Easy BACnet
  1. Home
  2. BACnet points lists
  3. Wilo
  4. CC Lift (BACnet IP / MS/TP)

Pump controller (lifting station switch box) · BACnet points list

Wilo CC Lift (BACnet IP / MS/TP) BACnet points list

Updated 6 November 2026

Short answer

Wilo's CC-family switch boxes run multi-pump systems and connect to a BMS through a plug-in BACnet IP or BACnet MS/TP extension module, acting as a BACnet server. The CC Lift list covers on/off, water level setpoints, level sensors, pump modes, pump state bits, running hours, error bits and an alarm history. Fieldbus write access is governed by a bus command timer that must be refreshed every five minutes.

This page lists 190 BACnet objects for the Wilo CC Lift (BACnet IP / MS/TP) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wilo’s own free documentation, linked below.

Manufacturer
Wilo
Model
CC Lift (BACnet IP / MS/TP)
Equipment
Pump controller (lifting station switch box)
Equipment type
VFDs & pumps
BACnet objects
190 (22 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
22
Also known as
Wilo CC Lift BACnet
Source document
BACnet - supplemental sheet CC manual (CC System): System-specific data-point list BACnet CC · wilo110044 · rev. CC BACnet 2016-04-05 (list 31.106)
Download CSV 190 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Wilo’s current documentation and the live device before use. Not official Wilo information. Terms of use.

BMS integration notes: Wilo CC Lift (BACnet IP / MS/TP)

Integration in brief

Map Drives on/off (BV 224) as the start/stop command and the water level setpoints (AV 1318-1337) if the BMS should adjust them. For fieldbus control, write Set to the Bus command timer (MV 208) and repeat it within five minutes. Read the collective run and fault signals (BV 976/977) and the Error state bits for alarms; acknowledge with BV 1985.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 224Drives on/offAutomatic operation and all pumps on/offWrite
AV 1318Set points water level 1Pump 1 start level, cmWrite
MV 208Bus command timerWrite Set (3) at least every 5 min to keep controlWrite
BV 1985AcknowledgeAlarm acknowledgeWrite
BV 976Switch box state (SBM)Collective run signalRead
AV 1313Level sensor 1Tank level, sensor 1Read
BV 977Switch box state (SSM)Collective fault signalRead

Enable & remote start

The Bus command timer (MV 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).

Heartbeat & communication loss

With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.

