Fan coil unit controller · BACnet points list

TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet points list

Updated 6 November 2026

Short answer

This BACnet MS/TP technical reference, hosted by TROX, covers the Titan Products FCU4 fan coil controller with firmware 4.9 and the TROX configuration FCU403 TRX. It lists 138 objects: thermistor and universal inputs, 0-10 V and triac outputs, setpoint, deadband and PID settings, fan, occupancy and flush functions, and group master/slave objects.

This page lists 138 BACnet objects for the TROX TITAN FCU403 fan coil controller (config FCU403 TRX) — 114 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.

Manufacturer
TROX
Model
TITAN FCU403 fan coil controller (config FCU403 TRX)
Equipment
Fan coil unit controller
Equipment type
VAV boxes & fan coils
BACnet objects
138 (114 writable)
Transport
BACnet MS/TP
Firmware
4.9 (configuration FCU403 TRX)
Also known as
FCU403, FCU4, FCU403 TRX, Titan FCU4, FCU403 TP1193E, Graphical RDU V2
Source document
TITAN FCU403 (Firmware v4.9, Config. FCU403 TRX) / Graphical RDU (V2) - BACnet Technical Reference · rev. 2020-02
Download CSV 138 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TROX’s current documentation and the live device before use. Not official TROX information. Terms of use.

BMS integration notes: TROX TITAN FCU403 fan coil controller (config FCU403 TRX)

Integration in brief

Set the device instance, MAC address and baud rate on the RDU first. Then write AV 300 Set Point and MV 605 User Fan, write AV 700 Ext Temp if the BMS supplies the outdoor temperature, and read MV 602 Active Mode, AI 700 RDU Temp, the valve positions and BV 603 Fan Alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 602Active ModeOperating mode (Off, Normal, Eco1, Eco2, Occ OR...)Write
MV 618Heat Cool CycleHeat, Off or Cool under manual controlWrite
MV 605User FanFan setting: Auto or speed 0-10Write
AV 300Set PointControl setpoint, °CWrite
AI 700RDU TempRoom display unit temperatureRead
MV 603Active FanCurrent fan settingRead
AV 222Heating %Heating valve position (TPC/PWM only)Read
AV 232Cooling %Cooling valve position (TPC/PWM only)Read
BV 603Fan AlarmFan proving alarmRead

Enable & remote start

MV 602 Active Mode is writable depending on BV 600 Off Selector (off signal from the RDU or a digital input). MV 600 Off Mode sets what runs while the unit is Off.

Sensors & values from the BMS

AV 700 Ext Temp takes an external temperature written over BACnet or from an analog input. Inputs (AI/BI) can be overridden only by setting Out_Of_Service True first.

