  3. Yaskawa
  4. JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)

Variable frequency drive BACnet IP option card · BACnet points list

Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet points list

Updated 28 October 2026

Short answer

The JOHB-SMP3 is a plug-in card that puts Yaskawa HVAC and general-purpose drives on BACnet IP. Each object maps to a drive Modbus register, so the same list covers several drive families; bypass-only and gateway-mode objects simply do not appear on a plain drive. AV29/AV30 give generic read/write access to any drive register.

This page lists 213 BACnet objects for the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) — 67 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Yaskawa’s own free documentation, linked below.

Manufacturer
Yaskawa
Model
JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)
Equipment
Variable frequency drive BACnet IP option card
Equipment type
VFDs & pumps
BACnet objects
213 (67 writable)
Transport
BACnet IP
Firmware
Option firmware 3.x (application VST9070xx); GA500/GA700/GA800/FP605 bypass need option software PRG 7001 or later
Also known as
JOHB-SMP3, SMP3, HV600 BACnet/IP, Z1000U BACnet/IP, FP605 BACnet/IP, GA800 BACnet/IP, SIEP C730600 0MB
Source document
YASKAWA AC Drive Option BACnet/IP Technical Manual, Model JOHB-SMP3 · SIEP C730600 0MB · rev. 2023-11
Download CSV 213 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)

Integration in brief

Set b1-01 = 3 (Option PCB) so the BMS sets frequency and b1-02 = 3 or 9 so it starts and stops the drive. Write BV1 Run FWD Cmd (BV58 on a bypass) and AV2 Frequency Cmd, read BV13/BV16 and AV10/AV12/AV13, and reset with BV4. Set the device instance in F6-48/F6-49 and the IP settings in F7-xx, and decide on the F7-57 bus timeout.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Run FWD CmdStart/stop from the BMS (drive)Command
AV 2Frequency CmdFrequency reference, units per o1-03Command
BV 4Drive Fault ResetReset a tripped driveCommand
BV 13RUN-STOPRunning statusRead
BV 15READYDrive ready to runRead
AV 10Output FrequencyOutput frequency, units per o1-03Read
AV 12Output CurrentMotor ampsRead
AV 13Output PowerDrive power in kWRead
BV 16FAULTAny active drive faultRead
AV 40Last Drive FaultMost recent fault codeRead

Enable & remote start

b1-01 Frequency Reference Selection 1 = 3 (Option PCB) and b1-02 Run Command Selection 1 = 3 (Option PCB) or 9 (AUTO Command + Option Run); both default to 1. On a bypass use BV58/BV59 instead of BV1/BV2. BV5 Drive Com Net Command and BV6 Drive Com Control Command (COM/LOCAL) are also provided. In HAND or LOCAL mode the drive ignores the network and disables the bus timeout.

Heartbeat & communication loss

F7-57 BACnet/IP bUS Timeout Value: when above 0 the BMS must keep sending AV2 Frequency Cmd or a run command (AV1, BV1, BV2, BV58, BV59, AV43-AV51). If none arrives within that time while the drive is running, it trips on bUS Option Communication Error, handled per F6-01 (0 ramp, 1 coast (default), 2 fast stop, 3 alarm only, 4 alarm and run at d1-04, 5 alarm and ramp stop). F7-57 = 0 disables it. Switching to AUTO/REMOTE with no recent command gives an immediate bUS. With F6-14 = 1 and F6-01 set to 0-2, the option resets the fault and returns control to BACnet when comms recover.

Sensors & values from the BMS

AV3 PI Setpoint Cmd lets the BMS write the PI setpoint; BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it as the setpoint input.

