Easy BACnet
  1. Home
  2. BACnet points lists
  3. Wilo
  4. Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)

Pump (CIF-Module BACnet interface) · BACnet points list

Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) BACnet points list

Updated 4 November 2026

Short answer

The Stratos GIGA2.0 accepts a CIF-Module for BACnet MS/TP or, with the Ethernet Multiprotocol module, BACnet IP. The BMS writes on/off, control mode and a relative duty point, and keeps control alive with a bus command timer. It reports speed, power, head, calculated flow and energy, plus warning and error codes, and exposes override, preset (fallback) and auxiliary parameter sets. This list adds heat/cooling energy metering and two extra analog inputs (AI 48/49).

This page lists 127 BACnet objects for the Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wilo’s own free documentation, linked below.

Manufacturer
Wilo
Model
Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)
Equipment
Pump (CIF-Module BACnet interface)
Equipment type
VFDs & pumps
BACnet objects
127 (30 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
CIF-Module 1.00-6.01 (EDE); datapoint list valid to 6.11
Also known as
Stratos GIGA2.0, Stratos GIGA2.0-I, Stratos GIGA2.0-D, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol, 2190367, 2211408
Source document
WILO BACnet - CIF-Module / IF-Module installation and operating instructions with functional description (datapoint list) and CIF-Module EDE files · wilo194261 (EDE: wilo254515 MS/TP, wilo666820 Ethernet) · rev. EDE 2024-09-23 (CIF-Module 1.00...6.01)
Download CSV 127 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Wilo’s current documentation and the live device before use. Not official Wilo information. Terms of use.

BMS integration notes: Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)

Integration in brief

Write the control mode (MO 0), the duty point setpoint in % (AO 0) and the on/off command (BO 0). To keep BMS control safe, write SET to the bus command timer (MO 1) more often than its timeout (AO 8, default 300 s); use SET_PRESET if the pump should load the Prs fallback values when the BMS goes quiet. Read status from BI 10, BI 13 and MI 1.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0device/functionOnInpPump on/off commandCommand
MO 0controlFunctionInpControl mode, e.g. dp-c, dp-v, constant speedCommand
AO 0dutyPointRelInpDuty point setpoint, % of the control rangeCommand
MO 1busCmd.TimerInp,ActHeartbeat: write SET (2) before the timeoutCommand
BI 10device/functionOnOutPump onRead
BI 15localOperationOutLocal override; BMS not in controlRead
AI 1speedP01OutPump speed, rpmRead
AI 4powerInputOutElectrical input power, WRead
BI 13errorPresentOutAny active errorRead
MI 1warning/errorMessageOutWilo error codeRead

Enable & remote start

Once the CIF-Module is set up, the pump's setpoint, control mode and on/off follow the values held in the module, not the local menu. BI 15 shows when a local action is overriding BMS control. MO 3 selects where the setpoint comes from (1 = IF-Module).

Heartbeat & communication loss

MO 1 bus command timer: write SET (2) again before the timeout in AO 8 (default 300 s). If it runs out the local menu is released and the display may show E50/E54; with SET_PRESET (6) the pump also loads the preset (Prs) on/off, control mode and duty point. Writing MANUAL (5) unlocks the local menu permanently; OFF (1) returns to the factory behaviour.

Sensors & values from the BMS

AO 9 / AO 10 accept reference temperatures T1/T2 from an external sensor and AO 11 an external sensor value; the selected values read back on AI 2009-2011.

