Pump controller (booster set switch box with frequency converter) · BACnet points list
Wilo CC...FC Booster (BACnet IP / MS/TP) BACnet points list
Updated 6 November 2026
Wilo's CC-family switch boxes run multi-pump systems and connect to a BMS through a plug-in BACnet IP or BACnet MS/TP extension module, acting as a BACnet server. The CC...FC Booster list covers on/off, setpoints, pump modes, pump state bits, running hours, error bits and an alarm history. Fieldbus write access is governed by a bus command timer that must be refreshed every five minutes.
This page lists 137 BACnet objects for the Wilo CC...FC Booster (BACnet IP / MS/TP) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wilo’s own free documentation, linked below.
- Manufacturer
- Wilo
- Model
- CC...FC Booster (BACnet IP / MS/TP)
- Equipment
- Pump controller (booster set switch box with frequency converter)
- Equipment type
- VFDs & pumps
- BACnet objects
- 137 (23 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 22
- Also known as
- CC-FC Booster, Wilo CC...FC BACnet
Reference only, provided as-is: verify against Wilo’s current documentation and the live device before use. Not official Wilo information. Terms of use.
BMS integration notes: Wilo CC...FC Booster (BACnet IP / MS/TP)
Map Drives on/off (BV 224) as the start/stop command and Set point 1 (AV 1072) as the setpoint. For fieldbus control, write Set to the Bus command timer (MV 208) and repeat it within five minutes. Read the collective run and fault signals (BV 976/977) and the Error state bits for alarms; acknowledge with BV 1985.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 224 | Drives on/off | Automatic operation and all pumps on/off | Write |
| AV 1072 | Set point 1 | Setpoint 1; unit follows the control mode | Write |
| MV 208 | Bus command timer | Write Set (3) at least every 5 min to keep control | Write |
| BV 1985 | Acknowledge | Alarm acknowledge | Write |
| BV 976 | Switch box state (SBM) | Collective run signal | Read |
| AV 400 | Current value | Measured value; unit follows the control mode | Read |
| BV 977 | Switch box state (SSM) | Collective fault signal | Read |
Enable & remote start
The Bus command timer (MV 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).
Heartbeat & communication loss
With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.
Network setup
- Menu 4.3.8.3 sets the BACnet device name (default WILO CC BAC) and device object ID (0-4194303, default 22).
- BACnet IP module: default IP 192.168.0.5, mask 255.255.255.0, gateway 0.0.0.0.
- BACnet MS/TP module: baud 9600, 19.2k, 38.4k or 76.8k; node address 0-127 (default 2); max master default 10; max info frames 1-127.
- The BACnet extension needs a switch box software update by Wilo service.
Watch out for
- In Bus command timer Off mode the HMI stays locked; if the fieldbus fails there is no access until it recovers.
- Active setpoint value (AV 416) is read-only in dp-v and dT-v control modes.
- Alarm history: write the index to AV 1990, then read the code, year, month/day and time objects. Month/day and time are packed (value mod 100 and value / 100).
