Variable frequency drive with bypass (HVAC) · BACnet points list

Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

On the Z1000U Matrix bypass the BACnet MS/TP connection is made at the bypass controller (terminal TB3), which exposes drive and bypass data from one address. The list has the drive objects plus bypass I/O, bypass run/transfer/smoke-purge commands, HOA and contactor status and bypass fault flags.

This page lists 181 BACnet objects for the Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP) — 52 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Yaskawa’s own free documentation, linked below.

Manufacturer
Yaskawa
Model
Z1000U HVAC Matrix Bypass (BACnet MS/TP)
Equipment
Variable frequency drive with bypass (HVAC)
Equipment type
VFDs & pumps
BACnet objects
181 (52 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
1
Also known as
Z1000U Bypass, Z1000U Matrix Bypass, Z1D1, Z1000U HVAC MATRIX Drive Bypass, Z1000U low harmonic bypass, SIEP YAIZ1D 01
Source document
YASKAWA Z1000U HVAC MATRIX Drive Bypass Technical Manual (Appendix C.6, BACnet MS/TP Objects) · SIEP YAIZ1D 01E · rev. 2026-07
Download CSV 181 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Yaskawa’s current documentation and the live device before use. Not official Yaskawa information. Terms of use.

BMS integration notes: Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP)

Integration in brief

Wire BACnet MS/TP to TB3 on the bypass controller and set Z3-01 = 3 (BACnet), Z3-02 node, Z3-03 baud and the device instance in Z3-08/Z3-09, then cycle power. Set Z1-07 = 2 and Z1-08 = 2 so the network supplies the speed reference and run command, put the HOA in AUTO, then write BV58 and AV2. Read BV89 and BV90, and choose the comm-loss action in Z3-05/Z3-06.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 58BYP Run Fwd CMDStart/stop from the BMS (bypass)Command
AV 2Frequency CmdFrequency reference, units per o1-03Command
BV 70BYP Fault Reset CMDReset a bypass faultCommand
BV 89BYP RUN StatusRunning statusRead
BV 82BYP AUTO Mode StatusHOA in AUTO, so BMS commands applyRead
AV 10Output FrequencyOutput frequency, units per o1-03Read
AV 31Motor CurrentMotor ampsRead
AV 13Output PowerDrive power in kWRead
BV 90BYP Fault StatusAny active bypass faultRead
AV 7Fault DetailsBit-coded active fault flagsRead

Enable & remote start

Table C.1: Z1-07 Speed Reference Select = 2 and Z1-08 Run Command Select = 2 (BACnet / serial) let the network set speed and start the unit; both default to 1 (terminals / bypass digital input). BV58/BV59 run the bypass forward/reverse, BV69 selects drive or bypass and BV67 selects AUTO. Monitoring, parameter access, fault set/reset and the multi-function inputs work at any time.

Heartbeat & communication loss

Z3-11 = 1 (default) enables comm-fault detection. Z3-05 sets the action when nothing is received for Z3-06 (0.0-99.9 s, default 2.0 s; 0.0 never times out): 0 ignore, 1 alarm only (default), 2 EF0 fault to the drive, 3 EF0 and open the bypass contactor K3, 4 alarm AL14 and run at the Z3-10 preset speed. Z3-13 can restore the last BACnet speed and/or run commands after a power loss (default 0 = off).

Sensors & values from the BMS

AV3 PID Setpoint Cmd lets the BMS write the PID setpoint (-100 to 100 %). BV72-BV79 can act as the bypass digital inputs from the network when Z3-12 = 1.

