 target for calibration point 6%Read
AI57O2 Target 7O2 target for calibration point 7%Read
AI58O2 Target 8O2 target for calibration point 8%Read
AI62WHM Uart3 errorsWHM serial link (UART3) error codeRead0=No errors, 1=Overrun Error, 2=Framing Error, 3=Parity Error, 4=Uart Sync Error, 5=CRC Error, 6=Unknown Error
AI63Nox Requirementrange 0 to 200Read
AI64Manifold Gas Pressurerange 0 to 90Read
AI65O2 at Cal Point 1O2, calibration point 1Read
AI66O2 at Cal Point 2O2, calibration point 2Read
AI67O2 at Cal Point 3O2, calibration point 3Read
AI68O2 at Cal Point 4O2, calibration point 4Read
AI69O2 at Cal Point 5O2, calibration point 5Read
AI70O2 at Cal Point 6O2, calibration point 6Read
AI71O2 at Cal Point 7O2, calibration point 7Read
AI72O2 at Cal Point 8O2, calibration point 8Read
AI73NOx at Cal 1NOx, calibration point 1Read
AI74NOx at Cal 2NOx, calibration point 2Read
AI75NOx at Cal 3NOx, calibration point 3Read
AI76NOx at Cal 4NOx, calibration point 4Read
AI77NOx at Cal 5NOx, calibration point 5Read
AI78NOx at Cal 6NOx, calibration point 6Read
AI79NOx at Cal 7NOx, calibration point 7Read
AI80NOx at Cal 8NOx, calibration point 8Read
AI81CO at Cal 1CO, calibration point 1Read
AI82CO at Cal 2CO, calibration point 2Read
AI83CO at Cal 3CO, calibration point 3Read
AI84CO at Cal 4CO, calibration point 4Read
AI85CO at Cal 5CO, calibration point 5Read
AI86CO at Cal 6CO, calibration point 6Read
AI87CO at Cal 7CO, calibration point 7Read
AI88CO at Cal 8CO, calibration point 8Read
AI89Flame Strength at Cal 1Flame Strength, calibration point 1Read
AI90Flame Strength at Cal 2Flame Strength, calibration point 2Read
AI91Flame Strength at Cal 3Flame Strength, calibration point 3Read
AI92Flame Strength at Cal 4Flame Strength, calibration point 4Read
AI93Flame Strength at Cal 5Flame Strength, calibration point 5Read
AI94Flame Strength at Cal 6Flame Strength, calibration point 6Read
AI95Flame Strength at Cal 7Flame Strength, calibration point 7Read
AI96Flame Strength at Cal 8Flame Strength, calibration point 8Read
AI97Calibration Timerange 12.00am to 11.59pmRead
AI98Calibration Daterange 0/0/0 to 12/31/9999Read
AI100Unit ModeRead0=Off, 1=WHM Client, 2=WHM Manager
AI101Plant Constant Setpointrange 20F to 245F°FRead
AI102Setback Setpointrange 20F to 245F°FRead
AI103Setback Start Timerange 12.00am to 11.59pmRead
AI104Setback Stop Timerange 0/0/0 to 12/31/9999Read
AI105Auto-Manager TransferReadValues: Disabled / Enabled
AI106OutletTempPlant outlet temperature°FRead
AI107UEnabledUnits enabled in the plantRead
AImin108Units FaultedUnits faulted in the plantRead
AI109Unit Addressrange 0 to 16Read
AI110Header TempHeader temperature°FRead
AI112Avg Fire RateAverage plant firing rate%Read
AI113Units IgnitedUnits firingRead
AI114Act SetptActive plant setpoint°FRead
AI115Next On Valve Posrange 16% to 100%%Read
AI116Setpt Hi Limrange 20F to 220F°FRead
AI117Setpt Low Limitrange 40F to 245F°FRead
AI118Cascade Temp Hi Limitrange 40F to 210F°FRead
AI119Operating ModeRead0 = Constant Setpoint
AI121DHW Setpointrange 40F to 170F°FRead
AI122Fuel TypeRead0=Natural Gas, 1=Propane
AI123Previous CAL Point 1Previous calibration point 1 settingRead
AI124Previous CAL Point 2Previous calibration point 2 settingRead
AI125Previous CAL Point 3Previous calibration point 3 settingRead
