- JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
Variable frequency drive BACnet IP option card · BACnet points list
Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet points list
Updated 28 October 2026
The JOHB-SMP3 is a plug-in card that puts Yaskawa HVAC and general-purpose drives on BACnet IP. Each object maps to a drive Modbus register, so the same list covers several drive families; bypass-only and gateway-mode objects simply do not appear on a plain drive. AV29/AV30 give generic read/write access to any drive register.
This page lists 213 BACnet objects for the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) — 67 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Yaskawa’s own free documentation, linked below.
- Manufacturer
- Yaskawa
- Model
- JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
- Equipment
- Variable frequency drive BACnet IP option card
- Equipment type
- VFDs & pumps
- BACnet objects
- 213 (67 writable)
- Transport
- BACnet IP
- Firmware
- Option firmware 3.x (application VST9070xx); GA500/GA700/GA800/FP605 bypass need option software PRG 7001 or later
- Also known as
- JOHB-SMP3, SMP3, HV600 BACnet/IP, Z1000U BACnet/IP, FP605 BACnet/IP, GA800 BACnet/IP, SIEP C730600 0MB
BMS integration notes: Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
Set b1-01 = 3 (Option PCB) so the BMS sets frequency and b1-02 = 3 or 9 so it starts and stops the drive. Write BV1 Run FWD Cmd (BV58 on a bypass) and AV2 Frequency Cmd, read BV13/BV16 and AV10/AV12/AV13, and reset with BV4. Set the device instance in F6-48/F6-49 and the IP settings in F7-xx, and decide on the F7-57 bus timeout.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1 | Run FWD Cmd | Start/stop from the BMS (drive) | Command |
| AV 2 | Frequency Cmd | Frequency reference, units per o1-03 | Command |
| BV 4 | Drive Fault Reset | Reset a tripped drive | Command |
| BV 13 | RUN-STOP | Running status | Read |
| BV 15 | READY | Drive ready to run | Read |
| AV 10 | Output Frequency | Output frequency, units per o1-03 | Read |
| AV 12 | Output Current | Motor amps | Read |
| AV 13 | Output Power | Drive power in kW | Read |
| BV 16 | FAULT | Any active drive fault | Read |
| AV 40 | Last Drive Fault | Most recent fault code | Read |
Enable & remote start
b1-01 Frequency Reference Selection 1 = 3 (Option PCB) and b1-02 Run Command Selection 1 = 3 (Option PCB) or 9 (AUTO Command + Option Run); both default to 1. On a bypass use BV58/BV59 instead of BV1/BV2. BV5 Drive Com Net Command and BV6 Drive Com Control Command (COM/LOCAL) are also provided. In HAND or LOCAL mode the drive ignores the network and disables the bus timeout.
Heartbeat & communication loss
F7-57 BACnet/IP bUS Timeout Value: when above 0 the BMS must keep sending AV2 Frequency Cmd or a run command (AV1, BV1, BV2, BV58, BV59, AV43-AV51). If none arrives within that time while the drive is running, it trips on bUS Option Communication Error, handled per F6-01 (0 ramp, 1 coast (default), 2 fast stop, 3 alarm only, 4 alarm and run at d1-04, 5 alarm and ramp stop). F7-57 = 0 disables it. Switching to AUTO/REMOTE with no recent command gives an immediate bUS. With F6-14 = 1 and F6-01 set to 0-2, the option resets the fault and returns control to BACnet when comms recover.
Sensors & values from the BMS
AV3 PI Setpoint Cmd lets the BMS write the PI setpoint; BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it as the setpoint input.
Network setup
- Device instance = F6-49 (high word) and F6-48 (low word), in hex; e.g. instance 1234 is F6-48 = 4D2, F6-49 = 0.
- F7-13 picks static or DHCP addressing (default DHCP); static IP, mask and gateway are F7-01 to F7-12 (defaults 192.168.1.20 / 255.255.255.0 / 192.168.1.1).
- F7-50 sets the BACnet UDP port (default 47808); F7-51 to F7-56 set BBMD foreign registration.
- F6-xx/F7-xx changes need a power cycle, or F6-15 = 1 Reload Now on non-Z1000U drives.
- DIP switch S1 must read 75 in monitor U4-75 (switches 1 and 3 on) for BACnet/IP to work.
- U6-80 to U6-83 show the IP address actually in use.
Watch out for
- Bits written to AV1 and BV7-BV11 are ORed with the hard-wired digital inputs.
- Do not combine AV4 with BO1-BO3/BV12, or AV5 with AV1, BO4 or BV9-BV11.
- F6-01 = 3 or 4 keeps the drive running after a bus fault; provide separate safety stops.
