Variable frequency drive (HVAC) · BACnet points list

Yaskawa HV600 HVAC drive (embedded BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The HV600 has BACnet MS/TP built into its RS-485 terminals (TB6); set H5-08 = 3 to select it. The fixed object list covers analog and digital I/O, run/fault/reset and emergency-override commands, frequency and PID setpoint references, output and energy monitors, fault codes and a long set of status flags. AV29/AV30 give indirect access to any drive parameter by Modbus register number.

This page lists 123 BACnet objects for the Yaskawa HV600 HVAC drive (embedded BACnet MS/TP) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Yaskawa’s own free documentation, linked below.

Manufacturer
Yaskawa
Model
HV600 HVAC drive (embedded BACnet MS/TP)
Equipment
Variable frequency drive (HVAC)
Equipment type
VFDs & pumps
BACnet objects
123 (34 writable)
Transport
BACnet MS/TP
Firmware
PICS lists application software VSEA010xx, firmware revision 2.01
Default device instance
1
Also known as
HV600, HV60U, HV600 AC drive, HV600 BACnet MS/TP, SIEPC71061732
Source document
YASKAWA HV600 Drive Technical Reference (section 6.3, BACnet Communications) · SIEPC71061732F · rev. 2024-02
Download CSV 123 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Yaskawa’s current documentation and the live device before use. Not official Yaskawa information. Terms of use.

BMS integration notes: Yaskawa HV600 HVAC drive (embedded BACnet MS/TP)

Integration in brief

Set H5-08 = 3 (BACnet), the MS/TP address in H5-01, the baud rate in H5-02, H5-12 = 0 and the device instance in H5-14/H5-15, then cycle power or set H5-20 = 1. Set b1-01 = 2 and b1-02 = 2 (or an AUTO + serial run setting) so the network supplies the frequency reference and run command. Write BV1 RUN FWD and AV2 Frequency Command, read BV13/BV16 and AV10/AV12/AV13, and reset faults with BV4.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1RUN FWDStart/stop from the BMS (drive)Command
AV 2Frequency CommandFrequency reference, units per o1-03Command
BV 4FAULT RESETReset a tripped driveCommand
BV 13RUN-STOPRunning statusRead
BV 15READYDrive ready to runRead
AV 10Output FrequencyOutput frequency, units per o1-03Read
AV 12Output CurrentMotor ampsRead
AV 13Output PowerDrive power in kWRead
BV 16FAULTAny active drive faultRead
AV 40Last Drive FaultMost recent fault codeRead

Enable & remote start

Set b1-01 Frequency Reference Selection 1 = 2 (Serial Communications) and b1-02 Run Command Selection 1 = 2 (Serial Communications); b1-02 = 7, 8 or 9 combine the keypad AUTO command with terminal, serial or option run. With H5-12 = 0, BV1 runs forward and BV2 runs reverse. Monitoring, parameter access, fault reset and the multi-function inputs work whatever b1-01/b1-02 are set to.

Heartbeat & communication loss

H5-05 = 1 (default) turns on CE detection: if the drive gets no data from the master for H5-09 (0.0-10.0 s, default 2.0 s) it acts per H5-04: 0 ramp to stop, 1 coast, 2 fast stop (C1-09), 3 alarm only and keep running (default), 4 run at the H5-34 speed (H5-35 can then coast to stop with a CE fault after a set time).

Sensors & values from the BMS

AV3 PID Setpoint lets the BMS write the PID setpoint (0-100 %); BO4 Ref Sel: PID Setpoint (or AV5 bit 1) selects it. The object list has no writable PID feedback.