Wilo CC...FC Booster (BACnet IP / MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 0 | Version communication profile | Version of the fieldbus data-point list | Read | ||
| BV | 16 | Wink service | Write >0 to blink the HMI indicator for 30 s | Write | ||
| MV | 32 | Switch box type | Controller type and variant | Read | 1=SC, 2=SC...FC, 3=SCe, 4=CC, 5=CC...FC, 6=CCe, 7=SCe NWB, 8=CCe NWB | |
| AV | 48 | Switch box version PLC | Read | |||
| AV | 80 | Switch box version HMI | Read | |||
| AV | 112 | Switch box ID | Read | |||
| AV | 144 | Switch box circuit number | Read | |||
| AV | 176 | Switch box build month | Read | |||
| AV | 192 | Switch box build year | Read | |||
| MVmin | 208 | Bus command timer | HMI vs fieldbus access; Set must be resent within 5 min | Write | 1=-, 2=Off, 3=Set, 4=Active, 5=Reset, 6=Manual | |
| BVmin | 224 | Drives on/off | Switches automatic operation and all pumps on/off | Write | ||
| BV | 368 | FC on/off | Enables the internal frequency converter | Read | ||
| MV | 384 | Control mode | Active control mode | Read | 1=p-c, 2=dp-c, 3=dp-v, 4=dT-c, 5=dT-v, 6=n(TV), 7=n(TR), 8=n(TP), 9=n(TA), 10=n-c, 11=fill, 12=empty, 13=FTS, 14=cleans/day, 15=cleans/month | |
| AVmin | 400 | Current value | Measured value; unit follows the control mode | bar / m / K / °C / cm / min / h / psi | Read | |
| AV | 416 | Active setpoint value | Active setpoint; read-only in dp-v and dT-v modes | bar / m / K / °C / psi | Write | |
| AV | 432 | Number of pumps | Pumps present in the system | Read | ||
| BV | 464 | Reserved pump on/off | A pump is kept as reserve for a failed pump | Read | ||
| BV | 480 | Reserved pump used | Reserve pump in use because a pump failed | Read | ||
| AV | 496 | Index BLP | Index of the pump running as base-load pump | Read | ||
| BV | 512 | Pump 1 state (Auto) | Bit of the Pump 1 state bitmap | Read | ||
| BV | 513 | Pump 1 state (Manu) | Bit of the Pump 1 state bitmap | Read | ||
| BV | 514 | Pump 1 state (Disabled) | Bit of the Pump 1 state bitmap | Read | ||
| BV | 515 | Pump 1 state (Running) | Bit of the Pump 1 state bitmap | Read | ||
| BV | 516 | Pump 1 state (Warning) | Bit of the Pump 1 state bitmap | Read | ||
| BV | 517 | Pump 1 state (Error) | Bit of the Pump 1 state bitmap | Read | ||
| BV | 518 | Pump 1 state (Reserve pump) | Bit of the Pump 1 state bitmap | Read | ||
| BV | 528 | Pump 2 state (Auto) | Bit of the Pump 2 state bitmap | Read | ||
| BV | 529 | Pump 2 state (Manu) | Bit of the Pump 2 state bitmap | Read | ||
| BV | 530 | Pump 2 state (Disabled) | Bit of the Pump 2 state bitmap | Read | ||
| BV | 531 | Pump 2 state (Running) | Bit of the Pump 2 state bitmap | Read | ||
| BV | 532 | Pump 2 state (Warning) | Bit of the Pump 2 state bitmap | Read | ||
| BV | 533 | Pump 2 state (Error) | Bit of the Pump 2 state bitmap | Read | ||
| BV | 534 | Pump 2 state (Reserve pump) | Bit of the Pump 2 state bitmap | Read | ||
| BV | 544 | Pump 3 state (Auto) | Bit of the Pump 3 state bitmap | Read | ||
| BV | 545 | Pump 3 state (Manu) | Bit of the Pump 3 state bitmap | Read | ||
| BV | 546 | Pump 3 state (Disabled) | Bit of the Pump 3 state bitmap | Read | ||
| BV | 547 | Pump 3 state (Running) | Bit of the Pump 3 state bitmap | Read | ||
| BV | 548 | Pump 3 state (Warning) | Bit of the Pump 3 state bitmap | Read | ||
| BV | 549 | Pump 3 state (Error) | Bit of the Pump 3 state bitmap | Read | ||
| BV | 550 | Pump 3 state (Reserve pump) | Bit of the Pump 3 state bitmap | Read | ||
| BV | 560 | Pump 4 state (Auto) | Bit of the Pump 4 state bitmap | Read | ||
| BV | 561 | Pump 4 state (Manu) | Bit of the Pump 4 state bitmap | Read | ||
| BV | 562 | Pump 4 state (Disabled) | Bit of the Pump 4 state bitmap | Read | ||
| BV | 563 | Pump 4 state (Running) | Bit of the Pump 4 state bitmap | Read | ||