Network setup

Watch out for

Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

127 of 127 shown
Type
Access
Show
Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) BACnet Points List
DescriptionStates
AI0dutyPointRelOutRelative duty point the pump is running at%Read
AImin1speedP01OutSpeed of the master pumprpmRead
AI2flowOutFlow (calculated; for monitoring only)m³/hRead
AI3pressureOutHead/pressure at the pump (may be estimated)barRead
AImin4powerInputOutElectrical input powerWRead
AI5temperatureFluid@DeviceOutFluid temperature measured at the pump°CRead
AI6operationTimeOutTotal run timeminRead
AI7energyConsumptionOutTotal electrical energy usedkWhRead
AI8speedMivActLowest speed available for the setpointrpmRead
AI9speedMavActHighest speed available for the setpointrpmRead
AI10pressureMinPHdVarActLowest head for dp-v (variable) controlbarRead
AI11pressureMaxPHdVarActHighest head for dp-v (variable) controlbarRead
AI12flowMavOutMaximum flow (full speed, zero head)m³/hRead
AI13pressureMinPHdConstActLowest head for dp-c (constant) controlbarRead
AI14pressureMaxPHdConstActHighest head for dp-c (constant) controlbarRead
AI15powerInputMavOutMaximum electrical input powerWRead
AI16temperat.FluidFwdOutSupply (forward) fluid temperature°CRead
AI17temperat.FluidRetOutReturn fluid temperature°CRead
AI18analogIn1MeasuredValOutValue measured at analog input 1Read
AI19analogIn2MeasuredValOutValue measured at analog input 2Read
AI20powerHeatingOutHeating power (supply warmer than return)WRead
AI21powerRefrigerationOutCooling power (supply colder than return)WRead
AI22energyHeatRrst.ableOutHeat energy meter, resettablekWhRead
AI23energyHeatRrst.ableSttOutStart time of resettable heat meter (Unix time)sRead
AI24energyRefrigRrst.ableOutCooling energy meter, resettablekWhRead
AI25energyRefrigRrst.ableSttOutStart time of resettable cooling meter (Unix time)sRead
AI26energyHeat.TotalOutHeat energy totalkWhRead
AI27energyRefrig.TotalOutCooling energy totalkWhRead
AI28voltageInputOutMains supply voltageVRead
AI30systemTimeOutPump system time (Unix epoch)sRead
AI31dutyPointRelMioActLower limit of the active relative duty point%Read
AI32dutyPointRelMaoActUpper limit of the active relative duty point%Read
AI33dutyPoint100%ValActValue that equals 100 % duty point (active)Read
AI34dutyPointRelActActive relative duty point (setpoint in use)%Read
AI35busCmd.TimerTimeRemain.OutTime left on the bus command timersRead
AI36flowLmiActActive lower flow limitm³/hRead
AI37flowLmaActActive upper flow limitm³/hRead
AI38flowLofActActive flow limit value (Lof)m³/hRead
AI39flowNominal4Ctrl.Fun.ActActive nominal flow for flow-dependent controlm³/hRead
AI40flowZeroSetpointRed.FactorActActive setpoint reduction at zero flow%Read
AI48analogIn3MeasuredValOutValue measured at analog input 3Read
AI49analogIn4MeasuredValOutValue measured at analog input 4Read
AI50pressureMavOutMaximum headbarRead
AI51flowMivOutMinimum flow (operating limit)m³/hRead
AI1031dutyPointRelMioLimLower limit of the duty point setting%Read
AI1032dutyPointRelMaoLimUpper limit of the duty point setting%Read
