Pump (CIF-Module BACnet interface) · BACnet points list
Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet) BACnet points list
Updated 4 November 2026
The SiFresh is a pump station that flushes and circulates domestic water to keep it hygienic. With a CIF-Module it gives BACnet MS/TP or BACnet IP access to on/off, control mode and duty point, the flushing type to start, the flushing phase and volumes, and 24 h min/avg/max supply and return temperatures. It uses the same bus command timer and preset/auxiliary scheme as Wilo pumps.
This page lists 109 BACnet objects for the Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet) — 25 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wilo’s own free documentation, linked below.
- Manufacturer
- Wilo
- Model
- SiFresh (CIF-Module BACnet MS/TP / Ethernet)
- Equipment
- Pump (CIF-Module BACnet interface)
- Equipment type
- VFDs & pumps
- BACnet objects
- 109 (25 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- CIF-Module 1.00-6.01 (EDE); datapoint list valid to 6.11
- Also known as
- SiFresh, Wilo-SiFresh, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol
Reference only, provided as-is: verify against Wilo’s current documentation and the live device before use. Not official Wilo information. Terms of use.
BMS integration notes: Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet)
Write the control mode (MO 0), the duty point setpoint in % (AO 0) and the on/off command (BO 0). To keep BMS control safe, write SET to the bus command timer (MO 1) more often than its timeout (AO 8, default 300 s); use SET_PRESET if the pump should load the Prs fallback values when the BMS goes quiet. Read status from BI 10, BI 13 and MI 1. On SiFresh, MO 5003 starts a flushing run and MI 5006 shows its phase.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 0 | device/functionOnInp | On/off command | Command |
| MO 5003 | flushingTypeFluInp | Flushing type to start, e.g. 4 = time-based | Command |
| MO 1 | busCmd.TimerInp,Act | Heartbeat: write SET (2) before the timeout | Command |
| BI 10 | device/functionOnOut | Pump on | Read |
| MI 5006 | flushingPhaseFluAct | Active flushing phase | Read |
| AI 5015 | flowFluOut | Flushing flow, m³/h | Read |
| AI 17 | temperat.FluidRetOut | Return water temperature, °C | Read |
| BI 13 | errorPresentOut | Any active error | Read |
| MI 1 | warning/errorMessageOut | Wilo error code | Read |
Enable & remote start
Once the CIF-Module is set up, the pump's setpoint, control mode and on/off follow the values held in the module, not the local menu. MO 3 selects where the setpoint comes from (1 = IF-Module).
Heartbeat & communication loss
MO 1 bus command timer: write SET (2) again before the timeout in AO 8 (default 300 s). If it runs out the local menu is released and the display may show E50/E54; with SET_PRESET (6) the pump also loads the preset (Prs) on/off, control mode and duty point. Writing MANUAL (5) unlocks the local menu permanently; OFF (1) returns to the factory behaviour.
Network setup
- BACnet MS/TP: the bus address set in the pump menu is the MS/TP MAC; 0-127 = manager (default use), 128-254 = subordinate.
- Baud rate is set with parameter A in the pump menu (9600 to 115200, plus 76800).
- The device instance is entered in the pump menu as parameters C, E and F; how the number is split across them depends on the pump type (Wilo's datapoint list has a calculator).
- CIF-Module Ethernet: extended settings via a web browser on port 80; default hostname is wilo- plus the ETH1 MAC address.
Watch out for
- AO 0 is a relative duty point; its range is not always 0-100 % and 0 % does not mean off. AI 33 gives the value that equals 100 %, with its units in MI 33.
- The flow reading (AI 2) is calculated and should not be used for closed-loop control.
- Commandable objects use priority 16 as a floating default; relinquishing every priority returns the static relinquish default (BO 0 = off, AO 0 = 100 %).
- BI 18 actuationLimitOut means the speed output is at a limit, so the pump cannot follow further changes in that direction.
Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | dutyPointRelOut | Relative duty point the pump is running at | % | Read | |
| AI | 1 | speedP01Out | Speed of the master pump | rpm | Read | |
| AI | 2 | flowOut | Flow (calculated; for monitoring only) | m³/h | Read | |
| AI | 3 | pressureOut | Head/pressure at the pump (may be estimated) | bar | Read | |
| AI | 4 | powerInputOut | Electrical input power | W | Read | |
| AI | 5 | temperatureFluid@DeviceOut | Fluid temperature measured at the pump | °C | Read | |
| AI | 7 | energyConsumptionOut | Total electrical energy used | kWh | Read | |
| AI | 8 | speedMivAct | Lowest speed available for the setpoint | rpm | Read | |
| AI | 9 | speedMavAct | Highest speed available for the setpoint | rpm | Read | |
| AI | 12 | flowMavOut | Maximum flow (full speed, zero head) | m³/h | Read | |
| AI | 15 | powerInputMavOut | Maximum electrical input power | W | Read | |
| AI | 16 | temperat.FluidFwdOut | Supply (forward) fluid temperature | °C | Read | |
| AImin | 17 | temperat.FluidRetOut | Return fluid temperature | °C | Read | |
| AI | 28 | voltageInputOut | Mains supply voltage | V | Read | |
| AI | 30 | systemTimeOut | Pump system time (Unix epoch) | s | Read | |
| AI | 31 | dutyPointRelMioAct | Lower limit of the active relative duty point | % | Read | |
| AI | 32 | dutyPointRelMaoAct | Upper limit of the active relative duty point | % | Read | |
| AI | 33 | dutyPoint100%ValAct | Value that equals 100 % duty point (active) | Read | ||
| AI | 34 | dutyPointRelAct | Active relative duty point (setpoint in use) | % | Read | |
| AI | 35 | busCmd.TimerTimeRemain.Out | Time left on the bus command timer | s | Read | |
| AI | 36 | flowLmiAct | Active lower flow limit | m³/h | Read | |
| AI | 37 | flowLmaAct | Active upper flow limit | m³/h | Read | |
| AI | 38 | flowLofAct | Active flow limit value (Lof) | m³/h | Read | |
| AI | 50 | pressureMavOut | Maximum head | bar | Read | |
| AI | 51 | flowMivOut | Minimum flow (operating limit) | m³/h | Read | |
| AI | 1031 | dutyPointRelMioLim | Lower limit of the duty point setting | % | Read | |
| AI | 1032 | dutyPointRelMaoLim | Upper limit of the duty point setting | % | Read | |
| AI | 1033 | dutyPoint100%ValLim | Value that equals 100 % duty point (limit) | Read | ||
| AI | 1034 | dutyPointRelSel | Selected relative duty point | % | Read | |
| AI | 1131 | dutyPointRelMioPrsLim | Lower limit of the preset duty point | % | Read | |
| AI | 1132 | dutyPointRelMaoPrsLim | Upper limit of the preset duty point | % | Read | |
| AI | 1133 | dutyPoint100%ValPrsLim | Value that equals 100 % (preset duty point) | Read | ||
| AI | 1231 | dutyPointRelMioAuxLim | Lower limit of the auxiliary duty point | % | Read | |
| AI | 1232 | dutyPointRelMaoAuxLim | Upper limit of the auxiliary duty point | % | Read | |
| AI | 1233 | dutyPoint100%ValAuxLim | Value that equals 100 % (auxiliary duty point) | Read | ||
| AI | 2031 | dutyPointRelMioSel | Lower limit of the selected duty point | % | Read | |
| AI | 2032 | dutyPointRelMaoSel | Upper limit of the selected duty point | % | Read | |
| AI | 2033 | dutyPoint100%ValSel | Value that equals 100 % (selected duty point) | Read | ||
