Air handling unit controller · BACnet points list

TROX X-CUBE Control BACnet data point list BACnet points list

Updated 28 October 2026

Short answer

TROX X-CUBE air handlers are controlled by a factory PLC (X-CUBE Control) that connects to a BMS over BACnet IP. TROX publishes the maximum data point list as an EDE-style table: 17 BMS write objects (heartbeat, reset, system mode, standby, external outdoor temperature and fan/temperature/humidity setpoints), about 100 analog inputs for temperatures, humidities, pressures, airflows, valve/damper/fan positions and filter data, and over 600 binary inputs for alarms, fire dampers, fans and heat recovery. Which objects are live depends on the unit's actual configuration.

This page lists 743 BACnet objects for the TROX X-CUBE Control BACnet data point list — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.

Manufacturer
TROX
Model
X-CUBE Control BACnet data point list
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
743 (17 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
200
Also known as
X-CUBE, TROX X-CUBE, X-CUBE Control, BACnet DPL, BACnet EDE XCUBE
Source document
BACnet EDE-File XCUBE (BACnet DPL) · V003 · rev. 2014-10
Download CSV 743 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: TROX X-CUBE Control BACnet data point list

Integration in brief

Write AO-5 eInSystemMode = 2 (auto) and keep BO-7 bInSPStandby false so the unit runs, toggle BO-1 bInHeartBeat2PLC so the PLC sees the BMS, and set the supply/extract fan and temperature/humidity setpoints in AO-8..17. Read back AI-89 eOutPVOperationMode, AI-1 eOutEventNotification and the main temperatures, and use BO-2 to reset errors. The list marks the objects that must be set in green; those are the AO/BO block.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 5eInSystemModeOperation mode command: 0 off, 1 manual, 2 autoCommand
BO 7bInSPStandbyStandby when true; must be false for auto runCommand
AO 8fInSPFanSUPSupply fan setpointCommand
AO 14fInSPTempSUPMinMinimum supply air temperature setpointCommand
BO 1bInHeartBeat2PLCBMS-to-PLC heartbeatCommand
BO 2bInResetErrorsResets all errorsCommand
AI 89eOutPVOperationModeActual operating modeRead
AI 3fOutPVTempSUPSupply air temperatureRead
AI 4fOutPVTempETAExtract air temperatureRead
AI 1eOutEventNotificationNo error / warning / critical errorRead

Enable & remote start

AO-5 eInSystemMode sets the operation mode (0=unit off, 1=manual, 2=auto); the unit runs in auto only when eInSystemMode is 2, BO-7 bInSPStandby is false and there is no critical error.

Heartbeat & communication loss

BO-1 bInHeartBeat2PLC is the heartbeat from the BMS to the unit PLC and BI-0 bOutHeartbeat2BMS is the PLC's heartbeat back to the BMS. The list does not state a timeout or what the unit does if the BMS heartbeat stops.

Sensors & values from the BMS

A BMS outdoor temperature can be written to AO-6 fInMeasTempOutdoor. No source-select or timeout object is listed for it.

Network setup

Watch out for

TROX X-CUBE Control BACnet data point list BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

