- TITAN FCU403 fan coil controller (config FCU403 TRX)
Fan coil unit controller · BACnet points list
TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet points list
Updated 6 November 2026
This BACnet MS/TP technical reference, hosted by TROX, covers the Titan Products FCU4 fan coil controller with firmware 4.9 and the TROX configuration FCU403 TRX. It lists 138 objects: thermistor and universal inputs, 0-10 V and triac outputs, setpoint, deadband and PID settings, fan, occupancy and flush functions, and group master/slave objects.
This page lists 138 BACnet objects for the TROX TITAN FCU403 fan coil controller (config FCU403 TRX) — 114 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.
- Manufacturer
- TROX
- Model
- TITAN FCU403 fan coil controller (config FCU403 TRX)
- Equipment
- Fan coil unit controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 138 (114 writable)
- Transport
- BACnet MS/TP
- Firmware
- 4.9 (configuration FCU403 TRX)
- Also known as
- FCU403, FCU4, FCU403 TRX, Titan FCU4, FCU403 TP1193E, Graphical RDU V2
Reference only, provided as-is: verify against TROX’s current documentation and the live device before use. Not official TROX information. Terms of use.
BMS integration notes: TROX TITAN FCU403 fan coil controller (config FCU403 TRX)
Set the device instance, MAC address and baud rate on the RDU first. Then write AV 300 Set Point and MV 605 User Fan, write AV 700 Ext Temp if the BMS supplies the outdoor temperature, and read MV 602 Active Mode, AI 700 RDU Temp, the valve positions and BV 603 Fan Alarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 602 | Active Mode | Operating mode (Off, Normal, Eco1, Eco2, Occ OR...) | Write |
| MV 618 | Heat Cool Cycle | Heat, Off or Cool under manual control | Write |
| MV 605 | User Fan | Fan setting: Auto or speed 0-10 | Write |
| AV 300 | Set Point | Control setpoint, °C | Write |
| AI 700 | RDU Temp | Room display unit temperature | Read |
| MV 603 | Active Fan | Current fan setting | Read |
| AV 222 | Heating % | Heating valve position (TPC/PWM only) | Read |
| AV 232 | Cooling % | Cooling valve position (TPC/PWM only) | Read |
| BV 603 | Fan Alarm | Fan proving alarm | Read |
Enable & remote start
MV 602 Active Mode is writable depending on BV 600 Off Selector (off signal from the RDU or a digital input). MV 600 Off Mode sets what runs while the unit is Off.
Sensors & values from the BMS
AV 700 Ext Temp takes an external temperature written over BACnet or from an analog input. Inputs (AI/BI) can be overridden only by setting Out_Of_Service True first.
Network setup
- Device instance, MAC address (1-127) and baud rate (9600, 19200, 38400, 76800) are set on the RDU or programming tool by pressing all four buttons together.
- With the default Device Object ID 0000000 the unit works on the local MS/TP network but does not send I-Am; enter a valid ID (1-4194302).
- Group operation: one Group_Master sends setpoint, fan, occupancy and input values to Group_Slaves with the same group number (MSV 1000/1001).
Watch out for
- Write BV 0 Flash Store only when you want current values kept after a reboot.
- User Fan (MV 605) states depend on MSV 609 Fan Speeds and BV 602 Auto Fan Enable.
- In a group, slaves use the grouped input only when their local input is out of service.
TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 100 | S1 | Thermistor input S1 | Read | ||
| AI | 101 | S2 | Thermistor input S2 | Read | ||
| AI | 1 | In1A | The analog signal present on Input 1 | Read | ||
| AI | 2 | In2A | The analog signal present on Input 2 | Read | ||
| AI | 3 | In3A | The analog signal present on Input 3 | Read | ||
| AI | 4 | In4A | The analog signal present on Input 4 | Read | ||
| AI | 5 | In5A | The analog signal present on Input 5 | Read | ||
| AImin | 700 | RDU Temp | The RDU Temperature sensor | Read | ||
| AO | 1 | AO1 | 0-10V Output | V | Command | |
| AO | 2 | AO2 | 0-10V Output | V | Command | |
| AO | 3 | AO3 | 0-10V Output | V | Command | |
| AV | 1 | S1 Offset | Temperature offset to AI 1 (S1) | °C | Write | |
| AV | 2 | S2 Offset | Temperature offset to AI 2 (S2) | °C | Write | |
| AV | 101 | Cond Dly On | Delay before output control resumes after condensate alarm clears | s | Write | |
| AV | 102 | Cond Dly Off | Delay before output control stops on condensate alarm | s | Write | |
| AV | 103 | Heat Iso Dly | The delay between the end of heating and the isolation relay opening | s | Write | |
| AV | 104 | Cool Iso Dly | The delay between the end of cooling and the isolation relay opening | s | Write | |
| AV | 201 | R4 Delay Off | Delay between an off signal and the aux relay opening | s | Write | |
| AV | 220 | TPC Heat | The run time for the heating valve | s | Write | |
| AV | 221 | HValve min | Minimum PWM duty to pre-heat the heating valve | % | Write | |
| AVmin | 222 | Heating % | Current heating valve position (TPC or PWM only) | % | Read | |
| AV | 230 | TPC Cool | The run time for the cooling valve | s | Write | |
| AV | 231 | CValve min | Minimum PWM duty to pre-heat the cooling valve | % | Write | |
| AVmin | 232 | Cooling % | Current cooling valve position (TPC or PWM only) | % | Read | |
| AVmin | 300 | Set Point | Control set point | °C | Write | |
| AV | 301 | Default SP | The default set point used on power up or switch on | °C | Write | |
| AV | 302 | Min SP | Minimum user selectable setpoint | °C | Write | |
| AV | 303 | Max SP | Maximum user selectable setpoint | °C | Write | |
| AV | 304 | RSP Reset | The maximum reset to the setpoint | °C | Write | |
| AV | 305 | Active DB | Current deadband width around the setpoint | °C | Read | |
| AV | 306 | Default DB | Default deadband width around the setpoint | °C | Write | |
| AV | 307 | Eco1 DB | The width of the deadband around the setpoint during Eco1 mode | °C | Write | |
| AV | 308 | Eco2 DB | The width of the deadband around the setpoint during Eco2 mode | °C | Write | |
| AV | 309 | P Band Heat | The width of the proportional band for heating | °C | Write | |
| AV | 310 | P Band Cool | The width of the proportional band for cooling | °C | Write | |
| AV | 311 | Int Time | Integral time of the control loop | min | Write | |
| AV | 312 | Slew Time | The time taken for the output to slew from 0-100% | s | Write | |
| AV | 313 | Accuracy | The accuracy of the control loop calculation | % | Write | |
| AV | 314 | Flush Time | The period for opening the valves to enable flushing | s | Write | |
| AV | 315 | Auto Flush | Automatic system flush period | h | Write | |
| AV | 320 | Max heating | The maximum heating allowed | % | Write | |
| AV | 321 | Min heating | The minimum heating allowed | % | Write | |
| AV | 322 | Max cooling | The maximum cooling allowed | % | Write | |
| AV | 323 | Min cooling | The minimum cooling allowed | % | Write | |
| AV | 400 | High limit | Exhaust temperature at which heating shuts off completely | °C | Write | |
| AV | 401 | High limit PB | Distance from the high limit where heating modulation starts | °C | Write | |
| AV | 402 | Low limit | Exhaust temperature at which cooling shuts off completely | °C | Write | |
| AV | 403 | Low limit PB | Distance from the low limit where cooling modulation starts | °C | Write | |
| AV | 500 | High Temp SP | The temperature threshold for high limit protection | °C | Write | |
| AV | 501 | Low Temp SP | The temperature threshold for low limit protection | °C | Write | |
| AV | 600 | Fan Start Up | The fan will start at full speed if required for this time | s | Write | |
| AV | 601 | Fan Overrun | Delays fan off by this time | min | Write | |
| AV | 602 | Fan Delay Start | Delays fan start up on heating and/or cooling | min | Write | |