| AI | 5000 | temperat.FluidRetHilFluAct | Active return temp upper limit for flushing | °C | Read | |
| AI | 5002 | temperat.FluidRetLolFluAct | Active return temp lower limit for flushing | °C | Read | |
| AI | 5008 | operationTimeRemain.FluOut | Time left in the current flushing run | s | Read | |
| AI | 5009 | operationTimeRst.ableMavFluOut | Longest flushing run time (resettable) | s | Read | |
| AI | 5010 | timeActive/IdlingFluOut | Time active or idle in flushing | s | Read | |
| AI | 5012 | device/functionOnAvwFluOut | Flushing activity, average over last week | Read | ||
| AI | 5013 | volumeFluOut | Volume flushed this cycle | m³ | Read | |
| AI | 5014 | temperat.FluidRetStvFluOut | Return temperature at start of flushing | °C | Read | |
| AImin | 5015 | flowFluOut | Flushing flow | m³/h | Read | |
| AI | 5016 | volumeAvwFluOut | Flushed volume, average over last 168 h | m³ | Read | |
| AI | 5017 | temperat.FluidRetMidOut | Return temperature, 24 h minimum | °C | Read | |
| AI | 5018 | temperat.FluidRetAvdOut | Return temperature, 24 h average | °C | Read | |
| AI | 5019 | temperat.FluidRetMadOut | Return temperature, 24 h maximum | °C | Read | |
| AI | 5020 | temperat.FluidFwdMidOut | Supply temperature, 24 h minimum | °C | Read | |
| AI | 5021 | temperat.FluidFwdAvdOut | Supply temperature, 24 h average | °C | Read | |
| AI | 5022 | temperat.FluidFwdMadOut | Supply temperature, 24 h maximum | °C | Read | |
| AO | 0 | dutyPointRelInp | Duty point setpoint from the BMS | % | Command | |
| AO | 8 | busCmd.TimerTimeoutInp,Act | Bus command timer timeout | s | Command | |
| AO | 36 | flowLmiInp | Lower flow limit setting | m³/h | Command | |
| AO | 37 | flowLmaInp | Upper flow limit setting | m³/h | Command | |
| AO | 38 | flowLofInp | Flow limit value setting (Lof) | m³/h | Command | |
| AO | 100 | dutyPointRelPrsInp,Lim | Preset duty point (startup / bus failure) | % | Command | |
| AO | 200 | dutyPointRelAuxInp | Duty point for the auxiliary parameter set | % | Command | |
| AO | 5000 | temperat.FluidRetHilFluInp | Return temp upper limit for flushing | °C | Command | |
| AO | 5002 | temperat.FluidRetLolFluInp | Return temp lower limit for flushing | °C | Command | |
| BI | 0 | device/functionOnAct | Active on/off command | Read | ||
| BI | 1 | overrideOffAct | Override OFF active (includes local Ext. Off) | Read | ||
| BI | 2 | overrideMaxAct | Override MAX active | Read | ||
| BI | 3 | overrideMinAct | Override MIN active | Read | ||
| BI | 9 | ready4OperationOut | Ready for operation | Read | ||
| BImin | 10 | device/functionOnOut | Pump on | Read | ||
| BI | 11 | serviceRequiredOut | Service required | Read | ||
| BI | 12 | warningPresentOut | Warning present | Read | ||
| BImin | 13 | errorPresentOut | Error present | Read | ||
| BI | 17 | overrideOnAct | Override ON active | Read | ||
| BI | 18 | actuationLimitOut | Pump at an actuation limit (pause the BMS PID) | Read | ||
| BI | 2000 | device/functionOnSel | Selected on/off command | Read | ||
| BOmin | 0 | device/functionOnInp | On/off command from the BMS | Command | ||
| BO | 1 | overrideOffInp | Override OFF (duty point 0 %) | Command | ||
| BO | 2 | overrideMaxInp | Override MAX (duty point 100 %) | Command | ||