743 of 743 shown
Type
Access
Show
TROX X-CUBE Control BACnet data point list BACnet Points List
DescriptionStates
DEV200TROX_856581Informational objectRead
FILE0CurrentConfig.xmlInformational objectRead
FILE1BACnetOnline_1010010.wbpInformational objectRead
Other0IOInformational objectRead
BOmin1bInHeartBeat2PLCHeart beat from BMS to the local PLCCommand
BOmin2bInResetErrorsreset all errorsCommand
BO3bInLightSwitch on/offCommand
BO4bInTestFireDampersstarts test of all fire dampersCommand
AOmin5eInSystemModeset the units operation modeCommand0=units off, 1=manual mode, 2=auto
AO6fInMeasTempOutdoorpresent value outdoor temperature°CCommand
BOmin7bInSPStandbyPuts the unit in standby when trueCommandtrue=standby, false=auto if eInSystemMode=2
AOmin8fInSPFanSUPsetpoint of the supply air fanCommand
AO9fInSPFanETAsetpoint of the extract air fanCommand
AO10fInSPTempMinsetpoint of the minimal air temperature°CCommand
AO11fInSPTempMaxsetpoint of the maximal air temperature°CCommand
AO12fInSPHumMinsetpoint of the minimal air humidityg/kgCommand
AO13fInSPHumMaxsetpoint of the maximal air humidityg/kgCommand
AOmin14fInSPTempSUPMinsetpoint of the minimal supply air temperature°CCommand
AO15fInSPTempSUPMaxsetpoint of the maximal supply air temperature°CCommand
AO16fInSPHumSUPMinsetpoint of the minimal supply air humidityg/kgCommand
AO17fInSPHumSUPMaxsetpoint of the maximal supply air humidityg/kgCommand
BI0bOutHeartbeat2BMSheart beat from to local plc to the BMSRead
BI1bOutLighttrue if the light is on otherwise falseRead
BI2bOutExtLockfalse if the unit have been lock over an external signal otherwiseRead
BI3bOutExtAlarm1State of the extern alarm number 1Read
BI4bOutExtAlarm2State of the extern alarm number 2Read
BI5bOutExtAlarm3State of the extern alarm number 3Read
BI6bOutExtAlarm4State of the extern alarm number 4Read
BI7bOutExtAlarm5State of the extern alarm number 5Read
BI8bOutExtAlarm6State of the extern alarm number 6Read
BI9bOutExtAlarm7State of the extern alarm number 7Read
BI10bOutExtAlarm8State of the extern alarm number 8Read
BI11bOutExtAlarm9State of the extern alarm number 9Read
BI12bOutExtAlarm10State of the extern alarm number 10Read
BI13bOutFireDamperClosed1contact fire damper 1 closedRead
BI14bOutFireDamperClosed2contact fire damper 2 closedRead
BI15bOutFireDamperClosed3contact fire damper 3 closedRead
BI16bOutFireDamperClosed4contact fire damper 4 closedRead
BI17bOutFireDamperClosed5contact fire damper 5 closedRead
BI18bOutFireDamperClosed6contact fire damper 6 closedRead
BI19bOutFireDamperClosed7contact fire damper 7 closedRead
BI20bOutFireDamperClosed8contact fire damper 8 closedRead
BI21bOutFireDamperClosed9contact fire damper 9 closedRead
BI22bOutFireDamperClosed10contact fire damper 10 closedRead
BI23bOutFireDamperClosed11contact fire damper 11 closedRead
BI24bOutFireDamperClosed12contact fire damper 12 closedRead
BI25bOutFireDamperClosed13contact fire damper 13 closedRead
BI26bOutFireDamperClosed14contact fire damper 14 closedRead
BI27bOutFireDamperClosed15contact fire damper 15 closedRead
BI28bOutFireDamperClosed16contact fire damper 16 closedRead
BI29bOutFireDamperClosed17contact fire damper 17 closedRead
BI30bOutFireDamperClosed18contact fire damper 18 closedRead
BI31bOutFireDamperClosed19contact fire damper 19 closedRead
BI32bOutFireDamperClosed20contact fire damper 20 closedRead
BI33bOutFireDamperClosed21contact fire damper 21 closedRead
BI34bOutFireDamperClosed22contact fire damper 22 closedRead
BI35bOutFireDamperClosed23contact fire damper 23 closedRead
BI36bOutFireDamperClosed24contact fire damper 24 closedRead
BI37bOutFireDamperClosed25contact fire damper 25 closedRead
BI38bOutFireDamperClosed26contact fire damper 26 closedRead
BI39bOutFireDamperClosed27contact fire damper 27 closedRead
BI40bOutFireDamperClosed28contact fire damper 28 closedRead
BI41bOutFireDamperClosed29contact fire damper 29 closedRead
BI42bOutFireDamperClosed30contact fire damper 30 closedRead
BI43bOutFireDamperClosed31contact fire damper 31 closedRead
