Easy BACnet
  1. Home
  2. BACnet points lists
  3. TROX
  4. X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)

VAV zone controller (master for up to 25 zone modules) · BACnet points list

TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP) BACnet points list

Updated 6 November 2026

Short answer

The X-AIRCONTROL Master has a built-in BACnet IP server (program version 1.00 and later). The protocol document lists 824 objects: AHU and section values (fan and temperature setpoints sent to the AHU, alarms, outdoor temperature, most-open damper/valve positions), per-zone readings and setpoints for up to 25 Zone Modules, master-chain alarms and the system clock. Values are scaled integers (for example 1/100 % and 1/100 °C).

This page lists 824 BACnet objects for the TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP) — 320 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.

Manufacturer
TROX
Model
X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)
Equipment
VAV zone controller (master for up to 25 zone modules)
Equipment type
VAV boxes & fan coils
BACnet objects
824 (320 writable)
Transport
BACnet IP
Firmware
Program version 1.00 and later
Default device instance
Last 5 digits of the IP address
Also known as
X-AIRCONTROL, X-AIRCONTROL Master, TROX Auranor X-AIRCONTROL, 67501-06/15, X-AIRCONTROL ZoneModule
Source document
X-AIRCONTROL BACnet protocol (TROX Auranor Norge) · 67501-06/15 · rev. 2015-06
Download CSV 824 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TROX’s current documentation and the live device before use. Not official TROX information. Terms of use.

BMS integration notes: TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)

Integration in brief

Read AI 111 for the master operating mode, AI 104 for the AHU state and AI 109/AI 110 for master and zone-module alarms. Per zone, write the room temperature setpoint (AV 1001 for zone 1, +100 per zone) and read room temperature (AI 1009), supply airflow (AI 1002) and zone status (AI 1000). Remember that values are scaled by 100.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1001ZoneModule 1 - Room Temperature SetpointZone 1 room setpoint, 1/100 °C (+100 per zone)Write
AI 111Zone Master Operation ModeMaster mode: normal, standby, night, fire...Read
AI 104AHU status0 normal, 1 stop, 2 summer night cooling, 3 fireRead
AI 108AHU Combined Outdoor Temp ValueOutdoor temperature, 1/100 °CRead
AI 1009ZoneModule 1 - Room Temperature Actual ValueZone 1 room temperature, 1/100 °CRead
AI 1002ZoneModule 1 - VAV Supply 1 FlowZone 1 supply airflow, m³/hRead
AI 1000ZoneModule 1 - StatusZone 1 state: 0 normal, 1 B-alarm, 2 A-alarmRead
AI 109Section Zone Master Alarm StatusMaster alarm: 0 none, 1 B-alarm, 2 A-alarmRead
AI 110Section Zone Module Alarm StatusZone module alarm: 0 none, 1 B-alarm, 2 A-alarmRead