| BV | 564 | Pump 4 state (Warning) | Bit of the Pump 4 state bitmap | Read | ||
| BV | 565 | Pump 4 state (Error) | Bit of the Pump 4 state bitmap | Read | ||
| BV | 566 | Pump 4 state (Reserve pump) | Bit of the Pump 4 state bitmap | Read | ||
| BV | 576 | Pump 5 state (Auto) | Bit of the Pump 5 state bitmap | Read | ||
| BV | 577 | Pump 5 state (Manu) | Bit of the Pump 5 state bitmap | Read | ||
| BV | 578 | Pump 5 state (Disabled) | Bit of the Pump 5 state bitmap | Read | ||
| BV | 579 | Pump 5 state (Running) | Bit of the Pump 5 state bitmap | Read | ||
| BV | 580 | Pump 5 state (Warning) | Bit of the Pump 5 state bitmap | Read | ||
| BV | 581 | Pump 5 state (Error) | Bit of the Pump 5 state bitmap | Read | ||
| BV | 582 | Pump 5 state (Reserve pump) | Bit of the Pump 5 state bitmap | Read | ||
| BV | 592 | Pump 6 state (Auto) | Bit of the Pump 6 state bitmap | Read | ||
| BV | 593 | Pump 6 state (Manu) | Bit of the Pump 6 state bitmap | Read | ||
| BV | 594 | Pump 6 state (Disabled) | Bit of the Pump 6 state bitmap | Read | ||
| BV | 595 | Pump 6 state (Running) | Bit of the Pump 6 state bitmap | Read | ||
| BV | 596 | Pump 6 state (Warning) | Bit of the Pump 6 state bitmap | Read | ||
| BV | 597 | Pump 6 state (Error) | Bit of the Pump 6 state bitmap | Read | ||
| BV | 598 | Pump 6 state (Reserve pump) | Bit of the Pump 6 state bitmap | Read | ||
| MV | 640 | Pump 1 mode | Mode of pump 1 | Write | 1=Off, 2=Hand, 3=Auto | |
| MV | 656 | Pump 2 mode | Mode of pump 2 | Write | 1=Off, 2=Hand, 3=Auto | |
| MV | 672 | Pump 3 mode | Mode of pump 3 | Write | 1=Off, 2=Hand, 3=Auto | |
| MV | 688 | Pump 4 mode | Mode of pump 4 | Write | 1=Off, 2=Hand, 3=Auto | |
| MV | 704 | Pump 5 mode | Mode of pump 5 | Write | 1=Off, 2=Hand, 3=Auto | |
| MV | 720 | Pump 6 mode | Mode of pump 6 | Write | 1=Off, 2=Hand, 3=Auto | |
| AV | 784 | Pump 1 actual speed | Actual speed of pump 1; unit depends on switch box | % / Hz / 1/min | Read | |
| AV | 800 | Pump 2 actual speed | Actual speed of pump 2; unit depends on switch box | % / Hz / 1/min | Read | |
| AV | 816 | Pump 3 actual speed | Actual speed of pump 3; unit depends on switch box | % / Hz / 1/min | Read | |
| AV | 832 | Pump 4 actual speed | Actual speed of pump 4; unit depends on switch box | % / Hz / 1/min | Read | |
| AV | 848 | Pump 5 actual speed | Actual speed of pump 5; unit depends on switch box | % / Hz / 1/min | Read | |
| AV | 864 | Pump 6 actual speed | Actual speed of pump 6; unit depends on switch box | % / Hz / 1/min | Read | |
| BVmin | 976 | Switch box state (SBM) | Collective run signal (operation) | Read | ||
| BVmin | 977 | Switch box state (SSM) | Collective fault signal (alarm) | Read | ||
| AVmin | 1072 | Set point 1 | First controller setpoint; unit follows the control mode | bar / m / K / °C / psi | Write | |
| AV | 1088 | Set point 2 | Second controller setpoint | bar / m / K / °C / psi | Write | |
| AV | 1104 | Set point 3 | Third controller setpoint | bar / m / K / °C / psi | Write | |
| AV | 1184 | External set point value | Setpoint read from the external analog input | bar / m / K / °C / psi | Read | |
| BV | 1200 | External set point on/off | Enables the external analog setpoint | Write | ||
| AV | 1216 | Switch box cycles | Total power-offs of the switch box | Read | ||
| AV | 1248 | Switch box total running hours | Total on-time of the switch box | h | Read | |
| AV | 1280 | Pump 1 switch cycles | Read | |||
| AV | 1312 | Pump 2 switch cycles | Read | |||
| AV | 1344 | Pump 3 switch cycles | Read | |||
| AV | 1376 | Pump 4 switch cycles | Read | |||
| AV | 1408 | Pump 5 switch cycles | Read | |||
| AV | 1440 | Pump 6 switch cycles | Read | |||
| AV | 1536 | Pump 1 total running hours | h | Read | ||
| AV | 1568 | Pump 2 total running hours | h | Read | ||