BI44bOutFireDamperClosed32contact fire damper 32 closedRead
BI45bOutFireDamperClosed33contact fire damper 33 closedRead
BI46bOutFireDamperClosed34contact fire damper 34 closedRead
BI47bOutFireDamperClosed35contact fire damper 35 closedRead
BI48bOutFireDamperClosed36contact fire damper 36 closedRead
BI49bOutFireDamperClosed37contact fire damper 37 closedRead
BI50bOutFireDamperClosed38contact fire damper 38 closedRead
BI51bOutFireDamperClosed39contact fire damper 39 closedRead
BI52bOutFireDamperClosed40contact fire damper 40 closedRead
BI53bOutFireDamperClosed41contact fire damper 41 closedRead
BI54bOutFireDamperClosed42contact fire damper 42 closedRead
BI55bOutFireDamperClosed43contact fire damper 43 closedRead
BI56bOutFireDamperClosed44contact fire damper 44 closedRead
BI57bOutFireDamperClosed45contact fire damper 45 closedRead
BI58bOutFireDamperClosed46contact fire damper 46 closedRead
BI59bOutFireDamperClosed47contact fire damper 47 closedRead
BI60bOutFireDamperClosed48contact fire damper 48 closedRead
BI61bOutFireDamperClosed49contact fire damper 49 closedRead
BI62bOutFireDamperClosed50contact fire damper 50 closedRead
BI63bOutFireDamperClosed51contact fire damper 51 closedRead
BI64bOutFireDamperClosed52contact fire damper 52 closedRead
BI65bOutFireDamperClosed53contact fire damper 53 closedRead
BI66bOutFireDamperClosed54contact fire damper 54 closedRead
BI67bOutFireDamperClosed55contact fire damper 55 closedRead
BI68bOutFireDamperClosed56contact fire damper 56 closedRead
BI69bOutFireDamperClosed57contact fire damper 57 closedRead
BI70bOutFireDamperClosed58contact fire damper 58 closedRead
BI71bOutFireDamperClosed59contact fire damper 59 closedRead
BI72bOutFireDamperClosed60contact fire damper 60 closedRead
BI73bOutFireDamperClosed61contact fire damper 61 closedRead
BI74bOutFireDamperClosed62contact fire damper 62 closedRead
BI75bOutFireDamperOpened1contact fire damper 1 OpenedRead
BI76bOutFireDamperOpened2contact fire damper 2 OpenedRead
BI77bOutFireDamperOpened3contact fire damper 3 OpenedRead
BI78bOutFireDamperOpened4contact fire damper 4 OpenedRead
BI79bOutFireDamperOpened5contact fire damper 5 OpenedRead
BI80bOutFireDamperOpened6contact fire damper 6 OpenedRead
BI81bOutFireDamperOpened7contact fire damper 7 OpenedRead
BI82bOutFireDamperOpened8contact fire damper 8 OpenedRead
BI83bOutFireDamperOpened9contact fire damper 9 OpenedRead
BI84bOutFireDamperOpened10contact fire damper 10 OpenedRead
BI85bOutFireDamperOpened11contact fire damper 11 OpenedRead
BI86bOutFireDamperOpened12contact fire damper 12 OpenedRead
BI87bOutFireDamperOpened13contact fire damper 13 OpenedRead
BI88bOutFireDamperOpened14contact fire damper 14 OpenedRead
BI89bOutFireDamperOpened15contact fire damper 15 OpenedRead
BI90bOutFireDamperOpened16contact fire damper 16 OpenedRead
BI91bOutFireDamperOpened17contact fire damper 17 OpenedRead
BI92bOutFireDamperOpened18contact fire damper 18 OpenedRead
BI93bOutFireDamperOpened19contact fire damper 19 OpenedRead
BI94bOutFireDamperOpened20contact fire damper 20 OpenedRead
BI95bOutFireDamperOpened21contact fire damper 21 OpenedRead
BI96bOutFireDamperOpened22contact fire damper 22 OpenedRead
BI97bOutFireDamperOpened23contact fire damper 23 OpenedRead
BI98bOutFireDamperOpened24contact fire damper 24 OpenedRead
BI99bOutFireDamperOpened25contact fire damper 25 OpenedRead
BI100bOutFireDamperOpened26contact fire damper 26 OpenedRead
BI101bOutFireDamperOpened27contact fire damper 27 OpenedRead
BI102bOutFireDamperOpened28contact fire damper 28 OpenedRead
BI103bOutFireDamperOpened29contact fire damper 29 OpenedRead
BI104bOutFireDamperOpened30contact fire damper 30 OpenedRead
BI105bOutFireDamperOpened31contact fire damper 31 OpenedRead
BI106bOutFireDamperOpened32contact fire damper 32 OpenedRead
BI107bOutFireDamperOpened33contact fire damper 33 OpenedRead
BI108bOutFireDamperOpened34contact fire damper 34 OpenedRead
BI109bOutFireDamperOpened35contact fire damper 35 OpenedRead
BI110bOutFireDamperOpened36contact fire damper 36 OpenedRead