- With RSTP ring networks, set F7-57 long enough for the ring to converge.
- Frequency units for AV2, AV9 and AV10 follow drive parameter o1-03.
- Bypass-only and gateway-mode objects are missing on a plain drive.
Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Drive Analog Input 1 Level | Shown as 'Drv Anlg In 1 Level'; Modbus 004E | % | Read | |
| AI | 2 | Drive Analog Input 2 Level | Shown as 'Drv Anlg In 2 Level'; Modbus 004F | % | Read | |
| AI | 3 | Drive Analog Input 3 Level | Shown as 'Drv Anlg In 3 Level'; not on all drives | % | Read | |
| AI | 4 | Bypass Analog Input 1 Level | Shown as 'Byp Anlg In 1 Level'; Modbus 8795; bypass only | % | Read | |
| AI | 6 | Display Format o1-03 | Modbus 0502 | Read | ||
| AI | 7 | Scale Format b5-20 | Modbus 01E2 | Read | ||
| AI | 8 | Inverter Model o2-04 | Modbus 0508 | Read | ||
| AI | 9 | Rated Current n9-01 | Modbus 05D0 | A | Read | |
| AI | 10 | Motor Current UB-01 | Modbus 8780; bypass only | A | Read | |
| AI | 11 | Contactor Voltage | Modbus 8790; bypass only | V | Read | |
| AO | 1 | Drive Analog Output 1 Level | Drive terminal FM; set H4-01 = 0 | % | Command | |
| AO | 2 | Drive Analog Output 2 Level | Drive terminal AM; set H4-01 = 0; not on all drives | % | Command | |
| AV | 1 | Drive Operation Command | Run/command bitmap, Modbus 0001; bits OR with hard-wired inputs | Command | ||
| AVmin | 2 | Frequency Cmd | Modbus 0002 | per o1-03 | Command | |
| AV | 3 | PI Setpoint Cmd | Modbus 0006 | % | Command | |
| AV | 4 | Drive Multi-Function Output Command | Bitmap for MF digital outputs and fault contact | Command | ||
| AV | 5 | Drive Reference Select Command | Bitmap selecting PID setpoint, PI2 target, MF inputs | Command | ||
| AV | 6 | System Status | Bitmap: run, reverse, ready, fault, outputs, com status | Read | ||
| AV | 7 | Fault Details | Bitmap of active fault groups | Read | ||
| AV | 8 | Data Link Status | Bitmap of register write and limit errors | Read | ||
| AV | 9 | Frequency Reference | Modbus 0040 | per o1-03 | Read | |
| AVmin | 10 | Output Frequency | Modbus 0041 | per o1-03 | Read | |
| AV | 11 | Output Voltage | Modbus 0045 | V | Read | |
| AVmin | 12 | Output Current | Modbus 0026 | A | Read | |
| AVmin | 13 | Output Power | Modbus 0047 | kW | Read | |
| AV | 14 | Torque Reference | Modbus 0048; not on all drives | % | Read | |
| AV | 15 | Drive Multi-Function Input Status | Shown as 'MF Input Status'; Modbus 002B | Read | ||
| AV | 16 | Drive Status 2 | Modbus 002C | Read | ||
| AV | 17 | Drive Multi-Function Output Status | Shown as 'MF Output Status'; Modbus 002D | Read | ||
| AV | 18 | DC Bus Voltage | Modbus 0031 | V | Read | |
| AV | 19 | PI Feedback Level | Modbus 0038 | % | Read | |
| AV | 20 | PI Input Level | Modbus 0039 | % | Read | |
| AV | 21 | PI Output Level | Modbus 003A | % | Read | |
| AV | 22 | CPU Software | Drive software number; bypass shows Drive SW Num | Read | ||
| AV | 23 | Flash Number | Flash number; bypass shows Bypass SW Num | Read | ||
| AV | 25 | KVA Setting | Modbus 0508 | Read | ||
| AV | 26 | Control Method | Modbus 0043 | Read | ||
| AV | 27 | Accel Time | Modbus 0200 | Sec | Write | |
| AV | 28 | Decel Time | Modbus 0201 | Sec | Write | |
| AV | 29 | Parameter Number | Register number to read or write via AV30 | Write | ||
| AV | 30 | Parameter Data | Data read from or written to register in AV29 | Write | ||
| AV | 31 | Motor Current | Modbus 8780; bypass only | A | Read | |
| AV | 32 | 120V to Kx Coils | Modbus 8790; bypass only | V | Read | |
| AV | 33 | Drive kWh consumed | Energy consumed | kWh | Read | |
| AV | 34 | Drive kWh Regenerated | Energy regenerated; Z1000U only | kWh | Read | |
| AV | 35 | Drive Run Time | Modbus 004C | Hours | Read | |