| AV | 1600 | Pump 3 total running hours | h | Read | ||
| AV | 1632 | Pump 4 total running hours | h | Read | ||
| AV | 1664 | Pump 5 total running hours | h | Read | ||
| AV | 1696 | Pump 6 total running hours | h | Read | ||
| AV | 1792 | Pump 1 today running hours | h | Read | ||
| AV | 1808 | Pump 2 today running hours | h | Read | ||
| AV | 1824 | Pump 3 today running hours | h | Read | ||
| AV | 1840 | Pump 4 today running hours | h | Read | ||
| AV | 1856 | Pump 5 today running hours | h | Read | ||
| AV | 1872 | Pump 6 today running hours | h | Read | ||
| AV | 1952 | FC actual frequency | Output frequency of the frequency converter | Hz | Read | |
| AV | 1960 | FC actual current | Output current of the frequency converter | A | Read | |
| BV | 1965 | Error state (Sensor error) | Bit of the Error state bitmap | Read | ||
| BV | 1966 | Error state (P man) | Bit of the Error state bitmap | Read | ||
| BV | 1967 | Error state (P min) | Bit of the Error state bitmap | Read | ||
| BV | 1968 | Error state (FC) | Bit of the Error state bitmap | Read | ||
| BV | 1969 | Error state (TLS) | Bit of the Error state bitmap | Read | ||
| BV | 1970 | Error state (Pump 1 Alarm) | Bit of the Error state bitmap | Read | ||
| BV | 1971 | Error state (Pump 2 Alarm) | Bit of the Error state bitmap | Read | ||
| BV | 1972 | Error state (Pump 3 Alarm) | Bit of the Error state bitmap | Read | ||
| BV | 1973 | Error state (Pump 4 Alarm) | Bit of the Error state bitmap | Read | ||
| BV | 1974 | Error state (Pump 5 Alarm) | Bit of the Error state bitmap | Read | ||
| BV | 1975 | Error state (Pump 6 Alarm) | Bit of the Error state bitmap | Read | ||
| BV | 1978 | Error state (Frost) | Bit of the Error state bitmap | Read | ||
| BV | 1979 | Error state (Battery Low) | Bit of the Error state bitmap | Read | ||
| BV | 1980 | Error state (High water) | Bit of the Error state bitmap | Read | ||
| BV | 1981 | Error state (Priority off) | Bit of the Error state bitmap | Read | ||
| BV | 1982 | Error state (Redundancy) | Bit of the Error state bitmap | Read | ||
| BV | 1983 | Error state (Plausibility) | Bit of the Error state bitmap | Read | ||
| BV | 1984 | Error state (Slave communication) | Bit of the Error state bitmap | Read | ||
| BV | 1986 | Error state (Net supply) | Bit of the Error state bitmap | Read | ||
| BV | 1987 | Error state (Leakage) | Bit of the Error state bitmap | Read | ||
| BVmin | 1985 | Acknowledge | Acknowledges an alarm | Write | ||
| AV | 1990 | Alarm history index | Selects an alarm history entry (CC 0-35) | Write | ||
| AV | 1995 | Alarm history error code | Error code of the selected history entry | Read | ||
| AV | 2000 | Alarm history year | Year of the selected history entry | Read | ||
| AV | 2005 | Alarm history month | Entry date: month = value mod 100, day = value / 100 | Read | ||
| AV | 2010 | Alarm history time | Entry time: minutes = value mod 100, hours = value / 100 | Read | ||
| BV | 1122 | System control (Extern off) | System control function | Write | ||
| BV | 1123 | System control (Pump change) | System control function | Write | ||
| BV | 1124 | System control (Add Pump) | System control function | Write | ||
| BV | 1125 | System control (Remove pump) | System control function | Write | ||
| BV | 1126 | System control (Regulator op. analog) | System control function | Write | ||
| BV | 1127 | System control (Regulator op. fieldbus) | System control function | Write | ||
| AV | 1139 | Value regulator operation | Regulator value in % when fieldbus regulator operation is on | % | Write | |
| MV | 2015 | FC type | Installed frequency converter type | Read | 1=FC202, 2=VLT2800, 3=VLT6000 | |
| BV | 2020 | FC state | Drive status bits under one ID: OK flags, running, warnings | Read |
No points match these filters.