AI126Previous CAL Point 4Previous calibration point 4 settingRead
AI127Previous CAL Point 5Previous calibration point 5 settingRead
AI128Previous CAL Point 6Previous calibration point 6 settingRead
AI129Previous CAL Point 7Previous calibration point 7 settingRead
AI130Previous CAL Point 8Previous calibration point 8 settingRead
AI131Pre Flame Strength at Cal 1Pre Flame Strength, calibration point 1Read
AI132Pre Flame Strength at Cal 2Pre Flame Strength, calibration point 2Read
AI133Pre Flame Strength at Cal 3Pre Flame Strength, calibration point 3Read
AI134Pre Flame Strength at Cal 4Pre Flame Strength, calibration point 4Read
AI135Pre Flame Strength at Cal 5Pre Flame Strength, calibration point 5Read
AI136Pre Flame Strength at Cal 6Pre Flame Strength, calibration point 6Read
AI137Pre Flame Strength at Cal 7Pre Flame Strength, calibration point 7Read
AI138Pre Flame Strength at Cal 8Pre Flame Strength, calibration point 8Read
AI146Current Blower VoltageBlower control voltageVRead
AI147Software VersionController software versionRead
AI148Unit AlphaRead0=E, 1=G, 2=H, 3=R, 4=N, 5=A
AI149Unit Yearrange 0 to 99Read
AI150Unit Serial #range 0 to 9999Read
AI151Fuel TypeRead0=Natural Gas, 1=Propane
AI152WHM Unit ModeRead0=OFF, 1=Client, 2=Manager
AI300Communication AddressWHM unit 1: Communication AddressRead
AI301unit StatusWHM unit 1: unit StatusRead0=Disabled, 1=Standby, 2=Manual, 3=Remote, 4=Auto, 5=Fault
AI302Fault CodeWHM unit 1: Fault CodeRead
AI303Outlet TemperatureWHM unit 1: Outlet Temperature°FRead
AI304FFWD TemperatureWHM unit 1: FFWD Temperature°FRead
AI305Inlet TemperatureWHM unit 1: Inlet Temperature°FRead
AI306Exhaust TemperatureWHM unit 1: Exhaust Temperature°FRead
AI307Inlet Air TemperatureWHM unit 1: Inlet Air Temperature°FRead
AI308Flame StrengthWHM unit 1: Flame Strength%Read
AI309Fire Rate InWHM unit 1: Fire Rate In%Read
AI310Fire Rate OutWHM unit 1: Fire Rate Out%Read
AI311Unit TypeWHM unit 1: Unit TypeRead
AI312Unit SizeWHM unit 1: Unit SizeRead
AI313Valve StateWHM unit 1: Valve StateRead
AI314Net Remote SetpointWHM unit 1: Net Remote SetpointRead
AI315Run Cycle UpperWHM unit 1: Run Cycle UpperRead
AI316Run Cycle LowerWHM unit 1: Run Cycle LowerRead
AI317Run Hours UpperWHM unit 1: Run Hours UpperRead
AI318Run Hours LowerWHM unit 1: Run Hours LowerRead
AI319Oxygen LvelWHM unit 1: Oxygen Lvel%Read
AV0Net Remote SetptRemote setpoint written by the network; range 0 to 9999Write
AV2Remote PasswordWrite
AV3PasswordWrite
AVmin4SetpointUnit temperature setpoint; range 20F to 245F°FWrite
AV5LanguageWrite0=English, 1=Spanish, 2=French
AV6Timerange 12.00am to 11.59pmWrite
AV7Daterange 0/0/0 to 12/31/9999Write
AV8Unit of MeasurementWriteValues: English / Metric
AV9Cascade Baud RateWrite0=9600, 1=19200, 2=38400, 3=57600, 4=76800, 5=115200
AV10Unit TypeWrite10 = Centurion
AV11Unit SizeWrite5=1600 MBH, 6=2000 MBH
AVmin12Operating ModeConstant or remote setpoint modeWrite0=Constant Setpt, 1=Remote Setpt
AVmin13Remote SignalSource of the remote setpointWrite0=4-20mA/1-5V, 1=0-20mA/0-5V, 2=Network, 3=BAS
AV18Setpoint Low Limitrange 40F to 245F°FWrite
AV19Setpoint High Limitrange 20F to 220F°FWrite
AV20Temperature High Limitrange 40F to 210F°FWrite
AV21Max Valve Positionrange 40 to 100Write
AV23Auxiliary Delayrange 0 to 240Write
