Pump controller (diesel fire pump switch box) · BACnet points list

Wilo SC Fire D EN12845 (BACnet MS/TP / IP) BACnet points list

Updated 7 November 2026

Short answer

Wilo's SC-family switch boxes control multi-pump systems and act as a BACnet MS/TP slave on their RS-485 port; BACnet IP needs an added gateway in the panel. The SC Fire D EN12845 list covers the operating command, fire-pump switch states, battery/engine or mains values and fire error bits. Fieldbus write access is governed by a bus command timer that must be refreshed every five minutes.

This page lists 62 BACnet objects for the Wilo SC Fire D EN12845 (BACnet MS/TP / IP) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wilo’s own free documentation, linked below.

Manufacturer
Wilo
Model
SC Fire D EN12845 (BACnet MS/TP / IP)
Equipment
Pump controller (diesel fire pump switch box)
Equipment type
VFDs & pumps
BACnet objects
62 (6 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Data-point list 31.200
Also known as
Wilo SC Fire D EN12845 BACnet, Smart-Controller SC, OPTION BACnet SC
Source document
BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC · wilo110041 (OPTION BACnet SC 2539869 Ed. 06) · rev. 2020-07-10 (list 31.200)
Download CSV 62 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Wilo’s current documentation and the live device before use. Not official Wilo information. Terms of use.

BMS integration notes: Wilo SC Fire D EN12845 (BACnet MS/TP / IP)

Integration in brief

Read the switch states (pump running, sprinkler request, standby) and the fire error bits for monitoring. Drives on/off (BO 224) switches automatic operation; for any fieldbus write, first write Set to the Bus command timer (MO 208) and repeat it within five minutes. Acknowledge alarms with BO 1985.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 224Drives on/offAutomatic operation and all pumps on/offWrite
MO 208Bus command timerWrite Set (3) at least every 5 min to keep controlWrite
BO 1985AcknowledgeAlarm acknowledgeWrite
BI 1649Switch states (Pump running ED)Pump runningRead
BI 1651Switch states (Sprinkler request ED)Sprinkler start requestRead
BI 1656Switch states (Collective error message)Collective error messageRead

Enable & remote start

The Bus command timer (MO 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).

Heartbeat & communication loss

With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.

Network setup

Watch out for

Wilo SC Fire D EN12845 (BACnet MS/TP / IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