| BO | 3 | overrideMinInp | Override MIN (minimum duty point) | Command | ||
| BO | 17 | overrideOnInp | Override ON | Command | ||
| BO | 100 | device/functionOnPrsInp,Lim | Preset on/off (startup / bus failure) | Command | ||
| BO | 200 | device/functionOnAuxInp | On/off for the auxiliary parameter set | Command | ||
| MI | 0 | controlFunctionAct | Active control mode | Read | 1=Gen_Spd, 6=Gen_PHdConst, 15=INVALID | |
| MImin | 1 | warning/errorMessageOut | Current Wilo warning/error code | Read | Wilo error code: 1=NO_ERROR, value n = code E(n-1); full list in the Wilo datapoint list | |
| MI | 2 | busCmd.TimerAct | Bus command timer state | Read | 1=OFF, 2=SET, 3=ACTIVE, 4=RESET, 5=MANUAL, 6=SET_PRESET, 7=ACTIVE_PRESET, 8=RESET_PRESET, 9=MANUAL_PRESET | |
| MI | 3 | setpointSignalSourceAct | Active setpoint source | Read | 1=IF-Module, 6=Internal, 9=INVALID | |
| MI | 4 | userTroubleCodeOut | Current Wilo trouble code (E400-E699) | Read | 1=no error (CODE_0); value n = Wilo trouble code E(n-1), E400-E699 | |
| MI | 33 | dutyPointRelunitsAct | Units of the active duty point | Read | 5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h | |
| MI | 1003 | setpointSignalSourceSel | Selected setpoint source | Read | 1=IF-Module, 6=Internal, 9=INVALID | |
| MI | 1033 | dutyPointRelunitsLim | Units of the duty point limits | Read | 5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h | |
| MI | 1133 | dutyPointRelunitsPrsLim | Units of the preset duty point | Read | 5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h | |
| MI | 1233 | dutyPointRelunitsAuxLim | Units of the auxiliary duty point | Read | 5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h | |
| MI | 2000 | controlFunctionSel | Selected control mode | Read | 1=Gen_Spd, 6=Gen_PHdConst, 15=INVALID | |
| MI | 2033 | dutyPointRelunitsSel | Units of the selected duty point | Read | 5=V, 19=kWh, 47=W, 55=bar, 62=Cel, 63=K, 73=s, 80=m3, 95={noUnit}, 104=min-1, 135=m3/h | |
| MI | 2034 | parameterSetSelectorSel | Parameter set in use | Read | 1=norm, 2=aux, 3=preset | |
| MI | 5003 | flushingTypeFluAct | Active flushing type | Read | 1=INVALID, 2=none, 3=temp-based, 4=time-based, 5=valve-kick, 6=sampling | |
| MI | 5004 | flushingTypeFluOut | Flushing type running | Read | 1=INVALID, 2=none, 3=temp-based, 4=time-based, 5=valve-kick, 6=sampling | |
| MI | 5005 | flushingPhaseFluLim | Flushing phase limit | Read | 1=INVALID, 2=inactive, 3=flushing1, 4=circulating, 5=flushing2 | |
| MImin | 5006 | flushingPhaseFluAct | Active flushing phase | Read | 1=INVALID, 2=inactive, 3=flushing1, 4=circulating, 5=flushing2 | |
| MI | 5007 | flushingPhaseFluOut | Current flushing phase | Read | 1=INVALID, 2=inactive, 3=flushing1, 4=circulating, 5=flushing2 | |
| MO | 0 | controlFunctionInp | Control mode command from the BMS | Command | 1=Gen_Spd, 6=Gen_PHdConst, 15=INVALID | |
| MOmin | 1 | busCmd.TimerInp,Act | Bus command timer (write SET before timeout) | Command | 1=OFF, 2=SET, 3=ACTIVE, 4=RESET, 5=MANUAL, 6=SET_PRESET, 7=ACTIVE_PRESET, 8=RESET_PRESET, 9=MANUAL_PRESET | |
| MO | 3 | setpointSignalSourceInp | Setpoint source selection | Command | 1=IF-Module, 6=Internal, 9=INVALID | |