Network setup

Watch out for

Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

213 of 213 shown
Type
Access
Show
Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet Points List
DescriptionStates
AI1Drive Analog Input 1 LevelShown as 'Drv Anlg In 1 Level'; Modbus 004E%Read
AI2Drive Analog Input 2 LevelShown as 'Drv Anlg In 2 Level'; Modbus 004F%Read
AI3Drive Analog Input 3 LevelShown as 'Drv Anlg In 3 Level'; not on all drives%Read
AI4Bypass Analog Input 1 LevelShown as 'Byp Anlg In 1 Level'; Modbus 8795; bypass only%Read
AI6Display Format o1-03Modbus 0502Read
AI7Scale Format b5-20Modbus 01E2Read
AI8Inverter Model o2-04Modbus 0508Read
AI9Rated Current n9-01Modbus 05D0ARead
AI10Motor Current UB-01Modbus 8780; bypass onlyARead
AI11Contactor VoltageModbus 8790; bypass onlyVRead
AO1Drive Analog Output 1 LevelDrive terminal FM; set H4-01 = 0%Command
AO2Drive Analog Output 2 LevelDrive terminal AM; set H4-01 = 0; not on all drives%Command
AV1Drive Operation CommandRun/command bitmap, Modbus 0001; bits OR with hard-wired inputsCommand
AVmin2Frequency CmdModbus 0002per o1-03Command
AV3PI Setpoint CmdModbus 0006%Command
AV4Drive Multi-Function Output CommandBitmap for MF digital outputs and fault contactCommand
AV5Drive Reference Select CommandBitmap selecting PID setpoint, PI2 target, MF inputsCommand
AV6System StatusBitmap: run, reverse, ready, fault, outputs, com statusRead
AV7Fault DetailsBitmap of active fault groupsRead
AV8Data Link StatusBitmap of register write and limit errorsRead
AV9Frequency ReferenceModbus 0040per o1-03Read
AVmin10Output FrequencyModbus 0041per o1-03Read
AV11Output VoltageModbus 0045VRead
AVmin12Output CurrentModbus 0026ARead
AVmin13Output PowerModbus 0047kWRead
AV14Torque ReferenceModbus 0048; not on all drives%Read
AV15Drive Multi-Function Input StatusShown as 'MF Input Status'; Modbus 002BRead
AV16Drive Status 2Modbus 002CRead
AV17Drive Multi-Function Output StatusShown as 'MF Output Status'; Modbus 002DRead
AV18DC Bus VoltageModbus 0031VRead
AV19PI Feedback LevelModbus 0038%Read
AV20PI Input LevelModbus 0039%Read
AV21PI Output LevelModbus 003A%Read
AV22CPU SoftwareDrive software number; bypass shows Drive SW NumRead
AV23Flash NumberFlash number; bypass shows Bypass SW NumRead
AV25KVA SettingModbus 0508Read
AV26Control MethodModbus 0043Read
AV27Accel TimeModbus 0200SecWrite
AV28Decel TimeModbus 0201SecWrite
AV29Parameter NumberRegister number to read or write via AV30Write
AV30Parameter DataData read from or written to register in AV29Write
AV31Motor CurrentModbus 8780; bypass onlyARead
AV32120V to Kx CoilsModbus 8790; bypass onlyVRead
AV33Drive kWh consumedEnergy consumedkWhRead
AV34Drive kWh RegeneratedEnergy regenerated; Z1000U onlykWhRead
AV35Drive Run TimeModbus 004CHoursRead
AV36Output Freq in %Modbus 003F%Read
AV37Output Freq in RPMModbus 003ERPMRead
AV38Torque Iq (U6-01)Modbus 0051%Read
AV39Drive HOA StatusHand/Off/Auto state; GA drives report Lo/ReRead
AVmin40Last Drive FaultModbus 0081Read
AV41Last BypassFaultModbus 878C; bypass onlyRead
