- Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)
Boiler and water heater plant gateway (multi-unit) · BACnet points list
AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list) BACnet points list
Updated 6 November 2026
AERCO's ProtoNode control-points workbook has a combined profile for a mixed plant: 12 C-More boilers (9 objects each), 4 Modulex boilers (10 each), 6 ECS/SmartPlate valves (7 each) and two BMS II managers (29 objects for the C-More plant, 13 for the Modulex plant), 232 Analog Values in all. Most are read-only; setpoints and Modulex direct-drive commands are writable.
This page lists 232 BACnet objects for the AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list) — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.
- Manufacturer
- AERCO
- Model
- Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)
- Equipment
- Boiler and water heater plant gateway (multi-unit)
- Equipment type
- Boilers & water heaters
- BACnet objects
- 232 (28 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- AERCO ProtoNode, C-More, Modulex, ECS, SmartPlate, BMS II, AERCO-ProtoNode-Control-Points
Reference only, provided as-is: verify against AERCO’s current documentation and the live device before use. Not official AERCO information. Terms of use.
BMS integration notes: AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)
Write the header setpoints to the two BMS II objects (setpt_128 for the C-More plant, setpt_228 for the Modulex plant), or per-unit setpoints and Modulex direct-drive commands where the plant is run unit by unit. Read header temperatures, boilers fired/online, each unit's fire rate, outlet temperature, status and display/error codes.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 262 | setpt_128 | C-More plant header setpoint from the BMS | Write |
| AV 302 | setpt_228 | Modulex plant header setpoint from the BMS | Write |
| AV 263 | localsuptemp_128 | C-More plant header temperature | Read |
| AV 303 | localsuptemp_228 | Modulex plant header temperature | Read |
| AV 266 | blrfired_128 | Number of C-More boilers firing | Read |
| AV 1 | boilerstate_1 | C-More boiler 1 fire rate (repeat per boiler) | Read |
| AV 8 | unitstat_1 | C-More boiler 1 unit status (repeat per boiler) | Read |
| AV 265 | dispcode_128 | C-More BMS II display (fault) code | Read |
| AV 128 | errcode_13 | Modulex 13 error code (repeat per unit) | Read |
Enable & remote start
The sheet marks setpt_128 / setpt_228 (network header setpoints), each C-More setpt_n (net remote setpoint), each Modulex setpt_n and boilercmd_n (requested outlet temperature and net direct drive) and each ECS rmsetpt_n as writable. It does not describe the BMS II or C-More modes needed for these to take effect.
Network setup
- Device addresses in this profile: C-More 1-12, Modulex 13-16, ECS/SmartPlate valves 17-22, BMS II 128 (C-More plant) and 228 (Modulex plant).
- The sheet title lists BACnet IP, BACnet MS/TP, Metasys N2 and LonWorks; it gives no device instance or network settings.
Watch out for
- Object IDs follow this combined profile only; the single-plant profiles (4/8/12 C-More, Modulex, ECS) use other IDs.
- Many objects share the same AERCO point label (01-Fire Rate Out ...); the unit is in the description and in the object name suffix.
- Units and ranges are not given in the sheet.
AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | boilerstate_1 | C-More boiler 1: 01-Fire Rate Out (Modbus 30009/1) | Read | ||
| AV | 2 | effectsetpt_1 | C-More boiler 1: 02-Active Setpoint (Modbus 30017/1) | Read | ||
| AV | 3 | setpt_1 | C-More boiler 1: 03-Net Remote Setpt (Modbus 40001/1) | Write | ||
| AV | 5 | boilerload_1 | C-More boiler 1: 05-Fire Rate In (Modbus 30018/1) | Read | ||
| AV | 6 | localsuptemp_1 | C-More boiler 1: 06-Outlet Temp (Modbus 30003/1) | Read | ||
| AV | 7 | dispcode_1 | C-More boiler 1: 07-Display Code (Modbus 30001/1) | Read | ||
| AVmin | 8 | unitstat_1 | C-More boiler 1: 08-Unit Status (Modbus 30002/1) | Read | ||
| AV | 9 | runcycles_1 | C-More boiler 1: 09-Run Cycles (Modbus 30012-30013/1) | Read | ||
| AV | 10 | runhours_1 | C-More boiler 1: 10-Run Hours (Modbus 30014-30015/1) | Read | ||
| AV | 11 | boilerstate_2 | C-More boiler 2: 01-Fire Rate Out (Modbus 30009/2) | Read | ||
