- Home
- BACnet points lists
- Wilo
- SC Clean (BACnet MS/TP / IP)
Pump controller (SC Clean switch box, one pump and two valves) · BACnet points list
Wilo SC Clean (BACnet MS/TP / IP) BACnet points list
Updated 7 November 2026
Wilo's SC-family switch boxes control multi-pump systems and act as a BACnet MS/TP slave on their RS-485 port; BACnet IP needs an added gateway in the panel. The SC Clean list covers the operating command, pump and valve modes and states, running hours and error bits. Fieldbus write access is governed by a bus command timer that must be refreshed every five minutes.
This page lists 41 BACnet objects for the Wilo SC Clean (BACnet MS/TP / IP) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wilo’s own free documentation, linked below.
- Manufacturer
- Wilo
- Model
- SC Clean (BACnet MS/TP / IP)
- Equipment
- Pump controller (SC Clean switch box, one pump and two valves)
- Equipment type
- VFDs & pumps
- BACnet objects
- 41 (10 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Data-point list 31.200
- Also known as
- Wilo SC Clean BACnet, Smart-Controller SC, OPTION BACnet SC
Reference only, provided as-is: verify against Wilo’s current documentation and the live device before use. Not official Wilo information. Terms of use.
BMS integration notes: Wilo SC Clean (BACnet MS/TP / IP)
Map Drives on/off (BO 224) as the start/stop command and the active setpoint (AO 416) as the setpoint. For fieldbus control, write Set to the Bus command timer (MO 208) and repeat it within five minutes. Read the collective run and fault signals (BI 976/977) and the Error state bits for alarms; acknowledge with BO 1985.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 224 | Drives on/off | Automatic operation and all pumps on/off | Write |
| AO 416 | Active setpoint value | Active setpoint of the automatic control | Write |
| MO 208 | Bus command timer | Write Set (3) at least every 5 min to keep control | Write |
| BO 1985 | Acknowledge | Alarm acknowledge | Write |
| BI 976 | Switch box state (SBM) | Collective run signal | Read |
| AI 400 | Current value | Measured value; unit follows the control mode | Read |
| BI 977 | Switch box state (SSM) | Collective fault signal | Read |
Enable & remote start
The Bus command timer (MO 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).
Heartbeat & communication loss
With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.
Network setup
- SC menus 5.1.2.1-5.1.2.5 set the BACnet MS/TP baud rate, bus address (MAC), parity, stop bits and device object ID.
- BACnet IP uses an extra gateway (HD67686) wired to the panel's RS-485 port: set the SC to 38400 baud, MAC 5, no parity, 1 stop bit. The gateway defaults to 192.168.0.10, UDP 47808, no DHCP; change it with the free Compositor SW67686 tool.
- Terminate the first and last node of the MS/TP segment (DIP switch or jumper, per panel hardware).
Watch out for
- In Bus command timer Off mode the HMI stays locked; if the fieldbus fails there is no access until it recovers.
- Alarm history: write the index (0-15 on SC) to AO 1990, then read the error code from AI 1995.
Wilo SC Clean (BACnet MS/TP / IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Version communication profile | Read | |||
| BO | 16 | Wink service | Write >0 to blink the HMI indicator for 30 s | Write | ||
| MI | 32 | Switch box type | Switch box type and variant | Read | 1=SC, 2=SC...FC, 3=SCe, 7=SCe NWB | |
| AI | 112 | Switch box ID | Read | |||
| MOmin | 208 | Bus command timer | HMI vs fieldbus access; Set must be resent within 5 min | Write | 1=-, 2=Off, 3=Set, 4=Active, 5=Reset, 6=Manual | |
| BOmin | 224 | Drives on/off | Automatic operation and all pumps on/off | Write | ||
| MI | 384 | Control mode | Active control mode | Read | 14=cleans/day, 15=cleans/month | |
| AImin | 400 | Current value | Measured value; unit follows the control mode | min / h | Read | |
