Variable frequency drive BACnet MS/TP option card · BACnet points list

Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive) BACnet points list

Updated 6 November 2026

Short answer

The SI-B3/V is the V1000 version of Yaskawa's BACnet MS/TP option card. Its fixed object list mirrors the drive's Modbus registers: analog and digital I/O, run/fault/reset commands, frequency and PI setpoint references, output monitors, fault and status flags, and (on newer option software) energy, run-time and fault-code objects. AV29/AV30 give generic access to any drive parameter.

This page lists 120 BACnet objects for the Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive) — 31 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Yaskawa’s own free documentation, linked below.

Manufacturer
Yaskawa
Model
SI-B3/V BACnet MS/TP option (V1000 drive)
Equipment
Variable frequency drive BACnet MS/TP option card
Equipment type
VFDs & pumps
BACnet objects
120 (31 writable)
Transport
BACnet MS/TP
Firmware
PICS lists application software VST80026x, firmware 1.8; AV33 needs VST800265+, AV35-AV42 and BI28-BI29 need VST800266+
Default device instance
1
Also known as
SI-B3/V, SI-B3 V1000, V1000 BACnet, V1000 BACnet MS/TP, CIMR-VA BACnet, TOEP YAICOM 19
Source document
YASKAWA AC Drive V1000 Option BACnet MS/TP Installation & Technical Manual, Type SI-B3/V · TOEP YAICOM 19B · rev. 2017-12
Download CSV 120 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Yaskawa’s current documentation and the live device before use. Not official Yaskawa information. Terms of use.

BMS integration notes: Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive)

Integration in brief

Fit the SI-B3/V, set the MS/TP address in F6-45, the baud rate in F6-46 and the device instance in F6-48/F6-49, and power-cycle. Set b1-01 = 3 and b1-02 = 3 (Option PCB) so BACnet supplies the frequency reference and run command. Write BV1 Run FWD Cmd and AV2 Frequency Cmd, read BV13/BV16 and AV10/AV12/AV13, and reset faults with BV4.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Run FWD CmdStart/stop from the BMS (drive)Command
AV 2Frequency CmdFrequency reference, units per o1-03Command
BV 4Fault Reset CmdReset a tripped driveCommand
BV 13RUN-STOPRunning statusRead
BV 15READYDrive ready to runRead
AV 10Output FrequencyOutput frequency, units per o1-03Read
AV 12Output CurrentMotor ampsRead
AV 13Output PowerDrive power in kWRead
BV 16FAULTAny active drive faultRead
AV 40Last Drive FaultMost recent fault codeRead

Enable & remote start

b1-01 Frequency Reference Selection = 3 (Option PCB) and b1-02 Run Command Selection = 3 (Option PCB); both default to 1 (terminals). b1-15/b1-16 = 3 do the same for External Reference 2. Monitoring, parameter access, fault set/reset and the multi-function inputs work at any time.

Heartbeat & communication loss

The drive raises bUS (Option Communication Error) when the link drops after communication was established, but only when the run command or frequency reference comes from the option (b1-01 = 3 or b1-02 = 3). F6-04 sets the bUS delay (default 2.0 s) and F7-16 a communication-loss timeout (0.0-30.0 s, default 0 = off, option software VST800265+); the fault is sent after F7-16 + F6-04. F6-01 = 3 or higher makes bUS an alarm only; F6-14 = 1 resets the fault when communication returns.

Sensors & values from the BMS

AV3 PI Setpoint Cmd lets the BMS write the PI setpoint (0-100 %); BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it.