| AV | 12 | effectsetpt_2 | C-More boiler 2: 02-Active Setpoint (Modbus 30017/2) | Read | ||
| AV | 13 | setpt_2 | C-More boiler 2: 03-Net Remote Setpt (Modbus 40001/2) | Write | ||
| AV | 15 | boilerload_2 | C-More boiler 2: 05-Fire Rate In (Modbus 30018/2) | Read | ||
| AV | 16 | localsuptemp_2 | C-More boiler 2: 06-Outlet Temp (Modbus 30003/2) | Read | ||
| AV | 17 | dispcode_2 | C-More boiler 2: 07-Display Code (Modbus 30001/2) | Read | ||
| AV | 18 | unitstat_2 | C-More boiler 2: 08-Unit Status (Modbus 30002/2) | Read | ||
| AV | 19 | runcycles_2 | C-More boiler 2: 09-Run Cycles (Modbus 30012-30013/2) | Read | ||
| AV | 20 | runhours_2 | C-More boiler 2: 10-Run Hours (Modbus 30014-30015/2) | Read | ||
| AV | 21 | boilerstate_3 | C-More boiler 3: 01-Fire Rate Out (Modbus 30009/3) | Read | ||
| AV | 22 | effectsetpt_3 | C-More boiler 3: 02-Active Setpoint (Modbus 30017/3) | Read | ||
| AV | 23 | setpt_3 | C-More boiler 3: 03-Net Remote Setpt (Modbus 40001/3) | Write | ||
| AV | 25 | boilerload_3 | C-More boiler 3: 05-Fire Rate In (Modbus 30018/3) | Read | ||
| AV | 26 | localsuptemp_3 | C-More boiler 3: 06-Outlet Temp (Modbus 30003/3) | Read | ||
| AV | 27 | dispcode_3 | C-More boiler 3: 07-Display Code (Modbus 30001/3) | Read | ||
| AV | 28 | unitstat_3 | C-More boiler 3: 08-Unit Status (Modbus 30002/3) | Read | ||
| AV | 29 | runcycles_3 | C-More boiler 3: 09-Run Cycles (Modbus 30012-30013/3) | Read | ||
| AV | 30 | runhours_3 | C-More boiler 3: 10-Run Hours (Modbus 30014-30015/3) | Read | ||
| AV | 31 | boilerstate_4 | C-More boiler 4: 01-Fire Rate Out (Modbus 30009/4) | Read | ||
| AV | 32 | effectsetpt_4 | C-More boiler 4: 02-Active Setpoint (Modbus 30017/4) | Read | ||
| AV | 33 | setpt_4 | C-More boiler 4: 03-Net Remote Setpt (Modbus 40001/4) | Write | ||
| AV | 35 | boilerload_4 | C-More boiler 4: 05-Fire Rate In (Modbus 30018/4) | Read | ||
| AV | 36 | localsuptemp_4 | C-More boiler 4: 06-Outlet Temp (Modbus 30003/4) | Read | ||
| AV | 37 | dispcode_4 | C-More boiler 4: 07-Display Code (Modbus 30001/4) | Read | ||
| AV | 38 | unitstat_4 | C-More boiler 4: 08-Unit Status (Modbus 30002/4) | Read | ||
| AV | 39 | runcycles_4 | C-More boiler 4: 09-Run Cycles (Modbus 30012-30013/4) | Read | ||
| AV | 40 | runhours_4 | C-More boiler 4: 10-Run Hours (Modbus 30014-30015/4) | Read | ||
| AV | 41 | boilerstate_5 | C-More boiler 5: 01-Fire Rate Out (Modbus 30009/5) | Read | ||
| AV | 42 | effectsetpt_5 | C-More boiler 5: 02-Active Setpoint (Modbus 30017/5) | Read | ||
| AV | 43 | setpt_5 | C-More boiler 5: 03-Net Remote Setpt (Modbus 40001/5) | Write | ||
| AV | 45 | boilerload_5 | C-More boiler 5: 05-Fire Rate In (Modbus 30018/5) | Read | ||
| AV | 46 | localsuptemp_5 | C-More boiler 5: 06-Outlet Temp (Modbus 30003/5) | Read | ||
| AV | 47 | dispcode_5 | C-More boiler 5: 07-Display Code (Modbus 30001/5) | Read | ||
| AV | 48 | unitstat_5 | C-More boiler 5: 08-Unit Status (Modbus 30002/5) | Read | ||
| AV | 49 | runcycles_5 | C-More boiler 5: 09-Run Cycles (Modbus 30012-30013/5) | Read | ||
| AV | 50 | runhours_5 | C-More boiler 5: 10-Run Hours (Modbus 30014-30015/5) | Read | ||
| AV | 51 | boilerstate_6 | C-More boiler 6: 01-Fire Rate Out (Modbus 30009/6) | Read | ||
| AV | 52 | effectsetpt_6 | C-More boiler 6: 02-Active Setpoint (Modbus 30017/6) | Read | ||
| AV | 53 | setpt_6 | C-More boiler 6: 03-Net Remote Setpt (Modbus 40001/6) | Write | ||
| AV | 55 | boilerload_6 | C-More boiler 6: 05-Fire Rate In (Modbus 30018/6) | Read | ||
| AV | 56 | localsuptemp_6 | C-More boiler 6: 06-Outlet Temp (Modbus 30003/6) | Read | ||
| AV | 57 | dispcode_6 | C-More boiler 6: 07-Display Code (Modbus 30001/6) | Read | ||
| AV | 58 | unitstat_6 | C-More boiler 6: 08-Unit Status (Modbus 30002/6) | Read | ||
| AV | 59 | runcycles_6 | C-More boiler 6: 09-Run Cycles (Modbus 30012-30013/6) | Read | ||
| AV | 60 | runhours_6 | C-More boiler 6: 10-Run Hours (Modbus 30014-30015/6) | Read | ||
| AV | 61 | boilerstate_7 | C-More boiler 7: 01-Fire Rate Out (Modbus 30009/7) | Read | ||
| AV | 62 | effectsetpt_7 | C-More boiler 7: 02-Active Setpoint (Modbus 30017/7) | Read | ||
| AV | 63 | setpt_7 | C-More boiler 7: 03-Net Remote Setpt (Modbus 40001/7) | Write | ||