AI1033dutyPoint100%ValLimValue that equals 100 % duty point (limit)Read
AI1034dutyPointRelSelSelected relative duty point%Read
AI1131dutyPointRelMioPrsLimLower limit of the preset duty point%Read
AI1132dutyPointRelMaoPrsLimUpper limit of the preset duty point%Read
AI1133dutyPoint100%ValPrsLimValue that equals 100 % (preset duty point)Read
AI1231dutyPointRelMioAuxLimLower limit of the auxiliary duty point%Read
AI1232dutyPointRelMaoAuxLimUpper limit of the auxiliary duty point%Read
AI1233dutyPoint100%ValAuxLimValue that equals 100 % (auxiliary duty point)Read
AI2009temperat.ReferenceT1SelSelected reference temperature T1°CRead
AI2010temperat.ReferenceT2SelSelected reference temperature T2°CRead
AI2011sensorSignalSelSelected external sensor valueRead
AI2031dutyPointRelMioSelLower limit of the selected duty point%Read
AI2032dutyPointRelMaoSelUpper limit of the selected duty point%Read
AI2033dutyPoint100%ValSelValue that equals 100 % (selected duty point)Read
AOmin0dutyPointRelInpDuty point setpoint from the BMS%Command
AO5pidKpInp,ActPID gain (user-defined PID mode)Command
AO6pidTiInp,ActPID integral timesCommand
AO7pidTdInp,ActPID derivative timesCommand
AO8busCmd.TimerTimeoutInp,ActBus command timer timeoutsCommand
AO9temperat.ReferenceT1InpReference temperature T1 from external sensor°CCommand
AO10temperat.ReferenceT2InpReference temperature T2 from external sensor°CCommand
AO11sensorSignalInpExternal sensor value written by the BMSCommand
AO36flowLmiInpLower flow limit settingm³/hCommand
AO37flowLmaInpUpper flow limit settingm³/hCommand
AO38flowLofInpFlow limit value setting (Lof)m³/hCommand
AO39flowNominal4Ctrl.Fun.InpNominal flow for flow-dependent controlm³/hCommand
AO40flowZeroSetpointRed.FactorInpSetpoint reduction at zero flow%Command
AO100dutyPointRelPrsInp,LimPreset duty point (startup / bus failure)%Command
AO200dutyPointRelAuxInpDuty point for the auxiliary parameter set%Command
BI0device/functionOnActActive on/off commandRead
BI1overrideOffActOverride OFF active (includes local Ext. Off)Read
BI2overrideMaxActOverride MAX activeRead
BI3overrideMinActOverride MIN activeRead
BI4lowRegulationLimitOutRunning at the low control limitRead
BI5highRegulationLimitOutRunning at the high control limitRead
BI6setpointOutOfRangeActSetpoint out of rangeRead
BI7setpointDifferenceOutSetpoint not reachedRead
BI8autoNightModeOutAutomatic night setback runningRead
BI9ready4OperationOutReady for operationRead
BImin10device/functionOnOutPump onRead
BI11serviceRequiredOutService requiredRead
BI12warningPresentOutWarning presentRead
BImin13errorPresentOutError presentRead
BImin15localOperationOutLocal override; BMS commands not in controlRead
BI16externalSetpointOutSetpoint from an external or preset sourceRead
BI17overrideOnActOverride ON activeRead
BI18actuationLimitOutPump at an actuation limit (pause the BMS PID)Read
BI19autoNightModeActAutomatic night setback enabledRead
BI2000device/functionOnSelSelected on/off commandRead
BOmin0device/functionOnInpOn/off command from the BMSCommand
BO1overrideOffInpOverride OFF (duty point 0 %)Command