| AOmin | 416 | Active setpoint value | Active setpoint; read-only on SCe NWB | Write | ||
| AI | 432 | Number of pumps | Read | |||
| BI | 512 | Pump 1 state (Auto) | Read | |||
| BI | 513 | Pump 1 state (Manu) | Read | |||
| BI | 514 | Pump 1 state (Disabled) | Read | |||
| BI | 515 | Pump 1 state (Running) | Read | |||
| BI | 517 | Pump 1 state (Error) | Read | |||
| BI | 544 | Valve 1 state (Auto) | Read | |||
| BI | 545 | Valve 1 state (Open) | Read | |||
| BI | 546 | Valve 1 state (Shut) | Read | |||
| BI | 560 | Valve 2 state (Auto) | Read | |||
| BI | 561 | Valve 2 state (Open) | Read | |||
| BI | 562 | Valve 2 state (Shut) | Read | |||
| MO | 640 | Pump 1 mode | Write | 1=Off, 2=Hand, 3=Auto | ||
| MO | 672 | Valve 1 mode | Write | 1=Open, 2=Shut, 3=Auto | ||
| MO | 688 | Valve 2 mode | Write | 1=Open, 2=Shut, 3=Auto | ||
| BImin | 976 | Switch box state (SBM) | Collective run signal | Read | ||
| BImin | 977 | Switch box state (SSM) | Collective fault signal | Read | ||
| MI | 1168 | Application | Application the switch box runs | Read | 1=Booster, 2=HVAC, 3=WP, 4=Lift, 5=FFS-Diesel, 6=FFS-Electro, 7=FLA, 8=Clean, 9=Rain | |
| AI | 1216 | Switch box cycles | Read | |||
| AI | 1248 | Switch box total running hours | h | Read | ||
| AI | 1280 | Pump 1 switch cycles | Read | |||
| AI | 1344 | Valve 1 switch cycles | Read | |||
| AI | 1376 | Valve 2 switch cycles | Read | |||
| AI | 1536 | Pump 1 total running hours | h | Read | ||
| BI | 1970 | Error state (Pump 1 Alarm) | Read | |||
| BI | 1987 | Error state (Leakage) | Read | |||
| BOmin | 1985 | Acknowledge | Write to acknowledge an alarm | Write | ||
| AO | 1990 | Alarm history index | Select an alarm history entry (SC: 0-15) | Write | ||
| AI | 1995 | Alarm history error code | Error code of the selected history entry | Read | ||
| AO | 2011 | Alarm histogram index | Write | |||
| AI | 2012 | Alarm histogram error code | Read | |||
| AI | 2013 | Alarm histogram error count | Read |
No points match these filters.
Object ID lookup: Wilo SC Clean point IDs by name
AI0Version communication profileBO16Wink serviceMI32Switch box typeAI112Switch box IDMO208Bus command timerBO224Drives on/offMI384Control modeAI400Current valueAO416Active setpoint valueAI432Number of pumpsBI512Pump 1 state (Auto)BI513Pump 1 state (Manu)BI514Pump 1 state (Disabled)BI515Pump 1 state (Running)BI517Pump 1 state (Error)BI544Valve 1 state (Auto)BI545Valve 1 state (Open)BI546Valve 1 state (Shut)BI560Valve 2 state (Auto)BI561Valve 2 state (Open)BI562Valve 2 state (Shut)MO640Pump 1 modeMO672Valve 1 modeMO688Valve 2 modeBI976Switch box state (SBM)BI977Switch box state (SSM)MI1168ApplicationAI1216Switch box cyclesAI1248Switch box total running hoursAI1280Pump 1 switch cyclesAI1344Valve 1 switch cyclesAI1376Valve 2 switch cyclesAI1536Pump 1 total running hoursBI1970Error state (Pump 1 Alarm)BI1987Error state (Leakage)BO1985AcknowledgeAO1990Alarm history indexAI1995Alarm history error codeAO2011Alarm histogram indexAI2012Alarm histogram error codeAI2013Alarm histogram error count
Integration notes
- Taken from the 'SC Clean' table in Wilo's SC BACnet supplement (English part, pp88-89). Wilo prints a 'BACnet ID' and an object type with its BACnet type code in brackets, e.g. 'Analog Input (0)'. The ID is used here as the instance and the type follows the code, so rows printed 'Binary Input (4)' are Binary Outputs.
- Where Wilo prints several IDs against one name (pump state, switch box state, error state and other bitmaps), each ID is its own binary object for the element printed beside it; the element is shown in brackets after the name.
- Analog objects that list several units report in the unit of the active control mode.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SC Clean (BACnet MS/TP / IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Wilo SC Clean (BACnet MS/TP / IP)
How many BACnet points does the Wilo SC Clean (BACnet MS/TP / IP) have?