| AV | 603 | Occ Override | Time of occupancy override on a button press | min | Write | |
| AV | 604 | Occ OR Time | Time remaining for occupancy override | min | Write | |
| AV | 605 | Autofan Pb Heat | Proportional band for autofan heat | °C | Write | |
| AV | 606 | Offset Heat | Auto fan heat offset | °C | Write | |
| AV | 607 | Autofan Pb Cool | Proportional band for autofan cool | °C | Write | |
| AV | 608 | Offset Cool | Auto fan cool offset | °C | Write | |
| AV | 609 | Fan Slew Time | Autofan slew rate | s | Write | |
| AV | 610 | Fan Prove Dly | Delay before the fan prove input causes a fan alarm | s | Write | |
| AV | 700 | Ext Temp | External temperature, written via BACnet or an analog input | °C | Write | |
| AV | 701 | SP Display | The time that the setpoint will be displayed for | s | Write | |
| AV | 702 | Backlight Disp | Backlight on-time after the last button press | s | Write | |
| AV | 706 | Maint. Passcode | The password to enter the maintenance menu | Write | ||
| AV | 707 | Set Up Passcode | The password to enter the set-up menu | Write | ||
| AV | 708 | Heat O.R. % | The percentage of heating while in commissioning override mode | % | Write | |
| AV | 709 | Cool O.R. % | The percentage of cooling while in commissioning override mode | % | Write | |
| AV | 710 | RDU Offset | The offset to be applied to the RDU temperature | °C | Write | |
| AV | 800 | Upper V | Upper threshold for ‘On/Off Ctrl’ of the Aux relay when used | V | Write | |
| AV | 801 | Lower V | Lower threshold for ‘On/Off Ctrl’ of the Aux relay when used | V | Write | |
| AV | 802 | Ctrl Dly On | An optional delay for the activation of the ‘On/Off Ctrl’ | s | Write | |
| AV | 803 | Ctrl Dly Off | An optional delay for the deactivation of the ‘On/Off Ctrl’ | s | Write | |
| AV | 1000 | Update Period | The time between group updates | s | Write | |
| BI | 1 | In1D | Digital signal present on Input 1 | Read | 0=Inactive, 1=Active | |
| BI | 2 | In2D | Digital signal present on Input 2 | Read | 0=Inactive, 1=Active | |
| BI | 3 | In3D | Digital signal present on Input 3 | Read | 0=Inactive, 1=Active | |
| BI | 4 | In4D | Digital signal present on Input 4 | Read | 0=Inactive, 1=Active | |
| BI | 5 | In5D | Digital signal present on Input 5 | Read | 0=Inactive, 1=Active | |
| BI | 700 | Card Status | Whether the card is inserted into the Card RDU or not | Read | 0=Not Inserted, 1=Inserted | |
| BO | 1 | DO1 | 24V Triac output | Command | 0=Inactive, 1=Active | |
| BO | 2 | DO2 | 24V Triac output | Command | 0=Inactive, 1=Active | |
| BO | 3 | DO3 | 24V Triac output | Command | 0=Inactive, 1=Active | |
| BO | 4 | Aux Relay | Auxiliary Relay (12A 24VDC 50VAC) | Command | 0=Inactive, 1=Active | |
| BV | 0 | Flash Store | Set True to store current values to flash | Write | 0=FALSE, 1=TRUE | |
| BV | 1 | Build Fail | True if the primary configuration file failed to build | Read | 0=FALSE, 1=TRUE | |
| BV | 51 | VB1 | Binary software point 1, assignable to input functions | Write | 0=Inactive, 1=Active | |
| BV | 52 | VB2 | Binary software point 2, assignable to input functions | Write | 0=Inactive, 1=Active | |
| BV | 100 | Cond Stop Fan | Controls whether the fan should stop during condensate alarm | Write | 0=No, 1=Yes | |
| BV | 500 | Off Default SP | Reset setpoint to default when the unit is turned off | Write | 0=Disabled, 1=Enabled | |
| BV | 600 | Off Selector | Source of ‘Off’ signal may be a digital input or the RDU | Write | 0=RDU, 1=Digital | |
| BV | 602 | Auto Fan Enable | Enables selection of the Auto fan mode | Write | 0=No, 1=Yes | |
| BVmin | 603 | Fan Alarm | Is set to True if fan proving is in alarm | Read | 0=No, 1=Yes | |
| BV | 604 | Auto Fan Enable | Autofan control | Write | 0=No, 1=Yes | |
| BV | 700 | Adjustable SP | Permits user adjustment of the setpoint | Write | 0=No, 1=Yes | |
| BV | 701 | Temp Units | Units for temperature display | Write | 0=Deg F, 1=Deg C | |
| BV | 702 | Display Temp | Allow the user to see the current temperature or not | Write | 0=No, 1=Yes | |
| BV | 703 | Disp Ext Temp | Allow the user to see the external temperature or not | Write | 0=No, 1=Yes | |
| BV | 704 | Display Faults | Show Fault if the selected temperature sensor is unreliable | Write | 0=No, 1=Yes | |