| AV | 36 | Output Freq in % | Modbus 003F | % | Read | |
| AV | 37 | Output Freq in RPM | Modbus 003E | RPM | Read | |
| AV | 38 | Torque Iq (U6-01) | Modbus 0051 | % | Read | |
| AV | 39 | Drive HOA Status | Hand/Off/Auto state; GA drives report Lo/Re | Read | ||
| AVmin | 40 | Last Drive Fault | Modbus 0081 | Read | ||
| AV | 41 | Last BypassFault | Modbus 878C; bypass only | Read | ||
| AV | 42 | Current Sys Fault | Shown as 'Current Sys Flt'; Modbus 0080 | Read | ||
| AV | 43 | Ext Drive Cmd Update | Modbus 15C5; gateway mode only | Command | ||
| AV | 44 | Ext Drive 1 Command | Modbus 15C6; gateway mode only | Command | ||
| AV | 45 | Ext Drive 1 Freq Ref | Modbus 15C7; gateway mode only | Command | ||
| AV | 46 | Ext Drive 2 Command | Modbus 15C8; gateway mode only | Command | ||
| AV | 47 | Ext Drive 2 Freq Ref | Modbus 15C9; gateway mode only | Command | ||
| AV | 48 | Ext Drive 3 Command | Modbus 15CA; gateway mode only | Command | ||
| AV | 49 | Ext Drive 3 Freq Ref | Modbus 15CB; gateway mode only | Command | ||
| AV | 50 | Ext Drive 4 Command | Modbus 15CC; gateway mode only | Command | ||
| AV | 51 | Ext Drive 4 Freq Ref | Modbus 15CD; gateway mode only | Command | ||
| AV | 52 | Ext Drive 1 Status | Modbus 15E7; gateway mode only | Read | ||
| AV | 53 | Ext Drive 1 Freq Output | Shown as 'Ext Drive 1 Freq Out'; Modbus 15E8; gateway mode only | Read | ||
| AV | 54 | Ext Drive 2 Status | Modbus 15E9; gateway mode only | Read | ||
| AV | 55 | Ext Drive 2 Freq Output | Shown as 'Ext Drive 2 Freq Out'; Modbus 15EA; gateway mode only | Read | ||
| AV | 56 | Ext Drive 3 Status | Modbus 15EB; gateway mode only | Read | ||
| AV | 57 | Ext Drive 3 Freq Output | Shown as 'Ext Drive 3 Freq Out'; Modbus 15EC; gateway mode only | Read | ||
| AV | 58 | Ext Drive 4 Status | Modbus 15ED; gateway mode only | Read | ||
| AV | 59 | Ext Drive 4 Freq Output | Shown as 'Ext Drive 4 Freq Out'; Modbus 15EE; gateway mode only | Read | ||
| AV | 60 | Ext Drive Register Write Access | Shown as 'Gateway Reg 0x15CE'; Modbus 15CE; gateway mode only | Write | ||
| AV | 61 | Ext Drive Write Register Number | Shown as 'Gateway Reg 0x15CF'; Modbus 15CF; gateway mode only | Write | ||
| AV | 62 | Ext Drive Write Register Data | Shown as 'Gateway Reg 0x15D0'; Modbus 15D0; gateway mode only | Write | ||
| AV | 63 | Ext Drive Register Read Access | Shown as 'Gateway Reg 0x15EF'; Modbus 15EF; gateway mode only | Read | ||
| AV | 64 | Ext Drive Read Register Number | Shown as 'Gateway Reg 0x15F0'; Modbus 15F0; gateway mode only | Read | ||
| AV | 65 | Ext Drive Read Register Data | Shown as 'Gateway Reg 0x15F1'; Modbus 15F1; gateway mode only | Read | ||
| BI | 1 | Drive Input Terminal 1 | Shown as 'Input Terminal 1'; Modbus 002B: Bit 0 | Read | Active: ON, Inactive: OFF | |
| BI | 2 | Drive Input Terminal 2 | Shown as 'Input Terminal 2'; Modbus 002B: Bit 1 | Read | Active: ON, Inactive: OFF | |
| BI | 3 | Drive Input Terminal 3 | Shown as 'Input Terminal 3'; Modbus 002B: Bit 2 | Read | Active: ON, Inactive: OFF | |
| BI | 4 | Drive Input Terminal 4 | Shown as 'Input Terminal 4'; Modbus 002B: Bit 3 | Read | Active: ON, Inactive: OFF | |
| BI | 5 | Drive Input Terminal 5 | Shown as 'Input Terminal 5'; Modbus 002B: Bit 4 | Read | Active: ON, Inactive: OFF | |
| BI | 6 | Drive Input Terminal 6 | Shown as 'Input Terminal 6'; Modbus 002B: Bit 5 | Read | Active: ON, Inactive: OFF | |
| BI | 7 | Drive Input Terminal 7 | Shown as 'Input Terminal 7'; Modbus 002B: Bit 6 | Read | Active: ON, Inactive: OFF | |
| BI | 8 | Drive MF Output 1 | Shown as 'Multi Function Out 1'; Modbus 0020: Bit 5 | Read | Active: ON, Inactive: OFF | |