Network setup

Watch out for

Yaskawa HV600 HVAC drive (embedded BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

123 of 123 shown
Type
Access
Show
Yaskawa HV600 HVAC drive (embedded BACnet MS/TP) BACnet Points List
DescriptionStates
AI1Analog Input 1 LevelShown as 'Drv Anlog In 1 Level'; Modbus 004E%Read
AI2Analog Input 2 LevelShown as 'Drv Anlog In 2 Level'; Modbus 004F%Read
AI6Display Format o1-03Modbus 0502Read
AI7Scale Format b5-20Modbus 01E2Read
AI8Inverter Model o2-04Modbus 0508Read
AI9Rated Current n9-01Modbus 05D0ARead
AO1Analog Output 1 LevelShown as 'Drv Anlg Out1 Level'; Modbus 0007%Command
AO2Analog Output 2 LevelShown as 'Drv Anlg Out2 Level'; Modbus 0008%Command
AV1Operation Cmd (Bitmapped)Packed run/command word; Shown as 'Operation Cmd'; Modbus 0001Command
AVmin2Frequency CommandFrequency reference; Shown as 'Frequency Cmd'; Modbus 0002Hz (display units per o1-03)Command
AV3PID SetpointPID setpoint, 0-100 %; Shown as 'PI Setpoint Cmd'; Modbus 0006%Command
AV4MF Output Cmd (Bitmapped)Packed MF output word; Shown as 'MF Output Cmd'; Modbus 0009Command
AV5Reference Select Cmd (Bitmapped)Packed reference select word; Shown as 'Reference Select Cmd'; Modbus 000FCommand
AV6Drive Status (Bitmapped)Bitmap: run, reverse, ready, fault, outputs; Shown as 'Drive Status'; Modbus 0020Read
AV7Fault Details (Bitmapped)Bitmap of active fault groups; Shown as 'Fault Details'; Modbus 0021Read
AV8Data Link Status (Bitmapped)Bitmap of write/limit errors; Shown as 'Data Link Status'; Modbus 0022Read
AV9Frequency ReferenceModbus 0040Hz (display units per o1-03)Read
AVmin10Output FrequencyModbus 0041Hz (display units per o1-03)Read
AV11Output VoltageModbus 0045VRead
AVmin12Output CurrentModbus 0026ARead
AVmin13Output PowerModbus 0047kWRead
AV14Torque ReferenceModbus 0048%Read
AV15MF Input StatusBitmap of multi-function input statesRead
AV16Drive Status 2Bitmap of operating status flagsRead
AV17MF Output StatusBitmap of multi-function output statesRead
AV18DC Bus VoltageModbus 0031VRead
AV19PID Feedback LevelShown as 'PI Feedback Level'; Modbus 0038%Read
AV20PID Input LevelShown as 'PI Input Level'; Modbus 0039%Read
AV21PID Output LevelShown as 'PI Output Level'; Modbus 003A%Read
AV22CPU SoftwareModbus 005BRead
AV23Flash NumberModbus 004DRead
AV24Comm Error DetailBitmap of serial communication errors; Modbus 003DRead
AV25kVA SettingModbus 0508Read
AV26Control MethodModbus 0043Read
AV27Accel TimeModbus 0200sWrite
AV28Decel TimeModbus 0201sWrite
AV29Param NumberRegister number (decimal) for AV30; Shown as 'Parameter Number'Write
AV30Param DataData for the register in AV29; Shown as 'Parameter Data'Write
AV33Drive kWh ConsumedShown as 'kWh Consumed'; Modbus 005C - 005DkWhRead
AV35Drive Run TimeModbus 004ChRead
AV36Out Freq in %Shown as 'Output Freq in %'; Modbus 003F%Read
AV37Out Freq in RPMShown as 'Output Freq in RPM'; Modbus 003ERPMRead
AV38Torque Iq (U6-01)Modbus 0051%Read
AV39Drive HOA StatusHand/Off/Auto state; Modbus 004BRead
AVmin40Last Drive FaultMost recent fault code; Modbus 0081Read
AV42Current Sys FaultActive fault code; Shown as 'Current Sys Flt'; Modbus 0080Read
BI1Drive Input Terminal 1Shown as 'Input Terminal 1'; Modbus 002B: bit 0ReadActive: ON, Inactive: OFF
BI2Drive Input Terminal 2Shown as 'Input Terminal 2'; Modbus 002B: bit 1ReadActive: ON, Inactive: OFF