BO2overrideMaxInpOverride MAX (duty point 100 %)Command
BO3overrideMinInpOverride MIN (minimum duty point)Command
BO17overrideOnInpOverride ONCommand
BO100device/functionOnPrsInp,LimPreset on/off (startup / bus failure)Command
BO200device/functionOnAuxInpOn/off for the auxiliary parameter setCommand
MI0controlFunctionActActive control modeRead1=Gen_Spd, 6=Gen_PHdConst, 7=Gen_PHdVar, 9=Gen_T, 10=Gen_TDiff, 13=Gen_UsrDfd, 15=INVALID, 16=HeatRadiator_PHd, 17=HeatRadiator_DA, 18=HeatRadiator_T, 19=HeatFloor_PHd, 20=HeatFloor_DA, 21=HeatFloor_T, 22=HeatCeiling_PHd, 23=HeatCeiling_DA, 24=HeatCeiling_T, 25=HeatFan_PHd, 26=HeatFan_DA, 27=HeatFan_T, 28=HeatB._T, 29=HeatB._TDiff, 30=HeatB._Acc.Flow, 31=HeatE._T, 32=HeatE._TDiff, 33=HeatE._Acc.Flow, 34=Heat_PHdConst, 35=Heat_PHdVar, 36=Heat_PHdExt, 37=Heat_DA, 38=Heat_VolFlow, 39=Heat_Acc.Flow, 40=Heat_T, 41=Heat_TDiff, 42=Heat_Spd, 43=CoolCeiling_PHd, 44=CoolCeiling_DA, 45=CoolCeiling_T, 46=CoolFloor_PHd, 47=CoolFloor_DA, 48=CoolFloor_T, 49=CoolFan_PHd, 50=CoolFan_DA, 51=CoolFan_T, 52=CoolB._T, 53=CoolB._TDiff, 54=CoolB._Acc.Flow, 55=CoolE._T, 56=CoolE._TDiff, 57=CoolE._Acc.Flow, 58=Cool_PHdConst, 59=Cool_PHdVar, 60=Cool_PHdExt, 61=Cool_DA, 62=Cool_VolFlow, 63=Cool_Acc.Flow, 64=Cool_T, 65=Cool_TDiff, 66=Cool_Spd, 68=SanW.Heat._TDiff, 69=SanL.S._T, 70=SanL.S._Acc.Flow, 71=San_PHdConst, 72=San_PHdVar, 73=San_PHdExternal, 74=San_VolFlow, 75=San_Acc.Flow, 76=San_T, 77=San_TDiff, 78=San_Spd, 79=Gen_PHdExt, 80=Gen_DA, 81=Gen_VolFlow, 82=Gen_Acc.Flow, 83=ScndPHdConst, 84=ScndPHdVar, 85=ScndFlow, 86=ScndSpd, 87=HeatConcrete_PHd, 88=HeatConcrete_DA, 90=HeatConcrete_Flow, 91=HeatBottle_Flow, 92=HeatMan_MFA, 93=HeatMan_Flow, 94=HeatTank_MFA, 95=HeatTank_Flow, 96=HeatExchanger_Flow, 97=HeatSource_TDiff, 98=HeatSource_Flow, 99=HeatDistrict_PHdConst, 100=HeatDistrict_PHdVar, 101=HeatDistrict_PHdExt, 102=CoolConcrete_PHd, 103=CoolConcrete_DA, 104=CoolConcrete_TDiff, 105=CoolConcrete_Flow, 106=CoolBottle_Flow, 107=CoolMan_MFA, 108=CoolMan_Flow, 109=CoolTank_MFA, 110=CoolTank_Flow, 111=CoolExchanger_Flow, 113=CoolCondensor_Flow, 114=CoolDistrict_PHdConst, 115=CoolDistrict_PHdVar, 116=CoolDistrict_PHdExt
MImin1warning/errorMessageOutCurrent Wilo warning/error codeReadWilo error code: 1=NO_ERROR, value n = code E(n-1); full list in the Wilo datapoint list
MI2busCmd.TimerActBus command timer stateRead1=OFF, 2=SET, 3=ACTIVE, 4=RESET, 5=MANUAL, 6=SET_PRESET, 7=ACTIVE_PRESET, 8=RESET_PRESET, 9=MANUAL_PRESET, 10=INVALID
MI3setpointSignalSourceActActive setpoint sourceRead1=IF-Module, 6=Internal, 7=EXT 1, 8=EXT 2, 9=INVALID, 10=EXT 3, 11=EXT 4
MI4userTroubleCodeOutCurrent Wilo trouble code (E400-E699)Read1=no error (CODE_0); value n = Wilo trouble code E(n-1), E400-E699
