Pump controller (lifting station switch box) · BACnet points list

Wilo SC Lift (BACnet MS/TP / IP) BACnet points list

Updated 7 November 2026

Short answer

Wilo's SC-family switch boxes control multi-pump systems and act as a BACnet MS/TP slave on their RS-485 port; BACnet IP needs an added gateway in the panel. The SC Lift list covers the operating command, level setpoints, float switch states, pump state bits, running hours and error bits. Fieldbus write access is governed by a bus command timer that must be refreshed every five minutes.

This page lists 79 BACnet objects for the Wilo SC Lift (BACnet MS/TP / IP) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wilo’s own free documentation, linked below.

Manufacturer
Wilo
Model
SC Lift (BACnet MS/TP / IP)
Equipment
Pump controller (lifting station switch box)
Equipment type
VFDs & pumps
BACnet objects
79 (20 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Data-point list 31.200
Also known as
Wilo SC Lift BACnet, Smart-Controller SC, OPTION BACnet SC
Source document
BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC · wilo110041 (OPTION BACnet SC 2539869 Ed. 06) · rev. 2020-07-10 (list 31.200)
Download CSV 79 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Wilo’s current documentation and the live device before use. Not official Wilo information. Terms of use.

BMS integration notes: Wilo SC Lift (BACnet MS/TP / IP)

Integration in brief

Map Drives on/off (BO 224) as the start/stop command. For fieldbus control, write Set to the Bus command timer (MO 208) and repeat it within five minutes. Read the collective run and fault signals (BI 976/977) and the Error state bits for alarms; acknowledge with BO 1985.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 224Drives on/offAutomatic operation and all pumps on/offWrite
MO 208Bus command timerWrite Set (3) at least every 5 min to keep controlWrite
BO 1985AcknowledgeAlarm acknowledgeWrite
BI 976Switch box state (SBM)Collective run signalRead
AI 400Current valueMeasured value; unit follows the control modeRead
BI 1301State Float switches (High water)High water float switchRead
BI 977Switch box state (SSM)Collective fault signalRead

Enable & remote start

The Bus command timer (MO 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).

Heartbeat & communication loss

With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.

Network setup

Watch out for

Wilo SC Lift (BACnet MS/TP / IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