Network setup

Watch out for

Wilo CC Lift (BACnet IP / MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

190 of 190 shown
Type
AnalogBinaryMulti-state
Access
Show
Wilo CC Lift (BACnet IP / MS/TP) BACnet Points List
DescriptionStates
AV0Version communication profileVersion of the fieldbus data-point listRead
BV16Wink serviceWrite >0 to blink the HMI indicator for 30 sWrite
MVmin208Bus command timerHMI vs fieldbus access; Set must be resent within 5 minWrite1=-, 2=Off, 3=Set, 4=Active, 5=Reset, 6=Manual
BVmin224Drives on/offSwitches automatic operation and all pumps on/offWrite
MV384Control modeActive control modeRead1=p-c, 2=dp-c, 3=dp-v, 4=dT-c, 5=dT-v, 6=n(TV), 7=n(TR), 8=n(TP), 9=n(TA), 10=n-c, 11=fill, 12=empty, 13=FTS, 14=cleans/day, 15=cleans/month
AV400Current valueMeasured value; unit follows the control modebar / m / K / °C / cm / min / h / psiRead
AV416Active setpoint valueActive setpoint; read-only in dp-v and dT-v modesbar / m / K / °C / psiWrite
AV432Number of pumpsPumps present in the systemRead
BV512Pump 1 state (Auto)Bit of the Pump 1 state bitmapRead
BV513Pump 1 state (Manu)Bit of the Pump 1 state bitmapRead
BV514Pump 1 state (Disabled)Bit of the Pump 1 state bitmapRead
BV515Pump 1 state (Running)Bit of the Pump 1 state bitmapRead
BV516Pump 1 state (Warning)Bit of the Pump 1 state bitmapRead
BV517Pump 1 state (Error)Bit of the Pump 1 state bitmapRead
BV518Pump 1 state (Reserve pump)Bit of the Pump 1 state bitmapRead
BV528Pump 2 state (Auto)Bit of the Pump 2 state bitmapRead
BV529Pump 2 state (Manu)Bit of the Pump 2 state bitmapRead
BV530Pump 2 state (Disabled)Bit of the Pump 2 state bitmapRead
BV531Pump 2 state (Running)Bit of the Pump 2 state bitmapRead
BV532Pump 2 state (Warning)Bit of the Pump 2 state bitmapRead
BV533Pump 2 state (Error)Bit of the Pump 2 state bitmapRead
BV534Pump 2 state (Reserve pump)Bit of the Pump 2 state bitmapRead
BV544Pump 3 state (Auto)Bit of the Pump 3 state bitmapRead
BV545Pump 3 state (Manu)Bit of the Pump 3 state bitmapRead
BV546Pump 3 state (Disabled)Bit of the Pump 3 state bitmapRead
BV547Pump 3 state (Running)Bit of the Pump 3 state bitmapRead
BV548Pump 3 state (Warning)Bit of the Pump 3 state bitmapRead
BV549Pump 3 state (Error)Bit of the Pump 3 state bitmapRead
BV550Pump 3 state (Reserve pump)Bit of the Pump 3 state bitmapRead
BV560Pump 4 state (Auto)Bit of the Pump 4 state bitmapRead
BV561Pump 4 state (Manu)Bit of the Pump 4 state bitmapRead
BV562Pump 4 state (Disabled)Bit of the Pump 4 state bitmapRead
BV563Pump 4 state (Running)Bit of the Pump 4 state bitmapRead
BV564Pump 4 state (Warning)Bit of the Pump 4 state bitmapRead
BV565Pump 4 state (Error)Bit of the Pump 4 state bitmapRead
BV566Pump 4 state (Reserve pump)Bit of the Pump 4 state bitmapRead
MV640Pump 1 modeMode of pump 1Write1=Off, 2=Hand, 3=Auto
MV656Pump 2 modeMode of pump 2Write1=Off, 2=Hand, 3=Auto
MV672Pump 3 modeMode of pump 3Write1=Off, 2=Hand, 3=Auto
MV688Pump 4 modeMode of pump 4Write1=Off, 2=Hand, 3=Auto
BVmin976Switch box state (SBM)Collective run signal (operation)Read
BVmin977Switch box state (SSM)Collective fault signal (alarm)Read
AV1216Switch box cyclesTotal power-offs of the switch boxRead
AV1248Switch box total running hoursTotal on-time of the switch boxhRead
AV1280Pump 1 switch cyclesRead
AV1312Pump 2 switch cyclesRead
AV1344Pump 3 switch cyclesRead
AV1376Pump 4 switch cyclesRead
AV1536Pump 1 total running hourshRead
AV1568Pump 2 total running hourshRead
AV1600Pump 3 total running hourshRead
AV1632Pump 4 total running hourshRead
BV1965Error state (Sensor error)Bit of the Error state bitmapRead
BV1966Error state (P man)Bit of the Error state bitmapRead
BV1967Error state (P min)Bit of the Error state bitmapRead
BV1968Error state (FC)Bit of the Error state bitmapRead
BV1969Error state (TLS)Bit of the Error state bitmapRead
BV1970Error state (Pump 1 Alarm)Bit of the Error state bitmapRead
BV1971Error state (Pump 2 Alarm)Bit of the Error state bitmapRead
BV1972Error state (Pump 3 Alarm)Bit of the Error state bitmapRead
BV1973Error state (Pump 4 Alarm)Bit of the Error state bitmapRead
BV1974Error state (Pump 5 Alarm)Bit of the Error state bitmapRead
BV1975Error state (Pump 6 Alarm)Bit of the Error state bitmapRead
BV1978Error state (Frost)Bit of the Error state bitmapRead
BV1979Error state (Battery Low)Bit of the Error state bitmapRead
BV1980Error state (High water)Bit of the Error state bitmapRead
BV1981Error state (Priority off)Bit of the Error state bitmapRead
BV1982Error state (Redundancy)Bit of the Error state bitmapRead
BV1983Error state (Plausibility)Bit of the Error state bitmapRead
BV1984Error state (Slave communication)Bit of the Error state bitmapRead
BV1986Error state (Net supply)Bit of the Error state bitmapRead