AV42Current Sys FaultShown as 'Current Sys Flt'; Modbus 0080Read
AV43Ext Drive Cmd UpdateModbus 15C5; gateway mode onlyCommand
AV44Ext Drive 1 CommandModbus 15C6; gateway mode onlyCommand
AV45Ext Drive 1 Freq RefModbus 15C7; gateway mode onlyCommand
AV46Ext Drive 2 CommandModbus 15C8; gateway mode onlyCommand
AV47Ext Drive 2 Freq RefModbus 15C9; gateway mode onlyCommand
AV48Ext Drive 3 CommandModbus 15CA; gateway mode onlyCommand
AV49Ext Drive 3 Freq RefModbus 15CB; gateway mode onlyCommand
AV50Ext Drive 4 CommandModbus 15CC; gateway mode onlyCommand
AV51Ext Drive 4 Freq RefModbus 15CD; gateway mode onlyCommand
AV52Ext Drive 1 StatusModbus 15E7; gateway mode onlyRead
AV53Ext Drive 1 Freq OutputShown as 'Ext Drive 1 Freq Out'; Modbus 15E8; gateway mode onlyRead
AV54Ext Drive 2 StatusModbus 15E9; gateway mode onlyRead
AV55Ext Drive 2 Freq OutputShown as 'Ext Drive 2 Freq Out'; Modbus 15EA; gateway mode onlyRead
AV56Ext Drive 3 StatusModbus 15EB; gateway mode onlyRead
AV57Ext Drive 3 Freq OutputShown as 'Ext Drive 3 Freq Out'; Modbus 15EC; gateway mode onlyRead
AV58Ext Drive 4 StatusModbus 15ED; gateway mode onlyRead
AV59Ext Drive 4 Freq OutputShown as 'Ext Drive 4 Freq Out'; Modbus 15EE; gateway mode onlyRead
AV60Ext Drive Register Write AccessShown as 'Gateway Reg 0x15CE'; Modbus 15CE; gateway mode onlyWrite
AV61Ext Drive Write Register NumberShown as 'Gateway Reg 0x15CF'; Modbus 15CF; gateway mode onlyWrite
AV62Ext Drive Write Register DataShown as 'Gateway Reg 0x15D0'; Modbus 15D0; gateway mode onlyWrite
AV63Ext Drive Register Read AccessShown as 'Gateway Reg 0x15EF'; Modbus 15EF; gateway mode onlyRead
AV64Ext Drive Read Register NumberShown as 'Gateway Reg 0x15F0'; Modbus 15F0; gateway mode onlyRead
AV65Ext Drive Read Register DataShown as 'Gateway Reg 0x15F1'; Modbus 15F1; gateway mode onlyRead
BI1Drive Input Terminal 1Shown as 'Input Terminal 1'; Modbus 002B: Bit 0ReadActive: ON, Inactive: OFF
BI2Drive Input Terminal 2Shown as 'Input Terminal 2'; Modbus 002B: Bit 1ReadActive: ON, Inactive: OFF
BI3Drive Input Terminal 3Shown as 'Input Terminal 3'; Modbus 002B: Bit 2ReadActive: ON, Inactive: OFF
BI4Drive Input Terminal 4Shown as 'Input Terminal 4'; Modbus 002B: Bit 3ReadActive: ON, Inactive: OFF
BI5Drive Input Terminal 5Shown as 'Input Terminal 5'; Modbus 002B: Bit 4ReadActive: ON, Inactive: OFF
BI6Drive Input Terminal 6Shown as 'Input Terminal 6'; Modbus 002B: Bit 5ReadActive: ON, Inactive: OFF
BI7Drive Input Terminal 7Shown as 'Input Terminal 7'; Modbus 002B: Bit 6ReadActive: ON, Inactive: OFF
BI8Drive MF Output 1Shown as 'Multi Function Out 1'; Modbus 0020: Bit 5ReadActive: ON, Inactive: OFF
BI9Drive MF Output 2Shown as 'Multi Function Out 2'; Modbus 0020: Bit 6ReadActive: ON, Inactive: OFF
BI10Drive MF Output 3On bypass this is BYP DI-1 STATReadActive: ON, Inactive: OFF
BI11Drive Input Terminal 8On bypass this is BYP DI-2 STATReadActive: ON, Inactive: OFF
BI12BYP DI-3 STATModbus 8781: Bit 2; bypass onlyReadActive: ON, Inactive: OFF
BI13BYP DI-4 STATModbus 8781: Bit 3; bypass onlyReadActive: ON, Inactive: OFF