Network setup

Watch out for

Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

181 of 181 shown
Type
Access
Show
Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP) BACnet Points List
DescriptionStates
AI1Analog Input 1 LevelModbus 004EH%Read
AI2Analog Input 2 LevelModbus 004FH%Read
AI6Display Format o1-03Modbus 0502HRead
AI7Scale Format b5-20Modbus 01E2HRead
AI8Inverter Model o2-04Modbus 0508FRead
AI9Rated Current n9-01Modbus 05D0HARead
AI10Motor Current UB-01Modbus 8780HARead
AI11Contactor VoltageModbus 8790HVRead
AO1Analog Output 1 LevelModbus 0007H%Command
AO2Analog Output 2 LevelModbus 0008H%Command
AV1Operation CmdPacked run/command word; Modbus 0001HCommand
AVmin2Frequency CmdFrequency reference; Modbus 8401HHz (display units per o1-03)Command
AV3PID Setpoint CmdPID setpoint, -100 to 100 %; Modbus 0006H%Command
AV4MF Output CmdPacked MF output word; Modbus 0009HCommand
AV5Reference Select CmdPacked reference select word; Modbus 000FHCommand
AV6Drive StatusBitmap: run, reverse, ready, fault, outputs; Modbus 0020HRead
AVmin7Fault DetailsBitmap of active fault groups; Modbus 0021HRead
AV8Data Link StatusBitmap of write/limit errors; Modbus 0022HRead
AV9Frequency ReferenceModbus 0040HHz (display units per o1-03)Read
AVmin10Output FrequencyModbus 0041HHz (display units per o1-03)Read
AV11Output VoltageModbus 0045HVRead
AV12Output CurrentModbus 0026HARead
AVmin13Output PowerModbus 0047HkWRead
AV14Torque ReferenceModbus 0048H%Read
AV15MF Input StatusBitmap of multi-function input states; Modbus 002BHRead
AV16Drive Status 2Bitmap of operating status flags; Modbus 002CHRead
AV17MF Output StatusBitmap of multi-function output states; Modbus 002DHRead
AV18DC Bus VoltageModbus 0031HVRead
AV19PID Feedback LevelModbus 0038H%Read
AV20PID Input LevelModbus 0039H%Read
AV21PID Output LevelModbus 003AH%Read
AV22Drive SW NumDrive software number; Modbus 004DHRead
AV23Bypass SW NumBypass software number; Modbus 8791HRead
AV24Comm Error DetailBitmap of serial communication errors; Modbus 003DHRead
AV25KVA SettingModbus 003EHRead
AV26Control MethodModbus 0043HRead
AV27Accel TimeModbus 0200HsWrite
AV28Decel TimeModbus 0201HsWrite
AV29Parameter NumberRegister number (decimal) for AV30Write
AV30Parameter DataData for the register in AV29Write
AVmin31Motor CurrentMotor current measured by the bypass; Modbus 8780HARead
AV32120 V to Kx CoilsContactor coil supply voltage; Modbus 8790HVRead
AV33Drive kWHEnergy used, 0.1 kWh resolution; Modbus 0x005C and 0x005DkWhRead
BI1Input Terminal 1Modbus 002BH:bit 0ReadActive: ON, Inactive: OFF
BI2Input Terminal 2Modbus 002BH:bit 1ReadActive: ON, Inactive: OFF
BI3Input Terminal 3Modbus 002BH:bit 2ReadActive: ON, Inactive: OFF
BI4Input Terminal 4Modbus 002BH:bit 3ReadActive: ON, Inactive: OFF
BI5Input Terminal 5Modbus 002BH:bit 4ReadActive: ON, Inactive: OFF
BI6Input Terminal 6Modbus 002BH:bit 5ReadActive: ON, Inactive: OFF
BI7Input Terminal 7Modbus 002BH:bit 6ReadActive: ON, Inactive: OFF
BI8Multi-Function Out 1Modbus 0020H:bit 5ReadActive: ON, Inactive: OFF
BI9Multi-Function Out 2Modbus 0020H:bit 6ReadActive: ON, Inactive: OFF
BI10BYP DI-1 STATModbus 8781H: bit 0ReadActive: ON, Inactive: OFF
BI11BYP DI-2 STATModbus 8781H: bit 1ReadActive: ON, Inactive: OFF