| AV | 65 | boilerload_7 | C-More boiler 7: 05-Fire Rate In (Modbus 30018/7) | Read | ||
| AV | 66 | localsuptemp_7 | C-More boiler 7: 06-Outlet Temp (Modbus 30003/7) | Read | ||
| AV | 67 | dispcode_7 | C-More boiler 7: 07-Display Code (Modbus 30001/7) | Read | ||
| AV | 68 | unitstat_7 | C-More boiler 7: 08-Unit Status (Modbus 30002/7) | Read | ||
| AV | 69 | runcycles_7 | C-More boiler 7: 09-Run Cycles (Modbus 30012-30013/7) | Read | ||
| AV | 70 | runhours_7 | C-More boiler 7: 10-Run Hours (Modbus 30014-30015/7) | Read | ||
| AV | 71 | boilerstate_8 | C-More boiler 8: 01-Fire Rate Out (Modbus 30009/8) | Read | ||
| AV | 72 | effectsetpt_8 | C-More boiler 8: 02-Active Setpoint (Modbus 30017/8) | Read | ||
| AV | 73 | setpt_8 | C-More boiler 8: 03-Net Remote Setpt (Modbus 40001/8) | Write | ||
| AV | 75 | boilerload_8 | C-More boiler 8: 05-Fire Rate In (Modbus 30018/8) | Read | ||
| AV | 76 | localsuptemp_8 | C-More boiler 8: 06-Outlet Temp (Modbus 30003/8) | Read | ||
| AV | 77 | dispcode_8 | C-More boiler 8: 07-Display Code (Modbus 30001/8) | Read | ||
| AV | 78 | unitstat_8 | C-More boiler 8: 08-Unit Status (Modbus 30002/8) | Read | ||
| AV | 79 | runcycles_8 | C-More boiler 8: 09-Run Cycles (Modbus 30012-30013/8) | Read | ||
| AV | 80 | runhours_8 | C-More boiler 8: 10-Run Hours (Modbus 30014-30015/8) | Read | ||
| AV | 81 | boilerstate_9 | C-More boiler 9: 01-Fire Rate Out (Modbus 30009/9) | Read | ||
| AV | 82 | effectsetpt_9 | C-More boiler 9: 02-Active Setpoint (Modbus 30017/9) | Read | ||
| AV | 83 | setpt_9 | C-More boiler 9: 03-Net Remote Setpt (Modbus 40001/9) | Write | ||
| AV | 85 | boilerload_9 | C-More boiler 9: 05-Fire Rate In (Modbus 30018/9) | Read | ||
| AV | 86 | localsuptemp_9 | C-More boiler 9: 06-Outlet Temp (Modbus 30003/9) | Read | ||
| AV | 87 | dispcode_9 | C-More boiler 9: 07-Display Code (Modbus 30001/9) | Read | ||
| AV | 88 | unitstat_9 | C-More boiler 9: 08-Unit Status (Modbus 30002/9) | Read | ||
| AV | 89 | runcycles_9 | C-More boiler 9: 09-Run Cycles (Modbus 30012-30013/9) | Read | ||
| AV | 90 | runhours_9 | C-More boiler 9: 10-Run Hours (Modbus 30014-30015/9) | Read | ||
| AV | 91 | boilerstate_10 | C-More boiler 10: 01-Fire Rate Out (Modbus 30009/10) | Read | ||
| AV | 92 | effectsetpt_10 | C-More boiler 10: 02-Active Setpoint (Modbus 30017/10) | Read | ||
| AV | 93 | setpt_10 | C-More boiler 10: 03-Net Remote Setpt (Modbus 40001/10) | Write | ||
| AV | 95 | boilerload_10 | C-More boiler 10: 05-Fire Rate In (Modbus 30018/10) | Read | ||
| AV | 96 | localsuptemp_10 | C-More boiler 10: 06-Outlet Temp (Modbus 30003/10) | Read | ||
| AV | 97 | dispcode_10 | C-More boiler 10: 07-Display Code (Modbus 30001/10) | Read | ||
| AV | 98 | unitstat_10 | C-More boiler 10: 08-Unit Status (Modbus 30002/10) | Read | ||
| AV | 99 | runcycles_10 | C-More boiler 10: 09-Run Cycles (Modbus 30012-30013/10) | Read | ||
| AV | 100 | runhours_10 | C-More boiler 10: 10-Run Hours (Modbus 30014-30015/10) | Read | ||
| AV | 101 | boilerstate_11 | C-More boiler 11: 01-Fire Rate Out (Modbus 30009/11) | Read | ||
| AV | 102 | effectsetpt_11 | C-More boiler 11: 02-Active Setpoint (Modbus 30017/11) | Read | ||
| AV | 103 | setpt_11 | C-More boiler 11: 03-Net Remote Setpt (Modbus 40001/11) | Write | ||
| AV | 105 | boilerload_11 | C-More boiler 11: 05-Fire Rate In (Modbus 30018/11) | Read | ||
| AV | 106 | localsuptemp_11 | C-More boiler 11: 06-Outlet Temp (Modbus 30003/11) | Read | ||
| AV | 107 | dispcode_11 | C-More boiler 11: 07-Display Code (Modbus 30001/11) | Read | ||
| AV | 108 | unitstat_11 | C-More boiler 11: 08-Unit Status (Modbus 30002/11) | Read | ||
| AV | 109 | runcycles_11 | C-More boiler 11: 09-Run Cycles (Modbus 30012-30013/11) | Read | ||
| AV | 110 | runhours_11 | C-More boiler 11: 10-Run Hours (Modbus 30014-30015/11) | Read | ||
| AV | 111 | boilerstate_12 | C-More boiler 12: 01-Fire Rate Out (Modbus 30009/12) | Read | ||
| AV | 112 | effectsetpt_12 | C-More boiler 12: 02-Active Setpoint (Modbus 30017/12) | Read | ||
| AV | 113 | setpt_12 | C-More boiler 12: 03-Net Remote Setpt (Modbus 40001/12) | Write | ||
| AV | 115 | boilerload_12 | C-More boiler 12: 05-Fire Rate In (Modbus 30018/12) | Read | ||