62 of 62 shown
Type
Access
Show
Wilo SC Fire D EN12845 (BACnet MS/TP / IP) BACnet Points List
DescriptionStates
AI0Version communication profileRead
BO16Wink serviceWrite >0 to blink the HMI indicator for 30 sWrite
MOmin208Bus command timerHMI vs fieldbus access; Set must be resent within 5 minWrite1=-, 2=Off, 3=Set, 4=Active, 5=Reset, 6=Manual
BOmin224Drives on/offAutomatic operation and all pumps on/offWrite
MI1168ApplicationApplication the switch box runsRead1=Booster, 2=HVAC, 3=WP, 4=Lift, 5=FFS-Diesel, 6=FFS-Electro, 7=FLA, 8=Clean, 9=Rain
AI1216Switch box cyclesRead
AI1248Switch box total running hourshRead
AI1280Pump 1 switch cyclesRead
BOmin1985AcknowledgeWrite to acknowledge an alarmWrite
AO1990Alarm history indexSelect an alarm history entry (SC: 0-15)Write
AI1995Alarm history error codeError code of the selected history entryRead
AO2011Alarm histogram indexWrite
AI2012Alarm histogram error codeRead
AI2013Alarm histogram error countRead
AI1538Voltage battery AVRead
AI1539Voltage battery BVRead
AI1540Current battery AARead
AI1541Current battery BARead
AI1542Start attempts battery ARead
AI1543Start attempts battery BRead
BI1648Switch states (Standby ED)Read
BImin1649Switch states (Pump running ED)Read
BI1650Switch states (Automatik OFF D)Read
BImin1651Switch states (Sprinkler request ED)Read
BI1652Switch states (Float switch request ED)Read
BI1653Switch states (Check manual start D)Read
BI1654Switch states (Manual stop ED)Read
BImin1656Switch states (Collective error message)Read
AI1545Oil pressurebarRead
AI1546Oil temperature°CRead
AI1547Water temperature°CRead
AI1548Water temperature external°CRead
AI1549Engine speedRPMRead
AI1551Pump total run minutesminRead
AI1552Pump last run minutesminRead
AI1554Remaining days to maintenancedRead
BI1572Error state Fire (No supply charger A D)Read
BI1573Error state Fire (No supply charger B D)Read
BI1574Error state Fire (LED No supply charger A D)Read
BI1575Error state Fire (LED No supply charger B D)Read
BI1576Error state Fire (Undervoltage battery A D)Read
BI1577Error state Fire (Undervoltage battery B D)Read
BI1578Error state Fire (No connection to aux HMI ED)Read
BI1579Error state Fire (Timeout charger A D)Read
BI1580Error state Fire (Timeout charger B D)Read
BI1581Error state Fire (Communication error A D)Read
BI1582Error state Fire (Communication error B D)Read
BI1583Error state Fire (Battery error A D)Read
BI1584Error state Fire (Battery error B D)Read
BI1585Error state Fire (Shortcut Battery A D)Read
BI1586Error state Fire (Shortcut Battery B D)Read
BI1587Error state Fire (Cable break Battery A D)Read
BI1588Error state Fire (Cable break Battery B D)Read
BI1589Error state Fire (Free error message ED)Read
BI1590Error state Fire (Minimum fuel D)Read
BI1591Error state Fire (No engine preheating D)Read
BI1592Error state Fire (Low oil pressure D)Read
BI1593Error state Fire (Overtemperature engine D)Read
BI1594Error state Fire (Start sprocket not engaged D)Read
BI1595Error state Fire (Sprocket wiring brocken D)Read
BI1596Error state Fire (Startup failed ED)Read
BI1597Error state Fire (Belt split D)Read
Object ID lookup: Wilo SC Fire D EN12845 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SC Fire D EN12845 (BACnet MS/TP / IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Wilo SC Fire D EN12845 (BACnet MS/TP / IP)

How many BACnet points does the Wilo SC Fire D EN12845 (BACnet MS/TP / IP) have?

This list has 62 BACnet objects: 21 analog inputs, 2 analog outputs, 34 binary inputs, 3 binary outputs, 1 multi-state input, 1 multi-state output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Wilo SC Fire D EN12845 (BACnet MS/TP / IP) BACnet points are writable?

6 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Wilo SC Fire D EN12845 (BACnet MS/TP / IP) BACnet documentation?

The source is BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC (wilo110041 (OPTION BACnet SC 2539869 Ed. 06)), revision 2020-07-10 (list 31.200), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo110041/4721760/wilo110041.pdf.

What are the minimum BACnet points to integrate the Wilo SC Fire D EN12845 (BACnet MS/TP / IP)?

Start with BO 224 Drives on/off (Automatic operation and all pumps on/off); MO 208 Bus command timer (Write Set (3) at least every 5 min to keep control); BO 1985 Acknowledge (Alarm acknowledge); BI 1649 Switch states (Pump running ED) (Pump running); BI 1651 Switch states (Sprinkler request ED) (Sprinkler start request); BI 1656 Switch states (Collective error message) (Collective error message).

How do I enable BMS control of the Wilo SC Fire D EN12845 (BACnet MS/TP / IP)?

The Bus command timer (MO 208) decides who may change settings. Manual: HMI and fieldbus both write, last value wins. Off: HMI locked, fieldbus only. Set: HMI locked and a 5-minute timer starts (state reads Active).

Does the Wilo SC Fire D EN12845 (BACnet MS/TP / IP) need a BACnet heartbeat or have a communication timeout?

With the Bus command timer in Set mode, Set must be written again at least every five minutes. If it lapses the state changes to Reset, the HMI gets access back and the fieldbus is locked until Set is written again.

How do I check these points on the real SC Fire D EN12845 (BACnet MS/TP / IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Wilo BACnet points lists

Source: BACnet - supplemental sheet SC manual (SC System): System-specific data-point list BACnet SC · wilo110041 (OPTION BACnet SC 2539869 Ed. 06) · rev. 2020-07-10 (list 31.200). Object names, instances and units are reproduced as published; descriptions are our own.