| BV | 705 | Disp After Hrs | Displays ‘After Hours’ during occupancy timed override | Write | 0=No, 1=Yes | |
| BV | 706 | Flash After Hrs | Whether the ‘After Hours’ message is flashing or constant | Write | 0=No, 1=Yes | |
| BV | 707 | Commission Heat | Heating outputs in normal or commissioning override mode | Write | 0=No, 1=Yes | |
| BV | 708 | Commission Cool | Cooling outputs in normal or commissioning override mode | Write | 0=No, 1=Yes | |
| BV | 709 | Activate Flush | Calls for System Flush behaviour | Write | 0=Inactive, 1=Start | |
| BV | 800 | Polarity | Polarity of the ‘On/Off Ctrl’ of the aux relay | Write | 0=Normal, 1=Reverse | |
| BV | 1000 | Transmit All | Copy the master's set-up to all group slaves | Write | 0=FALSE, 1=TRUE | |
| MO | 1 | 3-Stage Relay | Group of 3 mutually exclusive relays (12A 24VDC 50VAC) | Command | 0 / 1 / 2 / 3 | |
| MV | 0 | MAC | MAC address of this FCU | Read | 0-127 | |
| MV | 300 | System Flush | Determines which outputs will be flushed during System flush behaviour | Write | Heat / Cool / Both | |
| MV | 301 | SP Bias | The position of the SP in the heat/cool dead band | Write | Heat / Cool / Both | |
| MV | 302 | Fan Sim1 | Fan status 1 | Write | No Flt / Flt / Pulse Flt S / Pulse Flt L | |
| MV | 303 | Fan Sim2 | Fan status 2 | Write | No Flt / Flt / Pulse Flt S / Pulse Flt L | |
| MV | 600 | Off Mode | Mode that runs when the unit is 'Off' | Write | Off / Low Prot / High Prot / Both Prot / Eco1 / Eco2 | |
| MV | 601 | Unocc Mode | The operating mode of the FCU when unoccupied | Write | Normal / Eco1 / Eco2 / Off | |
| MVmin | 602 | Active Mode | The current operating mode of the FCU | Write | Off / Normal / Low Prot / High Prot / Window / Eco1 / Eco2 / Occ OR | |
| MVmin | 603 | Active Fan | The current fan setting | Read | Auto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 | |
| MV | 604 | Default Fan | The default fan setting | Write | Auto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 | |
| MVmin | 605 | User Fan | The current user fan setting | Write | Auto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 | |
| MV | 606 | ECO1 Fan | The fan setting to be used during ECO1 | Write | Auto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 | |
| MV | 607 | ECO2 Fan | The fan setting to be used during ECO2 | Write | Auto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 | |
| MV | 609 | Fan Speeds | The number of fan speeds under manual control | Write | 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 | |
| MV | 610 | Fan Max Man | The voltage required for maximum fan speed under manual control | Write | 0-10 in 0.1 steps | |
| MV | 611 | Fan Min Max | The voltage required for minimum fan speed under manual control | Write | 0-10 in 0.1 steps | |
| MV | 612 | Fan Max Auto C | The maximum fan voltage under auto control during a cooling cycle | Write | 0-10 in 0.1 steps | |
| MV | 613 | Fan Min Auto C | The minimum fan voltage under auto control during a cooling cycle | Write | 0-10 in 0.1 steps | |
| MV | 614 | Fan Max Auto H | The maximum fan voltage under auto control during a heating cycle | Write | 0-10 in 0.1 steps | |
| MV | 615 | Fan Min Auto H | The minimum fan voltage under auto control during a heating cycle | Write | 0-10 in 0.1 steps | |
| MVmin | 618 | Heat Cool Cycle | Whether the unit is in Heat, Cool or Off when under manual | Write | Heat / Off / Cool | |
| MV | 619 | Auto Inc Off | Fan runs at minimum in the deadband if No | Write | Yes/No | |
| MV | 620 | Heat Cool Default | Revert to Off or last state on entering occupancy | Write | Off / Last | |
| MV | 621 | Fan Start Mode | Determines if start delay is applied to Heat/Cool cycles | Write | None/Heat/Cool/Both | |
| MV | 700 | Fan Display | The type of indication used to display the current fan | Write | Numbers / Text / Graphics | |
| MV | 1000 | Group Number | The group number (1-64) | Write | 1-64 | |
| MV | 1001 | Group Type | The group type of this device | Write | None / Slave / Master | |
| MV | 1002 | Full Update | When the master sends a full update to the slaves | Write | Never / Reboot / Once | |
| NC | 1 | NC1 | Notification class with 1 configurable recipient | Read | ||
| NC | 2 | NC2 | Notification class with 1 configurable recipient | Read | ||
| FILE | 0 | File | Backup and Restore file | Read |
No points match these filters.