Network setup

Watch out for

Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

120 of 120 shown
Type
Access
Show
Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive) BACnet Points List
DescriptionStates
AI1Analog Input 1 LevelModbus 004EH%Read
AI2Analog Input 2 LevelModbus 004FH%Read
AI6Display Format o1-03Modbus 0502HRead
AI7Scale Format b5-20Modbus 01E2HRead
AI8Inverter Model o2-04Modbus 0508FRead
AI9Rated Current n9-01Modbus 05D0HARead
AO1Analog Output 1 LevelModbus 0007H%Command
AV1Operation CmdPacked run/command word; Modbus 0001HCommand
AVmin2Frequency CmdFrequency reference; Modbus 0002HHz (display units per o1-03)Command
AV3PI Setpoint CmdPI setpoint, 0-100 %; Modbus 0006H%Command
AV4MF Output 1 CmdPacked multi-function output word; Modbus 0009HCommand
AV5Reference Select CmdPacked reference select word; Modbus 000FHCommand
AV6Drive StatusBitmap of drive status; Modbus 0020HRead
AV7Fault DetailsBitmap of active fault groups; Modbus 0021HRead
AV8Data Link StatusBitmap of register write errors; Modbus 0022HRead
AV9Frequency ReferenceModbus 0040HHz (display units per o1-03)Read
AVmin10Output FrequencyModbus 0041HHz (display units per o1-03)Read
AV11Output VoltageModbus 0045HVRead
AVmin12Output CurrentModbus 0026HARead
AVmin13Output PowerModbus 0047kWRead
AV14Torque Reference (U1-09)Modbus 0048H%Read
AV15MF Input StatusBitmap of multi-function input states; Modbus 002BHRead
AV16Drive Status 2Bitmap of operating status flags; Modbus 002CHRead
AV17MF Output StatusBitmap of multi-function output states; Modbus 002DHRead
AV18DC Bus VoltageModbus 0031HVRead
AV19PI Feedback LevelModbus 0038H%Read
AV20PI Input LevelModbus 0039H%Read
AV21PI Output LevelModbus 003AH%Read
AV22CPU SoftwareModbus 004DHRead
AV23Flash NumberModbus 005BHRead
AV24Comm Error DetailBitmap of serial communication errors; Modbus 003DHRead
AV25kVA SettingModbus 0508HRead
AV26Control MethodModbus 0102HRead
AV27Accel TimeModbus 0200HsWrite
AV28Decel TimeModbus 0201HsWrite
AV29Parameter NumberRegister number (decimal) for AV30Write
AV30Parameter DataData for the register in AV29Write
AV33Drive kWhEnergy used, 0.1 kWh resolution; Modbus 005CH & 005DH; needs option software VST800265+Read
AV35Drive Run TimeModbus 004CH; needs option software VST800266+hRead
AV36Output Freq In %Modbus 003FH; needs option software VST800266+%Read
AV37Output Freq In RPMModbus 003EH; needs option software VST800266+RPMRead
AV38Torque Iq (U6-01)Modbus 0051H; needs option software VST800266+%Read
AV39Drv Ctrl StatusDrive control status; Modbus 07DDH; needs option software VST800266+Read
AVmin40Last Drive FaultMost recent fault code; Modbus 0081H; needs option software VST800266+Read
AV42Current Sys FaultActive fault code; Modbus 0080H; needs option software VST800266+Read
BI1Input Terminal 1Modbus 002BH:bit 0ReadActive: ON, Inactive: OFF
BI2Input Terminal 2Modbus 002BH:bit 1ReadActive: ON, Inactive: OFF
BI3Input Terminal 3Modbus 002BH:bit 2ReadActive: ON, Inactive: OFF
BI4Input Terminal 4Modbus 002BH:bit 3ReadActive: ON, Inactive: OFF
BI5Input Terminal 5Modbus 002BH:bit 4ReadActive: ON, Inactive: OFF
BI6Input Terminal 6Modbus 002BH:bit 5ReadActive: ON, Inactive: OFF
BI7Input Terminal 7Modbus 002BH:bit 6ReadActive: ON, Inactive: OFF
BI8Multi-Function Out 1Modbus 0020H:bit 5ReadActive: ON, Inactive: OFF
BI9Multi-Function Out 2Modbus 0020H:bit 6ReadActive: ON, Inactive: OFF
BI28Drive Fault StatusModbus 004BH:bit 7; needs option software VST800266+ReadActive: FAULT, Inactive: OK
BI29Drive Alarm StatusModbus 004BH:bit 6; needs option software VST800266+ReadActive: ALARM, Inactive: OK
BO1MF Output M1-M2Modbus 0009H:bit 0CommandActive: ON, Inactive: OFF
BO2MF Output P1-PCModbus 0009H:bit 1CommandActive: ON, Inactive: OFF
BO3MF Output P2-PCModbus 0009H:bit 2CommandActive: ON, Inactive: OFF
BO4Ref Sel: PI SetpointModbus 000FH:bit 1CommandActive: ON, Inactive: OFF
BO5Ref Sel: Term S5 INModbus 0001H: bit 8CommandActive: ON, Inactive: OFF
BO6Ref Sel: Term S6 INModbus 0001H: bit 9CommandActive: ON, Inactive: OFF
BO7Ref Sel: Term S7 INModbus 0001H: bit 10CommandActive: ON, Inactive: OFF
BVmin1Run FWD CmdRun forward command; Modbus 0001H:bit 0CommandActive: RUN, Inactive: OFF