MI18analogIn1MeasuredValunitsOutUnits of the analog input 1 valueRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI19analogIn2MeasuredValunitsOutUnits of the analog input 2 valueRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI33dutyPointRelunitsActUnits of the active duty pointRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI48analogIn3MeasuredValunitsOutUnits of the analog input 3 valueRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI49analogIn4MeasuredValunitsOutUnits of the analog input 4 valueRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI1003setpointSignalSourceSelSelected setpoint sourceRead1=IF-Module, 6=Internal, 7=EXT 1, 8=EXT 2, 9=INVALID, 10=EXT 3, 11=EXT 4
MI1033dutyPointRelunitsLimUnits of the duty point limitsRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI1133dutyPointRelunitsPrsLimUnits of the preset duty pointRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI1233dutyPointRelunitsAuxLimUnits of the auxiliary duty pointRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI2000controlFunctionSelSelected control modeRead1=Gen_Spd, 6=Gen_PHdConst, 7=Gen_PHdVar, 9=Gen_T, 10=Gen_TDiff, 13=Gen_UsrDfd, 15=INVALID, 16=HeatRadiator_PHd, 17=HeatRadiator_DA, 18=HeatRadiator_T, 19=HeatFloor_PHd, 20=HeatFloor_DA, 21=HeatFloor_T, 22=HeatCeiling_PHd, 23=HeatCeiling_DA, 24=HeatCeiling_T, 25=HeatFan_PHd, 26=HeatFan_DA, 27=HeatFan_T, 28=HeatB._T, 29=HeatB._TDiff, 30=HeatB._Acc.Flow, 31=HeatE._T, 32=HeatE._TDiff, 33=HeatE._Acc.Flow, 34=Heat_PHdConst, 35=Heat_PHdVar, 36=Heat_PHdExt, 37=Heat_DA, 38=Heat_VolFlow, 39=Heat_Acc.Flow, 40=Heat_T, 41=Heat_TDiff, 42=Heat_Spd, 43=CoolCeiling_PHd, 44=CoolCeiling_DA, 45=CoolCeiling_T, 46=CoolFloor_PHd, 47=CoolFloor_DA, 48=CoolFloor_T, 49=CoolFan_PHd, 50=CoolFan_DA, 51=CoolFan_T, 52=CoolB._T, 53=CoolB._TDiff, 54=CoolB._Acc.Flow, 55=CoolE._T, 56=CoolE._TDiff, 57=CoolE._Acc.Flow, 58=Cool_PHdConst, 59=Cool_PHdVar, 60=Cool_PHdExt, 61=Cool_DA, 62=Cool_VolFlow, 63=Cool_Acc.Flow, 64=Cool_T, 65=Cool_TDiff, 66=Cool_Spd, 68=SanW.Heat._TDiff, 69=SanL.S._T, 70=SanL.S._Acc.Flow, 71=San_PHdConst, 72=San_PHdVar, 73=San_PHdExternal, 74=San_VolFlow, 75=San_Acc.Flow, 76=San_T, 77=San_TDiff, 78=San_Spd, 79=Gen_PHdExt, 80=Gen_DA, 81=Gen_VolFlow, 82=Gen_Acc.Flow, 83=ScndPHdConst, 84=ScndPHdVar, 85=ScndFlow, 86=ScndSpd, 87=HeatConcrete_PHd, 88=HeatConcrete_DA, 90=HeatConcrete_Flow, 91=HeatBottle_Flow, 92=HeatMan_MFA, 93=HeatMan_Flow, 94=HeatTank_MFA, 95=HeatTank_Flow, 96=HeatExchanger_Flow, 97=HeatSource_TDiff, 98=HeatSource_Flow, 99=HeatDistrict_PHdConst, 100=HeatDistrict_PHdVar, 101=HeatDistrict_PHdExt, 102=CoolConcrete_PHd, 103=CoolConcrete_DA, 104=CoolConcrete_TDiff, 105=CoolConcrete_Flow, 106=CoolBottle_Flow, 107=CoolMan_MFA, 108=CoolMan_Flow, 109=CoolTank_MFA, 110=CoolTank_Flow, 111=CoolExchanger_Flow, 113=CoolCondensor_Flow, 114=CoolDistrict_PHdConst, 115=CoolDistrict_PHdVar, 116=CoolDistrict_PHdExt
MI2033dutyPointRelunitsSelUnits of the selected duty pointRead5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h
MI2034parameterSetSelectorSelParameter set in useRead1=norm, 2=aux, 3=preset