Object ID lookup: TROX TITAN FCU403 fan coil controller point IDs by name
AI100S1AI101S2AI1In1AAI2In2AAI3In3AAI4In4AAI5In5AAI700RDU TempAO1AO1AO2AO2AO3AO3AV1S1 OffsetAV2S2 OffsetAV101Cond Dly OnAV102Cond Dly OffAV103Heat Iso DlyAV104Cool Iso DlyAV201R4 Delay OffAV220TPC HeatAV221HValve minAV222Heating %AV230TPC CoolAV231CValve minAV232Cooling %AV300Set PointAV301Default SPAV302Min SPAV303Max SPAV304RSP ResetAV305Active DBAV306Default DBAV307Eco1 DBAV308Eco2 DBAV309P Band HeatAV310P Band CoolAV311Int TimeAV312Slew TimeAV313AccuracyAV314Flush TimeAV315Auto FlushAV320Max heatingAV321Min heatingAV322Max coolingAV323Min coolingAV400High limitAV401High limit PBAV402Low limitAV403Low limit PBAV500High Temp SPAV501Low Temp SPAV600Fan Start UpAV601Fan OverrunAV602Fan Delay StartAV603Occ OverrideAV604Occ OR TimeAV605Autofan Pb HeatAV606Offset HeatAV607Autofan Pb CoolAV608Offset CoolAV609Fan Slew TimeAV610Fan Prove DlyAV700Ext TempAV701SP DisplayAV702Backlight DispAV706Maint. PasscodeAV707Set Up PasscodeAV708Heat O.R. %AV709Cool O.R. %AV710RDU OffsetAV800Upper VAV801Lower VAV802Ctrl Dly OnAV803Ctrl Dly OffAV1000Update PeriodBI1In1DBI2In2DBI3In3DBI4In4DBI5In5DBI700Card StatusBO1DO1BO2DO2BO3DO3BO4Aux RelayBV0Flash StoreBV1Build FailBV51VB1BV52VB2BV100Cond Stop FanBV500Off Default SPBV600Off SelectorBV602Auto Fan EnableBV603Fan AlarmBV604Auto Fan EnableBV700Adjustable SPBV701Temp UnitsBV702Display TempBV703Disp Ext TempBV704Display FaultsBV705Disp After HrsBV706Flash After HrsBV707Commission HeatBV708Commission CoolBV709Activate FlushBV800PolarityBV1000Transmit AllMO13-Stage RelayMV0MACMV300System FlushMV301SP BiasMV302Fan Sim1MV303Fan Sim2MV600Off ModeMV601Unocc ModeMV602Active ModeMV603Active FanMV604Default FanMV605User FanMV606ECO1 FanMV607ECO2 FanMV609Fan SpeedsMV610Fan Max ManMV611Fan Min MaxMV612Fan Max Auto CMV613Fan Min Auto CMV614Fan Max Auto HMV615Fan Min Auto HMV618Heat Cool CycleMV619Auto Inc OffMV620Heat Cool DefaultMV621Fan Start ModeMV700Fan DisplayMV1000Group NumberMV1001Group TypeMV1002Full UpdateNC1NC1NC2NC2FILE0File
Integration notes
- The controller is made by Titan Products Ltd (PICS vendor name); TROX hosts this document for its FCU403 TRX configuration.
- Objects marked *1 in the document only exist with certain configurations; AV 220/221/222 and 230/231/232 change name with the valve type (TPC or PWM, heat, cool or combined).
- Inputs (AI/BI) are writable only when Out_Of_Service is True, so they are listed as read-only here.
- Outputs (AO/BO/MO) can be written above the controller priority 15 and are listed as commandable.