AV24Unit Failsafe ModeAction on lost BAS communicationWrite0=Shutdown, 1=Constant Setpt
AV25Low Fire Timerrange 2sec to 600SecsWrite
AV26Proportional Bandrange 1F to 120F°FWrite
AV27Integral Bandrange 0 to 2Write
AV28Derivative Bandrange 0 to 2minminWrite
AV29Min Load Adjrange -50 to 50F°FWrite
AV30Max Load Adjrange -50 to 50F°FWrite
AV31Outlet FeedbackWriteValues: No / Yes
AV32Feedback Gainrange 0.01 to 1Write
AV33Breakpt at 0%range -100 to 100F°FWrite
AV34Breakpt at 10%range -100 to 100F°FWrite
AV35Breakpt at 20%range -100 to 100F°FWrite
AV36Breakpt at 30%range -100 to 100F°FWrite
AV37Breakpt at 40%range -100 to 100F°FWrite
AV38Breakpt at 50%range -100 to 100F°FWrite
AV39Breakpt at 60%range -100 to 100F°FWrite
AV40Breakpt at 70%range -100 to 100F°FWrite
AV41Breakpt at 80%range -100 to 100F°FWrite
AV42Breakpt at 90%range -100 to 100F°FWrite
AV43Breakpt at 100%range -100 to 100F°FWrite
AV44Purge Timerrange 5Sec to 60SecsWrite
AV45Post Purge Timerrange 0 to 60SecsWrite
AV46Ignition Positionrange 5% to 60%%Write
AV47Stop Valve Positionrange 0 to 40%%Write
AV48Start Valve Positionrange 0 to 40%%Write
AV49On Delayrange 0 to 600SecsWrite
AV53Network TimeoutWHM manager: BAS network timeout; range 5 to 999 ssWrite
AV57Valve Pos Out DspWriteValues: Disable / Enable
AV58Exhaust Temp DspWriteValues: Disable / Enable
AV59Setpoint LimitingWriteValues: Disable / Enable
AV60Setpoint Limit Bandrange 0 to 10F°FWrite
AV62Inlet Temp DisplayWriteValues: Disable / Enable
AV64Water Temp ResetWriteValues: Manual / Automatic
AV65Gas Pressure ResetWriteValues: Manual / Automatic
AV70BASBAS protocol selectionWrite0=Off, 1=BACnet MSTP, 2=BACnet IP, 3=Modbus RTU, 4=Modbus TCP
AV71Cascade Baud RateWrite0=9600, 1=19200, 2=38400, 3=57600
AV72INTL CommunicationWriteValues: Disable / Enable
AV73Intl Baud RateWrite0=9600, 1=19200, 2=38400, 3=57600, 4=76800, 5=115200
AV75O2 TrimWriteValues: Disabled / Enabled
AVmin80Remote Disable CodeWrite 85 to disable the unit, 0 to enable (needs Allow System Disable = Yes)Write0=Enable Unit, 85=Disable Unit
AV201Setback Setpointrange 20F to 245F°FWrite
AV202Setback Start Timerange 12.00am to 11.59pmWrite
AV203Setback Stop Timerange 12.00am to 11.59pmWrite
AV204Setback ScheduleWriteValues: Disable / Enable
AV213Hdr Temp SensorHeader temperature sensor sourceWrite0=Network, 1=FFWD Temp, 2=Direct, 3=BAS, 4=OFF
AV214BAS Header TempHeader temperature written by the BAS; range 0F to 250F°FWrite
AV215Rtn Hdr Temp SensorReturn header temperature sensor sourceWrite0=OFF, 1=Network, 2=Direct, 3=BAS
AV216Rtn Hdr Temp SensorReturn header temperature (BAS value); range 0F to 250F°FWrite
AV219BASWrite0=OFF, 1=BACnet MSTP, 2=BACnet IP, 3=Modbus RTU, 4=Modbus TCP
AV220Baud RateWrite0=9600, 1=19200, 2=38400, 3=57600
AV221INTL CommunicationWrite0=Disabled, 1=Enabled
AV222Intl Baud RateWrite0=9600, 1=19200, 2=38400, 3=57600
AV224O2 TrimWrite0=Disabled, 1=Enabled
AV229Remote Disable CodeWrite 85 to disable the plant, 0 to enableWrite0=Enable Plant, 85=Disable Plant
AVmin245WHM SetpointWHM plant DHW setpoint; range 40F to 170F°FWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Edge [ii] water heater controller (standalone / WHM) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AERCO Edge [ii] water heater controller (standalone / WHM)