BI14BYP DI-5 STATModbus 8781: Bit 4; bypass onlyReadActive: ON, Inactive: OFF
BI15BYP DI-6 STATModbus 8781: Bit 5; bypass onlyReadActive: ON, Inactive: OFF
BI16BYP DI-7 STATModbus 8781: Bit 6; bypass onlyReadActive: ON, Inactive: OFF
BI17BYP DI-8 STATModbus 8781: Bit 7; bypass onlyReadActive: ON, Inactive: OFF
BI18BYP DO-1 STATModbus 8782: Bit 0; bypass onlyReadActive: ON, Inactive: OFF
BI19BYP DO-2 STATModbus 8782: Bit 1; bypass onlyReadActive: ON, Inactive: OFF
BI20BYP DO-3 STATModbus 8782: Bit 2; bypass onlyReadActive: ON, Inactive: OFF
BI21BYP DO-4 STATModbus 8782: Bit 3; bypass onlyReadActive: ON, Inactive: OFF
BI22BYP DO-5 STATModbus 8782: Bit 4; bypass onlyReadActive: ON, Inactive: OFF
BI23BYP DO-6 STATModbus 8782: Bit 5; bypass onlyReadActive: ON, Inactive: OFF
BI24BYP DO-7 STATModbus 8782: Bit 6; bypass onlyReadActive: ON, Inactive: OFF
BI25BYP DO-8 STATModbus 8782: Bit 7; bypass onlyReadActive: ON, Inactive: OFF
BI26BYP DO-9 STATModbus 8783: Bit 0; bypass onlyReadActive: ON, Inactive: OFF
BI27BYP DO-10 STATModbus 8783: Bit 1; bypass onlyReadActive: ON, Inactive: OFF
BI28Drive Fault StatusModbus 004B: Bit 7ReadActive: FAULT, Inactive: OK
BI29Drive Alarm StatusModbus 004B: Bit 6ReadActive: ALARM, Inactive: OK
BI30Sys Alarm StatusModbus 8784: Bit 8; bypass onlyReadActive: ALARM, Inactive: OK
BI31Safe Torque Off HW StatusShown as 'Saf Trq Off Hw Stat'; not on Z1000UReadActive: ALARM, Inactive: OK
BI32Safe Torque Off StatusShown as 'Saf Trq Off Stat'; not on Z1000UReadActive: ALARM, Inactive: OK
BO1MF Output, M1-M2Set H2-01 = F; GA500 uses MA-MB-MCCommandActive: ON, Inactive: OFF
BO2MF Output, M3-M4Set H2-02 = F; GA500 uses P1-C1CommandActive: ON, Inactive: OFF
BO3MF Output, M5-M6Set H2-03 = F; Z1000U MD-ME-MF, GA500 P2-C2CommandActive: ON, Inactive: OFF
BO4Ref Sel: PI SetpointModbus 000F: Bit 1CommandActive: ON, Inactive: OFF
BO5Ref Sel:Term S5 INModbus 0001: Bit 8CommandActive: ON, Inactive: OFF
BO6Ref Sel:Term S6 INModbus 0001: Bit 9CommandActive: ON, Inactive: OFF
BO7Ref Sel:Term S7 INModbus 0001: Bit ACommandActive: ON, Inactive: OFF
BO8BYP DO-07 COMMANDModbus 8403: Bit 6; set matching Z2 parameter to 99; bypass onlyCommandActive: ON, Inactive: OFF
BO9BYP DO-08 COMMANDModbus 8403: Bit 7; set matching Z2 parameter to 99; bypass onlyCommandActive: ON, Inactive: OFF
BO10BYP DO-09 COMMANDModbus 8403: Bit 8; set matching Z2 parameter to 99; bypass onlyCommandActive: ON, Inactive: OFF
BO11BYP DO-010 COMMANDModbus 8403: Bit 9; set matching Z2 parameter to 99; bypass onlyCommandActive: ON, Inactive: OFF
BVmin1Run FWD CmdModbus 0001: Bit 0; drive only; bypass uses BV58CommandActive: RUN, Inactive: OFF
BV2Run REV CmdModbus 0001: Bit 1; drive only; bypass uses BV59CommandActive: REV, Inactive: OFF
BV3Drive EF0Shown as 'Ext Fault Cmd'; Modbus 0001: Bit 2CommandActive: FAULT, Inactive: OFF
BVmin4Drive Fault ResetShown as 'Fault Reset Cmd'; Modbus 0001: Bit 3CommandActive: RESET, Inactive: OFF
BV5Drive Com Net CommandShown as 'Com Net Cmd'CommandActive: COM, Inactive: LOCAL