| BI | 9 | Drive MF Output 2 | Shown as 'Multi Function Out 2'; Modbus 0020: Bit 6 | Read | Active: ON, Inactive: OFF | |
| BI | 10 | Drive MF Output 3 | On bypass this is BYP DI-1 STAT | Read | Active: ON, Inactive: OFF | |
| BI | 11 | Drive Input Terminal 8 | On bypass this is BYP DI-2 STAT | Read | Active: ON, Inactive: OFF | |
| BI | 12 | BYP DI-3 STAT | Modbus 8781: Bit 2; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 13 | BYP DI-4 STAT | Modbus 8781: Bit 3; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 14 | BYP DI-5 STAT | Modbus 8781: Bit 4; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 15 | BYP DI-6 STAT | Modbus 8781: Bit 5; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 16 | BYP DI-7 STAT | Modbus 8781: Bit 6; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 17 | BYP DI-8 STAT | Modbus 8781: Bit 7; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 18 | BYP DO-1 STAT | Modbus 8782: Bit 0; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 19 | BYP DO-2 STAT | Modbus 8782: Bit 1; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 20 | BYP DO-3 STAT | Modbus 8782: Bit 2; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 21 | BYP DO-4 STAT | Modbus 8782: Bit 3; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 22 | BYP DO-5 STAT | Modbus 8782: Bit 4; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 23 | BYP DO-6 STAT | Modbus 8782: Bit 5; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 24 | BYP DO-7 STAT | Modbus 8782: Bit 6; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 25 | BYP DO-8 STAT | Modbus 8782: Bit 7; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 26 | BYP DO-9 STAT | Modbus 8783: Bit 0; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 27 | BYP DO-10 STAT | Modbus 8783: Bit 1; bypass only | Read | Active: ON, Inactive: OFF | |
| BI | 28 | Drive Fault Status | Modbus 004B: Bit 7 | Read | Active: FAULT, Inactive: OK | |
| BI | 29 | Drive Alarm Status | Modbus 004B: Bit 6 | Read | Active: ALARM, Inactive: OK | |
| BI | 30 | Sys Alarm Status | Modbus 8784: Bit 8; bypass only | Read | Active: ALARM, Inactive: OK | |
| BI | 31 | Safe Torque Off HW Status | Shown as 'Saf Trq Off Hw Stat'; not on Z1000U | Read | Active: ALARM, Inactive: OK | |
| BI | 32 | Safe Torque Off Status | Shown as 'Saf Trq Off Stat'; not on Z1000U | Read | Active: ALARM, Inactive: OK | |
| BO | 1 | MF Output, M1-M2 | Set H2-01 = F; GA500 uses MA-MB-MC | Command | Active: ON, Inactive: OFF | |
| BO | 2 | MF Output, M3-M4 | Set H2-02 = F; GA500 uses P1-C1 | Command | Active: ON, Inactive: OFF | |
| BO | 3 | MF Output, M5-M6 | Set H2-03 = F; Z1000U MD-ME-MF, GA500 P2-C2 | Command | Active: ON, Inactive: OFF | |
| BO | 4 | Ref Sel: PI Setpoint | Modbus 000F: Bit 1 | Command | Active: ON, Inactive: OFF | |
| BO | 5 | Ref Sel:Term S5 IN | Modbus 0001: Bit 8 | Command | Active: ON, Inactive: OFF | |
| BO | 6 | Ref Sel:Term S6 IN | Modbus 0001: Bit 9 | Command | Active: ON, Inactive: OFF | |
| BO | 7 | Ref Sel:Term S7 IN | Modbus 0001: Bit A | Command | Active: ON, Inactive: OFF | |
| BO | 8 | BYP DO-07 COMMAND | Modbus 8403: Bit 6; set matching Z2 parameter to 99; bypass only | Command | Active: ON, Inactive: OFF | |
| BO | 9 | BYP DO-08 COMMAND | Modbus 8403: Bit 7; set matching Z2 parameter to 99; bypass only | Command | Active: ON, Inactive: OFF | |
| BO | 10 | BYP DO-09 COMMAND | Modbus 8403: Bit 8; set matching Z2 parameter to 99; bypass only | Command | Active: ON, Inactive: OFF | |
| BO | 11 | BYP DO-010 COMMAND | Modbus 8403: Bit 9; set matching Z2 parameter to 99; bypass only | Command | Active: ON, Inactive: OFF | |
| BVmin | 1 | Run FWD Cmd | Modbus 0001: Bit 0; drive only; bypass uses BV58 | Command | Active: RUN, Inactive: OFF | |