BI3Drive Input Terminal 3Shown as 'Input Terminal 3'; Modbus 002B: bit 2ReadActive: ON, Inactive: OFF
BI4Drive Input Terminal 4Shown as 'Input Terminal 4'; Modbus 002B: bit 3ReadActive: ON, Inactive: OFF
BI5Drive Input Terminal 5Shown as 'Input Terminal 5'; Modbus 002B: bit 4ReadActive: ON, Inactive: OFF
BI6Drive Input Terminal 6Shown as 'Input Terminal 6'; Modbus 002B: bit 5ReadActive: ON, Inactive: OFF
BI7Drive Input Terminal 7Shown as 'Input Terminal 7'; Modbus 002B: bit 6ReadActive: ON, Inactive: OFF
BI8Drive Multi-Function Out 1Shown as 'Multi Function Out 1'; Modbus 0020: bit 5ReadActive: ON, Inactive: OFF
BI9Drive Multi-Function Out 2Shown as 'Multi Function Out 2'; Modbus 0020: bit 6ReadActive: ON, Inactive: OFF
BI28Drive Fault StatusModbus 004B: bit 7ReadActive: ON, Inactive: OFF
BI29Drive Alarm StatusModbus 004B: bit 6ReadActive: ON, Inactive: OFF
BO1MF Output M1-M2Shown as 'MF Output, M1 - M2'; Modbus 0009: bit 0CommandActive: ON, Inactive: OFF
BO2MF Output M3-M4Shown as 'MF Output, M3 - M4'; Modbus 0009: bit 1CommandActive: ON, Inactive: OFF
BO3MF Output M5-M6Shown as 'MF Output, M5 - M6'; Modbus 0009: bit 2CommandActive: ON, Inactive: OFF
BO4Ref Sel: PID SetpointShown as 'Ref Sel: PI Setpoint'; Modbus 000F: bit 1CommandActive: ON, Inactive: OFF
BO5Ref Sel: Term S5 INModbus 000F: bit 8CommandActive: ON, Inactive: OFF
BO6Ref Sel: Term S6 INModbus 000F: bit 9CommandActive: ON, Inactive: OFF
BO7Refl Sel: Term S7 INShown as 'Ref Sel: Term S7 In'; Modbus 000F: bit 10CommandActive: ON, Inactive: OFF
BVmin1RUN FWDRun forward command; Shown as 'Run FWD Cmd'; Modbus 0001: bit 0CommandActive: RUN, Inactive: OFF
BV2RUN REVRun reverse command; Shown as 'Run REV Cmd'; Modbus 0001: bit 1CommandActive: REV, Inactive: OFF
BV3EXT FAULTShown as 'Ext Fault Cmd'; Modbus 0001: bit 2CommandActive: FAULT, Inactive: OFF
BVmin4FAULT RESETReset drive fault; Shown as 'Fault Reset Cmd'; Modbus 0001: bit 3CommandActive: RESET, Inactive: OFF
BV5COM NETNetwork frequency reference; Shown as 'Com Net Cmd'; internal, no Modbus registerCommandActive: COM, Inactive: LOCAL
BV6COM CNTRLNetwork run command; Shown as 'Com Cntrl Cmd'; internal, no Modbus registerCommandActive: COM, Inactive: LOCAL
BV7MF Input 3 CmdModbus 0001: bit 6CommandActive: ON, Inactive: OFF
BV8MF Input 4 CmdModbus 0001: bit 7CommandActive: ON, Inactive: OFF
BV9MF Input 5 CmdModbus 0001: bit 8CommandActive: ON, Inactive: OFF
BV10MF Input 6 CmdModbus 0001: bit 9CommandActive: ON, Inactive: OFF
BV11MF Input 7 CmdModbus 0001: bit 10CommandActive: ON, Inactive: OFF
BV12Set Fault Contact CmdShown as 'Set Flt Contact Cmd'; Modbus 0009: bit 6CommandActive: ENABLE, Inactive: OFF
BVmin13RUN-STOPModbus 0020: bit 0ReadActive: RUN, Inactive: OFF
BV14REV-FWDModbus 0020: bit 1ReadActive: REV, Inactive: FWD
BVmin15READYModbus 0020: bit 2ReadActive: READY, Inactive: OFF
BVmin16FAULTModbus 0020: bit 3ReadActive: FAULTED, Inactive: OFF
BV17Data Set ErrorModbus 0020: bit 4ReadActive: ERROR, Inactive: OFF
BV18Overcurrent - Ground FaultShown as 'OverCurrent- Gnd Flt'; Modbus 0021: bit 0ReadActive: OC-GF, Inactive: OFF
BV19Main Circuit OvervoltageShown as 'Main Ckt OverVoltage'; Modbus 0021: bit 1ReadActive: OV, Inactive: OFF
BV20Drive OverloadModbus 0021: bit 2ReadActive: OL2, Inactive: OFF
BV21Drive OverheatModbus 0021: bit 3ReadActive: OH1-OH2, Inactive: OFF
BV22Fuse BlownModbus 0021: bit 5ReadActive: PUF, Inactive: OFF