BV6Drive Com Control CommandShown as 'Com Control Cmd'CommandActive: COM, Inactive: LOCAL
BV7Drive Multi-Function Input 3 CommandShown as 'MF Input 3 Cmd'; ORs with hard-wired inputsCommandActive: ON, Inactive: OFF
BV8Drive Multi-Function Input 4 CommandModbus 0001: Bit 7; ORs with hard-wired inputsCommandActive: ON, Inactive: OFF
BV9Drive Multi-Function Input 5 CommandShown as 'MF Input 5 Cmd'; ORs with hard-wired inputsCommandActive: ON, Inactive: OFF
BV10Drive Multi-Function Input 6 CommandShown as 'MF Input 6 Cmd'; ORs with hard-wired inputsCommandActive: ON, Inactive: OFF
BV11Drive Multi-Function Input 7 CommandShown as 'MF Input 7 Cmd'; ORs with hard-wired inputsCommandActive: ON, Inactive: OFF
BV12Set Fault Contact CmdShown as 'Set Flt Contact Cmd'; not on GA500CommandActive: ENABLE, Inactive: OFF
BVmin13RUN-STOPModbus 0020: Bit 0ReadActive: RUN, Inactive: OFF
BV14REV-FWDModbus 0020: Bit 1ReadActive: REV, Inactive: FWD
BVmin15READYModbus 004B: Bit 5ReadActive: READY, Inactive: OFF
BVmin16FAULTModbus 0020: Bit 3ReadActive: FAULTED, Inactive: OFF
BV17Data Set ErrorModbus 004B: Bit 8ReadActive: ERROR, Inactive: OFF
BV18Overcurrent – Ground FaultShown as 'Overcurrent– Gnd Flt'; Modbus 0021: Bit 0ReadActive: OC – GF, Inactive: OFF
BV19Main Circuit OvervoltageShown as 'Main Ckt Overvoltage'; Modbus 0021: Bit 1ReadActive: OV, Inactive: OFF
BV20Drive OverloadModbus 0021: Bit 2ReadActive: OL2, Inactive: OFF
BV21Drive OverheatModbus 0021: Bit 3ReadActive: OH1-OH2, Inactive: OFF
BV22Fuse BlownModbus 0021: Bit 5ReadActive: PUF, Inactive: OFF
BV23PI Feedback LossModbus 0021: Bit 6ReadActive: FBL, Inactive: OFF
BV24External FaultModbus 0021: Bit 7ReadActive: EF0 – EF, Inactive: OFF
BV25Hardware ErrorModbus 0021: Bit 8ReadActive: CPF, Inactive: OFF
BV26Motor Overload – OvertorqueShown as 'Mtr OvrLd – OvrTorque'; Modbus 0021: Bit 9ReadActive: OL1 – OL3, Inactive: OFF
BV27OverspeedModbus 0021: Bit AReadActive: OS –DEV, Inactive: OFF
BV28Main Circuit UndervoltageShown as 'Main Ckt Undrvoltage'; Modbus 0021: Bit BReadActive: UV, Inactive: OFF
BV29MCU, Control Power Supply ErrorShown as 'MCU Cntrl Pwr Sy Err'; Modbus 0021: Bit CReadActive: UV1-2-3, Inactive: OFF
BV30Output Phase LossModbus 0021: Bit DReadActive: LF, Inactive: OFF
BV31BUS FaultModbus 0021: Bit EReadActive: BUS, Inactive: OFF
BV32Operator DisconnectModbus 0021: Bit FReadActive: OPR, Inactive: OFF
BV33OperatingModbus 002C: Bit 0ReadActive: OPERATING, Inactive: OFF
BV34Zero SpeedModbus 002C: Bit 1ReadActive: ON, Inactive: OFF
BV35Frequency AgreeModbus 002C: Bit 2ReadActive: ON, Inactive: OFF
BV36Desired Frequency AgreeShown as 'Desired Freq Agree'; Modbus 002C: Bit 3ReadActive: ON, Inactive: OFF
BV37Frequency Detect 1Modbus 002C: Bit 4ReadActive: ON, Inactive: OFF
BV38Frequency Detect 2Modbus 002C: Bit 5ReadActive: ON, Inactive: OFF
BV39Drive Startup CompleteShown as 'Drv Startup Complete'; Modbus 002C: Bit 6ReadActive: ON, Inactive: OFF
BV40Low Voltage DetectModbus 002C: Bit 7ReadActive: ON, Inactive: OFF
BV41Base BlockModbus 002C: Bit 8ReadActive: ON, Inactive: OFF