Network setup

Watch out for

TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

824 of 824 shown
Type
Access
Show
TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP) BACnet Points List
DescriptionStates
BV0Automatic Daylight Saving TimeAutomatic summer/winter time changeWrite0=No, 1=Yes
BV100Summer/Winter Compensation EnableEnables summer/winter setpoint compensationWrite0=No, 1=Yes
BI100AHU Heating Pump StateHeating circulation pump stateRead
BI300Section PIR StatusAt least one zone activated by its PIR sensorRead
BI301Section Frost Protection StatusAt least one frost thermostat active (frost alarm)Read
BI1000ZoneModule 1 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 1)Read
BI1001ZoneModule 1 - PIR Active FlagPIR movement sensor activated (zone 1)Read
BI1002ZoneModule 1 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 1)Read
BI1003ZoneModule 1 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 1)Read
BI1100ZoneModule 2 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 2)Read
BI1101ZoneModule 2 - PIR Active FlagPIR movement sensor activated (zone 2)Read
BI1102ZoneModule 2 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 2)Read
BI1103ZoneModule 2 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 2)Read
BI1200ZoneModule 3 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 3)Read
BI1201ZoneModule 3 - PIR Active FlagPIR movement sensor activated (zone 3)Read
BI1202ZoneModule 3 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 3)Read
BI1203ZoneModule 3 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 3)Read
BI1300ZoneModule 4 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 4)Read
BI1301ZoneModule 4 - PIR Active FlagPIR movement sensor activated (zone 4)Read
BI1302ZoneModule 4 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 4)Read
BI1303ZoneModule 4 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 4)Read
BI1400ZoneModule 5 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 5)Read
BI1401ZoneModule 5 - PIR Active FlagPIR movement sensor activated (zone 5)Read
BI1402ZoneModule 5 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 5)Read
BI1403ZoneModule 5 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 5)Read
BI1500ZoneModule 6 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 6)Read
BI1501ZoneModule 6 - PIR Active FlagPIR movement sensor activated (zone 6)Read
BI1502ZoneModule 6 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 6)Read
BI1503ZoneModule 6 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 6)Read
BI1600ZoneModule 7 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 7)Read
BI1601ZoneModule 7 - PIR Active FlagPIR movement sensor activated (zone 7)Read
BI1602ZoneModule 7 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 7)Read
BI1603ZoneModule 7 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 7)Read
BI1700ZoneModule 8 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 8)Read
BI1701ZoneModule 8 - PIR Active FlagPIR movement sensor activated (zone 8)Read
BI1702ZoneModule 8 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 8)Read
BI1703ZoneModule 8 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 8)Read
BI1800ZoneModule 9 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 9)Read
BI1801ZoneModule 9 - PIR Active FlagPIR movement sensor activated (zone 9)Read
BI1802ZoneModule 9 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 9)Read
BI1803ZoneModule 9 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 9)Read
BI1900ZoneModule 10 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 10)Read
BI1901ZoneModule 10 - PIR Active FlagPIR movement sensor activated (zone 10)Read
BI1902ZoneModule 10 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 10)Read
BI1903ZoneModule 10 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 10)Read
BI2000ZoneModule 11 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 11)Read
BI2001ZoneModule 11 - PIR Active FlagPIR movement sensor activated (zone 11)Read
BI2002ZoneModule 11 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 11)Read
BI2003ZoneModule 11 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 11)Read
BI2100ZoneModule 12 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 12)Read
BI2101ZoneModule 12 - PIR Active FlagPIR movement sensor activated (zone 12)Read
BI2102ZoneModule 12 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 12)Read
BI2103ZoneModule 12 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 12)Read
BI2200ZoneModule 13 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 13)Read
BI2201ZoneModule 13 - PIR Active FlagPIR movement sensor activated (zone 13)Read
BI2202ZoneModule 13 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 13)Read
BI2203ZoneModule 13 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 13)Read
BI2300ZoneModule 14 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 14)Read
BI2301ZoneModule 14 - PIR Active FlagPIR movement sensor activated (zone 14)Read
BI2302ZoneModule 14 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 14)Read
BI2303ZoneModule 14 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 14)Read
BI2400ZoneModule 15 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 15)Read
BI2401ZoneModule 15 - PIR Active FlagPIR movement sensor activated (zone 15)Read
BI2402ZoneModule 15 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 15)Read
BI2403ZoneModule 15 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 15)Read
BI2500ZoneModule 16 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 16)Read
BI2501ZoneModule 16 - PIR Active FlagPIR movement sensor activated (zone 16)Read
BI2502ZoneModule 16 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 16)Read
BI2503ZoneModule 16 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 16)Read
BI2600ZoneModule 17 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 17)Read
BI2601ZoneModule 17 - PIR Active FlagPIR movement sensor activated (zone 17)Read
BI2602ZoneModule 17 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 17)Read
BI2603ZoneModule 17 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 17)Read
BI2700ZoneModule 18 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 18)Read
BI2701ZoneModule 18 - PIR Active FlagPIR movement sensor activated (zone 18)Read
BI2702ZoneModule 18 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 18)Read
BI2703ZoneModule 18 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 18)Read
BI2800ZoneModule 19 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 19)Read
BI2801ZoneModule 19 - PIR Active FlagPIR movement sensor activated (zone 19)Read
BI2802ZoneModule 19 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 19)Read
BI2803ZoneModule 19 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 19)Read
BI2900ZoneModule 20 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 20)Read
BI2901ZoneModule 20 - PIR Active FlagPIR movement sensor activated (zone 20)Read
BI2902ZoneModule 20 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 20)Read
BI2903ZoneModule 20 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 20)Read
BI3000ZoneModule 21 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 21)Read
BI3001ZoneModule 21 - PIR Active FlagPIR movement sensor activated (zone 21)Read
BI3002ZoneModule 21 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 21)Read
BI3003ZoneModule 21 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 21)Read
BI3100ZoneModule 22 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 22)Read
BI3101ZoneModule 22 - PIR Active FlagPIR movement sensor activated (zone 22)Read
BI3102ZoneModule 22 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 22)Read
BI3103ZoneModule 22 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 22)Read
BI3200ZoneModule 23 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 23)Read
BI3201ZoneModule 23 - PIR Active FlagPIR movement sensor activated (zone 23)Read
BI3202ZoneModule 23 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 23)Read
BI3203ZoneModule 23 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 23)Read
BI3300ZoneModule 24 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 24)Read
BI3301ZoneModule 24 - PIR Active FlagPIR movement sensor activated (zone 24)Read
BI3302ZoneModule 24 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 24)Read
BI3303ZoneModule 24 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 24)Read
BI3400ZoneModule 25 - Window/Frost ValueWindow/frost input: window 1 = closed, frost 0 = alarm (zone 25)Read
BI3401ZoneModule 25 - PIR Active FlagPIR movement sensor activated (zone 25)Read
BI3402ZoneModule 25 - Room Temp Sensor Short Circuit FlagRoom temperature sensor short circuit (zone 25)Read
BI3403ZoneModule 25 - Supply Temp Sensor Short Circuit FlagSupply temperature sensor short circuit (zone 25)Read
AI100AHU Supply Fan SetpointSupply fan signal setpoint sent to the AHU%Read
AI101AHU Extract Fan SetpointExtract fan signal setpoint sent to the AHU%Read
AI102AHU Supply Air Temp SetpointCalculated supply air temperature setpoint°CRead
AI103AHU Cooling Pump SetpointCalculated cooling water setpoint%Read
AImin104AHU statusAHU operationRead0=Normal, 1=Stop, 2=Summernight cooling, 3=Fire
AI105AHU Supply Fan Alarm StatusSupply fan alarmRead0=No alarm, 1=Alarm
AI106AHU Extract Fan Alarm StatusExtract fan alarmRead0=No alarm, 1=Alarm
AI107AHU Cooling Water Temp ValueActual cooling water temperature°CRead
AImin108AHU Combined Outdoor Temp ValueActual outdoor temperature°CRead
AImin109Section Zone Master Alarm StatusX-AIRCONTROL Master alarm stateRead0=No alarm, 1=B-alarm, 2=A-alarm
AImin110Section Zone Module Alarm StatusZone module alarm stateRead0=No alarm, 1=B-alarm, 2=A-alarm
AImin111Zone Master Operation ModeActual operation of the X-AIRCONTROL MasterRead0=Normal, 1=Standby, 2=Night reduction, 3=Summer night cooling, 4=Max. airflow, 5=Min. airflow, 6=Firemode - dampers open, fans running, 7=Firemode - dampers closed, fans stopped
AI112Actual Summer/Winter CompensationActual summer/winter compensationRead
AI300Number Of ZonemodulesNumber of connected zone modulesRead
AI301Section Supply Fan Max Damper PosMost-open supply VAV damper in the section%Read
AI302Section Extract Fan Max Damper PosMost-open extract VAV damper in the section%Read
AI303Section Heat Valve Max Valve PosMost-open heating valve in the section%Read
AI304Section Cool Valve Max Valve PosMost-open cooling valve in the section%Read
AI305Section Minimum Temperature SetpointActual minimum supply temperature°CRead
AImin1000ZoneModule 1 - StatusZone module state (zone 1)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1001ZoneModule 1 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 1)%Read
AImin1002ZoneModule 1 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 1)m³/hRead
AI1003ZoneModule 1 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 1)%Read
AI1004ZoneModule 1 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 1)m³/hRead
AI1005ZoneModule 1 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 1)%Read
AI1006ZoneModule 1 - VAV Extract FlowAirflow, extract VAV damper (zone 1)m³/hRead
AI1007ZoneModule 1 - Heating Actuator SetpointHeating valve opening (zone 1)%Read
AI1008ZoneModule 1 - Cooling Actuator setpointCooling valve opening (zone 1)%Read
AImin1009ZoneModule 1 - Room Temperature Actual ValueRoom temperature (zone 1)°CRead
AI1010ZoneModule 1 - Supply Temperature Actual ValueSupply air temperature (zone 1)°CRead
AI1011ZoneModule 1 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 1)°CRead