| MO | 34 | parameterSetSelectorInp | Parameter set selection | Command | 1=norm, 2=aux, 3=preset | |
| MO | 100 | controlFunctionPrsInp,Lim | Preset control mode (startup / bus failure) | Command | 1=Gen_Spd, 6=Gen_PHdConst, 15=INVALID | |
| MO | 101 | setpointSignalSourcePrsInp,Lim | Preset setpoint source (startup / bus failure) | Command | 1=IF-Module, 6=Internal, 9=INVALID | |
| MO | 200 | controlFunctionAuxInp | Control mode for the auxiliary parameter set | Command | 1=Gen_Spd, 6=Gen_PHdConst, 15=INVALID | |
| MO | 203 | setpointSignalSourceAuxInp | Setpoint source for the auxiliary set | Command | 1=IF-Module, 6=Internal, 9=INVALID | |
| MOmin | 5003 | flushingTypeFluInp | Flushing type to start | Command | 1=INVALID, 2=none, 3=temp-based, 4=time-based |
No points match these filters.
Object ID lookup: Wilo SiFresh point IDs by name
AI0dutyPointRelOutAI1speedP01OutAI2flowOutAI3pressureOutAI4powerInputOutAI5temperatureFluid@DeviceOutAI7energyConsumptionOutAI8speedMivActAI9speedMavActAI12flowMavOutAI15powerInputMavOutAI16temperat.FluidFwdOutAI17temperat.FluidRetOutAI28voltageInputOutAI30systemTimeOutAI31dutyPointRelMioActAI32dutyPointRelMaoActAI33dutyPoint100%ValActAI34dutyPointRelActAI35busCmd.TimerTimeRemain.OutAI36flowLmiActAI37flowLmaActAI38flowLofActAI50pressureMavOutAI51flowMivOutAI1031dutyPointRelMioLimAI1032dutyPointRelMaoLimAI1033dutyPoint100%ValLimAI1034dutyPointRelSelAI1131dutyPointRelMioPrsLimAI1132dutyPointRelMaoPrsLimAI1133dutyPoint100%ValPrsLimAI1231dutyPointRelMioAuxLimAI1232dutyPointRelMaoAuxLimAI1233dutyPoint100%ValAuxLimAI2031dutyPointRelMioSelAI2032dutyPointRelMaoSelAI2033dutyPoint100%ValSelAI5000temperat.FluidRetHilFluActAI5002temperat.FluidRetLolFluActAI5008operationTimeRemain.FluOutAI5009operationTimeRst.ableMavFluOutAI5010timeActive/IdlingFluOutAI5012device/functionOnAvwFluOutAI5013volumeFluOutAI5014temperat.FluidRetStvFluOutAI5015flowFluOutAI5016volumeAvwFluOutAI5017temperat.FluidRetMidOutAI5018temperat.FluidRetAvdOutAI5019temperat.FluidRetMadOutAI5020temperat.FluidFwdMidOutAI5021temperat.FluidFwdAvdOutAI5022temperat.FluidFwdMadOutAO0dutyPointRelInpAO8busCmd.TimerTimeoutInp,ActAO36flowLmiInpAO37flowLmaInpAO38flowLofInpAO100dutyPointRelPrsInp,LimAO200dutyPointRelAuxInpAO5000temperat.FluidRetHilFluInpAO5002temperat.FluidRetLolFluInpBI0device/functionOnActBI1overrideOffActBI2overrideMaxActBI3overrideMinActBI9ready4OperationOutBI10device/functionOnOutBI11serviceRequiredOutBI12warningPresentOutBI13errorPresentOutBI17overrideOnActBI18actuationLimitOutBI2000device/functionOnSelBO0device/functionOnInpBO1overrideOffInpBO2overrideMaxInpBO3overrideMinInpBO17overrideOnInpBO100device/functionOnPrsInp,LimBO200device/functionOnAuxInpMI0controlFunctionActMI1warning/errorMessageOutMI2busCmd.TimerActMI3setpointSignalSourceActMI4userTroubleCodeOutMI33dutyPointRelunitsActMI1003setpointSignalSourceSelMI1033dutyPointRelunitsLimMI1133dutyPointRelunitsPrsLimMI1233dutyPointRelunitsAuxLimMI2000controlFunctionSelMI2033dutyPointRelunitsSelMI2034parameterSetSelectorSelMI5003flushingTypeFluActMI5004flushingTypeFluOutMI5005flushingPhaseFluLimMI5006flushingPhaseFluActMI5007flushingPhaseFluOutMO0controlFunctionInpMO1busCmd.TimerInp,ActMO3setpointSignalSourceInpMO34parameterSetSelectorInpMO100controlFunctionPrsInp,LimMO101setpointSignalSourcePrsInp,LimMO200controlFunctionAuxInpMO203setpointSignalSourceAuxInpMO5003flushingTypeFluInp