This list has 41 BACnet objects: 13 analog inputs, 3 analog outputs, 15 binary inputs, 3 binary outputs, 3 multi-state inputs, 4 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Wilo SC Clean (BACnet MS/TP / IP) BACnet points are writable?
10 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Wilo SC Clean (BACnet MS/TP / IP) BACnet documentation?
The source is BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC (wilo110041 (OPTION BACnet SC 2539869 Ed. 06)), revision 2020-07-10 (list 31.200), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo110041/4721760/wilo110041.pdf.
What are the minimum BACnet points to integrate the Wilo SC Clean (BACnet MS/TP / IP)?
Start with BO 224 Drives on/off (Automatic operation and all pumps on/off); AO 416 Active setpoint value (Active setpoint of the automatic control); MO 208 Bus command timer (Write Set (3) at least every 5 min to keep control); BO 1985 Acknowledge (Alarm acknowledge); BI 976 Switch box state (SBM) (Collective run signal); AI 400 Current value (Measured value; unit follows the control mode); BI 977 Switch box state (SSM) (Collective fault signal).
How do I enable BMS control of the Wilo SC Clean (BACnet MS/TP / IP)?
The Bus command timer (MO 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).
Does the Wilo SC Clean (BACnet MS/TP / IP) need a BACnet heartbeat or have a communication timeout?
With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.
How do I check these points on the real SC Clean (BACnet MS/TP / IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Wilo BACnet points lists
- Pump controller (booster set switch box)
Wilo CC Booster (BACnet IP / MS/TP)
Wilo CC (Comfort-Controller) switch boxes on pressure-boosting pump sets, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Comfort-Controller CC, Wilo CC Booster BACnet, SPS extension BACnet IP slave, SPS extension BACnet MSTP slave - Pump controller (HVAC pump switch box)
Wilo CC HVAC (BACnet IP / MS/TP)
Wilo CC (Comfort-Controller) switch boxes on HVAC circulation pump systems, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Comfort-Controller CC HVAC, Wilo CC HVAC BACnet - Pump controller (lifting station switch box)
Wilo CC Lift (BACnet IP / MS/TP)
Wilo CC switch boxes running the Lift application on wastewater lifting stations, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CC Lift BACnet - Pump controller (booster set switch box with frequency converter)
Wilo CC...FC Booster (BACnet IP / MS/TP)
Wilo CC...FC switch boxes (with frequency converter) on pressure-boosting sets, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: CC-FC Booster, Wilo CC...FC BACnet - Pump controller (HVAC switch box with frequency converter)
Wilo CC...FC HVAC (BACnet IP / MS/TP)
Wilo CC...FC switch boxes (with frequency converter) on HVAC circulation pump systems, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: CC-FC HVAC, Wilo CC...FC HVAC BACnet - Pump controller (booster set switch box)
Wilo CCe Booster (BACnet IP / MS/TP)
Wilo CCe switch boxes for pressure-boosting sets with electronically controlled pumps, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe Booster BACnet - Pump controller (HVAC pump switch box)
Wilo CCe HVAC (BACnet IP / MS/TP)
Wilo CCe switch boxes on HVAC circulation pump systems with electronically controlled pumps, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe HVAC BACnet - Pump controller (booster set switch box)
Wilo CCe NWB Booster (BACnet IP / MS/TP)
Wilo CCe switch boxes that run their pumps over NWB, on pressure-boosting sets, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: CCe NWB, Wilo CCe NWB Booster BACnet - Pump controller (rainwater harvesting switch box)
Wilo CCe Rain (BACnet IP / MS/TP)
Wilo CCe switch boxes on rainwater utilisation systems (cistern pumps and replenishment valve), fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe Rain BACnet - Pump (CIF-Module BACnet interface)
Wilo Helix2.0-VE / Medana CH3-LE / Isar MODH1-E (CIF-Module BACnet)
Wilo Helix2.0-VE vertical and Medana CH3-LE horizontal multistage pumps, and the Isar MODH1-E, fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Helix2.0-VE, Helix 2.0 VE, Medana CH3-LE, Isar MODH1-E, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol - Pump (circulator BACnet MS/TP interface module)
Wilo IF-Module BACnet / IF-Module BACnet Stratos (BACnet MS/TP)
Wilo IF-Module BACnet (2097811, glanded pumps such as IL-E/IP-E/DL-E/BL-E and MVIE/MHIE) and IF-Module BACnet Stratos (2097810, Stratos/Stratos-D/-Z), the plug-in modules that put older Wilo electronic pumps on BACnet MS/TP.