AI1012ZoneModule 1 - CO2/VOC Actual ValueCO2/VOC level (zone 1)ppmRead
AI1013ZoneModule 1 - RH Actual ValueRelative humidity (zone 1)%Read
AI1014ZoneModule 1 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 1)°CRead
AI1100ZoneModule 2 - StatusZone module state (zone 2)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1101ZoneModule 2 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 2)%Read
AI1102ZoneModule 2 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 2)m³/hRead
AI1103ZoneModule 2 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 2)%Read
AI1104ZoneModule 2 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 2)m³/hRead
AI1105ZoneModule 2 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 2)%Read
AI1106ZoneModule 2 - VAV Extract FlowAirflow, extract VAV damper (zone 2)m³/hRead
AI1107ZoneModule 2 - Heating Actuator SetpointHeating valve opening (zone 2)%Read
AI1108ZoneModule 2 - Cooling Actuator setpointCooling valve opening (zone 2)%Read
AI1109ZoneModule 2 - Room Temperature Actual ValueRoom temperature (zone 2)°CRead
AI1110ZoneModule 2 - Supply Temperature Actual ValueSupply air temperature (zone 2)°CRead
AI1111ZoneModule 2 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 2)°CRead
AI1112ZoneModule 2 - CO2/VOC Actual ValueCO2/VOC level (zone 2)ppmRead
AI1113ZoneModule 2 - RH Actual ValueRelative humidity (zone 2)%Read
AI1114ZoneModule 2 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 2)°CRead
AI1200ZoneModule 3 - StatusZone module state (zone 3)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1201ZoneModule 3 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 3)%Read
AI1202ZoneModule 3 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 3)m³/hRead
AI1203ZoneModule 3 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 3)%Read
AI1204ZoneModule 3 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 3)m³/hRead
AI1205ZoneModule 3 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 3)%Read
AI1206ZoneModule 3 - VAV Extract FlowAirflow, extract VAV damper (zone 3)m³/hRead
AI1207ZoneModule 3 - Heating Actuator SetpointHeating valve opening (zone 3)%Read
AI1208ZoneModule 3 - Cooling Actuator setpointCooling valve opening (zone 3)%Read
AI1209ZoneModule 3 - Room Temperature Actual ValueRoom temperature (zone 3)°CRead
AI1210ZoneModule 3 - Supply Temperature Actual ValueSupply air temperature (zone 3)°CRead
AI1211ZoneModule 3 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 3)°CRead
AI1212ZoneModule 3 - CO2/VOC Actual ValueCO2/VOC level (zone 3)ppmRead
AI1213ZoneModule 3 - RH Actual ValueRelative humidity (zone 3)%Read
AI1214ZoneModule 3 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 3)°CRead
AI1300ZoneModule 4 - StatusZone module state (zone 4)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1301ZoneModule 4 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 4)%Read
AI1302ZoneModule 4 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 4)m³/hRead
AI1303ZoneModule 4 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 4)%Read
AI1304ZoneModule 4 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 4)m³/hRead
AI1305ZoneModule 4 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 4)%Read
AI1306ZoneModule 4 - VAV Extract FlowAirflow, extract VAV damper (zone 4)m³/hRead
AI1307ZoneModule 4 - Heating Actuator SetpointHeating valve opening (zone 4)%Read
AI1308ZoneModule 4 - Cooling Actuator setpointCooling valve opening (zone 4)%Read
AI1309ZoneModule 4 - Room Temperature Actual ValueRoom temperature (zone 4)°CRead
AI1310ZoneModule 4 - Supply Temperature Actual ValueSupply air temperature (zone 4)°CRead
AI1311ZoneModule 4 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 4)°CRead
AI1312ZoneModule 4 - CO2/VOC Actual ValueCO2/VOC level (zone 4)ppmRead
AI1313ZoneModule 4 - RH Actual ValueRelative humidity (zone 4)%Read
AI1314ZoneModule 4 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 4)°CRead
AI1400ZoneModule 5 - StatusZone module state (zone 5)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1401ZoneModule 5 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 5)%Read
AI1402ZoneModule 5 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 5)m³/hRead
AI1403ZoneModule 5 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 5)%Read
AI1404ZoneModule 5 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 5)m³/hRead
AI1405ZoneModule 5 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 5)%Read
AI1406ZoneModule 5 - VAV Extract FlowAirflow, extract VAV damper (zone 5)m³/hRead
AI1407ZoneModule 5 - Heating Actuator SetpointHeating valve opening (zone 5)%Read
AI1408ZoneModule 5 - Cooling Actuator setpointCooling valve opening (zone 5)%Read
AI1409ZoneModule 5 - Room Temperature Actual ValueRoom temperature (zone 5)°CRead
AI1410ZoneModule 5 - Supply Temperature Actual ValueSupply air temperature (zone 5)°CRead
AI1411ZoneModule 5 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 5)°CRead
AI1412ZoneModule 5 - CO2/VOC Actual ValueCO2/VOC level (zone 5)ppmRead
AI1413ZoneModule 5 - RH Actual ValueRelative humidity (zone 5)%Read
AI1414ZoneModule 5 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 5)°CRead
AI1500ZoneModule 6 - StatusZone module state (zone 6)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1501ZoneModule 6 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 6)%Read
AI1502ZoneModule 6 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 6)m³/hRead
AI1503ZoneModule 6 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 6)%Read
AI1504ZoneModule 6 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 6)m³/hRead
AI1505ZoneModule 6 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 6)%Read
AI1506ZoneModule 6 - VAV Extract FlowAirflow, extract VAV damper (zone 6)m³/hRead
AI1507ZoneModule 6 - Heating Actuator SetpointHeating valve opening (zone 6)%Read
AI1508ZoneModule 6 - Cooling Actuator setpointCooling valve opening (zone 6)%Read
AI1509ZoneModule 6 - Room Temperature Actual ValueRoom temperature (zone 6)°CRead
AI1510ZoneModule 6 - Supply Temperature Actual ValueSupply air temperature (zone 6)°CRead
AI1511ZoneModule 6 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 6)°CRead
AI1512ZoneModule 6 - CO2/VOC Actual ValueCO2/VOC level (zone 6)ppmRead
AI1513ZoneModule 6 - RH Actual ValueRelative humidity (zone 6)%Read
AI1514ZoneModule 6 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 6)°CRead
AI1600ZoneModule 7 - StatusZone module state (zone 7)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1601ZoneModule 7 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 7)%Read
AI1602ZoneModule 7 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 7)m³/hRead
AI1603ZoneModule 7 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 7)%Read
AI1604ZoneModule 7 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 7)m³/hRead
AI1605ZoneModule 7 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 7)%Read
AI1606ZoneModule 7 - VAV Extract FlowAirflow, extract VAV damper (zone 7)m³/hRead
AI1607ZoneModule 7 - Heating Actuator SetpointHeating valve opening (zone 7)%Read
AI1608ZoneModule 7 - Cooling Actuator setpointCooling valve opening (zone 7)%Read
AI1609ZoneModule 7 - Room Temperature Actual ValueRoom temperature (zone 7)°CRead
AI1610ZoneModule 7 - Supply Temperature Actual ValueSupply air temperature (zone 7)°CRead
AI1611ZoneModule 7 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 7)°CRead
AI1612ZoneModule 7 - CO2/VOC Actual ValueCO2/VOC level (zone 7)ppmRead
AI1613ZoneModule 7 - RH Actual ValueRelative humidity (zone 7)%Read
AI1614ZoneModule 7 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 7)°CRead
AI1700ZoneModule 8 - StatusZone module state (zone 8)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1701ZoneModule 8 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 8)%Read
AI1702ZoneModule 8 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 8)m³/hRead
AI1703ZoneModule 8 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 8)%Read
AI1704ZoneModule 8 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 8)m³/hRead
AI1705ZoneModule 8 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 8)%Read
AI1706ZoneModule 8 - VAV Extract FlowAirflow, extract VAV damper (zone 8)m³/hRead
AI1707ZoneModule 8 - Heating Actuator SetpointHeating valve opening (zone 8)%Read
AI1708ZoneModule 8 - Cooling Actuator setpointCooling valve opening (zone 8)%Read
AI1709ZoneModule 8 - Room Temperature Actual ValueRoom temperature (zone 8)°CRead
AI1710ZoneModule 8 - Supply Temperature Actual ValueSupply air temperature (zone 8)°CRead
AI1711ZoneModule 8 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 8)°CRead
AI1712ZoneModule 8 - CO2/VOC Actual ValueCO2/VOC level (zone 8)ppmRead
AI1713ZoneModule 8 - RH Actual ValueRelative humidity (zone 8)%Read
AI1714ZoneModule 8 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 8)°CRead
AI1800ZoneModule 9 - StatusZone module state (zone 9)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1801ZoneModule 9 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 9)%Read
AI1802ZoneModule 9 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 9)m³/hRead
AI1803ZoneModule 9 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 9)%Read
AI1804ZoneModule 9 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 9)m³/hRead
AI1805ZoneModule 9 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 9)%Read
AI1806ZoneModule 9 - VAV Extract FlowAirflow, extract VAV damper (zone 9)m³/hRead
AI1807ZoneModule 9 - Heating Actuator SetpointHeating valve opening (zone 9)%Read
AI1808ZoneModule 9 - Cooling Actuator setpointCooling valve opening (zone 9)%Read
AI1809ZoneModule 9 - Room Temperature Actual ValueRoom temperature (zone 9)°CRead
AI1810ZoneModule 9 - Supply Temperature Actual ValueSupply air temperature (zone 9)°CRead
AI1811ZoneModule 9 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 9)°CRead
AI1812ZoneModule 9 - CO2/VOC Actual ValueCO2/VOC level (zone 9)ppmRead
AI1813ZoneModule 9 - RH Actual ValueRelative humidity (zone 9)%Read
AI1814ZoneModule 9 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 9)°CRead
AI1900ZoneModule 10 - StatusZone module state (zone 10)Read0=Normal, 1=B-alarm, 2=A-alarm
AI1901ZoneModule 10 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 10)%Read
AI1902ZoneModule 10 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 10)m³/hRead
AI1903ZoneModule 10 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 10)%Read
AI1904ZoneModule 10 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 10)m³/hRead
AI1905ZoneModule 10 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 10)%Read
AI1906ZoneModule 10 - VAV Extract FlowAirflow, extract VAV damper (zone 10)m³/hRead
AI1907ZoneModule 10 - Heating Actuator SetpointHeating valve opening (zone 10)%Read
AI1908ZoneModule 10 - Cooling Actuator setpointCooling valve opening (zone 10)%Read
AI1909ZoneModule 10 - Room Temperature Actual ValueRoom temperature (zone 10)°CRead
AI1910ZoneModule 10 - Supply Temperature Actual ValueSupply air temperature (zone 10)°CRead
AI1911ZoneModule 10 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 10)°CRead
AI1912ZoneModule 10 - CO2/VOC Actual ValueCO2/VOC level (zone 10)ppmRead
AI1913ZoneModule 10 - RH Actual ValueRelative humidity (zone 10)%Read
AI1914ZoneModule 10 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 10)°CRead
AI2000ZoneModule 11 - StatusZone module state (zone 11)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2001ZoneModule 11 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 11)%Read