Object ID lookup: Wilo CC...FC Booster point IDs by name
AV0Version communication profileBV16Wink serviceMV32Switch box typeAV48Switch box version PLCAV80Switch box version HMIAV112Switch box IDAV144Switch box circuit numberAV176Switch box build monthAV192Switch box build yearMV208Bus command timerBV224Drives on/offBV368FC on/offMV384Control modeAV400Current valueAV416Active setpoint valueAV432Number of pumpsBV464Reserved pump on/offBV480Reserved pump usedAV496Index BLPBV512Pump 1 state (Auto)BV513Pump 1 state (Manu)BV514Pump 1 state (Disabled)BV515Pump 1 state (Running)BV516Pump 1 state (Warning)BV517Pump 1 state (Error)BV518Pump 1 state (Reserve pump)BV528Pump 2 state (Auto)BV529Pump 2 state (Manu)BV530Pump 2 state (Disabled)BV531Pump 2 state (Running)BV532Pump 2 state (Warning)BV533Pump 2 state (Error)BV534Pump 2 state (Reserve pump)BV544Pump 3 state (Auto)BV545Pump 3 state (Manu)BV546Pump 3 state (Disabled)BV547Pump 3 state (Running)BV548Pump 3 state (Warning)BV549Pump 3 state (Error)BV550Pump 3 state (Reserve pump)BV560Pump 4 state (Auto)BV561Pump 4 state (Manu)BV562Pump 4 state (Disabled)BV563Pump 4 state (Running)BV564Pump 4 state (Warning)BV565Pump 4 state (Error)BV566Pump 4 state (Reserve pump)BV576Pump 5 state (Auto)BV577Pump 5 state (Manu)BV578Pump 5 state (Disabled)BV579Pump 5 state (Running)BV580Pump 5 state (Warning)BV581Pump 5 state (Error)BV582Pump 5 state (Reserve pump)BV592Pump 6 state (Auto)BV593Pump 6 state (Manu)BV594Pump 6 state (Disabled)BV595Pump 6 state (Running)BV596Pump 6 state (Warning)BV597Pump 6 state (Error)BV598Pump 6 state (Reserve pump)MV640Pump 1 modeMV656Pump 2 modeMV672Pump 3 modeMV688Pump 4 modeMV704Pump 5 modeMV720Pump 6 modeAV784Pump 1 actual speedAV800Pump 2 actual speedAV816Pump 3 actual speedAV832Pump 4 actual speedAV848Pump 5 actual speedAV864Pump 6 actual speedBV976Switch box state (SBM)BV977Switch box state (SSM)AV1072Set point 1AV1088Set point 2AV1104Set point 3AV1184External set point valueBV1200External set point on/offAV1216Switch box cyclesAV1248Switch box total running hoursAV1280Pump 1 switch cyclesAV1312Pump 2 switch cyclesAV1344Pump 3 switch cyclesAV1376Pump 4 switch cyclesAV1408Pump 5 switch cyclesAV1440Pump 6 switch cyclesAV1536Pump 1 total running hoursAV1568Pump 2 total running hoursAV1600Pump 3 total running hoursAV1632Pump 4 total running hoursAV1664Pump 5 total running hoursAV1696Pump 6 total running hoursAV1792Pump 1 today running hoursAV1808Pump 2 today running hoursAV1824Pump 3 today running hoursAV1840Pump 4 today running hoursAV1856Pump 5 today running hoursAV1872Pump 6 today running hoursAV1952FC actual frequencyAV1960FC actual currentBV1965Error state (Sensor error)BV1966Error state (P man)BV1967Error state (P min)BV1968Error state (FC)BV1969Error state (TLS)BV1970Error state (Pump 1 Alarm)BV1971Error state (Pump 2 Alarm)BV1972Error state (Pump 3 Alarm)BV1973Error state (Pump 4 Alarm)BV1974Error state (Pump 5 Alarm)BV1975Error state (Pump 6 Alarm)BV1978Error state (Frost)BV1979Error state (Battery Low)BV1980Error state (High water)BV1981Error state (Priority off)BV1982Error state (Redundancy)BV1983Error state (Plausibility)BV1984Error state (Slave communication)BV1986Error state (Net supply)BV1987Error state (Leakage)BV1985AcknowledgeAV1990Alarm history indexAV1995Alarm history error codeAV2000Alarm history yearAV2005Alarm history monthAV2010Alarm history timeBV1122System control (Extern off)BV1123System control (Pump change)BV1124System control (Add Pump)BV1125System control (Remove pump)BV1126System control (Regulator op. analog)BV1127System control (Regulator op. fieldbus)AV1139Value regulator operationMV2015FC typeBV2020FC state
Integration notes
- Taken from the CC...FC Booster table in Wilo's CC BACnet supplement (English part, pp68-71). Wilo prints a 'BACnet ID' beside an explicit object type (AV, BV, MSV); the ID is used here as the object instance. The doc never says 'instance' in words, so confirm one point on the device.
- Where Wilo prints several IDs against one name (pump state, error state and other bitmaps), each ID is its own Binary Value for the element printed beside it; the element is shown in brackets after the name. Elements printed as '-' or '---' are unused and left out (2 here).
- Analog values with several units listed (bar, m, K, °C, psi...) report in the unit of the active control mode.
- The 'Added' column gives the list version each object appeared in (1.000, 31.000, 31.100); older switch box software may lack some objects.
- System control (BV 1122-1127) holds Extern off, pump change, add/remove pump and the regulator source (analog or fieldbus); with fieldbus regulator operation the BMS writes the value in % to AV 1139.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CC...FC Booster (BACnet IP / MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Wilo CC...FC Booster (BACnet IP / MS/TP)
How many BACnet points does the Wilo CC...FC Booster (BACnet IP / MS/TP) have?
This list has 137 BACnet objects: 49 analog values, 78 binary values, 10 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Wilo CC...FC Booster (BACnet IP / MS/TP) BACnet points are writable?
23 of the 137 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Wilo CC...FC Booster (BACnet IP / MS/TP) BACnet documentation?
The source is BACnet - supplemental sheet CC manual (CC System): System-specific data-point list BACnet CC (wilo110044), revision CC BACnet 2016-04-05 (list 31.106), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo110044/794249/wilo110044.pdf.
What are the minimum BACnet points to integrate the Wilo CC...FC Booster (BACnet IP / MS/TP)?
Start with BV 224 Drives on/off (Automatic operation and all pumps on/off); AV 1072 Set point 1 (Setpoint 1; unit follows the control mode); MV 208 Bus command timer (Write Set (3) at least every 5 min to keep control); BV 1985 Acknowledge (Alarm acknowledge); BV 976 Switch box state (SBM) (Collective run signal); AV 400 Current value (Measured value; unit follows the control mode); BV 977 Switch box state (SSM) (Collective fault signal).
How do I enable BMS control of the Wilo CC...FC Booster (BACnet IP / MS/TP)?
The Bus command timer (MV 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).
Does the Wilo CC...FC Booster (BACnet IP / MS/TP) need a BACnet heartbeat or have a communication timeout?