Also known as: IF-Modul BACnet, IF-Modul BACnet Stratos, 2097811, 2097810, Wilo IF-Module BACnet - Pump controller (booster set switch box)
Wilo SC Booster (BACnet MS/TP / IP)
Wilo SC switch boxes on pressure-boosting pump sets.
Also known as: Wilo SC Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (diesel fire pump switch box)
Wilo SC Fire D APSAD (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for diesel-driven sprinkler pumps built to the APSAD rules.
Also known as: Wilo SC Fire D APSAD BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (diesel fire pump switch box)
Wilo SC Fire D EN12845 (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for diesel-driven sprinkler pumps built to EN 12845.
Also known as: Wilo SC Fire D EN12845 BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (electric fire pump switch box)
Wilo SC Fire E APSAD (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for electric sprinkler pumps built to the APSAD rules.
Also known as: Wilo SC Fire E APSAD BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (electric fire pump switch box)
Wilo SC Fire E EN12845 (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for electric sprinkler pumps built to EN 12845.
Also known as: Wilo SC Fire E EN12845 BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC multi-pump switch box)
Wilo SC HVAC (BACnet MS/TP / IP)
Wilo SC switch boxes on multi-pump HVAC (heating/cooling circulation) systems.
Also known as: Wilo SC HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (lifting station switch box)
Wilo SC Lift (BACnet MS/TP / IP)
Wilo SC switch boxes on sewage/drainage lifting stations with level control.
Also known as: Wilo SC Lift BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box with frequency converter)
Wilo SC...FC Booster (BACnet MS/TP / IP)
Wilo SC...FC switch boxes (built-in frequency converter) on pressure-boosting pump sets.
Also known as: Wilo SC...FC Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC switch box with frequency converter)
Wilo SC...FC HVAC (BACnet MS/TP / IP)
Wilo SC...FC switch boxes (built-in frequency converter) on HVAC multi-pump systems.
Also known as: Wilo SC...FC HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box, electronic pumps)
Wilo SCe Booster (BACnet MS/TP / IP)
Wilo SCe switch boxes on pressure-boosting sets with speed-controlled (electronic) pumps.
Also known as: Wilo SCe Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (fire-fighting booster switch box)
Wilo SCe FFS Poland (BACnet MS/TP / IP)
Wilo SCe switch boxes on fire-fighting (FFS) booster sets in the Polish variant.
Also known as: Wilo SCe FFS Poland BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC switch box, electronic pumps)
Wilo SCe HVAC (BACnet MS/TP / IP)
Wilo SCe switch boxes on HVAC multi-pump systems with speed-controlled (electronic) pumps.
Also known as: Wilo SCe HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box, p-v control)
Wilo SCe PV Booster (BACnet MS/TP / IP)
Wilo SCe switch boxes on pressure-boosting sets running variable-pressure (p-v) control.
Also known as: Wilo SCe PV Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump (CIF-Module BACnet interface)
Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet)
Wilo SiFresh drinking-water flushing / hygiene circulation pump station fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: SiFresh, Wilo-SiFresh, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol - Pump (CIF-Module BACnet interface)
Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)
Wilo Stratos GIGA2.0-I / -D inline glandless high-efficiency pumps fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Stratos GIGA2.0, Stratos GIGA2.0-I, Stratos GIGA2.0-D, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol, 2190367, 2211408 - Pump (CIF-Module BACnet interface)
Wilo Stratos MAXO (CIF-Module BACnet MS/TP / Ethernet)
Wilo Stratos MAXO smart wet-rotor circulators fitted with a CIF-Module BACnet MS/TP (2190367) or CIF-Module Ethernet Multiprotocol for BACnet IP (2211408).
Also known as: Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol, 2190367, 2211408 - Pump (CIF-Module BACnet interface)
Wilo Yonos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)
Wilo Yonos GIGA2.0-I / -D glandless inline pumps fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Yonos GIGA2.0, Yonos GIGA2.0-I, Yonos GIGA2.0-D, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol
Source: BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC · wilo110041 (OPTION BACnet SC 2539869 Ed. 06) · rev. 2020-07-10 (list 31.200). Object names, instances and units are reproduced as published; descriptions are our own.