BV1987Error state (Leakage)Bit of the Error state bitmapRead
BVmin1985AcknowledgeAcknowledges an alarmWrite
AV1990Alarm history indexSelects an alarm history entry (CC 0-35)Write
AV1995Alarm history error codeError code of the selected history entryRead
AV2000Alarm history yearYear of the selected history entryRead
AV2005Alarm history monthEntry date: month = value mod 100, day = value / 100Read
AV2010Alarm history timeEntry time: minutes = value mod 100, hours = value / 100Read
BV1281Option Float switches (DR)Bit of the Option Float switches bitmapRead
BV1282Option Float switches (HW)Bit of the Option Float switches bitmapRead
BV1283Option Float switches (Level sensor mode)Bit of the Option Float switches bitmapRead
BV1284Option Float switches (Float switch mode)Bit of the Option Float switches bitmapRead
BV1285Option Float switches (fill control mode)Bit of the Option Float switches bitmapRead
BV1286Option Float switches (empty control mode)Bit of the Option Float switches bitmapRead
BV1287Option Float switches (FTS control mode)Bit of the Option Float switches bitmapRead
BV1288Option Float switches (2nd level sensor present)Bit of the Option Float switches bitmapRead
BV1297State Float switches (DR)Bit of the State Float switches bitmapRead
BV1298State Float switches (Ps off)Bit of the State Float switches bitmapRead
BV1299State Float switches (P1 on)Bit of the State Float switches bitmapRead
BV1300State Float switches (P2 on)Bit of the State Float switches bitmapRead
BV1301State Float switches (HW)Bit of the State Float switches bitmapRead
AVmin1313Level sensor 1Tank level from sensor 1cmRead
AV1314Level sensor 2Tank level from sensor 2cmRead
AV1315Maximum sensor differenceMaximum allowed difference between the level sensorscmRead
AV1316Offset level sensorDistance from tank bottom to the level sensorcmRead
AV1317Maximum tank levelMaximum possible fill levelcmRead
AVmin1318Set points water level 1Level where pump 1 startscmWrite
AV1319Set points water level 2Level where pump 2 startscmWrite
AV1320Set points water level 3Level where pump 3 startscmWrite
AV1321Set points water level 4Level where pump 4 startscmWrite
AV1326Set points water level 1Level where pump 1 stopscmWrite
AV1327Set points water level 2Level where pump 2 stopscmWrite
AV1328Set points water level 3Level where pump 3 stopscmWrite
AV1329Set points water level 4Level where pump 4 stopscmWrite
AV1334Dry run levelLevel where dry run is reportedcmWrite
AV1335Dry run level offLevel where the dry-run report resetscmWrite
AV1336High water levelLevel where high water is reportedcmWrite
AV1337High water level offLevel where the high-water report resetscmWrite
BV1338Error state Lift 1 (No feedback pump 1)Bit of the Error state Lift 1 bitmapRead
BV1339Error state Lift 1 (No feedback pump 2)Bit of the Error state Lift 1 bitmapRead
BV1340Error state Lift 1 (No feedback pump 3)Bit of the Error state Lift 1 bitmapRead
BV1341Error state Lift 1 (No feedback pump 4)Bit of the Error state Lift 1 bitmapRead
BV1342Error state Lift 1 (No feedback pump 5)Bit of the Error state Lift 1 bitmapRead
BV1343Error state Lift 1 (No feedback pump 6)Bit of the Error state Lift 1 bitmapRead
BV1345Error state Lift 1 (No feedback pump 7)Bit of the Error state Lift 1 bitmapRead
BV1346Error state Lift 1 (No feedback pump 8)Bit of the Error state Lift 1 bitmapRead
BV1347Error state Lift 1 (Tightness pump 1)Bit of the Error state Lift 1 bitmapRead
BV1348Error state Lift 1 (Tightness pump 2)Bit of the Error state Lift 1 bitmapRead
BV1349Error state Lift 1 (Tightness pump 3)Bit of the Error state Lift 1 bitmapRead
BV1350Error state Lift 1 (Tightness pump 4)Bit of the Error state Lift 1 bitmapRead
BV1351Error state Lift 1 (Tightness pump 5)Bit of the Error state Lift 1 bitmapRead
BV1352Error state Lift 1 (Tightness pump 6)Bit of the Error state Lift 1 bitmapRead
BV1353Error state Lift 1 (Tightness pump 7)Bit of the Error state Lift 1 bitmapRead
BV1354Error state Lift 1 (Tightness pump 8)Bit of the Error state Lift 1 bitmapRead
BV1355Error state Lift 1 (Warning WSK PTC pump 1)Bit of the Error state Lift 1 bitmapRead
BV1356Error state Lift 1 (Warning WSK PTC pump 2)Bit of the Error state Lift 1 bitmapRead
BV1357Error state Lift 1 (Warning WSK PTC pump 3)Bit of the Error state Lift 1 bitmapRead
BV1358Error state Lift 1 (Warning WSK PTC pump 4)Bit of the Error state Lift 1 bitmapRead
BV1359Error state Lift 1 (Warning WSK PTC pump 5)Bit of the Error state Lift 1 bitmapRead
BV1360Error state Lift 1 (Warning WSK PTC pump 6)Bit of the Error state Lift 1 bitmapRead
BV1361Error state Lift 1 (Warning WSK PTC pump 7)Bit of the Error state Lift 1 bitmapRead
BV1362Error state Lift 1 (Warning WSK PTC pump 8)Bit of the Error state Lift 1 bitmapRead
BV1363Error state Lift 1 (Error WSK PTC pump 1)Bit of the Error state Lift 1 bitmapRead