| BV | 2 | Run REV Cmd | Modbus 0001: Bit 1; drive only; bypass uses BV59 | Command | Active: REV, Inactive: OFF | |
| BV | 3 | Drive EF0 | Shown as 'Ext Fault Cmd'; Modbus 0001: Bit 2 | Command | Active: FAULT, Inactive: OFF | |
| BVmin | 4 | Drive Fault Reset | Shown as 'Fault Reset Cmd'; Modbus 0001: Bit 3 | Command | Active: RESET, Inactive: OFF | |
| BV | 5 | Drive Com Net Command | Shown as 'Com Net Cmd' | Command | Active: COM, Inactive: LOCAL | |
| BV | 6 | Drive Com Control Command | Shown as 'Com Control Cmd' | Command | Active: COM, Inactive: LOCAL | |
| BV | 7 | Drive Multi-Function Input 3 Command | Shown as 'MF Input 3 Cmd'; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 8 | Drive Multi-Function Input 4 Command | Modbus 0001: Bit 7; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 9 | Drive Multi-Function Input 5 Command | Shown as 'MF Input 5 Cmd'; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 10 | Drive Multi-Function Input 6 Command | Shown as 'MF Input 6 Cmd'; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 11 | Drive Multi-Function Input 7 Command | Shown as 'MF Input 7 Cmd'; ORs with hard-wired inputs | Command | Active: ON, Inactive: OFF | |
| BV | 12 | Set Fault Contact Cmd | Shown as 'Set Flt Contact Cmd'; not on GA500 | Command | Active: ENABLE, Inactive: OFF | |
| BVmin | 13 | RUN-STOP | Modbus 0020: Bit 0 | Read | Active: RUN, Inactive: OFF | |
| BV | 14 | REV-FWD | Modbus 0020: Bit 1 | Read | Active: REV, Inactive: FWD | |
| BVmin | 15 | READY | Modbus 004B: Bit 5 | Read | Active: READY, Inactive: OFF | |
| BVmin | 16 | FAULT | Modbus 0020: Bit 3 | Read | Active: FAULTED, Inactive: OFF | |
| BV | 17 | Data Set Error | Modbus 004B: Bit 8 | Read | Active: ERROR, Inactive: OFF | |
| BV | 18 | Overcurrent – Ground Fault | Shown as 'Overcurrent– Gnd Flt'; Modbus 0021: Bit 0 | Read | Active: OC – GF, Inactive: OFF | |
| BV | 19 | Main Circuit Overvoltage | Shown as 'Main Ckt Overvoltage'; Modbus 0021: Bit 1 | Read | Active: OV, Inactive: OFF | |
| BV | 20 | Drive Overload | Modbus 0021: Bit 2 | Read | Active: OL2, Inactive: OFF | |
| BV | 21 | Drive Overheat | Modbus 0021: Bit 3 | Read | Active: OH1-OH2, Inactive: OFF | |
| BV | 22 | Fuse Blown | Modbus 0021: Bit 5 | Read | Active: PUF, Inactive: OFF | |
| BV | 23 | PI Feedback Loss | Modbus 0021: Bit 6 | Read | Active: FBL, Inactive: OFF | |
| BV | 24 | External Fault | Modbus 0021: Bit 7 | Read | Active: EF0 – EF, Inactive: OFF | |
| BV | 25 | Hardware Error | Modbus 0021: Bit 8 | Read | Active: CPF, Inactive: OFF | |
| BV | 26 | Motor Overload – Overtorque | Shown as 'Mtr OvrLd – OvrTorque'; Modbus 0021: Bit 9 | Read | Active: OL1 – OL3, Inactive: OFF | |
| BV | 27 | Overspeed | Modbus 0021: Bit A | Read | Active: OS –DEV, Inactive: OFF | |
| BV | 28 | Main Circuit Undervoltage | Shown as 'Main Ckt Undrvoltage'; Modbus 0021: Bit B | Read | Active: UV, Inactive: OFF | |
| BV | 29 | MCU, Control Power Supply Error | Shown as 'MCU Cntrl Pwr Sy Err'; Modbus 0021: Bit C | Read | Active: UV1-2-3, Inactive: OFF | |
| BV | 30 | Output Phase Loss | Modbus 0021: Bit D | Read | Active: LF, Inactive: OFF | |
| BV | 31 | BUS Fault | Modbus 0021: Bit E | Read | Active: BUS, Inactive: OFF | |
| BV | 32 | Operator Disconnect | Modbus 0021: Bit F | Read | Active: OPR, Inactive: OFF | |
| BV | 33 | Operating | Modbus 002C: Bit 0 | Read | Active: OPERATING, Inactive: OFF | |
| BV | 34 | Zero Speed | Modbus 002C: Bit 1 | Read | Active: ON, Inactive: OFF | |
| BV | 35 | Frequency Agree | Modbus 002C: Bit 2 | Read | Active: ON, Inactive: OFF | |
| BV | 36 | Desired Frequency Agree | Shown as 'Desired Freq Agree'; Modbus 002C: Bit 3 | Read | Active: ON, Inactive: OFF | |