MOmin0controlFunctionInpControl mode command from the BMSCommand1=Gen_Spd, 6=Gen_PHdConst, 7=Gen_PHdVar, 9=Gen_T, 10=Gen_TDiff, 13=Gen_UsrDfd, 15=INVALID, 16=HeatRadiator_PHd, 17=HeatRadiator_DA, 18=HeatRadiator_T, 19=HeatFloor_PHd, 20=HeatFloor_DA, 21=HeatFloor_T, 22=HeatCeiling_PHd, 23=HeatCeiling_DA, 24=HeatCeiling_T, 25=HeatFan_PHd, 26=HeatFan_DA, 27=HeatFan_T, 28=HeatB._T, 29=HeatB._TDiff, 30=HeatB._Acc.Flow, 31=HeatE._T, 32=HeatE._TDiff, 33=HeatE._Acc.Flow, 34=Heat_PHdConst, 35=Heat_PHdVar, 36=Heat_PHdExt, 37=Heat_DA, 38=Heat_VolFlow, 39=Heat_Acc.Flow, 40=Heat_T, 41=Heat_TDiff, 42=Heat_Spd, 43=CoolCeiling_PHd, 44=CoolCeiling_DA, 45=CoolCeiling_T, 46=CoolFloor_PHd, 47=CoolFloor_DA, 48=CoolFloor_T, 49=CoolFan_PHd, 50=CoolFan_DA, 51=CoolFan_T, 52=CoolB._T, 53=CoolB._TDiff, 54=CoolB._Acc.Flow, 55=CoolE._T, 56=CoolE._TDiff, 57=CoolE._Acc.Flow, 58=Cool_PHdConst, 59=Cool_PHdVar, 60=Cool_PHdExt, 61=Cool_DA, 62=Cool_VolFlow, 63=Cool_Acc.Flow, 64=Cool_T, 65=Cool_TDiff, 66=Cool_Spd, 68=SanW.Heat._TDiff, 69=SanL.S._T, 70=SanL.S._Acc.Flow, 71=San_PHdConst, 72=San_PHdVar, 73=San_PHdExternal, 74=San_VolFlow, 75=San_Acc.Flow, 76=San_T, 77=San_TDiff, 78=San_Spd, 79=Gen_PHdExt, 80=Gen_DA, 81=Gen_VolFlow, 82=Gen_Acc.Flow, 83=ScndPHdConst, 84=ScndPHdVar, 85=ScndFlow, 86=ScndSpd, 87=HeatConcrete_PHd, 88=HeatConcrete_DA, 90=HeatConcrete_Flow, 91=HeatBottle_Flow, 92=HeatMan_MFA, 93=HeatMan_Flow, 94=HeatTank_MFA, 95=HeatTank_Flow, 96=HeatExchanger_Flow, 97=HeatSource_TDiff, 98=HeatSource_Flow, 99=HeatDistrict_PHdConst, 100=HeatDistrict_PHdVar, 101=HeatDistrict_PHdExt, 102=CoolConcrete_PHd, 103=CoolConcrete_DA, 104=CoolConcrete_TDiff, 105=CoolConcrete_Flow, 106=CoolBottle_Flow, 107=CoolMan_MFA, 108=CoolMan_Flow, 109=CoolTank_MFA, 110=CoolTank_Flow, 111=CoolExchanger_Flow, 113=CoolCondensor_Flow, 114=CoolDistrict_PHdConst, 115=CoolDistrict_PHdVar, 116=CoolDistrict_PHdExt
MOmin1busCmd.TimerInp,ActBus command timer (write SET before timeout)Command1=OFF, 2=SET, 3=ACTIVE, 4=RESET, 5=MANUAL, 6=SET_PRESET, 7=ACTIVE_PRESET, 8=RESET_PRESET, 9=MANUAL_PRESET, 10=INVALID
MO3setpointSignalSourceInpSetpoint source selectionCommand1=IF-Module, 6=Internal, 7=EXT 1, 8=EXT 2, 9=INVALID, 10=EXT 3, 11=EXT 4
MO34parameterSetSelectorInpParameter set selectionCommand1=norm, 2=aux, 3=preset
MO100controlFunctionPrsInp,LimPreset control mode (startup / bus failure)Command1=Gen_Spd, 6=Gen_PHdConst, 7=Gen_PHdVar, 9=Gen_T, 10=Gen_TDiff, 13=Gen_UsrDfd, 15=INVALID, 16=HeatRadiator_PHd, 17=HeatRadiator_DA, 18=HeatRadiator_T, 19=HeatFloor_PHd, 20=HeatFloor_DA, 21=HeatFloor_T, 22=HeatCeiling_PHd, 23=HeatCeiling_DA, 24=HeatCeiling_T, 25=HeatFan_PHd, 26=HeatFan_DA, 27=HeatFan_T, 28=HeatB._T, 29=HeatB._TDiff, 30=HeatB._Acc.Flow, 31=HeatE._T, 32=HeatE._TDiff, 33=HeatE._Acc.Flow, 34=Heat_PHdConst, 35=Heat_PHdVar, 36=Heat_PHdExt, 37=Heat_DA, 38=Heat_VolFlow, 39=Heat_Acc.Flow, 40=Heat_T, 41=Heat_TDiff, 42=Heat_Spd, 43=CoolCeiling_PHd, 44=CoolCeiling_DA, 45=CoolCeiling_T, 46=CoolFloor_PHd, 47=CoolFloor_DA, 48=CoolFloor_T, 49=CoolFan_PHd, 50=CoolFan_DA, 51=CoolFan_T, 52=CoolB._T, 53=CoolB._TDiff, 54=CoolB._Acc.Flow, 55=CoolE._T, 56=CoolE._TDiff, 57=CoolE._Acc.Flow, 58=Cool_PHdConst, 59=Cool_PHdVar, 60=Cool_PHdExt, 61=Cool_DA, 62=Cool_VolFlow, 63=Cool_Acc.Flow, 64=Cool_T, 65=Cool_TDiff, 66=Cool_Spd, 68=SanW.Heat._TDiff, 69=SanL.S._T, 70=SanL.S._Acc.Flow, 71=San_PHdConst, 72=San_PHdVar, 73=San_PHdExternal, 