BV42Frequency Reference ModeShown as 'Frequency Ref Mode'; Modbus 002C: Bit 9ReadActive: LOCAL, Inactive: COM
BV43Run Command ModeModbus 002C: Bit AReadActive: LOCAL, Inactive: COM
BV44Over Torque DetectModbus 002C: Bit BReadActive: ON, Inactive: OFF
BV45Frequency Reference LossShown as 'Frequency Ref Loss'; Modbus 002C: Bit CReadActive: ON, Inactive: OFF
BV46Retry ErrorModbus 002C: Bit DReadActive: ON, Inactive: OFF
BV55Parameter AcceptRuns the RAM enter commandWriteActive: ON, Inactive: OFF
BV56Parameter EnterRuns the ROM (EEPROM) enter commandWriteActive: ON, Inactive: OFF
BV58Bypass Forward Run CmdShown as 'BYP Run Fwd CMD'; Modbus 0001: Bit 0; bypass onlyCommandActive: ON, Inactive: OFF
BV59Bypass Reverse Run CmdShown as 'BYP Run Rev CMD'; Modbus 0001: Bit 1; bypass onlyCommandActive: ON, Inactive: OFF
BV60Emergency Override Drive ReverseHV600/FP605 only; needs b1-04 = 0CommandActive: ON, Inactive: OFF
BV61Bypass Transfer to Bypass CmdShown as 'BYP Xfer to BYP CMD'; bypass onlyCommandActive: ON, Inactive: OFF
BV62Emergency Overide BypassShown as 'Em Over BYPASS CMD'; Modbus 8400: Bit 4; bypass onlyCommandActive: ON, Inactive: OFF
BV63Emergency Override Drive ForwardShown as 'Em Over DRV FWD CMD'; HV600/FP605 onlyCommandActive: ON, Inactive: OFF
BV64Bypass Motor OR Select CommandShown as 'BYP Mtr OR Sel CMD'; bypass onlyCommandActive: ON, Inactive: OFF
BV65Bypass Motor AND Select CommandShown as 'BYP Mtr AND Sel CMD'; bypass onlyCommandActive: ON, Inactive: OFF
BV69Bypass BYPASS Select CommandShown as 'BYP BYPASS Sel CMD'; bypass only; needs Z1-39 = 3CommandActive: BYP, Inactive: DRV
BV70Bypass Fault Reset CommandShown as 'BYP Fault Reset CMD'; Modbus 8400: Bit D; bypass onlyCommandActive: ON, Inactive: OFF
BV71Bypass External Fault CommandShown as 'BYP Ext Fault CMD'; Modbus 8400: Bit E; bypass onlyCommandActive: ON, Inactive: OFF
BV72Bypass DI-01 CommandShown as 'BYP DI-01 Command'; bypass only; needs Z3-12 = 1CommandActive: ON, Inactive: OFF
BV73Bypass DI-02 CommandShown as 'BYP DI-02 Command'; bypass only; needs Z3-12 = 1CommandActive: ON, Inactive: OFF
BV74Bypass DI-03 CommandShown as 'BYP DI-03 Command'; bypass only; needs Z3-12 = 1CommandActive: ON, Inactive: OFF
BV75Bypass DI-04 CommandShown as 'BYP DI-04 Command'; bypass only; needs Z3-12 = 1CommandActive: ON, Inactive: OFF
BV76Bypass DI-05 CommandShown as 'BYP DI-05 Command'; bypass only; needs Z3-12 = 1CommandActive: ON, Inactive: OFF
BV77Bypass DI-06 CommandShown as 'BYP DI-06 Command'; bypass only; needs Z3-12 = 1CommandActive: ON, Inactive: OFF
BV78Bypass DI-07 CommandShown as 'BYP DI-07 Command'; bypass only; needs Z3-12 = 1CommandActive: ON, Inactive: OFF
BV79Bypass DI-08 CommandShown as 'BYP DI-08 Command'; bypass only; needs Z3-12 = 1CommandActive: ON, Inactive: OFF
BV80Bypass HAND Mode StatusShown as 'BYP HAND Mode Status'; Modbus 8784: Bit 0; bypass onlyReadActive: ON, Inactive: OFF
BV81Bypass OFF Mode StatusShown as 'BYP OFF Mode Status'; Modbus 8784: Bit 1; bypass onlyReadActive: ON, Inactive: OFF