79 of 79 shown
Type
Multi-state
Access
Show
Wilo SC Lift (BACnet MS/TP / IP) BACnet Points List
DescriptionStates
AI0Version communication profileRead
BO16Wink serviceWrite >0 to blink the HMI indicator for 30 sWrite
MOmin208Bus command timerHMI vs fieldbus access; Set must be resent within 5 minWrite1=-, 2=Off, 3=Set, 4=Active, 5=Reset, 6=Manual
BOmin224Drives on/offAutomatic operation and all pumps on/offWrite
AImin400Current valueMeasured value; unit follows the control modecmRead
BI512Pump 1 state (Auto)Read
BI513Pump 1 state (Manu)Read
BI514Pump 1 state (Disabled)Read
BI515Pump 1 state (Running)Read
BI517Pump 1 state (Error)Read
BI528Pump 2 state (Auto)Read
BI529Pump 2 state (Manu)Read
BI530Pump 2 state (Disabled)Read
BI531Pump 2 state (Running)Read
BI533Pump 2 state (Error)Read
BI544Pump 3 state (Auto)Read
BI545Pump 3 state (Manu)Read
BI546Pump 3 state (Disabled)Read
BI547Pump 3 state (Running)Read
BI549Pump 3 state (Error)Read
BI560Pump 4 state (Auto)Read
BI561Pump 4 state (Manu)Read
BI562Pump 4 state (Disabled)Read
BI563Pump 4 state (Running)Read
BI565Pump 4 state (Error)Read
MO640Pump 1 modeWrite1=Off, 2=Hand, 3=Auto
MO656Pump 2 modeWrite1=Off, 2=Hand, 3=Auto
MO672Pump 3 modeWrite1=Off, 2=Hand, 3=Auto
MO688Pump 4 modeWrite1=Off, 2=Hand, 3=Auto
BImin976Switch box state (SBM)Collective run signalRead
BImin977Switch box state (SSM)Collective fault signalRead
BI978Switch box state (External off)Read
BI980Switch box state (External setpoint)Read
BI981Switch box state (SBM output (0:Run / 1:Ready))Read
BI982Switch box state (SSM output (0:Fall / 1: Raise))Read
AI1216Switch box cyclesRead
AI1248Switch box total running hourshRead
AI1280Pump 1 switch cyclesRead
AI1312Pump 2 switch cyclesRead
AI1344Pump 3 switch cyclesRead
AI1376Pump 4 switch cyclesRead
AI1536Pump 1 total running hourshRead
AI1568Pump 2 total running hourshRead
AI1600Pump 3 total running hourshRead
AI1632Pump 4 total running hourshRead
BI1965Error state (Sensor error)Read
BI1969Error state (TLS)Read
BI1970Error state (Pump 1 Alarm)Read
BI1971Error state (Pump 2 Alarm)Read
BI1972Error state (Pump 3 Alarm)Read
BI1973Error state (Pump 4 Alarm)Read
BI1980Error state (High water)Read
BI1981Error state (Priority off)Read
BI1983Error state (Plausibility)Read
BI1984Error state (Slave communication)Read
BI1986Error state (Net supply)Read
BI1987Error state (Leakage)Read
BI1991Error state (E43.0 External signal)Read
BOmin1985AcknowledgeWrite to acknowledge an alarmWrite
AO1990Alarm history indexSelect an alarm history entry (SC: 0-15)Write
AI1995Alarm history error codeError code of the selected history entryRead
AO2011Alarm histogram indexWrite
AI2012Alarm histogram error codeRead
AI2013Alarm histogram error countRead
BI1297State Float switches (Dry run)Read
BI1298State Float switches (Pumps off)Read
BI1299State Float switches (Pump 1 on)Read
BI1300State Float switches (Pump 2 on)Read
BImin1301State Float switches (High water)Read
AO1318Set points water level 1 startcmWrite
AO1319Set points water level 2 startcmWrite
AO1320Set points water level 3 startcmWrite
AO1321Set points water level 4 startcmWrite
AO1326Set points water level 1 stopcmWrite
AO1327Set points water level 2 stopcmWrite
AO1328Set points water level 3 stopcmWrite
AO1329Set points water level 4 stopcmWrite
AO1334Dry run levelcmWrite
AO1336High water levelcmWrite
Object ID lookup: Wilo SC Lift point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SC Lift (BACnet MS/TP / IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Wilo SC Lift (BACnet MS/TP / IP)

How many BACnet points does the Wilo SC Lift (BACnet MS/TP / IP) have?

This list has 79 BACnet objects: 15 analog inputs, 12 analog outputs, 44 binary inputs, 3 binary outputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Wilo SC Lift (BACnet MS/TP / IP) BACnet points are writable?

20 of the 79 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Wilo SC Lift (BACnet MS/TP / IP) BACnet documentation?

The source is BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC (wilo110041 (OPTION BACnet SC 2539869 Ed. 06)), revision 2020-07-10 (list 31.200), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo110041/4721760/wilo110041.pdf.

What are the minimum BACnet points to integrate the Wilo SC Lift (BACnet MS/TP / IP)?

Start with BO 224 Drives on/off (Automatic operation and all pumps on/off); MO 208 Bus command timer (Write Set (3) at least every 5 min to keep control); BO 1985 Acknowledge (Alarm acknowledge); BI 976 Switch box state (SBM) (Collective run signal); AI 400 Current value (Measured value; unit follows the control mode); BI 1301 State Float switches (High water) (High water float switch); BI 977 Switch box state (SSM) (Collective fault signal).

How do I enable BMS control of the Wilo SC Lift (BACnet MS/TP / IP)?

The Bus command timer (MO 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).

Does the Wilo SC Lift (BACnet MS/TP / IP) need a BACnet heartbeat or have a communication timeout?

With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.

How do I check these points on the real SC Lift (BACnet MS/TP / IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Wilo BACnet points lists

Source: BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC · wilo110041 (OPTION BACnet SC 2539869 Ed. 06) · rev. 2020-07-10 (list 31.200). Object names, instances and units are reproduced as published; descriptions are our own.