74=San_VolFlow, 75=San_Acc.Flow, 76=San_T, 77=San_TDiff, 78=San_Spd, 79=Gen_PHdExt, 80=Gen_DA, 81=Gen_VolFlow, 82=Gen_Acc.Flow, 83=ScndPHdConst, 84=ScndPHdVar, 85=ScndFlow, 86=ScndSpd, 87=HeatConcrete_PHd, 88=HeatConcrete_DA, 90=HeatConcrete_Flow, 91=HeatBottle_Flow, 92=HeatMan_MFA, 93=HeatMan_Flow, 94=HeatTank_MFA, 95=HeatTank_Flow, 96=HeatExchanger_Flow, 97=HeatSource_TDiff, 98=HeatSource_Flow, 99=HeatDistrict_PHdConst, 100=HeatDistrict_PHdVar, 101=HeatDistrict_PHdExt, 102=CoolConcrete_PHd, 103=CoolConcrete_DA, 104=CoolConcrete_TDiff, 105=CoolConcrete_Flow, 106=CoolBottle_Flow, 107=CoolMan_MFA, 108=CoolMan_Flow, 109=CoolTank_MFA, 110=CoolTank_Flow, 111=CoolExchanger_Flow, 113=CoolCondensor_Flow, 114=CoolDistrict_PHdConst, 115=CoolDistrict_PHdVar, 116=CoolDistrict_PHdExt
MO101setpointSignalSourcePrsInp,LimPreset setpoint source (startup / bus failure)Command1=IF-Module, 6=Internal, 7=EXT 1, 8=EXT 2, 9=INVALID, 10=EXT 3, 11=EXT 4
MO200controlFunctionAuxInpControl mode for the auxiliary parameter setCommand1=Gen_Spd, 6=Gen_PHdConst, 7=Gen_PHdVar, 9=Gen_T, 10=Gen_TDiff, 13=Gen_UsrDfd, 15=INVALID, 16=HeatRadiator_PHd, 17=HeatRadiator_DA, 18=HeatRadiator_T, 19=HeatFloor_PHd, 20=HeatFloor_DA, 21=HeatFloor_T, 22=HeatCeiling_PHd, 23=HeatCeiling_DA, 24=HeatCeiling_T, 25=HeatFan_PHd, 26=HeatFan_DA, 27=HeatFan_T, 28=HeatB._T, 29=HeatB._TDiff, 30=HeatB._Acc.Flow, 31=HeatE._T, 32=HeatE._TDiff, 33=HeatE._Acc.Flow, 34=Heat_PHdConst, 35=Heat_PHdVar, 36=Heat_PHdExt, 37=Heat_DA, 38=Heat_VolFlow, 39=Heat_Acc.Flow, 40=Heat_T, 41=Heat_TDiff, 42=Heat_Spd, 43=CoolCeiling_PHd, 44=CoolCeiling_DA, 45=CoolCeiling_T, 46=CoolFloor_PHd, 47=CoolFloor_DA, 48=CoolFloor_T, 49=CoolFan_PHd, 50=CoolFan_DA, 51=CoolFan_T, 52=CoolB._T, 53=CoolB._TDiff, 54=CoolB._Acc.Flow, 55=CoolE._T, 56=CoolE._TDiff, 57=CoolE._Acc.Flow, 58=Cool_PHdConst, 59=Cool_PHdVar, 60=Cool_PHdExt, 61=Cool_DA, 62=Cool_VolFlow, 63=Cool_Acc.Flow, 64=Cool_T, 65=Cool_TDiff, 66=Cool_Spd, 68=SanW.Heat._TDiff, 69=SanL.S._T, 70=SanL.S._Acc.Flow, 71=San_PHdConst, 72=San_PHdVar, 73=San_PHdExternal, 74=San_VolFlow, 75=San_Acc.Flow, 76=San_T, 77=San_TDiff, 78=San_Spd, 79=Gen_PHdExt, 80=Gen_DA, 81=Gen_VolFlow, 82=Gen_Acc.Flow, 83=ScndPHdConst, 84=ScndPHdVar, 85=ScndFlow, 86=ScndSpd, 87=HeatConcrete_PHd, 88=HeatConcrete_DA, 90=HeatConcrete_Flow, 91=HeatBottle_Flow, 92=HeatMan_MFA, 93=HeatMan_Flow, 94=HeatTank_MFA, 95=HeatTank_Flow, 96=HeatExchanger_Flow, 97=HeatSource_TDiff, 98=HeatSource_Flow, 99=HeatDistrict_PHdConst, 100=HeatDistrict_PHdVar, 101=HeatDistrict_PHdExt, 102=CoolConcrete_PHd, 103=CoolConcrete_DA, 104=CoolConcrete_TDiff, 105=CoolConcrete_Flow, 106=CoolBottle_Flow, 107=CoolMan_MFA, 108=CoolMan_Flow, 109=CoolTank_MFA, 110=CoolTank_Flow, 111=CoolExchanger_Flow, 113=CoolCondensor_Flow, 114=CoolDistrict_PHdConst, 115=CoolDistrict_PHdVar, 116=CoolDistrict_PHdExt
MO203setpointSignalSourceAuxInpSetpoint source for the auxiliary setCommand1=IF-Module, 6=Internal, 7=EXT 1, 8=EXT 2, 9=INVALID, 10=EXT 3, 11=EXT 4
Object ID lookup: Wilo Stratos GIGA2.0 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)

