Pump controller (SC Clean switch box, one pump and two valves) · BACnet points list

Wilo SC Clean (BACnet MS/TP / IP) BACnet points list

Updated 7 November 2026

Short answer

Wilo's SC-family switch boxes control multi-pump systems and act as a BACnet MS/TP slave on their RS-485 port; BACnet IP needs an added gateway in the panel. The SC Clean list covers the operating command, pump and valve modes and states, running hours and error bits. Fieldbus write access is governed by a bus command timer that must be refreshed every five minutes.

This page lists 41 BACnet objects for the Wilo SC Clean (BACnet MS/TP / IP) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wilo’s own free documentation, linked below.

Manufacturer
Wilo
Model
SC Clean (BACnet MS/TP / IP)
Equipment
Pump controller (SC Clean switch box, one pump and two valves)
Equipment type
VFDs & pumps
BACnet objects
41 (10 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Data-point list 31.200
Also known as
Wilo SC Clean BACnet, Smart-Controller SC, OPTION BACnet SC
Source document
BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC · wilo110041 (OPTION BACnet SC 2539869 Ed. 06) · rev. 2020-07-10 (list 31.200)
Download CSV 41 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Wilo’s current documentation and the live device before use. Not official Wilo information. Terms of use.

BMS integration notes: Wilo SC Clean (BACnet MS/TP / IP)

Integration in brief

Map Drives on/off (BO 224) as the start/stop command and the active setpoint (AO 416) as the setpoint. For fieldbus control, write Set to the Bus command timer (MO 208) and repeat it within five minutes. Read the collective run and fault signals (BI 976/977) and the Error state bits for alarms; acknowledge with BO 1985.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 224Drives on/offAutomatic operation and all pumps on/offWrite
AO 416Active setpoint valueActive setpoint of the automatic controlWrite
MO 208Bus command timerWrite Set (3) at least every 5 min to keep controlWrite
BO 1985AcknowledgeAlarm acknowledgeWrite
BI 976Switch box state (SBM)Collective run signalRead
AI 400Current valueMeasured value; unit follows the control modeRead
BI 977Switch box state (SSM)Collective fault signalRead

Enable & remote start

The Bus command timer (MO 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).

Heartbeat & communication loss

With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.

Network setup

Watch out for

Wilo SC Clean (BACnet MS/TP / IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

41 of 41 shown
Type
Access
Show
Wilo SC Clean (BACnet MS/TP / IP) BACnet Points List
DescriptionStates
AI0Version communication profileRead
BO16Wink serviceWrite >0 to blink the HMI indicator for 30 sWrite
MI32Switch box typeSwitch box type and variantRead1=SC, 2=SC...FC, 3=SCe, 7=SCe NWB
AI112Switch box IDRead
MOmin208Bus command timerHMI vs fieldbus access; Set must be resent within 5 minWrite1=-, 2=Off, 3=Set, 4=Active, 5=Reset, 6=Manual
BOmin224Drives on/offAutomatic operation and all pumps on/offWrite
MI384Control modeActive control modeRead14=cleans/day, 15=cleans/month
AImin400Current valueMeasured value; unit follows the control modemin / hRead
AOmin416Active setpoint valueActive setpoint; read-only on SCe NWBWrite
AI432Number of pumpsRead
BI512Pump 1 state (Auto)Read
BI513Pump 1 state (Manu)Read
BI514Pump 1 state (Disabled)Read
BI515Pump 1 state (Running)Read
BI517Pump 1 state (Error)Read
BI544Valve 1 state (Auto)Read
BI545Valve 1 state (Open)Read
BI546Valve 1 state (Shut)Read
BI560Valve 2 state (Auto)Read
BI561Valve 2 state (Open)Read
BI562Valve 2 state (Shut)Read
MO640Pump 1 modeWrite1=Off, 2=Hand, 3=Auto
MO672Valve 1 modeWrite1=Open, 2=Shut, 3=Auto
MO688Valve 2 modeWrite1=Open, 2=Shut, 3=Auto
BImin976Switch box state (SBM)Collective run signalRead
BImin977Switch box state (SSM)Collective fault signalRead
MI1168ApplicationApplication the switch box runsRead1=Booster, 2=HVAC, 3=WP, 4=Lift, 5=FFS-Diesel, 6=FFS-Electro, 7=FLA, 8=Clean, 9=Rain
AI1216Switch box cyclesRead
AI1248Switch box total running hourshRead
AI1280Pump 1 switch cyclesRead
AI1344Valve 1 switch cyclesRead
AI1376Valve 2 switch cyclesRead
AI1536Pump 1 total running hourshRead
BI1970Error state (Pump 1 Alarm)Read
BI1987Error state (Leakage)Read
BOmin1985AcknowledgeWrite to acknowledge an alarmWrite
AO1990Alarm history indexSelect an alarm history entry (SC: 0-15)Write
AI1995Alarm history error codeError code of the selected history entryRead
AO2011Alarm histogram indexWrite
AI2012Alarm histogram error codeRead
AI2013Alarm histogram error countRead
Object ID lookup: Wilo SC Clean point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SC Clean (BACnet MS/TP / IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Wilo SC Clean (BACnet MS/TP / IP)

How many BACnet points does the Wilo SC Clean (BACnet MS/TP / IP) have?

This list has 41 BACnet objects: 13 analog inputs, 3 analog outputs, 15 binary inputs, 3 binary outputs, 3 multi-state inputs, 4 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Wilo SC Clean (BACnet MS/TP / IP) BACnet points are writable?

10 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Wilo SC Clean (BACnet MS/TP / IP) BACnet documentation?

The source is BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC (wilo110041 (OPTION BACnet SC 2539869 Ed. 06)), revision 2020-07-10 (list 31.200), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo110041/4721760/wilo110041.pdf.

What are the minimum BACnet points to integrate the Wilo SC Clean (BACnet MS/TP / IP)?

Start with BO 224 Drives on/off (Automatic operation and all pumps on/off); AO 416 Active setpoint value (Active setpoint of the automatic control); MO 208 Bus command timer (Write Set (3) at least every 5 min to keep control); BO 1985 Acknowledge (Alarm acknowledge); BI 976 Switch box state (SBM) (Collective run signal); AI 400 Current value (Measured value; unit follows the control mode); BI 977 Switch box state (SSM) (Collective fault signal).

How do I enable BMS control of the Wilo SC Clean (BACnet MS/TP / IP)?

The Bus command timer (MO 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).

Does the Wilo SC Clean (BACnet MS/TP / IP) need a BACnet heartbeat or have a communication timeout?

With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.

How do I check these points on the real SC Clean (BACnet MS/TP / IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Wilo BACnet points lists

Source: BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC · wilo110041 (OPTION BACnet SC 2539869 Ed. 06) · rev. 2020-07-10 (list 31.200). Object names, instances and units are reproduced as published; descriptions are our own.