AI2002ZoneModule 11 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 11)m³/hRead
AI2003ZoneModule 11 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 11)%Read
AI2004ZoneModule 11 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 11)m³/hRead
AI2005ZoneModule 11 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 11)%Read
AI2006ZoneModule 11 - VAV Extract FlowAirflow, extract VAV damper (zone 11)m³/hRead
AI2007ZoneModule 11 - Heating Actuator SetpointHeating valve opening (zone 11)%Read
AI2008ZoneModule 11 - Cooling Actuator setpointCooling valve opening (zone 11)%Read
AI2009ZoneModule 11 - Room Temperature Actual ValueRoom temperature (zone 11)°CRead
AI2010ZoneModule 11 - Supply Temperature Actual ValueSupply air temperature (zone 11)°CRead
AI2011ZoneModule 11 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 11)°CRead
AI2012ZoneModule 11 - CO2/VOC Actual ValueCO2/VOC level (zone 11)ppmRead
AI2013ZoneModule 11 - RH Actual ValueRelative humidity (zone 11)%Read
AI2014ZoneModule 11 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 11)°CRead
AI2100ZoneModule 12 - StatusZone module state (zone 12)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2101ZoneModule 12 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 12)%Read
AI2102ZoneModule 12 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 12)m³/hRead
AI2103ZoneModule 12 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 12)%Read
AI2104ZoneModule 12 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 12)m³/hRead
AI2105ZoneModule 12 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 12)%Read
AI2106ZoneModule 12 - VAV Extract FlowAirflow, extract VAV damper (zone 12)m³/hRead
AI2107ZoneModule 12 - Heating Actuator SetpointHeating valve opening (zone 12)%Read
AI2108ZoneModule 12 - Cooling Actuator setpointCooling valve opening (zone 12)%Read
AI2109ZoneModule 12 - Room Temperature Actual ValueRoom temperature (zone 12)°CRead
AI2110ZoneModule 12 - Supply Temperature Actual ValueSupply air temperature (zone 12)°CRead
AI2111ZoneModule 12 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 12)°CRead
AI2112ZoneModule 12 - CO2/VOC Actual ValueCO2/VOC level (zone 12)ppmRead
AI2113ZoneModule 12 - RH Actual ValueRelative humidity (zone 12)%Read
AI2114ZoneModule 12 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 12)°CRead
AI2200ZoneModule 13 - StatusZone module state (zone 13)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2201ZoneModule 13 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 13)%Read
AI2202ZoneModule 13 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 13)m³/hRead
AI2203ZoneModule 13 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 13)%Read
AI2204ZoneModule 13 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 13)m³/hRead
AI2205ZoneModule 13 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 13)%Read
AI2206ZoneModule 13 - VAV Extract FlowAirflow, extract VAV damper (zone 13)m³/hRead
AI2207ZoneModule 13 - Heating Actuator SetpointHeating valve opening (zone 13)%Read
AI2208ZoneModule 13 - Cooling Actuator setpointCooling valve opening (zone 13)%Read
AI2209ZoneModule 13 - Room Temperature Actual ValueRoom temperature (zone 13)°CRead
AI2210ZoneModule 13 - Supply Temperature Actual ValueSupply air temperature (zone 13)°CRead
AI2211ZoneModule 13 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 13)°CRead
AI2212ZoneModule 13 - CO2/VOC Actual ValueCO2/VOC level (zone 13)ppmRead
AI2213ZoneModule 13 - RH Actual ValueRelative humidity (zone 13)%Read
AI2214ZoneModule 13 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 13)°CRead
AI2300ZoneModule 14 - StatusZone module state (zone 14)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2301ZoneModule 14 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 14)%Read
AI2302ZoneModule 14 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 14)m³/hRead
AI2303ZoneModule 14 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 14)%Read
AI2304ZoneModule 14 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 14)m³/hRead
AI2305ZoneModule 14 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 14)%Read
AI2306ZoneModule 14 - VAV Extract FlowAirflow, extract VAV damper (zone 14)m³/hRead
AI2307ZoneModule 14 - Heating Actuator SetpointHeating valve opening (zone 14)%Read
AI2308ZoneModule 14 - Cooling Actuator setpointCooling valve opening (zone 14)%Read
AI2309ZoneModule 14 - Room Temperature Actual ValueRoom temperature (zone 14)°CRead
AI2310ZoneModule 14 - Supply Temperature Actual ValueSupply air temperature (zone 14)°CRead
AI2311ZoneModule 14 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 14)°CRead
AI2312ZoneModule 14 - CO2/VOC Actual ValueCO2/VOC level (zone 14)ppmRead
AI2313ZoneModule 14 - RH Actual ValueRelative humidity (zone 14)%Read
AI2314ZoneModule 14 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 14)°CRead
AI2400ZoneModule 15 - StatusZone module state (zone 15)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2401ZoneModule 15 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 15)%Read
AI2402ZoneModule 15 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 15)m³/hRead
AI2403ZoneModule 15 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 15)%Read
AI2404ZoneModule 15 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 15)m³/hRead
AI2405ZoneModule 15 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 15)%Read
AI2406ZoneModule 15 - VAV Extract FlowAirflow, extract VAV damper (zone 15)m³/hRead
AI2407ZoneModule 15 - Heating Actuator SetpointHeating valve opening (zone 15)%Read
AI2408ZoneModule 15 - Cooling Actuator setpointCooling valve opening (zone 15)%Read
AI2409ZoneModule 15 - Room Temperature Actual ValueRoom temperature (zone 15)°CRead
AI2410ZoneModule 15 - Supply Temperature Actual ValueSupply air temperature (zone 15)°CRead
AI2411ZoneModule 15 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 15)°CRead
AI2412ZoneModule 15 - CO2/VOC Actual ValueCO2/VOC level (zone 15)ppmRead
AI2413ZoneModule 15 - RH Actual ValueRelative humidity (zone 15)%Read
AI2414ZoneModule 15 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 15)°CRead
AI2500ZoneModule 16 - StatusZone module state (zone 16)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2501ZoneModule 16 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 16)%Read
AI2502ZoneModule 16 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 16)m³/hRead
AI2503ZoneModule 16 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 16)%Read
AI2504ZoneModule 16 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 16)m³/hRead
AI2505ZoneModule 16 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 16)%Read
AI2506ZoneModule 16 - VAV Extract FlowAirflow, extract VAV damper (zone 16)m³/hRead
AI2507ZoneModule 16 - Heating Actuator SetpointHeating valve opening (zone 16)%Read
AI2508ZoneModule 16 - Cooling Actuator setpointCooling valve opening (zone 16)%Read
AI2509ZoneModule 16 - Room Temperature Actual ValueRoom temperature (zone 16)°CRead
AI2510ZoneModule 16 - Supply Temperature Actual ValueSupply air temperature (zone 16)°CRead
AI2511ZoneModule 16 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 16)°CRead
AI2512ZoneModule 16 - CO2/VOC Actual ValueCO2/VOC level (zone 16)ppmRead
AI2513ZoneModule 16 - RH Actual ValueRelative humidity (zone 16)%Read
AI2514ZoneModule 16 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 16)°CRead
AI2600ZoneModule 17 - StatusZone module state (zone 17)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2601ZoneModule 17 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 17)%Read
AI2602ZoneModule 17 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 17)m³/hRead
AI2603ZoneModule 17 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 17)%Read
AI2604ZoneModule 17 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 17)m³/hRead
AI2605ZoneModule 17 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 17)%Read
AI2606ZoneModule 17 - VAV Extract FlowAirflow, extract VAV damper (zone 17)m³/hRead
AI2607ZoneModule 17 - Heating Actuator SetpointHeating valve opening (zone 17)%Read
AI2608ZoneModule 17 - Cooling Actuator setpointCooling valve opening (zone 17)%Read
AI2609ZoneModule 17 - Room Temperature Actual ValueRoom temperature (zone 17)°CRead
AI2610ZoneModule 17 - Supply Temperature Actual ValueSupply air temperature (zone 17)°CRead
AI2611ZoneModule 17 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 17)°CRead
AI2612ZoneModule 17 - CO2/VOC Actual ValueCO2/VOC level (zone 17)ppmRead
AI2613ZoneModule 17 - RH Actual ValueRelative humidity (zone 17)%Read
AI2614ZoneModule 17 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 17)°CRead
AI2700ZoneModule 18 - StatusZone module state (zone 18)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2701ZoneModule 18 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 18)%Read
AI2702ZoneModule 18 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 18)m³/hRead
AI2703ZoneModule 18 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 18)%Read
AI2704ZoneModule 18 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 18)m³/hRead
AI2705ZoneModule 18 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 18)%Read
AI2706ZoneModule 18 - VAV Extract FlowAirflow, extract VAV damper (zone 18)m³/hRead
AI2707ZoneModule 18 - Heating Actuator SetpointHeating valve opening (zone 18)%Read
AI2708ZoneModule 18 - Cooling Actuator setpointCooling valve opening (zone 18)%Read
AI2709ZoneModule 18 - Room Temperature Actual ValueRoom temperature (zone 18)°CRead
AI2710ZoneModule 18 - Supply Temperature Actual ValueSupply air temperature (zone 18)°CRead
AI2711ZoneModule 18 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 18)°CRead
AI2712ZoneModule 18 - CO2/VOC Actual ValueCO2/VOC level (zone 18)ppmRead
AI2713ZoneModule 18 - RH Actual ValueRelative humidity (zone 18)%Read
AI2714ZoneModule 18 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 18)°CRead
AI2800ZoneModule 19 - StatusZone module state (zone 19)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2801ZoneModule 19 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 19)%Read
AI2802ZoneModule 19 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 19)m³/hRead
AI2803ZoneModule 19 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 19)%Read
AI2804ZoneModule 19 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 19)m³/hRead
AI2805ZoneModule 19 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 19)%Read
AI2806ZoneModule 19 - VAV Extract FlowAirflow, extract VAV damper (zone 19)m³/hRead
AI2807ZoneModule 19 - Heating Actuator SetpointHeating valve opening (zone 19)%Read
AI2808ZoneModule 19 - Cooling Actuator setpointCooling valve opening (zone 19)%Read
AI2809ZoneModule 19 - Room Temperature Actual ValueRoom temperature (zone 19)°CRead
AI2810ZoneModule 19 - Supply Temperature Actual ValueSupply air temperature (zone 19)°CRead
AI2811ZoneModule 19 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 19)°CRead
AI2812ZoneModule 19 - CO2/VOC Actual ValueCO2/VOC level (zone 19)ppmRead
AI2813ZoneModule 19 - RH Actual ValueRelative humidity (zone 19)%Read
AI2814ZoneModule 19 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 19)°CRead
AI2900ZoneModule 20 - StatusZone module state (zone 20)Read0=Normal, 1=B-alarm, 2=A-alarm
AI2901ZoneModule 20 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 20)%Read
AI2902ZoneModule 20 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 20)m³/hRead