With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.
How do I check these points on the real CC...FC Booster (BACnet IP / MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Wilo BACnet points lists
- Pump controller (booster set switch box)
Wilo CC Booster (BACnet IP / MS/TP)
Wilo CC (Comfort-Controller) switch boxes on pressure-boosting pump sets, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Comfort-Controller CC, Wilo CC Booster BACnet, SPS extension BACnet IP slave, SPS extension BACnet MSTP slave - Pump controller (HVAC pump switch box)
Wilo CC HVAC (BACnet IP / MS/TP)
Wilo CC (Comfort-Controller) switch boxes on HVAC circulation pump systems, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Comfort-Controller CC HVAC, Wilo CC HVAC BACnet - Pump controller (lifting station switch box)
Wilo CC Lift (BACnet IP / MS/TP)
Wilo CC switch boxes running the Lift application on wastewater lifting stations, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CC Lift BACnet - Pump controller (HVAC switch box with frequency converter)
Wilo CC...FC HVAC (BACnet IP / MS/TP)
Wilo CC...FC switch boxes (with frequency converter) on HVAC circulation pump systems, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: CC-FC HVAC, Wilo CC...FC HVAC BACnet - Pump controller (booster set switch box)
Wilo CCe Booster (BACnet IP / MS/TP)
Wilo CCe switch boxes for pressure-boosting sets with electronically controlled pumps, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe Booster BACnet - Pump controller (HVAC pump switch box)
Wilo CCe HVAC (BACnet IP / MS/TP)
Wilo CCe switch boxes on HVAC circulation pump systems with electronically controlled pumps, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe HVAC BACnet - Pump controller (booster set switch box)
Wilo CCe NWB Booster (BACnet IP / MS/TP)
Wilo CCe switch boxes that run their pumps over NWB, on pressure-boosting sets, fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: CCe NWB, Wilo CCe NWB Booster BACnet - Pump controller (rainwater harvesting switch box)
Wilo CCe Rain (BACnet IP / MS/TP)
Wilo CCe switch boxes on rainwater utilisation systems (cistern pumps and replenishment valve), fitted with the BACnet IP or BACnet MS/TP extension module.
Also known as: Wilo CCe Rain BACnet - Pump (CIF-Module BACnet interface)
Wilo Helix2.0-VE / Medana CH3-LE / Isar MODH1-E (CIF-Module BACnet)
Wilo Helix2.0-VE vertical and Medana CH3-LE horizontal multistage pumps, and the Isar MODH1-E, fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Helix2.0-VE, Helix 2.0 VE, Medana CH3-LE, Isar MODH1-E, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol - Pump (circulator BACnet MS/TP interface module)
Wilo IF-Module BACnet / IF-Module BACnet Stratos (BACnet MS/TP)
Wilo IF-Module BACnet (2097811, glanded pumps such as IL-E/IP-E/DL-E/BL-E and MVIE/MHIE) and IF-Module BACnet Stratos (2097810, Stratos/Stratos-D/-Z), the plug-in modules that put older Wilo electronic pumps on BACnet MS/TP.
Also known as: IF-Modul BACnet, IF-Modul BACnet Stratos, 2097811, 2097810, Wilo IF-Module BACnet - Pump controller (booster set switch box)
Wilo SC Booster (BACnet MS/TP / IP)
Wilo SC switch boxes on pressure-boosting pump sets.
Also known as: Wilo SC Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (SC Clean switch box, one pump and two valves)
Wilo SC Clean (BACnet MS/TP / IP)
Wilo SC switch boxes set to the Clean application (one pump and two valves).
Also known as: Wilo SC Clean BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (diesel fire pump switch box)
Wilo SC Fire D APSAD (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for diesel-driven sprinkler pumps built to the APSAD rules.
Also known as: Wilo SC Fire D APSAD BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (diesel fire pump switch box)
Wilo SC Fire D EN12845 (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for diesel-driven sprinkler pumps built to EN 12845.
Also known as: Wilo SC Fire D EN12845 BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (electric fire pump switch box)
Wilo SC Fire E APSAD (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for electric sprinkler pumps built to the APSAD rules.