| AV | 116 | localsuptemp_12 | C-More boiler 12: 06-Outlet Temp (Modbus 30003/12) | Read | ||
| AV | 117 | dispcode_12 | C-More boiler 12: 07-Display Code (Modbus 30001/12) | Read | ||
| AV | 118 | unitstat_12 | C-More boiler 12: 08-Unit Status (Modbus 30002/12) | Read | ||
| AV | 119 | runcycles_12 | C-More boiler 12: 09-Run Cycles (Modbus 30012-30013/12) | Read | ||
| AV | 120 | runhours_12 | C-More boiler 12: 10-Run Hours (Modbus 30014-30015/12) | Read | ||
| AV | 121 | boilerstate_13 | Modulex 13: 01-Act Mod Lev (Modbus 41009/13) | Read | ||
| AV | 122 | effectsetpt_13 | Modulex 13: 02-Target Setpoint (Modbus 41019/13) | Read | ||
| AV | 123 | setpt_13 | Modulex 13: 03-Req Outlet Temp (Modbus 41005/13) | Write | ||
| AV | 124 | boilercmd_13 | Modulex 13: 04-Net Direct Drive (Modbus 40002/13) | Write | ||
| AV | 125 | boilerload_13 | Modulex 13: 05-Mod Lev In (Modbus 41201/13) | Read | ||
| AV | 126 | localsuptemp_13 | Modulex 13: 06-Flow Sens Temp (Modbus 41003/13) | Read | ||
| AV | 127 | dispcode_13 | Modulex 13: 07-Display Code (Modbus 30001/13) | Read | ||
| AVmin | 128 | errcode_13 | Modulex 13: 11-Error Code (Modbus 40001/13) | Read | ||
| AV | 129 | unitstat_13 | Modulex 13: 08-Unit Status (Modbus 30002/13) | Read | ||
| AV | 130 | returntemp_13 | Modulex 13: 09-Ret Flow Temp (Modbus 41004/13) | Read | ||
| AV | 131 | boilerstate_14 | Modulex 14: 01-Act Mod Lev (Modbus 41009/14) | Read | ||
| AV | 132 | effectsetpt_14 | Modulex 14: 02-Target Setpoint (Modbus 41019/14) | Read | ||
| AV | 133 | setpt_14 | Modulex 14: 03-Req Outlet Temp (Modbus 41005/14) | Write | ||
| AV | 134 | boilercmd_14 | Modulex 14: 04-Net Direct Drive (Modbus 40002/14) | Write | ||
| AV | 135 | boilerload_14 | Modulex 14: 05-Mod Lev In (Modbus 41201/14) | Read | ||
| AV | 136 | localsuptemp_14 | Modulex 14: 06-Flow Sens Temp (Modbus 41003/14) | Read | ||
| AV | 137 | dispcode_14 | Modulex 14: 07-Display Code (Modbus 30001/14) | Read | ||
| AV | 138 | errcode_14 | Modulex 14: 11-Error Code (Modbus 40001/14) | Read | ||
| AV | 139 | unitstat_14 | Modulex 14: 08-Unit Status (Modbus 30002/14) | Read | ||
| AV | 140 | returntemp_14 | Modulex 14: 09-Ret Flow Temp (Modbus 41004/14) | Read | ||
| AV | 141 | boilerstate_15 | Modulex 15: 01-Act Mod Lev (Modbus 41009/15) | Read | ||
| AV | 142 | effectsetpt_15 | Modulex 15: 02-Target Setpoint (Modbus 41019/15) | Read | ||
| AV | 143 | setpt_15 | Modulex 15: 03-Req Outlet Temp (Modbus 41005/15) | Write | ||
| AV | 144 | boilercmd_15 | Modulex 15: 04-Net Direct Drive (Modbus 40002/15) | Write | ||
| AV | 145 | boilerload_15 | Modulex 15: 05-Mod Lev In (Modbus 41201/15) | Read | ||
| AV | 146 | localsuptemp_15 | Modulex 15: 06-Flow Sens Temp (Modbus 41003/15) | Read | ||
| AV | 147 | dispcode_15 | Modulex 15: 07-Display Code (Modbus 30001/15) | Read | ||
| AV | 148 | errcode_15 | Modulex 15: 11-Error Code (Modbus 40001/15) | Read | ||
| AV | 149 | unitstat_15 | Modulex 15: 08-Unit Status (Modbus 30002/15) | Read | ||
| AV | 150 | returntemp_15 | Modulex 15: 09-Ret Flow Temp (Modbus 41004/15) | Read | ||
| AV | 151 | boilerstate_16 | Modulex 16: 01-Act Mod Lev (Modbus 41009/16) | Read | ||
| AV | 152 | effectsetpt_16 | Modulex 16: 02-Target Setpoint (Modbus 41019/16) | Read | ||
| AV | 153 | setpt_16 | Modulex 16: 03-Req Outlet Temp (Modbus 41005/16) | Write | ||
| AV | 154 | boilercmd_16 | Modulex 16: 04-Net Direct Drive (Modbus 40002/16) | Write | ||
| AV | 155 | boilerload_16 | Modulex 16: 05-Mod Lev In (Modbus 41201/16) | Read | ||
| AV | 156 | localsuptemp_16 | Modulex 16: 06-Flow Sens Temp (Modbus 41003/16) | Read | ||
| AV | 157 | dispcode_16 | Modulex 16: 07-Display Code (Modbus 30001/16) | Read | ||
| AV | 158 | errcode_16 | Modulex 16: 11-Error Code (Modbus 40001/16) | Read | ||
| AV | 159 | unitstat_16 | Modulex 16: 08-Unit Status (Modbus 30002/16) | Read | ||
| AV | 160 | returntemp_16 | Modulex 16: 09-Ret Flow Temp (Modbus 41004/16) | Read | ||
| AV | 171 | boilerstate_17 | ECS/SmartPlate valve 17: 01-Cntl Output Signal (Modbus 30004/17) | Read | ||
| AV | 172 | effectsetpt_17 | ECS/SmartPlate valve 17: 02-Setpoint (Modbus 30006/17) | Read | ||
| AV | 173 | rmsetpt_17 | ECS/SmartPlate valve 17: 03-RmSetpt (Modbus 40027/17) | Write | ||