Integration notes
- Object list taken from Wilo's EDE file for this pump (CIF-Module BACnet MS/TP and Ethernet Multiprotocol files list the same objects); names follow Wilo's datapoint list.
- Objects ending Prs are preset (startup / bus-failure fallback) values; objects ending Aux belong to the auxiliary parameter set chosen with MO 34.
- A few objects (e.g. AI 50, AI 51) need CIF-Module firmware 5.01 or later. Wilo's Ethernet Multiprotocol EDE shortens a few names (e.g. busCmd.TimerAct for MO 1, controlFunctionPrsLim for MO 100); names here follow the MS/TP EDE and the datapoint list.
- Multistate state lists show the values Wilo marks as supported for this pump; error-code objects use Wilo's E-code numbering (value = code + 1).
- Temperature-based flushing is started automatically by local settings only; MO 5003 starts other flushing types.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SiFresh (CIF-Module BACnet MS/TP / Ethernet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet)
How many BACnet points does the Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet) have?
This list has 109 BACnet objects: 54 analog inputs, 9 analog outputs, 12 binary inputs, 7 binary outputs, 18 multi-state inputs, 9 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet) BACnet points are writable?
25 of the 109 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet) BACnet documentation?
The source is WILO BACnet - CIF-Module / IF-Module installation and operating instructions with functional description (datapoint list) and CIF-Module EDE files (wilo194261 (EDE: wilo254515 MS/TP, wilo666820 Ethernet)), revision EDE 2024-09-23 (CIF-Module 1.00...6.01), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo194261/11516096/wilo194261.html.
What are the minimum BACnet points to integrate the Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet)?
Start with BO 0 device/functionOnInp (On/off command); MO 5003 flushingTypeFluInp (Flushing type to start, e.g. 4 = time-based); MO 1 busCmd.TimerInp,Act (Heartbeat: write SET (2) before the timeout); BI 10 device/functionOnOut (Pump on); MI 5006 flushingPhaseFluAct (Active flushing phase); AI 5015 flowFluOut (Flushing flow, m³/h); AI 17 temperat.FluidRetOut (Return water temperature, °C); BI 13 errorPresentOut (Any active error); MI 1 warning/errorMessageOut (Wilo error code).
How do I enable BMS control of the Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet)?
Once the CIF-Module is set up, the pump's setpoint, control mode and on/off follow the values held in the module, not the local menu. MO 3 selects where the setpoint comes from (1 = IF-Module).
Does the Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet) need a BACnet heartbeat or have a communication timeout?
MO 1 bus command timer: write SET (2) again before the timeout in AO 8 (default 300 s). If it runs out the local menu is released and the display may show E50/E54; with SET_PRESET (6) the pump also loads the preset (Prs) on/off, control mode and duty point. Writing MANUAL (5) unlocks the local menu permanently; OFF (1) returns to the factory behaviour.