How many BACnet points does the Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) have?

This list has 127 BACnet objects: 60 analog inputs, 15 analog outputs, 20 binary inputs, 7 binary outputs, 17 multi-state inputs, 8 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) BACnet points are writable?

30 of the 127 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) BACnet documentation?

The source is WILO BACnet - CIF-Module / IF-Module installation and operating instructions with functional description (datapoint list) and CIF-Module EDE files (wilo194261 (EDE: wilo254515 MS/TP, wilo666820 Ethernet)), revision EDE 2024-09-23 (CIF-Module 1.00...6.01), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo194261/11516096/wilo194261.html.

What are the minimum BACnet points to integrate the Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)?

Start with BO 0 device/functionOnInp (Pump on/off command); MO 0 controlFunctionInp (Control mode, e.g. dp-c, dp-v, constant speed); AO 0 dutyPointRelInp (Duty point setpoint, % of the control range); MO 1 busCmd.TimerInp,Act (Heartbeat: write SET (2) before the timeout); BI 10 device/functionOnOut (Pump on); BI 15 localOperationOut (Local override; BMS not in control); AI 1 speedP01Out (Pump speed, rpm); AI 4 powerInputOut (Electrical input power, W); BI 13 errorPresentOut (Any active error); MI 1 warning/errorMessageOut (Wilo error code).

How do I enable BMS control of the Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)?

Once the CIF-Module is set up, the pump's setpoint, control mode and on/off follow the values held in the module, not the local menu. BI 15 shows when a local action is overriding BMS control. MO 3 selects where the setpoint comes from (1 = IF-Module).

Does the Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet) need a BACnet heartbeat or have a communication timeout?

MO 1 bus command timer: write SET (2) again before the timeout in AO 8 (default 300 s). If it runs out the local menu is released and the display may show E50/E54; with SET_PRESET (6) the pump also loads the preset (Prs) on/off, control mode and duty point. Writing MANUAL (5) unlocks the local menu permanently; OFF (1) returns to the factory behaviour.

Can the BMS supply sensor values to the Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)?

AO 9 / AO 10 accept reference temperatures T1/T2 from an external sensor and AO 11 an external sensor value; the selected values read back on AI 2009-2011.

How do I check these points on the real Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Wilo BACnet points lists

Source: WILO BACnet - CIF-Module / IF-Module installation and operating instructions with functional description (datapoint list) and CIF-Module EDE files · wilo194261 (EDE: wilo254515 MS/TP, wilo666820 Ethernet) · rev. EDE 2024-09-23 (CIF-Module 1.00...6.01). Object names, instances and units are reproduced as published; descriptions are our own.