| BV | 37 | Frequency Detect 1 | Modbus 002C: Bit 4 | Read | Active: ON, Inactive: OFF | |
| BV | 38 | Frequency Detect 2 | Modbus 002C: Bit 5 | Read | Active: ON, Inactive: OFF | |
| BV | 39 | Drive Startup Complete | Shown as 'Drv Startup Complete'; Modbus 002C: Bit 6 | Read | Active: ON, Inactive: OFF | |
| BV | 40 | Low Voltage Detect | Modbus 002C: Bit 7 | Read | Active: ON, Inactive: OFF | |
| BV | 41 | Base Block | Modbus 002C: Bit 8 | Read | Active: ON, Inactive: OFF | |
| BV | 42 | Frequency Reference Mode | Shown as 'Frequency Ref Mode'; Modbus 002C: Bit 9 | Read | Active: LOCAL, Inactive: COM | |
| BV | 43 | Run Command Mode | Modbus 002C: Bit A | Read | Active: LOCAL, Inactive: COM | |
| BV | 44 | Over Torque Detect | Modbus 002C: Bit B | Read | Active: ON, Inactive: OFF | |
| BV | 45 | Frequency Reference Loss | Shown as 'Frequency Ref Loss'; Modbus 002C: Bit C | Read | Active: ON, Inactive: OFF | |
| BV | 46 | Retry Error | Modbus 002C: Bit D | Read | Active: ON, Inactive: OFF | |
| BV | 55 | Parameter Accept | Runs the RAM enter command | Write | Active: ON, Inactive: OFF | |
| BV | 56 | Parameter Enter | Runs the ROM (EEPROM) enter command | Write | Active: ON, Inactive: OFF | |
| BV | 58 | Bypass Forward Run Cmd | Shown as 'BYP Run Fwd CMD'; Modbus 0001: Bit 0; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 59 | Bypass Reverse Run Cmd | Shown as 'BYP Run Rev CMD'; Modbus 0001: Bit 1; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 60 | Emergency Override Drive Reverse | HV600/FP605 only; needs b1-04 = 0 | Command | Active: ON, Inactive: OFF | |
| BV | 61 | Bypass Transfer to Bypass Cmd | Shown as 'BYP Xfer to BYP CMD'; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 62 | Emergency Overide Bypass | Shown as 'Em Over BYPASS CMD'; Modbus 8400: Bit 4; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 63 | Emergency Override Drive Forward | Shown as 'Em Over DRV FWD CMD'; HV600/FP605 only | Command | Active: ON, Inactive: OFF | |
| BV | 64 | Bypass Motor OR Select Command | Shown as 'BYP Mtr OR Sel CMD'; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 65 | Bypass Motor AND Select Command | Shown as 'BYP Mtr AND Sel CMD'; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 69 | Bypass BYPASS Select Command | Shown as 'BYP BYPASS Sel CMD'; bypass only; needs Z1-39 = 3 | Command | Active: BYP, Inactive: DRV | |
| BV | 70 | Bypass Fault Reset Command | Shown as 'BYP Fault Reset CMD'; Modbus 8400: Bit D; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 71 | Bypass External Fault Command | Shown as 'BYP Ext Fault CMD'; Modbus 8400: Bit E; bypass only | Command | Active: ON, Inactive: OFF | |
| BV | 72 | Bypass DI-01 Command | Shown as 'BYP DI-01 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 73 | Bypass DI-02 Command | Shown as 'BYP DI-02 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 74 | Bypass DI-03 Command | Shown as 'BYP DI-03 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 75 | Bypass DI-04 Command | Shown as 'BYP DI-04 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 76 | Bypass DI-05 Command | Shown as 'BYP DI-05 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 77 | Bypass DI-06 Command | Shown as 'BYP DI-06 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 78 | Bypass DI-07 Command | Shown as 'BYP DI-07 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 79 | Bypass DI-08 Command | Shown as 'BYP DI-08 Command'; bypass only; needs Z3-12 = 1 | Command | Active: ON, Inactive: OFF | |