How do I check these points on the real SiFresh (CIF-Module BACnet MS/TP / Ethernet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Wilo BACnet points lists
- Pump controller (booster set switch box)
Wilo CC Booster (BACnet IP / MS/TP)
Wilo CC (Comfort-Controller) switch boxes on pressure-boosting pump sets, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Comfort-Controller CC, Wilo CC Booster BACnet, SPS extension BACnet IP slave, SPS extension BACnet MSTP slave - Pump controller (HVAC pump switch box)
Wilo CC HVAC (BACnet IP / MS/TP)
Wilo CC (Comfort-Controller) switch boxes on HVAC circulation pump systems, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Comfort-Controller CC HVAC, Wilo CC HVAC BACnet - Pump controller (lifting station switch box)
Wilo CC Lift (BACnet IP / MS/TP)
Wilo CC switch boxes running the Lift application on wastewater lifting stations, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CC Lift BACnet - Pump controller (booster set switch box with frequency converter)
Wilo CC...FC Booster (BACnet IP / MS/TP)
Wilo CC...FC switch boxes (with frequency converter) on pressure-boosting sets, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: CC-FC Booster, Wilo CC...FC BACnet - Pump controller (HVAC switch box with frequency converter)
Wilo CC...FC HVAC (BACnet IP / MS/TP)
Wilo CC...FC switch boxes (with frequency converter) on HVAC circulation pump systems, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: CC-FC HVAC, Wilo CC...FC HVAC BACnet - Pump controller (booster set switch box)
Wilo CCe Booster (BACnet IP / MS/TP)
Wilo CCe switch boxes for pressure-boosting sets with electronically controlled pumps, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe Booster BACnet - Pump controller (HVAC pump switch box)
Wilo CCe HVAC (BACnet IP / MS/TP)
Wilo CCe switch boxes on HVAC circulation pump systems with electronically controlled pumps, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe HVAC BACnet - Pump controller (booster set switch box)
Wilo CCe NWB Booster (BACnet IP / MS/TP)
Wilo CCe switch boxes that run their pumps over NWB, on pressure-boosting sets, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: CCe NWB, Wilo CCe NWB Booster BACnet - Pump controller (rainwater harvesting switch box)
Wilo CCe Rain (BACnet IP / MS/TP)
Wilo CCe switch boxes on rainwater utilisation systems (cistern pumps and replenishment valve), fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe Rain BACnet - Pump (CIF-Module BACnet interface)
Wilo Helix2.0-VE / Medana CH3-LE / Isar MODH1-E (CIF-Module BACnet)
Wilo Helix2.0-VE vertical and Medana CH3-LE horizontal multistage pumps, and the Isar MODH1-E, fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Helix2.0-VE, Helix 2.0 VE, Medana CH3-LE, Isar MODH1-E, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol - Pump (circulator BACnet MS/TP interface module)
Wilo IF-Module BACnet / IF-Module BACnet Stratos (BACnet MS/TP)
Wilo IF-Module BACnet (2097811, glanded pumps such as IL-E/IP-E/DL-E/BL-E and MVIE/MHIE) and IF-Module BACnet Stratos (2097810, Stratos/Stratos-D/-Z), the plug-in modules that put older Wilo electronic pumps on BACnet MS/TP.
Also known as: IF-Modul BACnet, IF-Modul BACnet Stratos, 2097811, 2097810, Wilo IF-Module BACnet - Pump controller (booster set switch box)
Wilo SC Booster (BACnet MS/TP / IP)
Wilo SC switch boxes on pressure-boosting pump sets.
Also known as: Wilo SC Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (SC Clean switch box, one pump and two valves)
Wilo SC Clean (BACnet MS/TP / IP)
Wilo SC switch boxes set to the Clean application (one pump and two valves).