AI2903ZoneModule 20 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 20)%Read
AI2904ZoneModule 20 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 20)m³/hRead
AI2905ZoneModule 20 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 20)%Read
AI2906ZoneModule 20 - VAV Extract FlowAirflow, extract VAV damper (zone 20)m³/hRead
AI2907ZoneModule 20 - Heating Actuator SetpointHeating valve opening (zone 20)%Read
AI2908ZoneModule 20 - Cooling Actuator setpointCooling valve opening (zone 20)%Read
AI2909ZoneModule 20 - Room Temperature Actual ValueRoom temperature (zone 20)°CRead
AI2910ZoneModule 20 - Supply Temperature Actual ValueSupply air temperature (zone 20)°CRead
AI2911ZoneModule 20 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 20)°CRead
AI2912ZoneModule 20 - CO2/VOC Actual ValueCO2/VOC level (zone 20)ppmRead
AI2913ZoneModule 20 - RH Actual ValueRelative humidity (zone 20)%Read
AI2914ZoneModule 20 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 20)°CRead
AI3000ZoneModule 21 - StatusZone module state (zone 21)Read0=Normal, 1=B-alarm, 2=A-alarm
AI3001ZoneModule 21 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 21)%Read
AI3002ZoneModule 21 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 21)m³/hRead
AI3003ZoneModule 21 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 21)%Read
AI3004ZoneModule 21 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 21)m³/hRead
AI3005ZoneModule 21 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 21)%Read
AI3006ZoneModule 21 - VAV Extract FlowAirflow, extract VAV damper (zone 21)m³/hRead
AI3007ZoneModule 21 - Heating Actuator SetpointHeating valve opening (zone 21)%Read
AI3008ZoneModule 21 - Cooling Actuator setpointCooling valve opening (zone 21)%Read
AI3009ZoneModule 21 - Room Temperature Actual ValueRoom temperature (zone 21)°CRead
AI3010ZoneModule 21 - Supply Temperature Actual ValueSupply air temperature (zone 21)°CRead
AI3011ZoneModule 21 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 21)°CRead
AI3012ZoneModule 21 - CO2/VOC Actual ValueCO2/VOC level (zone 21)ppmRead
AI3013ZoneModule 21 - RH Actual ValueRelative humidity (zone 21)%Read
AI3014ZoneModule 21 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 21)°CRead
AI3100ZoneModule 22 - StatusZone module state (zone 22)Read0=Normal, 1=B-alarm, 2=A-alarm
AI3101ZoneModule 22 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 22)%Read
AI3102ZoneModule 22 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 22)m³/hRead
AI3103ZoneModule 22 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 22)%Read
AI3104ZoneModule 22 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 22)m³/hRead
AI3105ZoneModule 22 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 22)%Read
AI3106ZoneModule 22 - VAV Extract FlowAirflow, extract VAV damper (zone 22)m³/hRead
AI3107ZoneModule 22 - Heating Actuator SetpointHeating valve opening (zone 22)%Read
AI3108ZoneModule 22 - Cooling Actuator setpointCooling valve opening (zone 22)%Read
AI3109ZoneModule 22 - Room Temperature Actual ValueRoom temperature (zone 22)°CRead
AI3110ZoneModule 22 - Supply Temperature Actual ValueSupply air temperature (zone 22)°CRead
AI3111ZoneModule 22 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 22)°CRead
AI3112ZoneModule 22 - CO2/VOC Actual ValueCO2/VOC level (zone 22)ppmRead
AI3113ZoneModule 22 - RH Actual ValueRelative humidity (zone 22)%Read
AI3114ZoneModule 22 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 22)°CRead
AI3200ZoneModule 23 - StatusZone module state (zone 23)Read0=Normal, 1=B-alarm, 2=A-alarm
AI3201ZoneModule 23 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 23)%Read
AI3202ZoneModule 23 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 23)m³/hRead
AI3203ZoneModule 23 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 23)%Read
AI3204ZoneModule 23 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 23)m³/hRead
AI3205ZoneModule 23 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 23)%Read
AI3206ZoneModule 23 - VAV Extract FlowAirflow, extract VAV damper (zone 23)m³/hRead
AI3207ZoneModule 23 - Heating Actuator SetpointHeating valve opening (zone 23)%Read
AI3208ZoneModule 23 - Cooling Actuator setpointCooling valve opening (zone 23)%Read
AI3209ZoneModule 23 - Room Temperature Actual ValueRoom temperature (zone 23)°CRead
AI3210ZoneModule 23 - Supply Temperature Actual ValueSupply air temperature (zone 23)°CRead
AI3211ZoneModule 23 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 23)°CRead
AI3212ZoneModule 23 - CO2/VOC Actual ValueCO2/VOC level (zone 23)ppmRead
AI3213ZoneModule 23 - RH Actual ValueRelative humidity (zone 23)%Read
AI3214ZoneModule 23 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 23)°CRead
AI3300ZoneModule 24 - StatusZone module state (zone 24)Read0=Normal, 1=B-alarm, 2=A-alarm
AI3301ZoneModule 24 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 24)%Read
AI3302ZoneModule 24 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 24)m³/hRead
AI3303ZoneModule 24 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 24)%Read
AI3304ZoneModule 24 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 24)m³/hRead
AI3305ZoneModule 24 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 24)%Read
AI3306ZoneModule 24 - VAV Extract FlowAirflow, extract VAV damper (zone 24)m³/hRead
AI3307ZoneModule 24 - Heating Actuator SetpointHeating valve opening (zone 24)%Read
AI3308ZoneModule 24 - Cooling Actuator setpointCooling valve opening (zone 24)%Read
AI3309ZoneModule 24 - Room Temperature Actual ValueRoom temperature (zone 24)°CRead
AI3310ZoneModule 24 - Supply Temperature Actual ValueSupply air temperature (zone 24)°CRead
AI3311ZoneModule 24 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 24)°CRead
AI3312ZoneModule 24 - CO2/VOC Actual ValueCO2/VOC level (zone 24)ppmRead
AI3313ZoneModule 24 - RH Actual ValueRelative humidity (zone 24)%Read
AI3314ZoneModule 24 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 24)°CRead
AI3400ZoneModule 25 - StatusZone module state (zone 25)Read0=Normal, 1=B-alarm, 2=A-alarm
AI3401ZoneModule 25 - VAV Supply 1 Actuator SetpointDamper position, supply VAV damper 1 (zone 25)%Read
AI3402ZoneModule 25 - VAV Supply 1 FlowAirflow, supply VAV damper 1 (zone 25)m³/hRead
AI3403ZoneModule 25 - VAV Supply 2 Actuator SetpointDamper position, supply VAV damper 2 (zone 25)%Read
AI3404ZoneModule 25 - VAV Supply 2 FlowAirflow, supply VAV damper 2 (zone 25)m³/hRead
AI3405ZoneModule 25 - VAV Extract Actuator SetpointDamper position, extract VAV damper (zone 25)%Read
AI3406ZoneModule 25 - VAV Extract FlowAirflow, extract VAV damper (zone 25)m³/hRead
AI3407ZoneModule 25 - Heating Actuator SetpointHeating valve opening (zone 25)%Read
AI3408ZoneModule 25 - Cooling Actuator setpointCooling valve opening (zone 25)%Read
AI3409ZoneModule 25 - Room Temperature Actual ValueRoom temperature (zone 25)°CRead
AI3410ZoneModule 25 - Supply Temperature Actual ValueSupply air temperature (zone 25)°CRead
AI3411ZoneModule 25 - Remote Setpoint Offset Actual ValueActual setpoint offset (zone 25)°CRead
AI3412ZoneModule 25 - CO2/VOC Actual ValueCO2/VOC level (zone 25)ppmRead
AI3413ZoneModule 25 - RH Actual ValueRelative humidity (zone 25)%Read
AI3414ZoneModule 25 - Room Temperature Actual SetpointCalculated room temperature setpoint (zone 25)°CRead
AI3500Number Of ZonemastersNumber of linked/online X-AIRCONTROL MastersRead
AI3501ZoneMaster Chain IDChain ID of this X-AIRCONTROL MasterRead
AI4000ZoneMaster 1 - ZoneMaster Local Alarm StatusAlarm state of X-AIRCONTROL Master no. 1Read0=Normal, 1=B-alarm, 2=A-alarm
AI4100ZoneMaster 2 - ZoneMaster Local Alarm StatusAlarm state of X-AIRCONTROL Master no. 2Read0=Normal, 1=B-alarm, 2=A-alarm
AI4200ZoneMaster 3 - ZoneMaster Local Alarm StatusAlarm state of X-AIRCONTROL Master no. 3Read0=Normal, 1=B-alarm, 2=A-alarm
AI4300ZoneMaster 4 - ZoneMaster Local Alarm StatusAlarm state of X-AIRCONTROL Master no. 4Read0=Normal, 1=B-alarm, 2=A-alarm
AI4400ZoneMaster 5 - ZoneMaster Local Alarm StatusAlarm state of X-AIRCONTROL Master no. 5Read0=Normal, 1=B-alarm, 2=A-alarm
AV0System Time YearClock: yearWrite
AV1System Time MonthClock: monthWrite
AV2System Time DateClock: day of monthWrite
AV3System Time HourClock: hourWrite
AV4System Time MinuteClock: minuteWrite
AV5System Time SecondClock: secondWrite
AV100AHU Min Supply Fan SpeedSupply fan minimum speed%Write
AV101AHU Max Supply Fan SpeedSupply fan maximum speed%Write
AV102AHU Min Extract Fan SpeedExtract fan minimum speed%Write
AV103AHU Max Extract Fan SpeedExtract fan maximum speed%Write
AV104Minimum Supply Air TemperatureMinimum supply air temperature°CWrite
AV105Highest Allowed Cooling Water TempMaximum cooling water temperature°CWrite
AV106Winter Start TemperatureWinter compensation: low outdoor temperature point°CWrite
AV107Winter Max TemperatureWinter compensation: high outdoor temperature point°CWrite
AV108Winter Temp DiffWinter compensation amount°CWrite
AV109Summer Start TemperatureSummer compensation: low outdoor temperature point°CWrite
AV110Summer Max TemperatureSummer compensation: high outdoor temperature point°CWrite
AV111Summer Temp DiffSummer compensation amount°CWrite
AVmin1001ZoneModule 1 - Room Temperature SetpointRoom temperature setpoint (zone 1)°CWrite
AV1002ZoneModule 1 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 1)°CWrite
AV1003ZoneModule 1 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 1)°CWrite
AV1004ZoneModule 1 - Room CO2 SetpointRoom CO2 setpoint (zone 1)ppmWrite
AV1005ZoneModule 1 - Room RH SetpointRoom relative humidity setpoint (zone 1)%Write
AV1006ZoneModule 1 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 1)%Write
AV1007ZoneModule 1 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 1)%Write
AV1008ZoneModule 1 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 1)%Write
AV1009ZoneModule 1 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 1)%Write
AV1010ZoneModule 1 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 1)%Write
AV1011ZoneModule 1 - VAV Extract Min. Air FlowMinimum extract airflow (zone 1)%Write
AV1012ZoneModule 1 - VAV Extract Max. Air FlowMaximum extract airflow (zone 1)%Write
AV1101ZoneModule 2 - Room Temperature SetpointRoom temperature setpoint (zone 2)°CWrite
AV1102ZoneModule 2 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 2)°CWrite
AV1103ZoneModule 2 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 2)°CWrite
AV1104ZoneModule 2 - Room CO2 SetpointRoom CO2 setpoint (zone 2)ppmWrite
AV1105ZoneModule 2 - Room RH SetpointRoom relative humidity setpoint (zone 2)%Write
AV1106ZoneModule 2 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 2)%Write
AV1107ZoneModule 2 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 2)%Write
AV1108ZoneModule 2 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 2)%Write
AV1109ZoneModule 2 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 2)%Write
AV1110ZoneModule 2 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 2)%Write
AV1111ZoneModule 2 - VAV Extract Min. Air FlowMinimum extract airflow (zone 2)%Write
AV1112ZoneModule 2 - VAV Extract Max. Air FlowMaximum extract airflow (zone 2)%Write
AV1201ZoneModule 3 - Room Temperature SetpointRoom temperature setpoint (zone 3)°CWrite
AV1202ZoneModule 3 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 3)°CWrite
AV1203ZoneModule 3 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 3)°CWrite
AV1204ZoneModule 3 - Room CO2 SetpointRoom CO2 setpoint (zone 3)ppmWrite
AV1205ZoneModule 3 - Room RH SetpointRoom relative humidity setpoint (zone 3)%Write