- AV 608 is named "Offset Cool" in the function table and "Offset Heat" in the range table; the function-table name is used.
- Analog input units and ranges depend on the input profile chosen in the engineer menu, so none are given.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TITAN FCU403 fan coil controller (config FCU403 TRX) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the TROX TITAN FCU403 fan coil controller (config FCU403 TRX)
How many BACnet points does the TROX TITAN FCU403 fan coil controller (config FCU403 TRX) have?
This list has 138 BACnet objects: 8 analog inputs, 3 analog outputs, 63 analog values, 6 binary inputs, 4 binary outputs, 22 binary values, 1 file, 1 multi-state output, 2 notification classs, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet points are writable?
114 of the 138 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet documentation?
The source is TITAN FCU403 (Firmware v4.9, Config. FCU403 TRX) / Graphical RDU (V2) - BACnet Technical Reference, revision 2020-02, published free by TROX at https://cdn.trox.de/b0d9ce11f7cbaedf/b57cbc9c9289/BACnet-Manual--Firmware-4.9-FCU403-TRX--02-2020.pdf.
What are the minimum BACnet points to integrate the TROX TITAN FCU403 fan coil controller (config FCU403 TRX)?
Start with MV 602 Active Mode (Operating mode (Off, Normal, Eco1, Eco2, Occ OR...)); MV 618 Heat Cool Cycle (Heat, Off or Cool under manual control); MV 605 User Fan (Fan setting: Auto or speed 0-10); AV 300 Set Point (Control setpoint, °C); AI 700 RDU Temp (Room display unit temperature); MV 603 Active Fan (Current fan setting); AV 222 Heating % (Heating valve position (TPC/PWM only)); AV 232 Cooling % (Cooling valve position (TPC/PWM only)); BV 603 Fan Alarm (Fan proving alarm).
How do I enable BMS control of the TROX TITAN FCU403 fan coil controller (config FCU403 TRX)?
MV 602 Active Mode is writable depending on BV 600 Off Selector (off signal from the RDU or a digital input). MV 600 Off Mode sets what runs while the unit is Off.
Can the BMS supply sensor values to the TROX TITAN FCU403 fan coil controller (config FCU403 TRX)?
AV 700 Ext Temp takes an external temperature written over BACnet or from an analog input. Inputs (AI/BI) can be overridden only by setting Out_Of_Service True first.
How do I check these points on the real TITAN FCU403 fan coil controller (config FCU403 TRX)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More TROX BACnet points lists
- VAV box controller (compact, built-in damper drive)
TROX BM0-D8 VAV control component (BACnet MS/TP)
TROX VAV terminal units fitted with the BM0-D8 compact control component (LMV/NMV-D3-M/B-X TR actuators).
Also known as: BM0-D8, BM0, LMV-D3-M/B-X TR, NMV-D3-M/B-X TR, ..MV-D3-M/B-X, ..MV-D3-M/B-FX, TROX VAV Compact - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM with room management function (RMF) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM with room management function (RMF), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code TAM-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM with room management function (RMF) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM with room management function (RMF), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code TAM-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM without room management function (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM without room management function, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code TAM - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM without room management function (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM without room management function, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code TAM - Laboratory VAV airflow controller
TROX EASYLAB TCU3 all EASYLAB applications (combined list) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as all EASYLAB applications (combined list), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code ELAB - Laboratory VAV airflow controller
TROX EASYLAB TCU3 all EASYLAB applications (combined list) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as all EASYLAB applications (combined list), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code ELAB - Laboratory VAV controller (fume cupboard)
TROX EASYLAB TCU3 fume cupboard controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as fume cupboard controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code FH - Laboratory VAV controller (fume cupboard)
TROX EASYLAB TCU3 fume cupboard controller (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as fume cupboard controller, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code FH - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller with room management function (RMF) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller with room management function (RMF), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code LAB-RMF / CLR-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller with room management function (RMF) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller with room management function (RMF), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code LAB-RMF / CLR-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller without room management function (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller without room management function, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code LAB / CLR - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller without room management function (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller without room management function, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code LAB / CLR - Laboratory VAV airflow controller
TROX EASYLAB TCU3 single extract or supply air controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as single extract or supply air controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code EC / SC - Laboratory VAV airflow controller
TROX EASYLAB TCU3 single extract or supply air controller (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as single extract or supply air controller, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code EC / SC - Decentralised ventilation unit / zone controller
TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)
TROX FSL decentralised (single-room) ventilation units with the FSL-CONTROL II / X-AIRCONTROL controller and the EM-BAC-MOD-01 XAC BACnet MS/TP card.