BV1364Error state Lift 1 (Error WSK PTC pump 2)Bit of the Error state Lift 1 bitmapRead
BV1365Error state Lift 1 (Error WSK PTC pump 3)Bit of the Error state Lift 1 bitmapRead
BV1366Error state Lift 1 (Error WSK PTC pump 4)Bit of the Error state Lift 1 bitmapRead
BV1367Error state Lift 1 (Error WSK PTC pump 5)Bit of the Error state Lift 1 bitmapRead
BV1368Error state Lift 1 (Error WSK PTC pump 6)Bit of the Error state Lift 1 bitmapRead
BV1369Error state Lift 1 (Error WSK PTC pump 7)Bit of the Error state Lift 1 bitmapRead
BV1370Error state Lift 1 (Error WSK PTC pump 8)Bit of the Error state Lift 1 bitmapRead
BV1371Error state Lift 2 (Short-circuit pump 1)Bit of the Error state Lift 2 bitmapRead
BV1372Error state Lift 2 (Short-circuit pump 2)Bit of the Error state Lift 2 bitmapRead
BV1373Error state Lift 2 (Short-circuit pump 3)Bit of the Error state Lift 2 bitmapRead
BV1374Error state Lift 2 (Short-circuit pump 4)Bit of the Error state Lift 2 bitmapRead
BV1375Error state Lift 2 (Short-circuit pump 5)Bit of the Error state Lift 2 bitmapRead
BV1377Error state Lift 2 (Short-circuit pump 6)Bit of the Error state Lift 2 bitmapRead
BV1378Error state Lift 2 (Short-circuit pump 7)Bit of the Error state Lift 2 bitmapRead
BV1379Error state Lift 2 (Short-circuit pump 8)Bit of the Error state Lift 2 bitmapRead
BV1380Error state Lift 2 (Runtime exceeded pump 1)Bit of the Error state Lift 2 bitmapRead
BV1381Error state Lift 2 (Runtime exceeded pump 2)Bit of the Error state Lift 2 bitmapRead
BV1382Error state Lift 2 (Runtime exceeded pump 3)Bit of the Error state Lift 2 bitmapRead
BV1383Error state Lift 2 (Runtime exceeded pump 4)Bit of the Error state Lift 2 bitmapRead
BV1384Error state Lift 2 (Runtime exceeded pump 5)Bit of the Error state Lift 2 bitmapRead
BV1385Error state Lift 2 (Runtime exceeded pump 6)Bit of the Error state Lift 2 bitmapRead
BV1386Error state Lift 2 (Runtime exceeded pump 7)Bit of the Error state Lift 2 bitmapRead
BV1387Error state Lift 2 (Runtime exceeded pump 8)Bit of the Error state Lift 2 bitmapRead
BV1388Error state Lift 2 (Dry run)Bit of the Error state Lift 2 bitmapRead
BV1389Error state Lift 2 (High water)Bit of the Error state Lift 2 bitmapRead
BV1390Error state Lift 2 (FC error)Bit of the Error state Lift 2 bitmapRead
BV1391Error state Lift 2 (Sensor failure)Bit of the Error state Lift 2 bitmapRead
BV1392Error state Lift 2 (Battery min)Bit of the Error state Lift 2 bitmapRead
BV1393Error state Lift 2 (Net error)Bit of the Error state Lift 2 bitmapRead
BV1394Error state Lift 2 (Plausibility DR-P1&2off)Bit of the Error state Lift 2 bitmapRead
BV1395Error state Lift 2 (Plausibility P1&2off-P1on)Bit of the Error state Lift 2 bitmapRead
BV1396Error state Lift 2 (Plausibility P1on-P2on)Bit of the Error state Lift 2 bitmapRead
BV1397Error state Lift 2 (Plausibility P2on-HW)Bit of the Error state Lift 2 bitmapRead
BV1398Error state Lift 2 (Plausibility DR-P2on)Bit of the Error state Lift 2 bitmapRead
BV1399Error state Lift 2 (Plausibility P2-P1)Bit of the Error state Lift 2 bitmapRead
BV1400Error state Lift 2 (Plausibility P1on-P1&2off)Bit of the Error state Lift 2 bitmapRead
BV1401Error state Lift 2 (Plausibility P1&P2off-HW)Bit of the Error state Lift 2 bitmapRead
BV1402Error state Lift 2 (Plausibility DR-HW)Bit of the Error state Lift 2 bitmapRead
BV1403Error state Lift 2 (Plausibility P1on-HW)Bit of the Error state Lift 2 bitmapRead
BV1404Error state Lift 3 (Plausibility DR-P1on)Bit of the Error state Lift 3 bitmapRead
BV1405Error state Lift 3 (Priority off - extern dry run)Bit of the Error state Lift 3 bitmapRead
BV1406Error state Lift 3 (Priority off - extern high water)Bit of the Error state Lift 3 bitmapRead
BV1407Error state Lift 3 (sensor 1 failure)Bit of the Error state Lift 3 bitmapRead
BV1409Error state Lift 3 (sensor 2 failure)Bit of the Error state Lift 3 bitmapRead
BV1410Error state Lift 3 (Plausibility Sensors)Bit of the Error state Lift 3 bitmapRead
BV1441Error state Lift 3 (Plausibility float switch)Bit of the Error state Lift 3 bitmapRead
BV1442Error state Lift 3 (Slave communication)Bit of the Error state Lift 3 bitmapRead
AV1434Cycles float switches DRRead
AV1435Cycles float switches Pumps offRead
AV1436Cycles float switches P1 onRead
AV137Cycles float switches P2 onRead
AV1438Cycles float switches HWRead
AV1257Cycles float switches today DRRead
AV1258Cycles float switches today pumps offRead
AV1259Cycles float switches today pump 1 onRead
AV1260Cycles float switches today pump 2 onRead
AV1261Cycles float switches today HWRead
Object ID lookup: Wilo CC Lift point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CC Lift (BACnet IP / MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Wilo CC Lift (BACnet IP / MS/TP)