Network setup

Watch out for

TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

138 of 138 shown
Type
Access
Show
TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet Points List
DescriptionStates
AI100S1Thermistor input S1Read
AI101S2Thermistor input S2Read
AI1In1AThe analog signal present on Input 1Read
AI2In2AThe analog signal present on Input 2Read
AI3In3AThe analog signal present on Input 3Read
AI4In4AThe analog signal present on Input 4Read
AI5In5AThe analog signal present on Input 5Read
AImin700RDU TempThe RDU Temperature sensorRead
AO1AO10-10V OutputVCommand
AO2AO20-10V OutputVCommand
AO3AO30-10V OutputVCommand
AV1S1 OffsetTemperature offset to AI 1 (S1)°CWrite
AV2S2 OffsetTemperature offset to AI 2 (S2)°CWrite
AV101Cond Dly OnDelay before output control resumes after condensate alarm clearssWrite
AV102Cond Dly OffDelay before output control stops on condensate alarmsWrite
AV103Heat Iso DlyThe delay between the end of heating and the isolation relay openingsWrite
AV104Cool Iso DlyThe delay between the end of cooling and the isolation relay openingsWrite
AV201R4 Delay OffDelay between an off signal and the aux relay openingsWrite
AV220TPC HeatThe run time for the heating valvesWrite
AV221HValve minMinimum PWM duty to pre-heat the heating valve%Write
AVmin222Heating %Current heating valve position (TPC or PWM only)%Read
AV230TPC CoolThe run time for the cooling valvesWrite
AV231CValve minMinimum PWM duty to pre-heat the cooling valve%Write
AVmin232Cooling %Current cooling valve position (TPC or PWM only)%Read
AVmin300Set PointControl set point°CWrite
AV301Default SPThe default set point used on power up or switch on°CWrite
AV302Min SPMinimum user selectable setpoint°CWrite
AV303Max SPMaximum user selectable setpoint°CWrite
AV304RSP ResetThe maximum reset to the setpoint°CWrite
AV305Active DBCurrent deadband width around the setpoint°CRead
AV306Default DBDefault deadband width around the setpoint°CWrite
AV307Eco1 DBThe width of the deadband around the setpoint during Eco1 mode°CWrite
AV308Eco2 DBThe width of the deadband around the setpoint during Eco2 mode°CWrite
AV309P Band HeatThe width of the proportional band for heating°CWrite
AV310P Band CoolThe width of the proportional band for cooling°CWrite
AV311Int TimeIntegral time of the control loopminWrite
AV312Slew TimeThe time taken for the output to slew from 0-100%sWrite
AV313AccuracyThe accuracy of the control loop calculation%Write
AV314Flush TimeThe period for opening the valves to enable flushingsWrite
AV315Auto FlushAutomatic system flush periodhWrite
AV320Max heatingThe maximum heating allowed%Write
AV321Min heatingThe minimum heating allowed%Write
AV322Max coolingThe maximum cooling allowed%Write
AV323Min coolingThe minimum cooling allowed%Write
AV400High limitExhaust temperature at which heating shuts off completely°CWrite
AV401High limit PBDistance from the high limit where heating modulation starts°CWrite
AV402Low limitExhaust temperature at which cooling shuts off completely°CWrite
AV403Low limit PBDistance from the low limit where cooling modulation starts°CWrite
AV500High Temp SPThe temperature threshold for high limit protection°CWrite
AV501Low Temp SPThe temperature threshold for low limit protection°CWrite
AV600Fan Start UpThe fan will start at full speed if required for this timesWrite
AV601Fan OverrunDelays fan off by this timeminWrite
AV602Fan Delay StartDelays fan start up on heating and/or coolingminWrite
AV603Occ OverrideTime of occupancy override on a button pressminWrite
AV604Occ OR TimeTime remaining for occupancy overrideminWrite
AV605Autofan Pb HeatProportional band for autofan heat°CWrite
AV606Offset HeatAuto fan heat offset°CWrite
AV607Autofan Pb CoolProportional band for autofan cool°CWrite
AV608Offset CoolAuto fan cool offset°CWrite
AV609Fan Slew TimeAutofan slew ratesWrite
AV610Fan Prove DlyDelay before the fan prove input causes a fan alarmsWrite
AV700Ext TempExternal temperature, written via BACnet or an analog input°CWrite
AV701SP DisplayThe time that the setpoint will be displayed forsWrite
AV702Backlight DispBacklight on-time after the last button presssWrite
AV706Maint. PasscodeThe password to enter the maintenance menuWrite
AV707Set Up PasscodeThe password to enter the set-up menuWrite
AV708Heat O.R. %The percentage of heating while in commissioning override mode%Write
AV709Cool O.R. %The percentage of cooling while in commissioning override mode%Write
AV710RDU OffsetThe offset to be applied to the RDU temperature°CWrite
AV800Upper VUpper threshold for ‘On/Off Ctrl’ of the Aux relay when usedVWrite
AV801Lower VLower threshold for ‘On/Off Ctrl’ of the Aux relay when usedVWrite
AV802Ctrl Dly OnAn optional delay for the activation of the ‘On/Off Ctrl’sWrite
AV803Ctrl Dly OffAn optional delay for the deactivation of the ‘On/Off Ctrl’sWrite
AV1000Update PeriodThe time between group updatessWrite
BI1In1DDigital signal present on Input 1Read0=Inactive, 1=Active
BI2In2DDigital signal present on Input 2Read0=Inactive, 1=Active
BI3In3DDigital signal present on Input 3Read0=Inactive, 1=Active
BI4In4DDigital signal present on Input 4Read0=Inactive, 1=Active
BI5In5DDigital signal present on Input 5Read0=Inactive, 1=Active
BI700Card StatusWhether the card is inserted into the Card RDU or notRead0=Not Inserted, 1=Inserted