BI12BYP DI-3 STATModbus 8781H: bit 2ReadActive: ON, Inactive: OFF
BI13BYP DI-4 STATModbus 8781H: bit 3ReadActive: ON, Inactive: OFF
BI14BYP DI-5 STATModbus 8781H: bit 4ReadActive: ON, Inactive: OFF
BI15BYP DI-6 STATModbus 8781H: bit 5ReadActive: ON, Inactive: OFF
BI16BYP DI-7 STATModbus 8781H: bit 6ReadActive: ON, Inactive: OFF
BI17BYP DI-8 STATModbus 8781H: bit 7ReadActive: ON, Inactive: OFF
BI18BYP DO-1 STATModbus 8782H: bit 0ReadActive: ON, Inactive: OFF
BI19BYP DO-2 STATModbus 8782H: bit 1ReadActive: ON, Inactive: OFF
BI20BYP DO-3 STATModbus 8782H: bit 2ReadActive: ON, Inactive: OFF
BI21BYP DO-4 STATModbus 8782H: bit 3ReadActive: ON, Inactive: OFF
BI22BYP DO-5 STATModbus 8782H: bit 4ReadActive: ON, Inactive: OFF
BI23BYP DO-6 STATModbus 8782H: bit 5ReadActive: ON, Inactive: OFF
BI24BYP DO-7 STATModbus 8782H: bit 6ReadActive: ON, Inactive: OFF
BI25BYP DO-8 STATModbus 8782H: bit 7ReadActive: ON, Inactive: OFF
BI26BYP DO-9 STATModbus 8783H: bit 0ReadActive: ON, Inactive: OFF
BI27BYP DO-10 STATModbus 8783H: bit 1ReadActive: ON, Inactive: OFF
BO1MF Output M1-M2Modbus 0009H:bit 0CommandActive: ON, Inactive: OFF
BO2MF Output M3-M4Modbus 0009H:bit 1CommandActive: ON, Inactive: OFF
BO3MF Output M5-M6Modbus 0009H:bit 2CommandActive: ON, Inactive: OFF
BO4Ref Sel: PID SetpointModbus 000FH:bit 1CommandActive: ON, Inactive: OFF
BO5Ref Sel: Term S5 INModbus 8480H:bit 8CommandActive: ON, Inactive: OFF
BO6Ref Sel: Term S6 INModbus 8480H:bit 9CommandActive: ON, Inactive: OFF
BO7Refl Sel: Term S7 INModbus 8480H:bit 10CommandActive: ON, Inactive: OFF
BO8BYP DO-07 COMMANDModbus 8403H:bit 6CommandActive: ON, Inactive: OFF
BO9BYP DO-08 COMMANDModbus 8403H:bit 7CommandActive: ON, Inactive: OFF
BO10BYP DO-09 COMMANDModbus 8403H:bit 8CommandActive: ON, Inactive: OFF
BO11BYP DO-10 COMMANDModbus 8403H:bit 9CommandActive: ON, Inactive: OFF
BV3Ext Fault CmdModbus 8480H:bit 2CommandActive: FAULT, Inactive: OFF
BV4Fault Reset CmdReset drive fault; Modbus 8480H:bit 3CommandActive: RESET, Inactive: OFF
BV7MF Input 3 CmdModbus 8480H:bit 6CommandActive: ON, Inactive: OFF
BV8MF Input 4 CmdModbus 8480H:bit 7CommandActive: ON, Inactive: OFF
BV9MF Input 5 CmdModbus 8480H:bit 8CommandActive: ON, Inactive: OFF
BV10MF Input 6 CmdModbus 8480H:bit 9CommandActive: ON, Inactive: OFF
BV11MF Input 7 CmdModbus 8480H:bit 10CommandActive: ON, Inactive: OFF
BV12Set Fault Contact CmdModbus 0009H:bit 6CommandActive: ENABLE, Inactive: OFF
BV13RUN-STOPModbus 0020H:bit 0ReadActive: RUN, Inactive: OFF
BV14REV-FWDModbus 0020H:bit 1ReadActive: REV, Inactive: FWD
BV15READYModbus 0020H:bit 2ReadActive: READY, Inactive: OFF
BV16FAULTModbus 0020H:bit 3ReadActive: FAULTED, Inactive: OFF
BV17Data Set ErrorModbus 0020H:bit 4ReadActive: ERROR, Inactive: OFF
BV18Overcurrent – Gnd FltModbus 0021H:bit 0ReadActive: OC-GF, Inactive: OFF
BV19Main Ckt OverVoltageModbus 0021H:bit 1ReadActive: OV, Inactive: OFF
BV20Drive OverLoadModbus 0021H:bit 2ReadActive: OL2, Inactive: OFF
BV21Drive OverHeatModbus 0021H:bit 3ReadActive: OH1-OH2, Inactive: OFF
BV22Fuse BlownModbus 0021H:bit 5ReadActive: PUF, Inactive: OFF
BV23PID Feedback LossModbus 0021H:bit 6ReadActive: FBL, Inactive: OFF
BV24External FaultModbus 0021H:bit 7ReadActive: EF0-EF, Inactive: OFF
BV25Hardware ErrorModbus 0021H:bit 8ReadActive: CPF, Inactive: OFF