How many BACnet points does the AERCO Edge [ii] water heater controller (standalone / WHM) have?

This list has 206 BACnet objects: 133 analog inputs, 73 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AERCO Edge [ii] water heater controller (standalone / WHM) BACnet points are writable?

73 of the 206 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AERCO Edge [ii] water heater controller (standalone / WHM) BACnet documentation?

The source is Edge [ii] Controller Communication Manual (OMM-0162C), revision 2025-10-15, published free by AERCO at https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/659416-source/omm-0176-aerco-edge-ii-communication-manual-4-1-25.pdf.

What are the minimum BACnet points to integrate the AERCO Edge [ii] water heater controller (standalone / WHM)?

Start with AV 80 Remote Disable Code (85 = disable unit, 0 = enable); AV 12 Operating Mode (Selects constant or remote setpoint); AV 13 Remote Signal (Set to BAS so the remote setpoint comes from BACnet); AV 4 Setpoint (Unit temperature setpoint, 20-245 °F); AV 245 WHM Setpoint (Plant setpoint on a WHM manager); AI 1 Unit Status (Standby / manual / remote / auto / fault state); AI 2 Outlet (Outlet water temperature); AI 8 Current Valve Position (Firing (valve) position, %); AI 0 Message Code (Active event / fault code); AI 108 Units Faulted (Units faulted in the WHM plant).

How do I enable BMS control of the AERCO Edge [ii] water heater controller (standalone / WHM)?

Under Advanced Setup > Comm & Network > BAS pick BACnet IP or BACnet MSTP (default Off). The BAS controls the unit through AV 12 Operating Mode (1 = Remote Setpt), AV 13 Remote Signal (3 = BAS) and the setpoint (AV 4, or AV 245 on a WHM manager). AV 80 Remote Disable Code (AV 229 for the plant) disables with 85 and enables with 0, but only when Allow System Disable = Yes in the BAS menu.

Does the AERCO Edge [ii] water heater controller (standalone / WHM) need a BACnet heartbeat or have a communication timeout?

The BAS screen has a BAS Comm Timeout setting (range and default not given). On a WHM manager, AV 53 Network Timeout is listed as 5-999 s. AV 24 Unit Failsafe Mode sets what a unit does on lost communication: 0 = Shutdown, 1 = Constant Setpt.

Can the BMS supply sensor values to the AERCO Edge [ii] water heater controller (standalone / WHM)?

On a WHM manager AV 213 Hdr Temp Sensor can be set to 3 = BAS, after which the BAS writes the header temperature to AV 214. AV 215 selects the return header sensor source.

How do I check these points on the real Edge [ii] water heater controller (standalone / WHM)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AERCO BACnet points lists

Source: Edge [ii] Controller Communication Manual · OMM-0162C · rev. 2025-10-15. Object names, instances and units are reproduced as published; descriptions are our own.