BV82Bypass AUTO Mode StatusShown as 'BYPAUTO Mode Status'; Modbus 8784: Bit 2; bypass onlyReadActive: ON, Inactive: OFF
BV83Bypass DRIVE Mode StatusShown as 'BYP DRV Mode Status'; Modbus 8784: Bit 3; bypass onlyReadActive: ON, Inactive: OFF
BV84Bypass BYPASS Mode StatusShown as 'BYP BYPASS Mode Stat'; Modbus 8784: Bit 4; bypass onlyReadActive: ON, Inactive: OFF
BV85Bypass Emergency Run Bypass StatusShown as 'BYP Em-Over BYP Stat'; Modbus 8784: Bit 5; bypass onlyReadActive: ACTIVE, Inactive: OFF
BV86Bypass Emergency Run Drive Fwd StatusShown as 'BYP Em-Over DRV Stat'; Modbus 8784: Bit 6; bypass onlyReadActive: ACTIVE, Inactive: OFF
BV87Bypass Safety StatusShown as 'BYP Safety Status'; Modbus 8784: Bit 7; bypass onlyReadActive: OPEN, Inactive: CLOSED
BV88Bypass BAS Interlock StatusShown as 'BYP BAS Interlk Stat'; Modbus 8785: Bit 0; bypass onlyReadActive: OPEN, Inactive: CLOSED
BV89Bypass Run StatusShown as 'BYP RUN Status'; Modbus 8785: Bit 1; bypass onlyReadActive: RUN, Inactive: OFF
BV90Bypass Fault StatusShown as 'BYP Fault Status'; Modbus 8785: Bit 2; bypass onlyReadActive: FAULT, Inactive: OFF
BV91Bypass Auto Transfer StatusShown as 'BYPAuto Xfer Status'; Modbus 8785: Bit 3; bypass onlyReadActive: ACTIVE, Inactive: OFF
BV92Bypass Remote Transfer StatusShown as 'BYP Remote Xfer Stat'; Modbus 8785: Bit 4; bypass onlyReadActive: ACTIVE, Inactive: OFF
BV93Bypass Energy Savings StatusShown as 'BYP Energy Save Stat'; Modbus 8785: Bit 5; bypass onlyReadActive: ACTIVE, Inactive: OFF
BV94Bypass Motor 1 Select StatusShown as 'BYP Motor 1 Sel Stat'; bypass onlyReadActive: SELECT, Inactive: OFF
BV95Bypass Motor 2 Select StatusShown as 'BYP Motor 2 Sel Stat'; bypass onlyReadActive: SELECT, Inactive: OFF
BV96Bypass Drive Fault StatusShown as 'BYP Drive Flt Status'; Modbus 8786: Bit 0; bypass onlyReadActive: FAULT, Inactive: OFF
BV97BYP Safety Status 2Shown as 'BYP Safety Status 2'; Modbus 8786: Bit 1; bypass onlyReadActive: OPEN, Inactive: CLOSED
BV98Bypass BAS Interlock Fault StatusShown as 'BYP BAS ILock Status'; Modbus 8786: Bit 2; bypass onlyReadActive: FAULT, Inactive: OFF
BV99Bypass External Fault StatusShown as 'BYP Ext Fault Stat'; Modbus 8786: Bit 3; bypass onlyReadActive: FAULT, Inactive: OFF
BV101Bypass Motor OL StatusShown as 'BYP Motor OL Stat'; Modbus 8786: Bit 5; bypass onlyReadActive: FAULT, Inactive: OFF
BV102Bypass Motor 1 External OL StatusShown as 'BYP Motor 1 OL Stat'; bypass onlyReadActive: FAULT, Inactive: OFF
BV103Bypass Motor 2 External OL StatusShown as 'BYP Mtr 2 OL Stat'; bypass onlyReadActive: FAULT, Inactive: OFF
BV104Bypass Brownout Detect StatusShown as 'BYP Brownout Detect'; Modbus 8787: Bit 0; bypass onlyReadActive: FAULT, Inactive: OFF
BV105Bypass Drive Comms StatusShown as 'BYP Drive Comms'; Modbus 8787: Bit 2; bypass onlyReadActive: FAULT, Inactive: OFF
BV106Bypass Loss of Load StatusShown as 'BYP Loss Of Load'; Modbus 8787: Bit 5; bypass onlyReadActive: FAULT, Inactive: OFF
BV107Option Board on Drive StatusShown as 'BYP Option Brd Comms'; Modbus 8787: Bit 4; bypass onlyReadActive: FAULT, Inactive: OFF