| AV | 174 | localsuptemp_17 | ECS/SmartPlate valve 17: 04-Outlet Temp (Modbus 30002/17) | Read | ||
| AV | 175 | localrettemp_17 | ECS/SmartPlate valve 17: 05-FBk Sensor Temp (Modbus 30170/17) | Read | ||
| AV | 176 | unitstat_17 | ECS/SmartPlate valve 17: 06-Over Temp Alarm (Modbus 30075/17) | Read | ||
| AV | 177 | flowrate_17 | ECS/SmartPlate valve 17: 07-Flow Rate (Modbus 30171/17) | Read | ||
| AV | 181 | boilerstate_18 | ECS/SmartPlate valve 18: 01-Cntl Output Signal (Modbus 18004/18) | Read | ||
| AV | 182 | effectsetpt_18 | ECS/SmartPlate valve 18: 02-Setpoint (Modbus 18006/18) | Read | ||
| AV | 183 | rmsetpt_18 | ECS/SmartPlate valve 18: 03-RmSetpt (Modbus 40027/18) | Write | ||
| AV | 184 | localsuptemp_18 | ECS/SmartPlate valve 18: 04-Outlet Temp (Modbus 18002/18) | Read | ||
| AV | 185 | localrettemp_18 | ECS/SmartPlate valve 18: 05-FBk Sensor Temp (Modbus 18290/18) | Read | ||
| AV | 186 | unitstat_18 | ECS/SmartPlate valve 18: 06-Over Temp Alarm (Modbus 18075/18) | Read | ||
| AV | 187 | flowrate_18 | ECS/SmartPlate valve 18: 07-Flow Rate (Modbus 18291/18) | Read | ||
| AV | 191 | boilerstate_19 | ECS/SmartPlate valve 19: 01-Cntl Output Signal (Modbus 30004/19) | Read | ||
| AV | 192 | effectsetpt_19 | ECS/SmartPlate valve 19: 02-Setpoint (Modbus 30006/19) | Read | ||
| AV | 193 | rmsetpt_19 | ECS/SmartPlate valve 19: 03-RmSetpt (Modbus 40027/19) | Write | ||
| AV | 194 | localsuptemp_19 | ECS/SmartPlate valve 19: 04-Outlet Temp (Modbus 30002/19) | Read | ||
| AV | 195 | localrettemp_19 | ECS/SmartPlate valve 19: 05-FBk Sensor Temp (Modbus 30290/19) | Read | ||
| AV | 196 | unitstat_19 | ECS/SmartPlate valve 19: 06-Over Temp Alarm (Modbus 30075/19) | Read | ||
| AV | 197 | flowrate_19 | ECS/SmartPlate valve 19: 07-Flow Rate (Modbus 30291/19) | Read | ||
| AV | 201 | boilerstate_20 | ECS/SmartPlate valve 20: 01-Cntl Output Signal (Modbus 30004/20) | Read | ||
| AV | 202 | effectsetpt_20 | ECS/SmartPlate valve 20: 02-Setpoint (Modbus 30006/20) | Read | ||
| AV | 203 | rmsetpt_20 | ECS/SmartPlate valve 20: 03-RmSetpt (Modbus 40027/20) | Write | ||
| AV | 204 | localsuptemp_20 | ECS/SmartPlate valve 20: 04-Outlet Temp (Modbus 30002/20) | Read | ||
| AV | 205 | localrettemp_20 | ECS/SmartPlate valve 20: 05-FBk Sensor Temp (Modbus 30290/20) | Read | ||
| AV | 206 | unitstat_20 | ECS/SmartPlate valve 20: 06-Over Temp Alarm (Modbus 30075/20) | Read | ||
| AV | 207 | flowrate_20 | ECS/SmartPlate valve 20: 07-Flow Rate (Modbus 30291/20) | Read | ||
| AV | 211 | boilerstate_21 | ECS/SmartPlate valve 21: 01-Cntl Output Signal (Modbus 30004/21) | Read | ||
| AV | 212 | effectsetpt_21 | ECS/SmartPlate valve 21: 02-Setpoint (Modbus 30006/21) | Read | ||
| AV | 213 | rmsetpt_21 | ECS/SmartPlate valve 21: 03-RmSetpt (Modbus 40027/21) | Write | ||
| AV | 214 | localsuptemp_21 | ECS/SmartPlate valve 21: 04-Outlet Temp (Modbus 30002/21) | Read | ||
| AV | 215 | localrettemp_21 | ECS/SmartPlate valve 21: 05-FBk Sensor Temp (Modbus 30290/21) | Read | ||
| AV | 216 | unitstat_21 | ECS/SmartPlate valve 21: 06-Over Temp Alarm (Modbus 30075/21) | Read | ||
| AV | 217 | flowrate_21 | ECS/SmartPlate valve 21: 07-Flow Rate (Modbus 30291/21) | Read | ||
| AV | 221 | boilerstate_22 | ECS/SmartPlate valve 22: 01-Cntl Output Signal (Modbus 30004/22) | Read | ||
| AV | 222 | effectsetpt_22 | ECS/SmartPlate valve 22: 02-Setpoint (Modbus 30006/22) | Read | ||
| AV | 223 | rmsetpt_22 | ECS/SmartPlate valve 22: 03-RmSetpt (Modbus 40027/22) | Write | ||
| AV | 224 | localsuptemp_22 | ECS/SmartPlate valve 22: 04-Outlet Temp (Modbus 30002/22) | Read | ||
| AV | 225 | localrettemp_22 | ECS/SmartPlate valve 22: 05-FBk Sensor Temp (Modbus 30290/22) | Read | ||
| AV | 226 | unitstat_22 | ECS/SmartPlate valve 22: 06-Over Temp Alarm (Modbus 30075/22) | Read | ||
| AV | 227 | flowrate_22 | ECS/SmartPlate valve 22: 07-Flow Rate (Modbus 30291/22) | Read | ||
| AV | 260 | boilerstate_128 | BMS II addr 128 (C-More BMS): 01-Fire Rate Out (Modbus 30005/128) | Read | ||
| AV | 261 | effectsetpt_128 | BMS II addr 128 (C-More BMS): 02-Header Set Temp (Modbus 30006/128) | Read | ||
| AVmin | 262 | setpt_128 | BMS II addr 128 (C-More BMS): 03-Net Header Set Temp (Modbus 40005/128) | Write | ||
| AVmin | 263 | localsuptemp_128 | BMS II addr 128 (C-More BMS): 04-Header Temp (Modbus 30002/128) | Read | ||
