Digital DHW mixing valve system (water tempering) · BACnet points list

AERCO ADMS Smart Water Tempering System BACnet points list

Updated 4 November 2026

Short answer

The ADMS control module (built by tekmar for AERCO) supports BACnet IP, BACnet MS/TP or Modbus RTU, picked in the BAS menu. The BACnet object list is small: temperatures, pressures, flows, mix ratio, energy, an error code, the recirculation pump relay and one writable DHW target.

This page lists 16 BACnet objects for the AERCO ADMS Smart Water Tempering System — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AERCO’s own free documentation, linked below.

Manufacturer
AERCO
Model
ADMS Smart Water Tempering System
Equipment
Digital DHW mixing valve system (water tempering)
Equipment type
Valves & actuators
BACnet objects
16 (1 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Application software J1268A (per the PICS)
Default device instance
1
Also known as
ADMS, AERCO ADMS, Smart Water Tempering System, 106902, OMM-0126
Source document
ADMS Smart Water Tempering System User Guide & Instruction Manual (BAS Integration section) · OMM-0126C · rev. 04/09/2026
Download CSV 16 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AERCO’s current documentation and the live device before use. Not official AERCO information. Terms of use.

BMS integration notes: AERCO ADMS Smart Water Tempering System

Integration in brief

Set BAS Type to BAC-IP or BAC-MSTP in the Building Automation menu and set the device ID (and MAC/baud for MS/TP). Set BAS Setpoint Max at the control to limit remote changes, then write AV 0 for the mixed outlet target. The rest is monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0DHW TargetMixed outlet target, °F (capped by AI 10)Write
AI 0DHW TempMixed outlet temperature, °FRead
AI 1DHW Recirc TempRecirculation return temperature, °FRead
AI 11Mix %Mix ratio, %Read
BO 0Recirc Pump RelayRecirculation pump running (read-only)Read
AI 13Error CodeError code, 0-30Read

Enable & remote start

No enable point. With a BAS type selected the BMS can write AV 0; the BAS Setpoint Max setting at the control (default 140 °F, range 80 °F up to the mixed outlet maximum less 10 °F) limits it.

Network setup

Watch out for

AERCO ADMS Smart Water Tempering System BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

16 of 16 shown
Type
Binary
Access
Show
AERCO ADMS Smart Water Tempering System BACnet Points List
DescriptionStates
AImin0DHW TempMixed outlet temperature°FRead
AImin1DHW Recirc TempRecirculation return temperature°FRead
AI2Hot TempHot inlet supply temperature°FRead
AI3Cold TempCold inlet supply temperature°FRead
AI4DHW PressureMixed outlet pressurepsiRead
AI5DHW Recirc PressureRecirculation pump inlet pressurepsiRead
AI6Hot PressureHot supply inlet pressurepsiRead
AI7Cold PressureCold supply inlet pressurepsiRead
AI8DHW FlowMixed outlet flow rategpmRead
AI9Recirc FlowRecirculation return flow rategpmRead
AI10DHW Target MaxHighest DHW target the BAS may set°FRead
AImin11Mix %Mix ratio: (DHW - cold) / (hot - cold)%Read
AI12Energy UsedTotalized energy through the unitthermsRead
AImin13Error CodeNumeric error code, 0-30Read
AVmin0DHW TargetMixed outlet temperature target, 50-180 °F°FWrite
BOmin0Recirc Pump RelayRecirculation pump statusRead0=Off, 1=On
Object ID lookup: AERCO ADMS Smart Water Tempering System point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ADMS Smart Water Tempering System and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AERCO ADMS Smart Water Tempering System

How many BACnet points does the AERCO ADMS Smart Water Tempering System have?

This list has 16 BACnet objects: 14 analog inputs, 1 analog value, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AERCO ADMS Smart Water Tempering System BACnet points are writable?

1 of the 16 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AERCO ADMS Smart Water Tempering System BACnet documentation?

The source is ADMS Smart Water Tempering System User Guide & Instruction Manual (BAS Integration section) (OMM-0126C), revision 04/09/2026, published free by AERCO at https://www.aerco.com/dfsmedia/0533dbba17714b1ab581ab07a4cbb521/658965-source/638779906930000000/adms-operation-and-maintenance-manual-omm-126.pdf.

What are the minimum BACnet points to integrate the AERCO ADMS Smart Water Tempering System?

Start with AV 0 DHW Target (Mixed outlet target, °F (capped by AI 10)); AI 0 DHW Temp (Mixed outlet temperature, °F); AI 1 DHW Recirc Temp (Recirculation return temperature, °F); AI 11 Mix % (Mix ratio, %); BO 0 Recirc Pump Relay (Recirculation pump running (read-only)); AI 13 Error Code (Error code, 0-30).

How do I enable BMS control of the AERCO ADMS Smart Water Tempering System?

No enable point. With a BAS type selected the BMS can write AV 0; the BAS Setpoint Max setting at the control (default 140 °F, range 80 °F up to the mixed outlet maximum less 10 °F) limits it.

How do I check these points on the real ADMS Smart Water Tempering System?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AERCO BACnet points lists

Source: ADMS Smart Water Tempering System User Guide & Instruction Manual (BAS Integration section) · OMM-0126C · rev. 04/09/2026. Object names, instances and units are reproduced as published; descriptions are our own.