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)

How many BACnet points does the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) have?

This list has 213 BACnet objects: 10 analog inputs, 2 analog outputs, 64 analog values, 32 binary inputs, 11 binary outputs, 94 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet points are writable?

67 of the 213 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) BACnet documentation?

The source is YASKAWA AC Drive Option BACnet/IP Technical Manual, Model JOHB-SMP3 (SIEP C730600 0MB), revision 2023-11, published free by Yaskawa at https://www.yaskawa.eu.com/_downloads/download_d22897.

What are the minimum BACnet points to integrate the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?

Start with BV 1 Run FWD Cmd (Start/stop from the BMS (drive)); AV 2 Frequency Cmd (Frequency reference, units per o1-03); BV 4 Drive Fault Reset (Reset a tripped drive); BV 13 RUN-STOP (Running status); BV 15 READY (Drive ready to run); AV 10 Output Frequency (Output frequency, units per o1-03); AV 12 Output Current (Motor amps); AV 13 Output Power (Drive power in kW); BV 16 FAULT (Any active drive fault); AV 40 Last Drive Fault (Most recent fault code).

How do I enable BMS control of the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?

b1-01 Frequency Reference Selection 1 = 3 (Option PCB) and b1-02 Run Command Selection 1 = 3 (Option PCB) or 9 (AUTO Command + Option Run); both default to 1. On a bypass use BV58/BV59 instead of BV1/BV2. BV5 Drive Com Net Command and BV6 Drive Com Control Command (COM/LOCAL) are also provided. In HAND or LOCAL mode the drive ignores the network and disables the bus timeout.

Does the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives) need a BACnet heartbeat or have a communication timeout?

F7-57 BACnet/IP bUS Timeout Value: when above 0 the BMS must keep sending AV2 Frequency Cmd or a run command (AV1, BV1, BV2, BV58, BV59, AV43-AV51). If none arrives within that time while the drive is running, it trips on bUS Option Communication Error, handled per F6-01 (0 ramp, 1 coast (default), 2 fast stop, 3 alarm only, 4 alarm and run at d1-04, 5 alarm and ramp stop). F7-57 = 0 disables it. Switching to AUTO/REMOTE with no recent command gives an immediate bUS. With F6-14 = 1 and F6-01 set to 0-2, the option resets the fault and returns control to BACnet when comms recover.

Can the BMS supply sensor values to the Yaskawa JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?

AV3 PI Setpoint Cmd lets the BMS write the PI setpoint; BO4 Ref Sel: PI Setpoint (or AV5 bit 1) selects it as the setpoint input.

How do I check these points on the real JOHB-SMP3 BACnet/IP option (HV600, Z1000U, GA800 drives)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Yaskawa BACnet points lists

Source: YASKAWA AC Drive Option BACnet/IP Technical Manual, Model JOHB-SMP3 · SIEP C730600 0MB · rev. 2023-11. Object names, instances and units are reproduced as published; descriptions are our own.