| AV | 264 | localoatemp_128 | BMS II addr 128 (C-More BMS): 05-Outside Air Temp (Modbus 30003/128) | Read | ||
| AVmin | 265 | dispcode_128 | BMS II addr 128 (C-More BMS): 06-Display Code (Modbus 30011/128) | Read | ||
| AVmin | 266 | blrfired_128 | BMS II addr 128 (C-More BMS): 07-Num Boilers Fired (Modbus 30008/128) | Read | ||
| AV | 267 | blronline_128 | BMS II addr 128 (C-More BMS): 08-Num Boilers Online (Modbus 30009/128) | Read | ||
| AV | 268 | blrlast_128 | BMS II addr 128 (C-More BMS): 09-Last Blr Fired (Modbus 30017/128) | Read | ||
| AV | 269 | blr1stat_128 | BMS II addr 128 (C-More BMS): 10-Boiler 1 Status (Modbus 30018/128) | Read | ||
| AV | 270 | blr2stat_128 | BMS II addr 128 (C-More BMS): 11-Boiler 2 Status (Modbus 30019/128) | Read | ||
| AV | 271 | blr3stat_128 | BMS II addr 128 (C-More BMS): 12-Boiler 3 Status (Modbus 30020/128) | Read | ||
| AV | 272 | blr4stat_128 | BMS II addr 128 (C-More BMS): 13-Boiler 4 Status (Modbus 30021/128) | Read | ||
| AV | 273 | blr5stat_128 | BMS II addr 128 (C-More BMS): 14-Boiler 5 Status (Modbus 30022/128) | Read | ||
| AV | 274 | blr6stat_128 | BMS II addr 128 (C-More BMS): 15-Boiler 6 Status (Modbus 30023/128) | Read | ||
| AV | 275 | blr7stat_128 | BMS II addr 128 (C-More BMS): 16-Boiler 7 Status (Modbus 30024/128) | Read | ||
| AV | 276 | blr8stat_128 | BMS II addr 128 (C-More BMS): 17-Boiler 8 Status (Modbus 30025/128) | Read | ||
| AV | 277 | blr9stat_128 | BMS II addr 128 (C-More BMS): 18-Net Blr 1 Status (Modbus 30026/128) | Read | ||
| AV | 278 | blr10stat_128 | BMS II addr 128 (C-More BMS): 19-Net Blr 2 Status (Modbus 30027/128) | Read | ||
| AV | 279 | blr11stat_128 | BMS II addr 128 (C-More BMS): 20-Net Blr 3 Status (Modbus 30028/128) | Read | ||
| AV | 280 | blr12stat_128 | BMS II addr 128 (C-More BMS): 21-Net Blr 4 Status (Modbus 30029/128) | Read | ||
| AV | 281 | blr13stat_128 | BMS II addr 128 (C-More BMS): 22-Net Blr 5 Status (Modbus 30030/128) | Read | ||
| AV | 282 | blr14stat_128 | BMS II addr 128 (C-More BMS): 23-Net Blr 6 Status (Modbus 30031/128) | Read | ||
| AV | 283 | blr15stat_128 | BMS II addr 128 (C-More BMS): 24-Net Blr 7 Status (Modbus 30032/128) | Read | ||
| AV | 284 | blr16stat_128 | BMS II addr 128 (C-More BMS): 25-Net Blr 8 Status (Modbus 30033/128) | Read | ||
| AV | 285 | blr17stat_128 | BMS II addr 128 (C-More BMS): 26-Net Blr 9 Status (Modbus 30034/128) | Read | ||
| AV | 286 | blr18stat_128 | BMS II addr 128 (C-More BMS): 27-Net Blr 10 Status (Modbus 30035/128) | Read | ||
| AV | 287 | blr19stat_128 | BMS II addr 128 (C-More BMS): 28-Net Blr 11 Status (Modbus 30036/128) | Read | ||
| AV | 288 | blr20stat_128 | BMS II addr 128 (C-More BMS): 29-Net Blr 12 Status (Modbus 30037/128) | Read | ||
| AV | 300 | boilerstate_228 | BMS II addr 228 (Modulex BCM): 01-Fire Rate Out (Modbus 30005/228) | Read | ||
| AV | 301 | effectsetpt_228 | BMS II addr 228 (Modulex BCM): 02-Header Set Temp (Modbus 30006/228) | Read | ||
| AVmin | 302 | setpt_228 | BMS II addr 228 (Modulex BCM): 03-Net Header Set Temp (Modbus 40005/228) | Write | ||
| AVmin | 303 | localsuptemp_228 | BMS II addr 228 (Modulex BCM): 04-Header Temp (Modbus 30002/228) | Read | ||
| AV | 304 | localoatemp_228 | BMS II addr 228 (Modulex BCM): 05-Outside Air Temp (Modbus 30003/228) | Read | ||
| AV | 305 | dispcode_228 | BMS II addr 228 (Modulex BCM): 06-Display Code (Modbus 30011/228) | Read | ||
| AV | 306 | blrfired_228 | BMS II addr 228 (Modulex BCM): 07-Num Boilers Fired (Modbus 30008/228) | Read | ||
| AV | 307 | blronline_228 | BMS II addr 228 (Modulex BCM): 08-Num Boilers Online (Modbus 30009/228) | Read | ||
| AV | 308 | blrlast_228 | BMS II addr 228 (Modulex BCM): 09-Last Blr Fired (Modbus 30017/228) | Read | ||
| AV | 309 | blr9stat_228 | BMS II addr 228 (Modulex BCM): 18-Net Blr 1 Status (Modbus 30026/228) | Read | ||
| AV | 310 | blr10stat_228 | BMS II addr 228 (Modulex BCM): 19-Net Blr 2 Status (Modbus 30027/228) | Read | ||
| AV | 311 | blr11stat_228 | BMS II addr 228 (Modulex BCM): 20-Net Blr 3 Status (Modbus 30028/228) | Read | ||
| AV | 312 | blr12stat_228 | BMS II addr 228 (Modulex BCM): 21-Net Blr 4 Status (Modbus 30029/228) | Read |
No points match these filters.