AV1206ZoneModule 3 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 3)%Write
AV1207ZoneModule 3 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 3)%Write
AV1208ZoneModule 3 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 3)%Write
AV1209ZoneModule 3 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 3)%Write
AV1210ZoneModule 3 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 3)%Write
AV1211ZoneModule 3 - VAV Extract Min. Air FlowMinimum extract airflow (zone 3)%Write
AV1212ZoneModule 3 - VAV Extract Max. Air FlowMaximum extract airflow (zone 3)%Write
AV1301ZoneModule 4 - Room Temperature SetpointRoom temperature setpoint (zone 4)°CWrite
AV1302ZoneModule 4 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 4)°CWrite
AV1303ZoneModule 4 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 4)°CWrite
AV1304ZoneModule 4 - Room CO2 SetpointRoom CO2 setpoint (zone 4)ppmWrite
AV1305ZoneModule 4 - Room RH SetpointRoom relative humidity setpoint (zone 4)%Write
AV1306ZoneModule 4 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 4)%Write
AV1307ZoneModule 4 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 4)%Write
AV1308ZoneModule 4 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 4)%Write
AV1309ZoneModule 4 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 4)%Write
AV1310ZoneModule 4 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 4)%Write
AV1311ZoneModule 4 - VAV Extract Min. Air FlowMinimum extract airflow (zone 4)%Write
AV1312ZoneModule 4 - VAV Extract Max. Air FlowMaximum extract airflow (zone 4)%Write
AV1401ZoneModule 5 - Room Temperature SetpointRoom temperature setpoint (zone 5)°CWrite
AV1402ZoneModule 5 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 5)°CWrite
AV1403ZoneModule 5 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 5)°CWrite
AV1404ZoneModule 5 - Room CO2 SetpointRoom CO2 setpoint (zone 5)ppmWrite
AV1405ZoneModule 5 - Room RH SetpointRoom relative humidity setpoint (zone 5)%Write
AV1406ZoneModule 5 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 5)%Write
AV1407ZoneModule 5 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 5)%Write
AV1408ZoneModule 5 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 5)%Write
AV1409ZoneModule 5 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 5)%Write
AV1410ZoneModule 5 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 5)%Write
AV1411ZoneModule 5 - VAV Extract Min. Air FlowMinimum extract airflow (zone 5)%Write
AV1412ZoneModule 5 - VAV Extract Max. Air FlowMaximum extract airflow (zone 5)%Write
AV1501ZoneModule 6 - Room Temperature SetpointRoom temperature setpoint (zone 6)°CWrite
AV1502ZoneModule 6 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 6)°CWrite
AV1503ZoneModule 6 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 6)°CWrite
AV1504ZoneModule 6 - Room CO2 SetpointRoom CO2 setpoint (zone 6)ppmWrite
AV1505ZoneModule 6 - Room RH SetpointRoom relative humidity setpoint (zone 6)%Write
AV1506ZoneModule 6 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 6)%Write
AV1507ZoneModule 6 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 6)%Write
AV1508ZoneModule 6 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 6)%Write
AV1509ZoneModule 6 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 6)%Write
AV1510ZoneModule 6 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 6)%Write
AV1511ZoneModule 6 - VAV Extract Min. Air FlowMinimum extract airflow (zone 6)%Write
AV1512ZoneModule 6 - VAV Extract Max. Air FlowMaximum extract airflow (zone 6)%Write
AV1601ZoneModule 7 - Room Temperature SetpointRoom temperature setpoint (zone 7)°CWrite
AV1602ZoneModule 7 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 7)°CWrite
AV1603ZoneModule 7 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 7)°CWrite
AV1604ZoneModule 7 - Room CO2 SetpointRoom CO2 setpoint (zone 7)ppmWrite
AV1605ZoneModule 7 - Room RH SetpointRoom relative humidity setpoint (zone 7)%Write
AV1606ZoneModule 7 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 7)%Write
AV1607ZoneModule 7 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 7)%Write
AV1608ZoneModule 7 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 7)%Write
AV1609ZoneModule 7 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 7)%Write
AV1610ZoneModule 7 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 7)%Write
AV1611ZoneModule 7 - VAV Extract Min. Air FlowMinimum extract airflow (zone 7)%Write
AV1612ZoneModule 7 - VAV Extract Max. Air FlowMaximum extract airflow (zone 7)%Write
AV1701ZoneModule 8 - Room Temperature SetpointRoom temperature setpoint (zone 8)°CWrite
AV1702ZoneModule 8 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 8)°CWrite
AV1703ZoneModule 8 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 8)°CWrite
AV1704ZoneModule 8 - Room CO2 SetpointRoom CO2 setpoint (zone 8)ppmWrite
AV1705ZoneModule 8 - Room RH SetpointRoom relative humidity setpoint (zone 8)%Write
AV1706ZoneModule 8 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 8)%Write
AV1707ZoneModule 8 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 8)%Write
AV1708ZoneModule 8 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 8)%Write
AV1709ZoneModule 8 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 8)%Write
AV1710ZoneModule 8 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 8)%Write
AV1711ZoneModule 8 - VAV Extract Min. Air FlowMinimum extract airflow (zone 8)%Write
AV1712ZoneModule 8 - VAV Extract Max. Air FlowMaximum extract airflow (zone 8)%Write
AV1801ZoneModule 9 - Room Temperature SetpointRoom temperature setpoint (zone 9)°CWrite
AV1802ZoneModule 9 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 9)°CWrite
AV1803ZoneModule 9 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 9)°CWrite
AV1804ZoneModule 9 - Room CO2 SetpointRoom CO2 setpoint (zone 9)ppmWrite
AV1805ZoneModule 9 - Room RH SetpointRoom relative humidity setpoint (zone 9)%Write
AV1806ZoneModule 9 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 9)%Write
AV1807ZoneModule 9 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 9)%Write
AV1808ZoneModule 9 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 9)%Write
AV1809ZoneModule 9 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 9)%Write
AV1810ZoneModule 9 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 9)%Write
AV1811ZoneModule 9 - VAV Extract Min. Air FlowMinimum extract airflow (zone 9)%Write
AV1812ZoneModule 9 - VAV Extract Max. Air FlowMaximum extract airflow (zone 9)%Write
AV1901ZoneModule 10 - Room Temperature SetpointRoom temperature setpoint (zone 10)°CWrite
AV1902ZoneModule 10 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 10)°CWrite
AV1903ZoneModule 10 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 10)°CWrite
AV1904ZoneModule 10 - Room CO2 SetpointRoom CO2 setpoint (zone 10)ppmWrite
AV1905ZoneModule 10 - Room RH SetpointRoom relative humidity setpoint (zone 10)%Write
AV1906ZoneModule 10 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 10)%Write
AV1907ZoneModule 10 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 10)%Write
AV1908ZoneModule 10 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 10)%Write
AV1909ZoneModule 10 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 10)%Write
AV1910ZoneModule 10 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 10)%Write
AV1911ZoneModule 10 - VAV Extract Min. Air FlowMinimum extract airflow (zone 10)%Write
AV1912ZoneModule 10 - VAV Extract Max. Air FlowMaximum extract airflow (zone 10)%Write
AV2001ZoneModule 11 - Room Temperature SetpointRoom temperature setpoint (zone 11)°CWrite
AV2002ZoneModule 11 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 11)°CWrite
AV2003ZoneModule 11 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 11)°CWrite
AV2004ZoneModule 11 - Room CO2 SetpointRoom CO2 setpoint (zone 11)ppmWrite
AV2005ZoneModule 11 - Room RH SetpointRoom relative humidity setpoint (zone 11)%Write
AV2006ZoneModule 11 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 11)%Write
AV2007ZoneModule 11 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 11)%Write
AV2008ZoneModule 11 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 11)%Write
AV2009ZoneModule 11 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 11)%Write
AV2010ZoneModule 11 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 11)%Write
AV2011ZoneModule 11 - VAV Extract Min. Air FlowMinimum extract airflow (zone 11)%Write
AV2012ZoneModule 11 - VAV Extract Max. Air FlowMaximum extract airflow (zone 11)%Write
AV2101ZoneModule 12 - Room Temperature SetpointRoom temperature setpoint (zone 12)°CWrite
AV2102ZoneModule 12 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 12)°CWrite
AV2103ZoneModule 12 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 12)°CWrite
AV2104ZoneModule 12 - Room CO2 SetpointRoom CO2 setpoint (zone 12)ppmWrite
AV2105ZoneModule 12 - Room RH SetpointRoom relative humidity setpoint (zone 12)%Write
AV2106ZoneModule 12 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 12)%Write
AV2107ZoneModule 12 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 12)%Write
AV2108ZoneModule 12 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 12)%Write
AV2109ZoneModule 12 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 12)%Write
AV2110ZoneModule 12 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 12)%Write
AV2111ZoneModule 12 - VAV Extract Min. Air FlowMinimum extract airflow (zone 12)%Write
AV2112ZoneModule 12 - VAV Extract Max. Air FlowMaximum extract airflow (zone 12)%Write
AV2201ZoneModule 13 - Room Temperature SetpointRoom temperature setpoint (zone 13)°CWrite
AV2202ZoneModule 13 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 13)°CWrite
AV2203ZoneModule 13 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 13)°CWrite
AV2204ZoneModule 13 - Room CO2 SetpointRoom CO2 setpoint (zone 13)ppmWrite
AV2205ZoneModule 13 - Room RH SetpointRoom relative humidity setpoint (zone 13)%Write
AV2206ZoneModule 13 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 13)%Write
AV2207ZoneModule 13 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 13)%Write
AV2208ZoneModule 13 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 13)%Write
AV2209ZoneModule 13 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 13)%Write
AV2210ZoneModule 13 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 13)%Write
AV2211ZoneModule 13 - VAV Extract Min. Air FlowMinimum extract airflow (zone 13)%Write
AV2212ZoneModule 13 - VAV Extract Max. Air FlowMaximum extract airflow (zone 13)%Write
AV2301ZoneModule 14 - Room Temperature SetpointRoom temperature setpoint (zone 14)°CWrite
AV2302ZoneModule 14 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 14)°CWrite
AV2303ZoneModule 14 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 14)°CWrite
AV2304ZoneModule 14 - Room CO2 SetpointRoom CO2 setpoint (zone 14)ppmWrite
AV2305ZoneModule 14 - Room RH SetpointRoom relative humidity setpoint (zone 14)%Write
AV2306ZoneModule 14 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 14)%Write
AV2307ZoneModule 14 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 14)%Write
AV2308ZoneModule 14 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 14)%Write
AV2309ZoneModule 14 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 14)%Write
AV2310ZoneModule 14 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 14)%Write
AV2311ZoneModule 14 - VAV Extract Min. Air FlowMinimum extract airflow (zone 14)%Write