How many BACnet points does the Wilo CC Lift (BACnet IP / MS/TP) have?

This list has 190 BACnet objects: 46 analog values, 138 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Wilo CC Lift (BACnet IP / MS/TP) BACnet points are writable?

22 of the 190 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Wilo CC Lift (BACnet IP / MS/TP) BACnet documentation?

The source is BACnet - supplemental sheet CC manual (CC System): System-specific data-point list BACnet CC (wilo110044), revision CC BACnet 2016-04-05 (list 31.106), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo110044/794249/wilo110044.pdf.

What are the minimum BACnet points to integrate the Wilo CC Lift (BACnet IP / MS/TP)?

Start with BV 224 Drives on/off (Automatic operation and all pumps on/off); AV 1318 Set points water level 1 (Pump 1 start level, cm); MV 208 Bus command timer (Write Set (3) at least every 5 min to keep control); BV 1985 Acknowledge (Alarm acknowledge); BV 976 Switch box state (SBM) (Collective run signal); AV 1313 Level sensor 1 (Tank level, sensor 1); BV 977 Switch box state (SSM) (Collective fault signal).

How do I enable BMS control of the Wilo CC Lift (BACnet IP / MS/TP)?

The Bus command timer (MV 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).

Does the Wilo CC Lift (BACnet IP / MS/TP) need a BACnet heartbeat or have a communication timeout?

With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.

How do I check these points on the real CC Lift (BACnet IP / MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Wilo BACnet points lists

Source: BACnet - supplemental sheet CC manual (CC System): System-specific data-point list BACnet CC · wilo110044 · rev. CC BACnet 2016-04-05 (list 31.106). Object names, instances and units are reproduced as published; descriptions are our own.