BO1DO124V Triac outputCommand0=Inactive, 1=Active
BO2DO224V Triac outputCommand0=Inactive, 1=Active
BO3DO324V Triac outputCommand0=Inactive, 1=Active
BO4Aux RelayAuxiliary Relay (12A 24VDC 50VAC)Command0=Inactive, 1=Active
BV0Flash StoreSet True to store current values to flashWrite0=FALSE, 1=TRUE
BV1Build FailTrue if the primary configuration file failed to buildRead0=FALSE, 1=TRUE
BV51VB1Binary software point 1, assignable to input functionsWrite0=Inactive, 1=Active
BV52VB2Binary software point 2, assignable to input functionsWrite0=Inactive, 1=Active
BV100Cond Stop FanControls whether the fan should stop during condensate alarmWrite0=No, 1=Yes
BV500Off Default SPReset setpoint to default when the unit is turned offWrite0=Disabled, 1=Enabled
BV600Off SelectorSource of ‘Off’ signal may be a digital input or the RDUWrite0=RDU, 1=Digital
BV602Auto Fan EnableEnables selection of the Auto fan modeWrite0=No, 1=Yes
BVmin603Fan AlarmIs set to True if fan proving is in alarmRead0=No, 1=Yes
BV604Auto Fan EnableAutofan controlWrite0=No, 1=Yes
BV700Adjustable SPPermits user adjustment of the setpointWrite0=No, 1=Yes
BV701Temp UnitsUnits for temperature displayWrite0=Deg F, 1=Deg C
BV702Display TempAllow the user to see the current temperature or notWrite0=No, 1=Yes
BV703Disp Ext TempAllow the user to see the external temperature or notWrite0=No, 1=Yes
BV704Display FaultsShow Fault if the selected temperature sensor is unreliableWrite0=No, 1=Yes
BV705Disp After HrsDisplays ‘After Hours’ during occupancy timed overrideWrite0=No, 1=Yes
BV706Flash After HrsWhether the ‘After Hours’ message is flashing or constantWrite0=No, 1=Yes
BV707Commission HeatHeating outputs in normal or commissioning override modeWrite0=No, 1=Yes
BV708Commission CoolCooling outputs in normal or commissioning override modeWrite0=No, 1=Yes
BV709Activate FlushCalls for System Flush behaviourWrite0=Inactive, 1=Start
BV800PolarityPolarity of the ‘On/Off Ctrl’ of the aux relayWrite0=Normal, 1=Reverse
BV1000Transmit AllCopy the master's set-up to all group slavesWrite0=FALSE, 1=TRUE
MO13-Stage RelayGroup of 3 mutually exclusive relays (12A 24VDC 50VAC)Command0 / 1 / 2 / 3
MV0MACMAC address of this FCURead0-127
MV300System FlushDetermines which outputs will be flushed during System flush behaviourWriteHeat / Cool / Both
MV301SP BiasThe position of the SP in the heat/cool dead bandWriteHeat / Cool / Both
MV302Fan Sim1Fan status 1WriteNo Flt / Flt / Pulse Flt S / Pulse Flt L
MV303Fan Sim2Fan status 2WriteNo Flt / Flt / Pulse Flt S / Pulse Flt L
MV600Off ModeMode that runs when the unit is 'Off'WriteOff / Low Prot / High Prot / Both Prot / Eco1 / Eco2
MV601Unocc ModeThe operating mode of the FCU when unoccupiedWriteNormal / Eco1 / Eco2 / Off
MVmin602Active ModeThe current operating mode of the FCUWriteOff / Normal / Low Prot / High Prot / Window / Eco1 / Eco2 / Occ OR
MVmin603Active FanThe current fan settingReadAuto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10
MV604Default FanThe default fan settingWriteAuto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10
MVmin605User FanThe current user fan settingWriteAuto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10
MV606ECO1 FanThe fan setting to be used during ECO1WriteAuto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10
MV607ECO2 FanThe fan setting to be used during ECO2WriteAuto / 0 / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10
MV609Fan SpeedsThe number of fan speeds under manual controlWrite1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10
MV610Fan Max ManThe voltage required for maximum fan speed under manual controlWrite0-10 in 0.1 steps
MV611Fan Min MaxThe voltage required for minimum fan speed under manual controlWrite0-10 in 0.1 steps
MV612Fan Max Auto CThe maximum fan voltage under auto control during a cooling cycleWrite0-10 in 0.1 steps
MV613Fan Min Auto CThe minimum fan voltage under auto control during a cooling cycleWrite0-10 in 0.1 steps
MV614Fan Max Auto HThe maximum fan voltage under auto control during a heating cycleWrite0-10 in 0.1 steps
MV615Fan Min Auto HThe minimum fan voltage under auto control during a heating cycleWrite0-10 in 0.1 steps
MVmin618Heat Cool CycleWhether the unit is in Heat, Cool or Off when under manualWriteHeat / Off / Cool
MV619Auto Inc OffFan runs at minimum in the deadband if NoWriteYes/No
MV620Heat Cool DefaultRevert to Off or last state on entering occupancyWriteOff / Last
MV621Fan Start ModeDetermines if start delay is applied to Heat/Cool cyclesWriteNone/Heat/Cool/Both
MV700Fan DisplayThe type of indication used to display the current fanWriteNumbers / Text / Graphics
MV1000Group NumberThe group number (1-64)Write1-64
MV1001Group TypeThe group type of this deviceWriteNone / Slave / Master
MV1002Full UpdateWhen the master sends a full update to the slavesWriteNever / Reboot / Once
NC1NC1Notification class with 1 configurable recipientRead
NC2NC2Notification class with 1 configurable recipientRead
FILE0FileBackup and Restore fileRead
Object ID lookup: TROX TITAN FCU403 fan coil controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TITAN FCU403 fan coil controller (config FCU403 TRX) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TROX TITAN FCU403 fan coil controller (config FCU403 TRX)