BV23PID Feedback LossShown as 'PI Feedback Loss'; Modbus 0021: bit 6ReadActive: FBL, Inactive: OFF
BV24External FaultModbus 0021: bit 7ReadActive: EF0-EF, Inactive: OFF
BV25Hardware ErrorModbus 0021: bit 8ReadActive: CPF, Inactive: OFF
BV26Mtr Ovrld-OvrTorqueModbus 0021: bit 9ReadActive: OL1-OL3, Inactive: OFF
BV27OverspeedModbus 0021: bit 10ReadActive: OS-DEV, Inactive: OFF
BV28Main CKT UndervoltageShown as 'Main Ckt UndrVoltage'; Modbus 0021: bit 11ReadActive: UV, Inactive: OFF
BV29MCU, Cntl Pwr Sy ErrShown as 'MCU Cntrl Pwr Sy Err'; Modbus 0021: bit 12ReadActive: UV1-2-3, Inactive: OFF
BV30Output Phase LossModbus 0021: bit 13ReadActive: LF, Inactive: OFF
BV31Communication ErrorModbus 0021: bit 14ReadActive: CE, Inactive: OFF
BV32Operator DisconnectModbus 0021: bit 15ReadActive: OPR, Inactive: OFF
BV33OperatingModbus 002C: bit 0ReadActive: OPERATING, Inactive: OFF
BV34Zero SpeedModbus 002C: bit 1ReadActive: ON, Inactive: OFF
BV35Frequency AgreeModbus 002C: bit 2ReadActive: ON, Inactive: OFF
BV36Desired Frequency AgreeShown as 'Desired Freq Agree'; Modbus 002C: bit 3ReadActive: ON, Inactive: OFF
BV37Frequency Detect 1Modbus 002C: bit 4ReadActive: ON, Inactive: OFF
BV38Frequency Detect 2Modbus 002C: bit 5ReadActive: ON, Inactive: OFF
BV39Drive Startup CompleteShown as 'Drv Startup Complete'; Modbus 002C: bit 6ReadActive: ON, Inactive: OFF
BV40Low Voltage DetectModbus 002C: bit 7ReadActive: ON, Inactive: OFF
BV41Base BlockModbus 002C: bit 8ReadActive: ON, Inactive: OFF
BV42Frequency Reference ModeShown as 'Frequency Ref Mode'; Modbus 002C: bit 9ReadActive: LOCAL, Inactive: COM
BV43Run Command ModeModbus 002C: bit 10ReadActive: LOCAL, Inactive: COM
BV44Overtorque DetectModbus 002C: bit 11ReadActive: ON, Inactive: OFF
BV45Frequency Refer LostShown as 'Frequency Ref Loss'; Modbus 002C: bit 12ReadActive: ON, Inactive: OFF
BV46Retry ErrorModbus 002C: bit 13ReadActive: ON, Inactive: OFF
BV47Modbus Comms ErrorModbus 002C: bit 14ReadActive: ON, Inactive: OFF
BV48Modbus Timeout ErrorModbus 002C: bit 15ReadActive: ON, Inactive: OFF
BV49CRC ErrorModbus 003D: bit 0ReadActive: ON, Inactive: OFF
BV50Invalid Data LengthModbus 003D: bit 1ReadActive: ON, Inactive: OFF
BV51Parity ErrorModbus 003D: bit 3ReadActive: ON, Inactive: OFF
BV52Overrun ErrorModbus 003D: bit 4ReadActive: ON, Inactive: OFF
BV53Framing ErrorModbus 003D: bit 5ReadActive: ON, Inactive: OFF
BV54Timeout ErrorModbus 003D: bit 6ReadActive: ON, Inactive: OFF
BV55Parameter AcceptON = apply AV29/AV30 write to RAM only; internal, no Modbus registerWriteActive: ON, Inactive: OFF
BV56Parameter EnterON = apply AV29/AV30 write and save to EEPROM; internal, no Modbus registerWriteActive: ON, Inactive: OFF
BV57Drive Comm ErrorShown as 'Drive Comms Error'; Modbus 002C: bit FReadActive: ON, Inactive: OFF
BV60Emergency Override Drive ReverseEmergency override, drive reverse; Shown as 'Em Over DRV REV CMD'; internal, no Modbus registerCommandActive: ON, Inactive: OFF
BV63Emergency Override Drive ForwardEmergency override, drive forward; Shown as 'Em Over DRV FWD CMD'; internal, no Modbus registerCommandActive: ON, Inactive: OFF
Object ID lookup: Yaskawa HV600 HVAC drive point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HV600 HVAC drive (embedded BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Yaskawa HV600 HVAC drive (embedded BACnet MS/TP)