AV2312ZoneModule 14 - VAV Extract Max. Air FlowMaximum extract airflow (zone 14)%Write
AV2401ZoneModule 15 - Room Temperature SetpointRoom temperature setpoint (zone 15)°CWrite
AV2402ZoneModule 15 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 15)°CWrite
AV2403ZoneModule 15 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 15)°CWrite
AV2404ZoneModule 15 - Room CO2 SetpointRoom CO2 setpoint (zone 15)ppmWrite
AV2405ZoneModule 15 - Room RH SetpointRoom relative humidity setpoint (zone 15)%Write
AV2406ZoneModule 15 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 15)%Write
AV2407ZoneModule 15 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 15)%Write
AV2408ZoneModule 15 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 15)%Write
AV2409ZoneModule 15 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 15)%Write
AV2410ZoneModule 15 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 15)%Write
AV2411ZoneModule 15 - VAV Extract Min. Air FlowMinimum extract airflow (zone 15)%Write
AV2412ZoneModule 15 - VAV Extract Max. Air FlowMaximum extract airflow (zone 15)%Write
AV2501ZoneModule 16 - Room Temperature SetpointRoom temperature setpoint (zone 16)°CWrite
AV2502ZoneModule 16 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 16)°CWrite
AV2503ZoneModule 16 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 16)°CWrite
AV2504ZoneModule 16 - Room CO2 SetpointRoom CO2 setpoint (zone 16)ppmWrite
AV2505ZoneModule 16 - Room RH SetpointRoom relative humidity setpoint (zone 16)%Write
AV2506ZoneModule 16 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 16)%Write
AV2507ZoneModule 16 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 16)%Write
AV2508ZoneModule 16 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 16)%Write
AV2509ZoneModule 16 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 16)%Write
AV2510ZoneModule 16 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 16)%Write
AV2511ZoneModule 16 - VAV Extract Min. Air FlowMinimum extract airflow (zone 16)%Write
AV2512ZoneModule 16 - VAV Extract Max. Air FlowMaximum extract airflow (zone 16)%Write
AV2601ZoneModule 17 - Room Temperature SetpointRoom temperature setpoint (zone 17)°CWrite
AV2602ZoneModule 17 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 17)°CWrite
AV2603ZoneModule 17 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 17)°CWrite
AV2604ZoneModule 17 - Room CO2 SetpointRoom CO2 setpoint (zone 17)ppmWrite
AV2605ZoneModule 17 - Room RH SetpointRoom relative humidity setpoint (zone 17)%Write
AV2606ZoneModule 17 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 17)%Write
AV2607ZoneModule 17 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 17)%Write
AV2608ZoneModule 17 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 17)%Write
AV2609ZoneModule 17 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 17)%Write
AV2610ZoneModule 17 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 17)%Write
AV2611ZoneModule 17 - VAV Extract Min. Air FlowMinimum extract airflow (zone 17)%Write
AV2612ZoneModule 17 - VAV Extract Max. Air FlowMaximum extract airflow (zone 17)%Write
AV2701ZoneModule 18 - Room Temperature SetpointRoom temperature setpoint (zone 18)°CWrite
AV2702ZoneModule 18 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 18)°CWrite
AV2703ZoneModule 18 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 18)°CWrite
AV2704ZoneModule 18 - Room CO2 SetpointRoom CO2 setpoint (zone 18)ppmWrite
AV2705ZoneModule 18 - Room RH SetpointRoom relative humidity setpoint (zone 18)%Write
AV2706ZoneModule 18 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 18)%Write
AV2707ZoneModule 18 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 18)%Write
AV2708ZoneModule 18 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 18)%Write
AV2709ZoneModule 18 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 18)%Write
AV2710ZoneModule 18 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 18)%Write
AV2711ZoneModule 18 - VAV Extract Min. Air FlowMinimum extract airflow (zone 18)%Write
AV2712ZoneModule 18 - VAV Extract Max. Air FlowMaximum extract airflow (zone 18)%Write
AV2801ZoneModule 19 - Room Temperature SetpointRoom temperature setpoint (zone 19)°CWrite
AV2802ZoneModule 19 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 19)°CWrite
AV2803ZoneModule 19 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 19)°CWrite
AV2804ZoneModule 19 - Room CO2 SetpointRoom CO2 setpoint (zone 19)ppmWrite
AV2805ZoneModule 19 - Room RH SetpointRoom relative humidity setpoint (zone 19)%Write
AV2806ZoneModule 19 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 19)%Write
AV2807ZoneModule 19 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 19)%Write
AV2808ZoneModule 19 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 19)%Write
AV2809ZoneModule 19 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 19)%Write
AV2810ZoneModule 19 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 19)%Write
AV2811ZoneModule 19 - VAV Extract Min. Air FlowMinimum extract airflow (zone 19)%Write
AV2812ZoneModule 19 - VAV Extract Max. Air FlowMaximum extract airflow (zone 19)%Write
AV2901ZoneModule 20 - Room Temperature SetpointRoom temperature setpoint (zone 20)°CWrite
AV2902ZoneModule 20 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 20)°CWrite
AV2903ZoneModule 20 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 20)°CWrite
AV2904ZoneModule 20 - Room CO2 SetpointRoom CO2 setpoint (zone 20)ppmWrite
AV2905ZoneModule 20 - Room RH SetpointRoom relative humidity setpoint (zone 20)%Write
AV2906ZoneModule 20 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 20)%Write
AV2907ZoneModule 20 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 20)%Write
AV2908ZoneModule 20 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 20)%Write
AV2909ZoneModule 20 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 20)%Write
AV2910ZoneModule 20 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 20)%Write
AV2911ZoneModule 20 - VAV Extract Min. Air FlowMinimum extract airflow (zone 20)%Write
AV2912ZoneModule 20 - VAV Extract Max. Air FlowMaximum extract airflow (zone 20)%Write
AV3001ZoneModule 21 - Room Temperature SetpointRoom temperature setpoint (zone 21)°CWrite
AV3002ZoneModule 21 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 21)°CWrite
AV3003ZoneModule 21 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 21)°CWrite
AV3004ZoneModule 21 - Room CO2 SetpointRoom CO2 setpoint (zone 21)ppmWrite
AV3005ZoneModule 21 - Room RH SetpointRoom relative humidity setpoint (zone 21)%Write
AV3006ZoneModule 21 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 21)%Write
AV3007ZoneModule 21 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 21)%Write
AV3008ZoneModule 21 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 21)%Write
AV3009ZoneModule 21 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 21)%Write
AV3010ZoneModule 21 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 21)%Write
AV3011ZoneModule 21 - VAV Extract Min. Air FlowMinimum extract airflow (zone 21)%Write
AV3012ZoneModule 21 - VAV Extract Max. Air FlowMaximum extract airflow (zone 21)%Write
AV3101ZoneModule 22 - Room Temperature SetpointRoom temperature setpoint (zone 22)°CWrite
AV3102ZoneModule 22 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 22)°CWrite
AV3103ZoneModule 22 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 22)°CWrite
AV3104ZoneModule 22 - Room CO2 SetpointRoom CO2 setpoint (zone 22)ppmWrite
AV3105ZoneModule 22 - Room RH SetpointRoom relative humidity setpoint (zone 22)%Write
AV3106ZoneModule 22 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 22)%Write
AV3107ZoneModule 22 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 22)%Write
AV3108ZoneModule 22 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 22)%Write
AV3109ZoneModule 22 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 22)%Write
AV3110ZoneModule 22 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 22)%Write
AV3111ZoneModule 22 - VAV Extract Min. Air FlowMinimum extract airflow (zone 22)%Write
AV3112ZoneModule 22 - VAV Extract Max. Air FlowMaximum extract airflow (zone 22)%Write
AV3201ZoneModule 23 - Room Temperature SetpointRoom temperature setpoint (zone 23)°CWrite
AV3202ZoneModule 23 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 23)°CWrite
AV3203ZoneModule 23 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 23)°CWrite
AV3204ZoneModule 23 - Room CO2 SetpointRoom CO2 setpoint (zone 23)ppmWrite
AV3205ZoneModule 23 - Room RH SetpointRoom relative humidity setpoint (zone 23)%Write
AV3206ZoneModule 23 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 23)%Write
AV3207ZoneModule 23 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 23)%Write
AV3208ZoneModule 23 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 23)%Write
AV3209ZoneModule 23 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 23)%Write
AV3210ZoneModule 23 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 23)%Write
AV3211ZoneModule 23 - VAV Extract Min. Air FlowMinimum extract airflow (zone 23)%Write
AV3212ZoneModule 23 - VAV Extract Max. Air FlowMaximum extract airflow (zone 23)%Write
AV3301ZoneModule 24 - Room Temperature SetpointRoom temperature setpoint (zone 24)°CWrite
AV3302ZoneModule 24 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 24)°CWrite
AV3303ZoneModule 24 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 24)°CWrite
AV3304ZoneModule 24 - Room CO2 SetpointRoom CO2 setpoint (zone 24)ppmWrite
AV3305ZoneModule 24 - Room RH SetpointRoom relative humidity setpoint (zone 24)%Write
AV3306ZoneModule 24 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 24)%Write
AV3307ZoneModule 24 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 24)%Write
AV3308ZoneModule 24 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 24)%Write
AV3309ZoneModule 24 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 24)%Write
AV3310ZoneModule 24 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 24)%Write
AV3311ZoneModule 24 - VAV Extract Min. Air FlowMinimum extract airflow (zone 24)%Write
AV3312ZoneModule 24 - VAV Extract Max. Air FlowMaximum extract airflow (zone 24)%Write
AV3401ZoneModule 25 - Room Temperature SetpointRoom temperature setpoint (zone 25)°CWrite
AV3402ZoneModule 25 - Minimum Supply TemperatureMinimum supply temperature setpoint (zone 25)°CWrite
AV3403ZoneModule 25 - Maximum Supply TemperatureMaximum supply temperature setpoint (zone 25)°CWrite
AV3404ZoneModule 25 - Room CO2 SetpointRoom CO2 setpoint (zone 25)ppmWrite
AV3405ZoneModule 25 - Room RH SetpointRoom relative humidity setpoint (zone 25)%Write
AV3406ZoneModule 25 - VAV Supply PIR Min. Air FlowMinimum supply airflow when the zone is active (PIR) (zone 25)%Write
AV3407ZoneModule 25 - VAV Supply 1 Min. Air FlowMinimum airflow, supply VAV damper 1 (zone 25)%Write
AV3408ZoneModule 25 - VAV Supply 1 Max. Air FlowMaximum airflow, supply VAV damper 1 (zone 25)%Write
AV3409ZoneModule 25 - VAV Supply 2 Min. Air FlowMinimum airflow, supply VAV damper 2 (zone 25)%Write
AV3410ZoneModule 25 - VAV Supply 2 Max. Air FlowMaximum airflow, supply VAV damper 2 (zone 25)%Write
AV3411ZoneModule 25 - VAV Extract Min. Air FlowMinimum extract airflow (zone 25)%Write
AV3412ZoneModule 25 - VAV Extract Max. Air FlowMaximum extract airflow (zone 25)%Write
Object ID lookup: TROX X-AIRCONTROL Master zone controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)