BV26Mtr Ovrld-OvrTorqueModbus 0021H:bit 9ReadActive: OL1-OL3, Inactive: OFF
BV27OverSpeedModbus 0021H:bit 10ReadActive: OS-DEV, Inactive: OFF
BV28Main Ckt UnderVoltageModbus 0021H:bit 11ReadActive: UV, Inactive: OFF
BV29MCU Cntl Pwr Sy ErrModbus 0021H:bit 12ReadActive: UV1-2-3, Inactive: OFF
BV30Output Phase LossModbus 0021H:bit 13ReadActive: LF, Inactive: OFF
BV31Communication ErrorModbus 0021H:bit 14ReadActive: CE, Inactive: OFF
BV32Operator DisconnectModbus 0021H:bit 15ReadActive: OPR, Inactive: OFF
BV33OperatingModbus 002CH:bit 0ReadActive: OPERATING, Inactive: OFF
BV34Zero SpeedModbus 002CH:bit 1ReadActive: ON, Inactive: OFF
BV35Frequency AgreeModbus 002CH:bit 2ReadActive: ON, Inactive: OFF
BV36Desired Freq AgreeModbus 002CH:bit 3ReadActive: ON, Inactive: OFF
BV37Frequency Detect 1Modbus 002CH:bit 4ReadActive: ON, Inactive: OFF
BV38Frequency Detect 2Modbus 002CH:bit 5ReadActive: ON, Inactive: OFF
BV39Drv Startup CompleteModbus 002CH:bit 6ReadActive: ON, Inactive: OFF
BV40Low Voltage DetectModbus 002CH:bit 7ReadActive: ON, Inactive: OFF
BV41Base BlockModbus 002CH:bit 8ReadActive: ON, Inactive: OFF
BV42Frequency Ref ModeModbus 8785H:bit 8ReadActive: COM, Inactive: LOCAL
BV43Run Command ModeModbus 8485H:bit 9ReadActive: COM, Inactive: LOCAL
BV44Over Torque DetectModbus 002CH:bit 11ReadActive: ON, Inactive: OFF
BV45Frequency Ref LostModbus 002CH:bit 12ReadActive: ON, Inactive: OFF
BV46Retry ErrorModbus 002CH:bit 13ReadActive: ON, Inactive: OFF
BV47Modbus Comms ErrorModbus 002CH:bit 14ReadActive: ON, Inactive: OFF
BV48Modbus Timeout ErrorModbus 002CH:bit 15ReadActive: ON, Inactive: OFF
BV49CRC ErrorModbus 003DH:bit 0ReadActive: ON, Inactive: OFF
BV50Invalid Data LengthModbus 003DH:bit 1ReadActive: ON, Inactive: OFF
BV51Parity ErrorModbus 003DH:bit 3ReadActive: ON, Inactive: OFF
BV52Overrun ErrorModbus 003DH:bit 4ReadActive: ON, Inactive: OFF
BV53Framing ErrorModbus 003DH:bit 5ReadActive: ON, Inactive: OFF
BV54Timeout ErrorModbus 003DH:bit 6ReadActive: ON, Inactive: OFF
BV55Parameter AcceptON = apply AV29/AV30 write to RAM only; Modbus 0910H:bit 0WriteActive: ON, Inactive: OFF
BV56Parameter EnterON = apply AV29/AV30 write and save to EEPROM; Modbus 0900H:bit 0WriteActive: ON, Inactive: OFF
BV57Drive Comms ErrorModbus 002CH:bit 15ReadActive: ON, Inactive: OFF
BVmin58BYP Run Fwd CMDRun bypass forward; Modbus 8400H: bit 0CommandActive: ON, Inactive: OFF
BV59BYP Run Rev CMDRun bypass reverse; Modbus 8400H: bit 1CommandActive: ON, Inactive: OFF
BV61BYP Xfer to BYP CMDTransfer motor to bypass; Modbus 8400H: bit 3CommandActive: ON, Inactive: OFF
BV62BYP Smok Prg BYP CMDSmoke purge in bypass; Modbus 8400H: bit 4CommandActive: ON, Inactive: OFF
BV63BYP Smok Prg DRV CMDSmoke purge on the drive; Modbus 8400H: bit 5CommandActive: ON, Inactive: OFF
BV64BYP Mtr OR Sel CMDModbus 8400H: bit 6CommandActive: ON, Inactive: OFF
BV65BYP Mtr AND Sel CMDModbus 8400H: bit 7CommandActive: ON, Inactive: OFF
BV66BYP Drive Select CMDSelect drive mode; Modbus 8400H: bit 9CommandActive: ON, Inactive: OFF
BV67BYP Auto Select CMDSelect AUTO mode; Modbus 8400H: bit 10CommandActive: ON, Inactive: OFF
BV69BYP BYPASS Sel CMDSelect bypass (BYP) or drive (DRV); Modbus 8400H: bit 12CommandActive: BYP, Inactive: DRV