How many BACnet points does the Yaskawa HV600 HVAC drive (embedded BACnet MS/TP) have?

This list has 123 BACnet objects: 6 analog inputs, 2 analog outputs, 38 analog values, 11 binary inputs, 7 binary outputs, 59 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Yaskawa HV600 HVAC drive (embedded BACnet MS/TP) BACnet points are writable?

34 of the 123 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Yaskawa HV600 HVAC drive (embedded BACnet MS/TP) BACnet documentation?

The source is YASKAWA HV600 Drive Technical Reference (section 6.3, BACnet Communications) (SIEPC71061732F), revision 2024-02, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPC71061732&cmd=documents&documentName=SIEPC71061732.pdf.

What are the minimum BACnet points to integrate the Yaskawa HV600 HVAC drive (embedded BACnet MS/TP)?

Start with BV 1 RUN FWD (Start/stop from the BMS (drive)); AV 2 Frequency Command (Frequency reference, units per o1-03); BV 4 FAULT RESET (Reset a tripped drive); BV 13 RUN-STOP (Running status); BV 15 READY (Drive ready to run); AV 10 Output Frequency (Output frequency, units per o1-03); AV 12 Output Current (Motor amps); AV 13 Output Power (Drive power in kW); BV 16 FAULT (Any active drive fault); AV 40 Last Drive Fault (Most recent fault code).

How do I enable BMS control of the Yaskawa HV600 HVAC drive (embedded BACnet MS/TP)?

Set b1-01 Frequency Reference Selection 1 = 2 (Serial Communications) and b1-02 Run Command Selection 1 = 2 (Serial Communications); b1-02 = 7, 8 or 9 combine the keypad AUTO command with terminal, serial or option run. With H5-12 = 0, BV1 runs forward and BV2 runs reverse. Monitoring, parameter access, fault reset and the multi-function inputs work whatever b1-01/b1-02 are set to.

Does the Yaskawa HV600 HVAC drive (embedded BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

H5-05 = 1 (default) turns on CE detection: if the drive gets no data from the master for H5-09 (0.0-10.0 s, default 2.0 s) it acts per H5-04: 0 ramp to stop, 1 coast, 2 fast stop (C1-09), 3 alarm only and keep running (default), 4 run at the H5-34 speed (H5-35 can then coast to stop with a CE fault after a set time).

Can the BMS supply sensor values to the Yaskawa HV600 HVAC drive (embedded BACnet MS/TP)?

AV3 PID Setpoint lets the BMS write the PID setpoint (0-100 %); BO4 Ref Sel: PID Setpoint (or AV5 bit 1) selects it. The object list has no writable PID feedback.

How do I check these points on the real HV600 HVAC drive (embedded BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Yaskawa BACnet points lists

Source: YASKAWA HV600 Drive Technical Reference (section 6.3, BACnet Communications) · SIEPC71061732F · rev. 2024-02. Object names, instances and units are reproduced as published; descriptions are our own.