How many BACnet points does the TROX TITAN FCU403 fan coil controller (config FCU403 TRX) have?

This list has 138 BACnet objects: 8 analog inputs, 3 analog outputs, 63 analog values, 6 binary inputs, 4 binary outputs, 22 binary values, 1 file, 1 multi-state output, 2 notification classs, 28 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet points are writable?

114 of the 138 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TROX TITAN FCU403 fan coil controller (config FCU403 TRX) BACnet documentation?

The source is TITAN FCU403 (Firmware v4.9, Config. FCU403 TRX) / Graphical RDU (V2) - BACnet Technical Reference, revision 2020-02, published free by TROX at https://cdn.trox.de/b0d9ce11f7cbaedf/b57cbc9c9289/BACnet-Manual--Firmware-4.9-FCU403-TRX--02-2020.pdf.

What are the minimum BACnet points to integrate the TROX TITAN FCU403 fan coil controller (config FCU403 TRX)?

Start with MV 602 Active Mode (Operating mode (Off, Normal, Eco1, Eco2, Occ OR...)); MV 618 Heat Cool Cycle (Heat, Off or Cool under manual control); MV 605 User Fan (Fan setting: Auto or speed 0-10); AV 300 Set Point (Control setpoint, °C); AI 700 RDU Temp (Room display unit temperature); MV 603 Active Fan (Current fan setting); AV 222 Heating % (Heating valve position (TPC/PWM only)); AV 232 Cooling % (Cooling valve position (TPC/PWM only)); BV 603 Fan Alarm (Fan proving alarm).

How do I enable BMS control of the TROX TITAN FCU403 fan coil controller (config FCU403 TRX)?

MV 602 Active Mode is writable depending on BV 600 Off Selector (off signal from the RDU or a digital input). MV 600 Off Mode sets what runs while the unit is Off.

Can the BMS supply sensor values to the TROX TITAN FCU403 fan coil controller (config FCU403 TRX)?

AV 700 Ext Temp takes an external temperature written over BACnet or from an analog input. Inputs (AI/BI) can be overridden only by setting Out_Of_Service True first.

How do I check these points on the real TITAN FCU403 fan coil controller (config FCU403 TRX)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TROX BACnet points lists