Also known as: Wilo SC Clean BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (diesel fire pump switch box)
Wilo SC Fire D APSAD (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for diesel-driven sprinkler pumps built to the APSAD rules.
Also known as: Wilo SC Fire D APSAD BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (diesel fire pump switch box)
Wilo SC Fire D EN12845 (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for diesel-driven sprinkler pumps built to EN 12845.
Also known as: Wilo SC Fire D EN12845 BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (electric fire pump switch box)
Wilo SC Fire E APSAD (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for electric sprinkler pumps built to the APSAD rules.
Also known as: Wilo SC Fire E APSAD BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (electric fire pump switch box)
Wilo SC Fire E EN12845 (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for electric sprinkler pumps built to EN 12845.
Also known as: Wilo SC Fire E EN12845 BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC multi-pump switch box)
Wilo SC HVAC (BACnet MS/TP / IP)
Wilo SC switch boxes on multi-pump HVAC (heating/cooling circulation) systems.
Also known as: Wilo SC HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (lifting station switch box)
Wilo SC Lift (BACnet MS/TP / IP)
Wilo SC switch boxes on sewage/drainage lifting stations with level control.
Also known as: Wilo SC Lift BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box with frequency converter)
Wilo SC...FC Booster (BACnet MS/TP / IP)
Wilo SC...FC switch boxes (built-in frequency converter) on pressure-boosting pump sets.
Also known as: Wilo SC...FC Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC switch box with frequency converter)
Wilo SC...FC HVAC (BACnet MS/TP / IP)
Wilo SC...FC switch boxes (built-in frequency converter) on HVAC multi-pump systems.
Also known as: Wilo SC...FC HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box, electronic pumps)
Wilo SCe Booster (BACnet MS/TP / IP)
Wilo SCe switch boxes on pressure-boosting sets with speed-controlled (electronic) pumps.
Also known as: Wilo SCe Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (fire-fighting booster switch box)
Wilo SCe FFS Poland (BACnet MS/TP / IP)
Wilo SCe switch boxes on fire-fighting (FFS) booster sets in the Polish variant.
Also known as: Wilo SCe FFS Poland BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC switch box, electronic pumps)
Wilo SCe HVAC (BACnet MS/TP / IP)
Wilo SCe switch boxes on HVAC multi-pump systems with speed-controlled (electronic) pumps.
Also known as: Wilo SCe HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box, p-v control)
Wilo SCe PV Booster (BACnet MS/TP / IP)
Wilo SCe switch boxes on pressure-boosting sets running variable-pressure (p-v) control.
Also known as: Wilo SCe PV Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump (CIF-Module BACnet interface)
Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)
Wilo Stratos GIGA2.0-I / -D inline glandless high-efficiency pumps fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Stratos GIGA2.0, Stratos GIGA2.0-I, Stratos GIGA2.0-D, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol, 2190367, 2211408 - Pump (CIF-Module BACnet interface)
Wilo Stratos MAXO (CIF-Module BACnet MS/TP / Ethernet)
Wilo Stratos MAXO smart wet-rotor circulators fitted with a CIF-Module BACnet MS/TP (2190367) or CIF-Module Ethernet Multiprotocol for BACnet IP (2211408).
Also known as: Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol, 2190367, 2211408 - Pump (CIF-Module BACnet interface)
Wilo Yonos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)
Wilo Yonos GIGA2.0-I / -D glandless inline pumps fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Yonos GIGA2.0, Yonos GIGA2.0-I, Yonos GIGA2.0-D, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol
Source: WILO BACnet - CIF-Module / IF-Module installation and operating instructions with functional description (datapoint list) and CIF-Module EDE files · wilo194261 (EDE: wilo254515 MS/TP, wilo666820 Ethernet) · rev. EDE 2024-09-23 (CIF-Module 1.00...6.01). Object names, instances and units are reproduced as published; descriptions are our own.