BV2Run REV CmdRun reverse command; Modbus 0001H:bit 1CommandActive: REV, Inactive: OFF
BV3Ext Fault CmdModbus 0001H:bit 2CommandActive: FAULT, Inactive: OFF
BVmin4Fault Reset CmdReset drive fault; Modbus 0001H:bit 3CommandActive: RESET, Inactive: OFF
BV5Com Net CmdFrequency reference from network; Modbus 0001H:bit 4CommandActive: COM, Inactive: LOCAL
BV6Com Cntrl CmdRun command from network; Modbus 0001H:bit 5CommandActive: COM, Inactive: LOCAL
BV7MF Input 3 CmdModbus 0001H:bit 6CommandActive: ON, Inactive: OFF
BV8MF Input 4 CmdModbus 0001H:bit 7CommandActive: ON, Inactive: OFF
BV9MF Input 5 CmdModbus 0001H:bit 8CommandActive: ON, Inactive: OFF
BV10MF Input 6 CmdModbus 0001H:bit 9CommandActive: ON, Inactive: OFF
BV11MF Input 7 CmdModbus 0001H:bit 10CommandActive: ON, Inactive: OFF
BV12Set Fault Contact CmdModbus 0009H:bit 6CommandActive: ENABLE, Inactive: OFF
BVmin13RUN-STOPModbus 0020H:bit 0ReadActive: RUN, Inactive: OFF
BV14REV-FWDModbus 0020H:bit 1ReadActive: REV, Inactive: FWD
BVmin15READYModbus 0020H:bit 2ReadActive: READY, Inactive: OFF
BVmin16FAULTModbus 0020H:bit 3ReadActive: FAULTED, Inactive: OFF
BV17Data Set ErrorModbus 0020H:bit 4ReadActive: ERROR, Inactive: OFF
BV18Overcurrent – Gnd FaultModbus 0021H:bit 0ReadActive: OC-GF, Inactive: OFF
BV19Main Ckt OvervoltageModbus 0021H:bit 1ReadActive: OV, Inactive: OFF
BV20Drive OverloadModbus 0021H:bit 2ReadActive: OL2, Inactive: OFF
BV21Drive OverheatModbus 0021H:bit 3ReadActive: OH1-OH2, Inactive: OFF
BV22Fuse BlownModbus 0021H:bit 5ReadActive: PUF, Inactive: OFF
BV23PI Feedback LossModbus 0021H:bit 6ReadActive: FBL, Inactive: OFF
BV24External FaultModbus 0021H:bit 7ReadActive: EF0-EF, Inactive: OFF
BV25Hardware ErrorModbus 0021H:bit 8ReadActive: CPF, Inactive: OFF
BV26Mtr Ovrld-OvrTorqueModbus 0021H:bit 9ReadActive: OL1-OL3, Inactive: OFF
BV27OverspeedModbus 0021H:bit 10ReadActive: OS-DEV, Inactive: OFF
BV28Main Ckt UndervoltageModbus 0021H:bit 11ReadActive: UV, Inactive: OFF
BV29MCU, Cntl Pwr Sy ErrModbus 0021H:bit 12ReadActive: UV1-2-3, Inactive: OFF
BV30Output Phase LossModbus 0021H:bit 13ReadActive: LF, Inactive: OFF
BV31Communication ErrorModbus 0021H:bit 14ReadActive: CE, Inactive: OFF
BV32Operator DisconnectModbus 0021H:bit 15ReadActive: OPR, Inactive: OFF
BV33OperatingModbus 002CH:bit 0ReadActive: OPERATING, Inactive: OFF
BV34Zero SpeedModbus 002CH:bit 1ReadActive: ON, Inactive: OFF
BV35Frequency AgreeModbus 002CH:bit 2ReadActive: ON, Inactive: OFF
BV36Desired Freq AgreeModbus 002CH:bit 3ReadActive: ON, Inactive: OFF
BV37Frequency Detect 1Modbus 002CH:bit 4ReadActive: ON, Inactive: OFF
BV38Frequency Detect 2Modbus 002CH:bit 5ReadActive: ON, Inactive: OFF
BV39Drv Startup CompleteModbus 002CH:bit 6ReadActive: ON, Inactive: OFF
BV40Low Voltage DetectModbus 002CH:bit 7ReadActive: ON, Inactive: OFF
BV41Base BlockModbus 002CH:bit 8ReadActive: ON, Inactive: OFF
BV42Frequency Ref ModeModbus 002CH:bit 9ReadActive: COM, Inactive: LOCAL
BV43Run Command ModeModbus 002CH:bit 10ReadActive: COM, Inactive: LOCAL
BV44Overtorque DetectModbus 002CH:bit 11ReadActive: ON, Inactive: OFF
BV45Frequency Refer LostModbus 002CH:bit 12ReadActive: ON, Inactive: OFF
BV46Retry ErrorModbus 002CH:bit 13ReadActive: ON, Inactive: OFF
BV47Modbus Comms ErrorModbus 002CH:bit 14ReadActive: ON, Inactive: OFF
BV48Modbus Timeout ErrorModbus 002CH:bit 15ReadActive: ON, Inactive: OFF
BV49CRC ErrorModbus 003DH:bit 0ReadActive: ON, Inactive: OFF
BV50Invalid Data LengthModbus 003DH:bit 1ReadActive: ON, Inactive: OFF
BV51Parity ErrorModbus 003DH:bit 3ReadActive: ON, Inactive: OFF
BV52Overrun ErrorModbus 003DH:bit 4ReadActive: ON, Inactive: OFF
BV53Framing ErrorModbus 003DH:bit 5ReadActive: ON, Inactive: OFF
BV54Timeout ErrorModbus 003DH:bit 6ReadActive: ON, Inactive: OFF
BV55Parameter AcceptON = apply AV29/AV30 write to RAM only; Modbus 0910H:bit 0WriteActive: ON, Inactive: OFF
BV56Parameter EnterON = apply AV29/AV30 write and save to EEPROM; Modbus 0900H:bit 0WriteActive: ON, Inactive: OFF
BV57Drive Comms ErrorReadActive: ON, Inactive: OFF
Object ID lookup: Yaskawa SI-B3/V BACnet MS/TP option point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SI-B3/V BACnet MS/TP option (V1000 drive) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive)