How many BACnet points does the TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP) have?

This list has 824 BACnet objects: 401 analog inputs, 318 analog values, 103 binary inputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP) BACnet points are writable?

320 of the 824 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP) BACnet documentation?

The source is X-AIRCONTROL BACnet protocol (TROX Auranor Norge) (67501-06/15), revision 2015-06, published free by TROX at https://cdn.trox.de/b3191a6566564c17/7372a74fb43e/X-AIRCONTROL_BACnet_Protokol_GB.pdf.

What are the minimum BACnet points to integrate the TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)?

Start with AV 1001 ZoneModule 1 - Room Temperature Setpoint (Zone 1 room setpoint, 1/100 °C (+100 per zone)); AI 111 Zone Master Operation Mode (Master mode: normal, standby, night, fire); AI 104 AHU status (0 normal, 1 stop, 2 summer night cooling, 3 fire); AI 108 AHU Combined Outdoor Temp Value (Outdoor temperature, 1/100 °C); AI 1009 ZoneModule 1 - Room Temperature Actual Value (Zone 1 room temperature, 1/100 °C); AI 1002 ZoneModule 1 - VAV Supply 1 Flow (Zone 1 supply airflow, m³/h); AI 1000 ZoneModule 1 - Status (Zone 1 state: 0 normal, 1 B-alarm, 2 A-alarm); AI 109 Section Zone Master Alarm Status (Master alarm: 0 none, 1 B-alarm, 2 A-alarm); AI 110 Section Zone Module Alarm Status (Zone module alarm: 0 none, 1 B-alarm, 2 A-alarm).

How do I check these points on the real X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TROX BACnet points lists

Source: X-AIRCONTROL BACnet protocol (TROX Auranor Norge) · 67501-06/15 · rev. 2015-06. Object names, instances and units are reproduced as published; descriptions are our own.