Object ID lookup: AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II point IDs by name
AV1boilerstate_1AV2effectsetpt_1AV3setpt_1AV5boilerload_1AV6localsuptemp_1AV7dispcode_1AV8unitstat_1AV9runcycles_1AV10runhours_1AV11boilerstate_2AV12effectsetpt_2AV13setpt_2AV15boilerload_2AV16localsuptemp_2AV17dispcode_2AV18unitstat_2AV19runcycles_2AV20runhours_2AV21boilerstate_3AV22effectsetpt_3AV23setpt_3AV25boilerload_3AV26localsuptemp_3AV27dispcode_3AV28unitstat_3AV29runcycles_3AV30runhours_3AV31boilerstate_4AV32effectsetpt_4AV33setpt_4AV35boilerload_4AV36localsuptemp_4AV37dispcode_4AV38unitstat_4AV39runcycles_4AV40runhours_4AV41boilerstate_5AV42effectsetpt_5AV43setpt_5AV45boilerload_5AV46localsuptemp_5AV47dispcode_5AV48unitstat_5AV49runcycles_5AV50runhours_5AV51boilerstate_6AV52effectsetpt_6AV53setpt_6AV55boilerload_6AV56localsuptemp_6AV57dispcode_6AV58unitstat_6AV59runcycles_6AV60runhours_6AV61boilerstate_7AV62effectsetpt_7AV63setpt_7AV65boilerload_7AV66localsuptemp_7AV67dispcode_7AV68unitstat_7AV69runcycles_7AV70runhours_7AV71boilerstate_8AV72effectsetpt_8AV73setpt_8AV75boilerload_8AV76localsuptemp_8AV77dispcode_8AV78unitstat_8AV79runcycles_8AV80runhours_8AV81boilerstate_9AV82effectsetpt_9AV83setpt_9AV85boilerload_9AV86localsuptemp_9AV87dispcode_9AV88unitstat_9AV89runcycles_9AV90runhours_9AV91boilerstate_10AV92effectsetpt_10AV93setpt_10AV95boilerload_10AV96localsuptemp_10AV97dispcode_10AV98unitstat_10AV99runcycles_10AV100runhours_10AV101boilerstate_11AV102effectsetpt_11AV103setpt_11AV105boilerload_11AV106localsuptemp_11AV107dispcode_11AV108unitstat_11AV109runcycles_11AV110runhours_11AV111boilerstate_12AV112effectsetpt_12AV113setpt_12AV115boilerload_12AV116localsuptemp_12AV117dispcode_12AV118unitstat_12AV119runcycles_12AV120runhours_12AV121boilerstate_13AV122effectsetpt_13AV123setpt_13AV124boilercmd_13AV125boilerload_13AV126localsuptemp_13AV127dispcode_13AV128errcode_13AV129unitstat_13AV130returntemp_13AV131boilerstate_14AV132effectsetpt_14AV133setpt_14AV134boilercmd_14AV135boilerload_14AV136localsuptemp_14AV137dispcode_14AV138errcode_14AV139unitstat_14AV140returntemp_14AV141boilerstate_15AV142effectsetpt_15AV143setpt_15AV144boilercmd_15AV145boilerload_15AV146localsuptemp_15AV147dispcode_15AV148errcode_15AV149unitstat_15AV150returntemp_15AV151boilerstate_16AV152effectsetpt_16AV153setpt_16AV154boilercmd_16AV155boilerload_16AV156localsuptemp_16AV157dispcode_16AV158errcode_16AV159unitstat_16AV160returntemp_16AV171boilerstate_17AV172effectsetpt_17AV173rmsetpt_17AV174localsuptemp_17AV175localrettemp_17AV176unitstat_17AV177flowrate_17AV181boilerstate_18AV182effectsetpt_18AV183rmsetpt_18AV184localsuptemp_18AV185localrettemp_18AV186unitstat_18AV187flowrate_18AV191boilerstate_19AV192effectsetpt_19AV193rmsetpt_19AV194localsuptemp_19AV195localrettemp_19AV196unitstat_19AV197flowrate_19AV201boilerstate_20AV202effectsetpt_20AV203rmsetpt_20AV204localsuptemp_20AV205localrettemp_20AV206unitstat_20AV207flowrate_20AV211boilerstate_21AV212effectsetpt_21AV213rmsetpt_21AV214localsuptemp_21AV215localrettemp_21AV216unitstat_21AV217flowrate_21AV221boilerstate_22AV222effectsetpt_22AV223rmsetpt_22AV224localsuptemp_22AV225localrettemp_22AV226unitstat_22AV227flowrate_22AV260boilerstate_128AV261effectsetpt_128AV262setpt_128AV263localsuptemp_128AV264localoatemp_128AV265dispcode_128AV266blrfired_128AV267blronline_128AV268blrlast_128AV269blr1stat_128AV270blr2stat_128AV271blr3stat_128AV272blr4stat_128AV273blr5stat_128AV274blr6stat_128AV275blr7stat_128AV276blr8stat_128AV277blr9stat_128AV278blr10stat_128AV279blr11stat_128AV280blr12stat_128AV281blr13stat_128AV282blr14stat_128AV283blr15stat_128AV284blr16stat_128AV285blr17stat_128AV286blr18stat_128AV287blr19stat_128AV288blr20stat_128AV300boilerstate_228AV301effectsetpt_228AV302setpt_228AV303localsuptemp_228AV304localoatemp_228AV305dispcode_228AV306blrfired_228AV307blronline_228AV308blrlast_228AV309blr9stat_228AV310blr10stat_228AV311blr11stat_228AV312blr12stat_228
Integration notes
- Taken from the sheet "12CMore-6MLX-4EC,SP-2ACS" of AERCO-ProtoNode-Control-Points.xlsx (an Excel file).
- The worksheet tab is named "12CMore-6MLX-4EC,SP-2ACS", but its title and table have 6 ECS valves (addresses 17-22) and 4 Modulex boilers (13-16).