| BV | 80 | Bypass HAND Mode Status | Shown as 'BYP HAND Mode Status'; Modbus 8784: Bit 0; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 81 | Bypass OFF Mode Status | Shown as 'BYP OFF Mode Status'; Modbus 8784: Bit 1; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 82 | Bypass AUTO Mode Status | Shown as 'BYPAUTO Mode Status'; Modbus 8784: Bit 2; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 83 | Bypass DRIVE Mode Status | Shown as 'BYP DRV Mode Status'; Modbus 8784: Bit 3; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 84 | Bypass BYPASS Mode Status | Shown as 'BYP BYPASS Mode Stat'; Modbus 8784: Bit 4; bypass only | Read | Active: ON, Inactive: OFF | |
| BV | 85 | Bypass Emergency Run Bypass Status | Shown as 'BYP Em-Over BYP Stat'; Modbus 8784: Bit 5; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 86 | Bypass Emergency Run Drive Fwd Status | Shown as 'BYP Em-Over DRV Stat'; Modbus 8784: Bit 6; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 87 | Bypass Safety Status | Shown as 'BYP Safety Status'; Modbus 8784: Bit 7; bypass only | Read | Active: OPEN, Inactive: CLOSED | |
| BV | 88 | Bypass BAS Interlock Status | Shown as 'BYP BAS Interlk Stat'; Modbus 8785: Bit 0; bypass only | Read | Active: OPEN, Inactive: CLOSED | |
| BV | 89 | Bypass Run Status | Shown as 'BYP RUN Status'; Modbus 8785: Bit 1; bypass only | Read | Active: RUN, Inactive: OFF | |
| BV | 90 | Bypass Fault Status | Shown as 'BYP Fault Status'; Modbus 8785: Bit 2; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 91 | Bypass Auto Transfer Status | Shown as 'BYPAuto Xfer Status'; Modbus 8785: Bit 3; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 92 | Bypass Remote Transfer Status | Shown as 'BYP Remote Xfer Stat'; Modbus 8785: Bit 4; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 93 | Bypass Energy Savings Status | Shown as 'BYP Energy Save Stat'; Modbus 8785: Bit 5; bypass only | Read | Active: ACTIVE, Inactive: OFF | |
| BV | 94 | Bypass Motor 1 Select Status | Shown as 'BYP Motor 1 Sel Stat'; bypass only | Read | Active: SELECT, Inactive: OFF | |
| BV | 95 | Bypass Motor 2 Select Status | Shown as 'BYP Motor 2 Sel Stat'; bypass only | Read | Active: SELECT, Inactive: OFF | |
| BV | 96 | Bypass Drive Fault Status | Shown as 'BYP Drive Flt Status'; Modbus 8786: Bit 0; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 97 | BYP Safety Status 2 | Shown as 'BYP Safety Status 2'; Modbus 8786: Bit 1; bypass only | Read | Active: OPEN, Inactive: CLOSED | |
| BV | 98 | Bypass BAS Interlock Fault Status | Shown as 'BYP BAS ILock Status'; Modbus 8786: Bit 2; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 99 | Bypass External Fault Status | Shown as 'BYP Ext Fault Stat'; Modbus 8786: Bit 3; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 101 | Bypass Motor OL Status | Shown as 'BYP Motor OL Stat'; Modbus 8786: Bit 5; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 102 | Bypass Motor 1 External OL Status | Shown as 'BYP Motor 1 OL Stat'; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 103 | Bypass Motor 2 External OL Status | Shown as 'BYP Mtr 2 OL Stat'; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 104 | Bypass Brownout Detect Status | Shown as 'BYP Brownout Detect'; Modbus 8787: Bit 0; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 105 | Bypass Drive Comms Status | Shown as 'BYP Drive Comms'; Modbus 8787: Bit 2; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 106 | Bypass Loss of Load Status | Shown as 'BYP Loss Of Load'; Modbus 8787: Bit 5; bypass only | Read | Active: FAULT, Inactive: OFF | |
| BV | 107 | Option Board on Drive Status | Shown as 'BYP Option Brd Comms'; Modbus 8787: Bit 4; bypass only | Read | Active: FAULT, Inactive: OFF |
No points match these filters.
Integration notes
- Device instance is built from drive parameters F6-49 and F6-48; the default object name is 'Yaskawa VFD ID' plus those values in hex.