BVmin70BYP Fault Reset CMDReset bypass fault; Modbus 8400H: bit 13CommandActive: ON, Inactive: OFF
BV71BYP Ext Fault CMDExternal bypass fault; Modbus 8400H: bit 14CommandActive: ON, Inactive: OFF
BV72BYP DI-01 CommandModbus 8402H: bit 0; disabled unless Z3-12 = 1WriteActive: ON, Inactive: OFF
BV73BYP DI-02 CommandModbus 8402H: bit 1; disabled unless Z3-12 = 1WriteActive: ON, Inactive: OFF
BV74BYP DI-03 CommandModbus 8402H: bit 2; disabled unless Z3-12 = 1WriteActive: ON, Inactive: OFF
BV75BYP DI-04 CommandModbus 8402H: bit 3; disabled unless Z3-12 = 1WriteActive: ON, Inactive: OFF
BV76BYP DI-05 CommandModbus 8402H: bit 4; disabled unless Z3-12 = 1WriteActive: ON, Inactive: OFF
BV77BYP DI-06 CommandModbus 8402H: bit 5; disabled unless Z3-12 = 1WriteActive: ON, Inactive: OFF
BV78BYP DI-07 CommandModbus 8402H: bit 6; disabled unless Z3-12 = 1WriteActive: ON, Inactive: OFF
BV79BYP DI-08 CommandModbus 8402H: bit 7; disabled unless Z3-12 = 1WriteActive: ON, Inactive: OFF
BV80BYP HAND Mode StatusModbus 8784H: bit 0ReadActive: ON, Inactive: OFF
BV81BYP OFF Mode StatusModbus 8784H: bit 1ReadActive: ON, Inactive: OFF
BVmin82BYP AUTO Mode StatusModbus 8784H: bit 2ReadActive: ON, Inactive: OFF
BV83BYP DRV Mode StatusModbus 8784H: bit 3ReadActive: ON, Inactive: OFF
BV84BYP BYPASS Mode StatModbus 8784H: bit 4ReadActive: ON, Inactive: OFF
BV85BYP Smk Prg BYP StatModbus 8784H: bit 5ReadActive: ACTIVE, Inactive: OFF
BV86BYP Smk Prg DRV StatModbus 8784H: bit 6ReadActive: ACTIVE, Inactive: OFF
BV87BYP Safety StatusModbus 8784H: bit 7ReadActive: OPEN, Inactive: CLOSED
BV88BYP BAS Interlk StatModbus 8785H: bit 0ReadActive: OPEN, Inactive: CLOSED
BVmin89BYP RUN StatusRunning (drive or bypass); Modbus 8785H: bit 1ReadActive: RUN, Inactive: OFF
BVmin90BYP Fault StatusAny active bypass fault; Modbus 8785H: bit 2ReadActive: FAULT, Inactive: OFF
BV91BYP Auto Xfer StatusModbus 8785H: bit 3ReadActive: ACTIVE, Inactive: OFF
BV92BYP Remote Xfer StatModbus 8785H: bit 4ReadActive: ACTIVE, Inactive: OFF
BV93BYP Energy Save StatModbus 8785H: bit 5ReadActive: ACTIVE, Inactive: OFF
BV94BYP Motor 1 Sel StatModbus 8785H: bit 6ReadActive: SELECT, Inactive: OFF
BV95BYP Motor 2 Sel StatModbus 8785H: bit 7ReadActive: SELECT, Inactive: OFF
BV96BYP Drive Flt StatusModbus 8786H: bit 0ReadActive: FAULT, Inactive: OFF
BV97BYP Safety Flt StatModbus 8786H: bit 1ReadActive: FAULT, Inactive: OFF
BV98BYP BAS ILock StatusModbus 8786H: bit 2ReadActive: FAULT, Inactive: OFF
BV99BYP Ext Fault StatModbus 8786H: bit 3ReadActive: FAULT, Inactive: OFF
BV101BYP Motor OL StatModbus 8786H: bit 5ReadActive: FAULT, Inactive: OFF
BV102BYP Motor 1 OL StatModbus 8786H: bit 6ReadActive: FAULT, Inactive: OFF
BV103BYP Mtr 2 OL StatModbus 8786H: bit 7ReadActive: FAULT, Inactive: OFF
BV104BYP Input Phase LossModbus 8787H: bit 0ReadActive: FAULT, Inactive: OFF
BV105BYP Drive CommsModbus 8787H: bit 2ReadActive: FAULT, Inactive: OFF
BV106BYP Loss Of LoadModbus 8787H: bit 5ReadActive: FAULT, Inactive: OFF
BV107BYP Option Brd CommsModbus 8787H: bit 3ReadActive: FAULT, Inactive: OFF
Object ID lookup: Yaskawa Z1000U HVAC Matrix Bypass point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Z1000U HVAC Matrix Bypass (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP)