- The sheet has a point label column and a Name column; the Name (unique per object) is used as the object name, and the AERCO label is in the description.
- Read-only follows the sheet's Read Only check mark; unmarked objects are listed as writable.
- The other sheets of the workbook (4/8/12 C-More, Modulex, ECS) repeat profiles already in the library (aerco/*-protonode), so they are not listed again.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)
How many BACnet points does the AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list) have?
This list has 232 BACnet objects: 232 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list) BACnet points are writable?
28 of the 232 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list) BACnet documentation?
The source is AERCO ProtoNode Control Points (BACnet/IP, BACnet MS/TP, Metasys N2 and LonWorks Points List), sheet 12 C-Mores, 6 ECS/SP, 4 Modulex and 2 BMS II, published free by AERCO at https://www.watts.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/57673-source/AERCO-ProtoNode-Control-Points.xlsx.
What are the minimum BACnet points to integrate the AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)?
Start with AV 262 setpt_128 (C-More plant header setpoint from the BMS); AV 302 setpt_228 (Modulex plant header setpoint from the BMS); AV 263 localsuptemp_128 (C-More plant header temperature); AV 303 localsuptemp_228 (Modulex plant header temperature); AV 266 blrfired_128 (Number of C-More boilers firing); AV 1 boilerstate_1 (C-More boiler 1 fire rate (repeat per boiler)); AV 8 unitstat_1 (C-More boiler 1 unit status (repeat per boiler)); AV 265 dispcode_128 (C-More BMS II display (fault) code); AV 128 errcode_13 (Modulex 13 error code (repeat per unit)).
How do I enable BMS control of the AERCO Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)?
The sheet marks setpt_128 / setpt_228 (network header setpoints), each C-More setpt_n (net remote setpoint), each Modulex setpt_n and boilercmd_n (requested outlet temperature and net direct drive) and each ECS rmsetpt_n as writable. It does not describe the BMS II or C-More modes needed for these to take effect.
How do I check these points on the real Combined plant: 12 C-More, 4 Modulex, 6 ECS/SmartPlate, 2 BMS II (ProtoNode points list)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AERCO BACnet points lists
- Digital DHW mixing valve system (water tempering)
AERCO ADMS Smart Water Tempering System
AERCO ADMS digital mixing (water tempering) systems for domestic hot water.
Also known as: ADMS, AERCO ADMS, Smart Water Tempering System, 106902, OMM-0126 - Boiler / water heater controller gateway
AERCO AM Series Dependent boiler / water heater (ProtoNode FPC-N34/N35)
AERCO AM Series boilers or water heaters set up as dependent units of a cascade, read through the AERCO ProtoNode FPC-N34 / FPC-N35.
Also known as: AM Series, AM Dependent, AM Dep, AERCO AM, ProtoNode FPC-N34, FPC-N35 - Boiler / water heater cascade controller gateway
AERCO AM Series Managing boiler / water heater (ProtoNode FPC-N34/N35)
AERCO AM Series boilers or water heaters set up as the managing (or stand-alone) unit of a cascade, read through the AERCO ProtoNode FPC-N34 / FPC-N35.
Also known as: AM Series, AM Manager, AM Mngr, AERCO AM, ProtoNode FPC-N34, FPC-N35 - Boiler controller
AERCO Benchmark E / Edge X
AERCO Benchmark E (BMK E) condensing boilers with the Edge X controller, including BST cascade plants; the table also lists the legacy Benchmark (BMK) Edge equivalents.
Also known as: BMK E, BMKE, Benchmark, Edge X, Edge controller, OMM-0173 - Boiler and water heater plant controller via ProtoNode gateway
AERCO C-More boilers / water heaters with BST or WHM (ProtoNode RER SSD)
AERCO C-More boilers running on-board BST sequencing and C-More water heaters (KC, Innovation) running WHM, up to 8 units, through the ProtoNode RER SSD profile.
Also known as: C-More, BST, Boiler Sequencing Technology, WHM, Water Heater Management, SSD, Slave/Slave Device, Innovation, KC, Benchmark, ProtoNode RER, 64084, GF-129, OMM-0080 - Boiler controller and plant sequencer via ProtoNode gateway
AERCO C-More boilers with ACS / BMS II (ProtoNode RER)
AERCO boilers with the C-More controller plus an ACS or BMS II plant sequencer, read through the AERCO ProtoNode RER.
Also known as: C-More, C-More controller, ACS, BMS II, BMS, ProtoNode RER, ProtoNode-RER, 64084, FPC-N34, GF-129, OMM-0080 - Water heater controller via ProtoNode gateway
AERCO ECS and SmartPlate water heaters (ProtoNode RER)
AERCO SmartPlate and ECS (Electric Valve) water heaters, up to four, read through the AERCO ProtoNode RER.
Also known as: ECS, Electronic Control System, SmartPlate, SmartPlate water heater, E Valve, ProtoNode RER, 64084, GF-129, OMM-0080 - Commercial water heater controller
AERCO Edge [ii] water heater controller (standalone / WHM)
AERCO Innovation 1600-2000 water heaters with the Edge [ii] controller, run standalone or as a WHM (Water Heater Management) manager or client.
Also known as: Edge [ii], Edge ii, Edge 2, WHM, Water Heater Management, Centurion, OMM-0176, Innovation 1600-2000 - Boiler controller and plant sequencer via ProtoNode gateway
AERCO Modulex boilers with BCM and ACS / BMS II (ProtoNode RER)
AERCO Modulex boilers with a BCM, up to four, plus an ACS or BMS II sequencer, read through the AERCO ProtoNode RER.
Also known as: Modulex, MLX, Modulex E8, BCM, ACS, BMS II, ProtoNode RER, 64084, GF-129, OMM-0080
Source: AERCO ProtoNode Control Points (BACnet/IP, BACnet MS/TP, Metasys N2 and LonWorks Points List), sheet 12 C-Mores, 6 ECS/SP, 4 Modulex and 2 BMS II. Object names, instances and units are reproduced as published; descriptions are our own.