- IP settings come from F7-01 to F7-13 (or DHCP); the UDP port is set by F7-50.
- Object names in the drive may use the shorter network display name shown in each description.
- Points marked 'bypass only' exist only when the card is in an HV600 or FP605 bypass.
- AV43-AV65 are gateway-mode objects for up to four downstream drives and only appear in gateway mode.
- AV4 must not be combined with BO1-BO3 or BV12; AV5 must not be combined with AV1, BO4 or BV9-BV11.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
How many BACnet points does the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) have?
This list has 213 BACnet objects: 10 analog inputs, 2 analog outputs, 64 analog values, 32 binary inputs, 11 binary outputs, 94 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet points are writable?
67 of the 213 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet documentation?
The source is YASKAWA AC Drive Option BACnet/IP Technical Manual, Model JOHB-SMP3 (SIEP C730600 0MB), revision 2023-11, published free by Yaskawa at https://www.yaskawa.eu.com/_downloads/download_d22897.
What are the minimum BACnet points to integrate the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?
Start with BV 1 Run FWD Cmd (Start/stop from the BMS (drive)); AV 2 Frequency Cmd (Frequency reference, units per o1-03); BV 4 Drive Fault Reset (Reset a tripped drive); BV 13 RUN-STOP (Running status); BV 15 READY (Drive ready to run); AV 10 Output Frequency (Output frequency, units per o1-03); AV 12 Output Current (Motor amps); AV 13 Output Power (Drive power in kW); BV 16 FAULT (Any active drive fault); AV 40 Last Drive Fault (Most recent fault code).
How do I enable BMS control of the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?
b1-01 Frequency Reference Selection 1 = 3 (Option PCB) and b1-02 Run Command Selection 1 = 3 (Option PCB) or 9 (AUTO Command + Option Run); both default to 1. On a bypass use BV58/BV59 instead of BV1/BV2. BV5 Drive Com Net Command and BV6 Drive Com Control Command (COM/LOCAL) are also provided. In HAND or LOCAL mode the drive ignores the network and disables the bus timeout.
Does the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) need a BACnet heartbeat or have a communication timeout?
F7-57 BACnet/IP bUS Timeout Value: when above 0 the BMS must keep sending AV2 Frequency Cmd or a run command (AV1, BV1, BV2, BV58, BV59, AV43-AV51). If none arrives within that time while the drive is running, it trips on bUS Option Communication Error, handled per F6-01 (0 ramp, 1 coast (default), 2 fast stop, 3 alarm only, 4 alarm and run at d1-04, 5 alarm and ramp stop). F7-57 = 0 disables it. Switching to AUTO/REMOTE with no recent command gives an immediate bUS. With F6-14 = 1 and F6-01 set to 0-2, the option resets the fault and returns control to BACnet when comms recover.
Can the BMS supply sensor values to the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?
AV3 PI Setpoint Cmd lets the BMS write the PI setpoint; BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it as the setpoint input.
How do I check these points on the real JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Yaskawa BACnet points lists
- Variable frequency drive BACnet MS/TP option card
Yaskawa SI-B3 BACnet MS/TP option (A1000, P1000, U1000, FP605 drives)
Yaskawa A1000, P1000, iQpump1000, U1000, FP605 and iQpump605 drives fitted with the SI-B3 BACnet MS/TP option card.
Also known as: SI-B3, SI-B3/V, A1000 BACnet, P1000 BACnet, iQpump1000 BACnet, U1000 BACnet, FP605 BACnet, iQpump605 BACnet, TOEPYAICOM22 - Variable frequency drive with bypass (HVAC)
Yaskawa Z1000 Bypass (BACnet MS/TP)
Yaskawa Z1000 Bypass packages (Z1B1, 208 V and 480 V) connected to BACnet MS/TP at the bypass controller.
Also known as: Z1000 Bypass, Z1B1, Z1000 drive bypass, Z1000 bypass controller, SIEP YAIZ1B 01 - Variable frequency drive (HVAC)
Yaskawa Z1000 HVAC drive (embedded BACnet MS/TP)
Yaskawa Z1000 HVAC fan and pump drives (CIMR-ZU, 200 V and 400 V class) using the built-in RS-485 port with H5-08 set to BACnet.
Also known as: Z1000, CIMR-ZU, CIMR-ZUA, Z1000 AC Drive for HVAC Fan and Pump, SIEP C710616 45
Source: YASKAWA AC Drive Option BACnet/IP Technical Manual, Model JOHB-SMP3 · SIEP C730600 0MB · rev. 2023-11. Object names, instances and units are reproduced as published; descriptions are our own.