Also known as: FSL-CONTROL II, X-AIRCONTROL, EM-BAC-MOD-01 XAC, A00000020207, Schoolair, FSL decentralised ventilation - Decentralised ventilation unit controller
TROX FSL-CONTROL III decentralised ventilation controller (software 8.0)
TROX FSL decentralised (single-room) ventilation units with the FSL-CONTROL III controller, software version 8.0.
Also known as: FSL-CONTROL III, FSL-C-III, Schoolair, FSL decentralised ventilation, M172 - VAV room airflow controller
TROX UNIVERSAL all TROX UNIVERSAL applications (combined list) (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as all TROX UNIVERSAL applications (combined list), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code TU* - VAV room airflow controller
TROX UNIVERSAL all TROX UNIVERSAL applications (combined list) (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as all TROX UNIVERSAL applications (combined list), fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code TU* - VAV room / duct pressure controller
TROX UNIVERSAL duct pressure controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as duct pressure controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PDS / PDE - VAV room airflow controller
TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code RS / RE - VAV room airflow controller
TROX UNIVERSAL room airflow controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code RS / RE - VAV room airflow controller
TROX UNIVERSAL room airflow controller, master (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, master, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code RS/M / RE/M - VAV room airflow controller
TROX UNIVERSAL room airflow controller, master (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, master, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code RS/M / RE/M - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code PRS / PRE / PDS / PDE - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller, master (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, master, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code PRS/M / PRE/M / PDS/M / PDE/M, TROX UNIVERSAL PD master - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller, master (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, master, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PRS/M / PRE/M / PDS/M / PDE/M, TROX UNIVERSAL PD master - VAV room / duct pressure controller
TROX UNIVERSAL room pressure controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room pressure controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PRS / PRE - VAV / static pressure controller
TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)
TROX UNIVERSAL static BUPNF controllers (VRU-D3/M1/M1R-BAC control electronics) for airflow, duct pressure and room pressure control.
Also known as: BUPNF, TROX UNIVERSAL static, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-D3-M/B TR, VRU-M1-M/B TR, VRU-M1R-M/B TR - Fire and smoke damper control module
TROX TROXNETCOM MB-BAC-WA1/2 fire damper module (BACnet MS/TP)
TROX TROXNETCOM MB-BAC-WA1/2 modules that drive and monitor up to 2 fire or smoke extract dampers (motorised or limit-switch only).
Also known as: MB-BAC-WA1/2, MB-BAC-WA1B3, TROXNETCOM, MB-BAC-WA1-2 - Fire and smoke damper control module
TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)
TROX TROXNETCOM MB-BAC-WA1/4 modules that drive and monitor up to 4 fire or smoke extract dampers (motorised or limit-switch only).
Also known as: MB-BAC-WA1/4, TROXNETCOM, MB-BAC-WA1-4 - VAV zone controller (master for up to 25 zone modules)
TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)
TROX Auranor X-AIRCONTROL VAV zone control systems: one Master with up to 25 Zone Modules, linked to an AHU.
Also known as: X-AIRCONTROL, X-AIRCONTROL Master, TROX Auranor X-AIRCONTROL, 67501-06/15, X-AIRCONTROL ZoneModule - Air handling unit controller
TROX X-CUBE Control BACnet data point list
TROX X-CUBE central air handling units with the factory X-CUBE Control system.
Also known as: X-CUBE, TROX X-CUBE, X-CUBE Control, BACnet DPL, BACnet EDE XCUBE - VAV box controller (compact, built-in damper drive)
TROX XDMB0 compact VAV control component (TVE, BACnet MS/TP)
TROX TVE and TVE-Q VAV terminal units fitted with the XDMB0 compact control component.
Also known as: XDMB0, TVE XDMB0, TVE-Q, Compact XDMB0
Source: TITAN FCU403 (Firmware v4.9, Config. FCU403 TRX) / Graphical RDU (V2) - BACnet Technical Reference · rev. 2020-02. Object names, instances and units are reproduced as published; descriptions are our own.