Also known as: Wilo SC Fire E APSAD BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (electric fire pump switch box)
Wilo SC Fire E EN12845 (BACnet MS/TP / IP)
Wilo SC-Fire switch boxes for electric sprinkler pumps built to EN 12845.
Also known as: Wilo SC Fire E EN12845 BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC multi-pump switch box)
Wilo SC HVAC (BACnet MS/TP / IP)
Wilo SC switch boxes on multi-pump HVAC (heating/cooling circulation) systems.
Also known as: Wilo SC HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (lifting station switch box)
Wilo SC Lift (BACnet MS/TP / IP)
Wilo SC switch boxes on sewage/drainage lifting stations with level control.
Also known as: Wilo SC Lift BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box with frequency converter)
Wilo SC...FC Booster (BACnet MS/TP / IP)
Wilo SC...FC switch boxes (built-in frequency converter) on pressure-boosting pump sets.
Also known as: Wilo SC...FC Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC switch box with frequency converter)
Wilo SC...FC HVAC (BACnet MS/TP / IP)
Wilo SC...FC switch boxes (built-in frequency converter) on HVAC multi-pump systems.
Also known as: Wilo SC...FC HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box, electronic pumps)
Wilo SCe Booster (BACnet MS/TP / IP)
Wilo SCe switch boxes on pressure-boosting sets with speed-controlled (electronic) pumps.
Also known as: Wilo SCe Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (fire-fighting booster switch box)
Wilo SCe FFS Poland (BACnet MS/TP / IP)
Wilo SCe switch boxes on fire-fighting (FFS) booster sets in the Polish variant.
Also known as: Wilo SCe FFS Poland BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (HVAC switch box, electronic pumps)
Wilo SCe HVAC (BACnet MS/TP / IP)
Wilo SCe switch boxes on HVAC multi-pump systems with speed-controlled (electronic) pumps.
Also known as: Wilo SCe HVAC BACnet, Smart-Controller SC, OPTION BACnet SC - Pump controller (booster set switch box, p-v control)
Wilo SCe PV Booster (BACnet MS/TP / IP)
Wilo SCe switch boxes on pressure-boosting sets running variable-pressure (p-v) control.
Also known as: Wilo SCe PV Booster BACnet, Smart-Controller SC, OPTION BACnet SC - Pump (CIF-Module BACnet interface)
Wilo SiFresh (CIF-Module BACnet MS/TP / Ethernet)
Wilo SiFresh drinking-water flushing / hygiene circulation pump station fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: SiFresh, Wilo-SiFresh, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol - Pump (CIF-Module BACnet interface)
Wilo Stratos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)
Wilo Stratos GIGA2.0-I / -D inline glandless high-efficiency pumps fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Stratos GIGA2.0, Stratos GIGA2.0-I, Stratos GIGA2.0-D, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol, 2190367, 2211408 - Pump (CIF-Module BACnet interface)
Wilo Stratos MAXO (CIF-Module BACnet MS/TP / Ethernet)
Wilo Stratos MAXO smart wet-rotor circulators fitted with a CIF-Module BACnet MS/TP (2190367) or CIF-Module Ethernet Multiprotocol for BACnet IP (2211408).
Also known as: Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol, 2190367, 2211408 - Pump (CIF-Module BACnet interface)
Wilo Yonos GIGA2.0 (CIF-Module BACnet MS/TP / Ethernet)
Wilo Yonos GIGA2.0-I / -D glandless inline pumps fitted with a CIF-Module BACnet MS/TP or Ethernet Multiprotocol (BACnet IP).
Also known as: Yonos GIGA2.0, Yonos GIGA2.0-I, Yonos GIGA2.0-D, CIF-Module BACnet MS/TP, CIF-Module Ethernet Multiprotocol
Source: BACnet - supplemental sheet CC manual (CC System): System-specific data-point list BACnet CC · wilo110044 · rev. CC BACnet 2016-04-05 (list 31.106). Object names, instances and units are reproduced as published; descriptions are our own.