How many BACnet points does the Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP) have?

This list has 181 BACnet objects: 8 analog inputs, 2 analog outputs, 33 analog values, 27 binary inputs, 11 binary outputs, 100 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP) BACnet points are writable?

52 of the 181 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP) BACnet documentation?

The source is YASKAWA Z1000U HVAC MATRIX Drive Bypass Technical Manual (Appendix C.6, BACnet MS/TP Objects) (SIEP YAIZ1D 01E), revision 2026-07, published free by Yaskawa at https://www.yaskawa.com/delegate/getAttachment?documentId=SIEPYAIZ1D01&cmd=documents&documentName=SIEPYAIZ1D01.pdf.

What are the minimum BACnet points to integrate the Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP)?

Start with BV 58 BYP Run Fwd CMD (Start/stop from the BMS (bypass)); AV 2 Frequency Cmd (Frequency reference, units per o1-03); BV 70 BYP Fault Reset CMD (Reset a bypass fault); BV 89 BYP RUN Status (Running status); BV 82 BYP AUTO Mode Status (HOA in AUTO, so BMS commands apply); AV 10 Output Frequency (Output frequency, units per o1-03); AV 31 Motor Current (Motor amps); AV 13 Output Power (Drive power in kW); BV 90 BYP Fault Status (Any active bypass fault); AV 7 Fault Details (Bit-coded active fault flags).

How do I enable BMS control of the Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP)?

Table C.1: Z1-07 Speed Reference Select = 2 and Z1-08 Run Command Select = 2 (BACnet / serial) let the network set speed and start the unit; both default to 1 (terminals / bypass digital input). BV58/BV59 run the bypass forward/reverse, BV69 selects drive or bypass and BV67 selects AUTO. Monitoring, parameter access, fault set/reset and the multi-function inputs work at any time.

Does the Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

Z3-11 = 1 (default) enables comm-fault detection. Z3-05 sets the action when nothing is received for Z3-06 (0.0-99.9 s, default 2.0 s; 0.0 never times out): 0 ignore, 1 alarm only (default), 2 EF0 fault to the drive, 3 EF0 and open the bypass contactor K3, 4 alarm AL14 and run at the Z3-10 preset speed. Z3-13 can restore the last BACnet speed and/or run commands after a power loss (default 0 = off).

Can the BMS supply sensor values to the Yaskawa Z1000U HVAC Matrix Bypass (BACnet MS/TP)?

AV3 PID Setpoint Cmd lets the BMS write the PID setpoint (-100 to 100 %). BV72-BV79 can act as the bypass digital inputs from the network when Z3-12 = 1.

How do I check these points on the real Z1000U HVAC Matrix Bypass (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Yaskawa BACnet points lists

Source: YASKAWA Z1000U HVAC MATRIX Drive Bypass Technical Manual (Appendix C.6, BACnet MS/TP Objects) · SIEP YAIZ1D 01E · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.