How many BACnet points does the Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive) have?

This list has 120 BACnet objects: 6 analog inputs, 1 analog output, 38 analog values, 11 binary inputs, 7 binary outputs, 57 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive) BACnet points are writable?

31 of the 120 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive) BACnet documentation?

The source is YASKAWA AC Drive V1000 Option BACnet MS/TP Installation & Technical Manual, Type SI-B3/V (TOEP YAICOM 19B), revision 2017-12, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=TOEPYAICOM19&cmd=documents&documentName=TOEPYAICOM19.pdf.

What are the minimum BACnet points to integrate the Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive)?

Start with BV 1 Run FWD Cmd (Start/stop from the BMS (drive)); AV 2 Frequency Cmd (Frequency reference, units per o1-03); BV 4 Fault Reset Cmd (Reset a tripped drive); BV 13 RUN-STOP (Running status); BV 15 READY (Drive ready to run); AV 10 Output Frequency (Output frequency, units per o1-03); AV 12 Output Current (Motor amps); AV 13 Output Power (Drive power in kW); BV 16 FAULT (Any active drive fault); AV 40 Last Drive Fault (Most recent fault code).

How do I enable BMS control of the Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive)?

b1-01 Frequency Reference Selection = 3 (Option PCB) and b1-02 Run Command Selection = 3 (Option PCB); both default to 1 (terminals). b1-15/b1-16 = 3 do the same for External Reference 2. Monitoring, parameter access, fault set/reset and the multi-function inputs work at any time.

Does the Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive) need a BACnet heartbeat or have a communication timeout?

The drive raises bUS (Option Communication Error) when the link drops after communication was established, but only when the run command or frequency reference comes from the option (b1-01 = 3 or b1-02 = 3). F6-04 sets the bUS delay (default 2.0 s) and F7-16 a communication-loss timeout (0.0-30.0 s, default 0 = off, option software VST800265+); the fault is sent after F7-16 + F6-04. F6-01 = 3 or higher makes bUS an alarm only; F6-14 = 1 resets the fault when communication returns.

Can the BMS supply sensor values to the Yaskawa SI-B3/V BACnet MS/TP option (V1000 drive)?

AV3 PI Setpoint Cmd lets the BMS write the PI setpoint (0-100 %); BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it.

How do I check these points on the real SI-B3/V BACnet MS/TP option (V1000 drive)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.