BI111bOutFireDamperOpened37contact fire damper 37 OpenedRead
BI112bOutFireDamperOpened38contact fire damper 38 OpenedRead
BI113bOutFireDamperOpened39contact fire damper 39 OpenedRead
BI114bOutFireDamperOpened40contact fire damper 40 OpenedRead
BI115bOutFireDamperOpened41contact fire damper 41 OpenedRead
BI116bOutFireDamperOpened42contact fire damper 42 OpenedRead
BI117bOutFireDamperOpened43contact fire damper 43 OpenedRead
BI118bOutFireDamperOpened44contact fire damper 44 OpenedRead
BI119bOutFireDamperOpened45contact fire damper 45 OpenedRead
BI120bOutFireDamperOpened46contact fire damper 46 OpenedRead
BI121bOutFireDamperOpened47contact fire damper 47 OpenedRead
BI122bOutFireDamperOpened48contact fire damper 48 OpenedRead
BI123bOutFireDamperOpened49contact fire damper 49 OpenedRead
BI124bOutFireDamperOpened50contact fire damper 50 OpenedRead
BI125bOutFireDamperOpened51contact fire damper 51 OpenedRead
BI126bOutFireDamperOpened52contact fire damper 52 OpenedRead
BI127bOutFireDamperOpened53contact fire damper 53 OpenedRead
BI128bOutFireDamperOpened54contact fire damper 54 OpenedRead
BI129bOutFireDamperOpened55contact fire damper 55 OpenedRead
BI130bOutFireDamperOpened56contact fire damper 56 OpenedRead
BI131bOutFireDamperOpened57contact fire damper 57 OpenedRead
BI132bOutFireDamperOpened58contact fire damper 58 OpenedRead
BI133bOutFireDamperOpened59contact fire damper 59 OpenedRead
BI134bOutFireDamperOpened60contact fire damper 60 OpenedRead
BI135bOutFireDamperOpened61contact fire damper 61 OpenedRead
BI136bOutFireDamperOpened62contact fire damper 62 OpenedRead
BI137bOutFireDamperErrClosingRuntime1Error closing runtime fire damper 1, normally closedRead
BI138bOutFireDamperErrClosingRuntime2Error closing runtime fire damper 2, normally closedRead
BI139bOutFireDamperErrClosingRuntime3Error closing runtime fire damper 3, normally closedRead
BI140bOutFireDamperErrClosingRuntime4Error closing runtime fire damper 4, normally closedRead
BI141bOutFireDamperErrClosingRuntime5Error closing runtime fire damper 5, normally closedRead
BI142bOutFireDamperErrClosingRuntime6Error closing runtime fire damper 6, normally closedRead
BI143bOutFireDamperErrClosingRuntime7Error closing runtime fire damper 7, normally closedRead
BI144bOutFireDamperErrClosingRuntime8Error closing runtime fire damper 8, normally closedRead
BI145bOutFireDamperErrClosingRuntime9Error closing runtime fire damper 9, normally closedRead
BI146bOutFireDamperErrClosingRuntime10Error closing runtime fire damper 10, normally closedRead
BI147bOutFireDamperErrClosingRuntime11Error closing runtime fire damper 11, normally closedRead
BI148bOutFireDamperErrClosingRuntime12Error closing runtime fire damper 12, normally closedRead
BI149bOutFireDamperErrClosingRuntime13Error closing runtime fire damper 13, normally closedRead
BI150bOutFireDamperErrClosingRuntime14Error closing runtime fire damper 14, normally closedRead
BI151bOutFireDamperErrClosingRuntime15Error closing runtime fire damper 15, normally closedRead
BI152bOutFireDamperErrClosingRuntime16Error closing runtime fire damper 16, normally closedRead
BI153bOutFireDamperErrClosingRuntime17Error closing runtime fire damper 17, normally closedRead
BI154bOutFireDamperErrClosingRuntime18Error closing runtime fire damper 18, normally closedRead
BI155bOutFireDamperErrClosingRuntime19Error closing runtime fire damper 19, normally closedRead
BI156bOutFireDamperErrClosingRuntime20Error closing runtime fire damper 20, normally closedRead
BI157bOutFireDamperErrClosingRuntime21Error closing runtime fire damper 21, normally closedRead
BI158bOutFireDamperErrClosingRuntime22Error closing runtime fire damper 22, normally closedRead
BI159bOutFireDamperErrClosingRuntime23Error closing runtime fire damper 23, normally closedRead
BI160bOutFireDamperErrClosingRuntime24Error closing runtime fire damper 24, normally closedRead
BI161bOutFireDamperErrClosingRuntime25Error closing runtime fire damper 25, normally closedRead
BI162bOutFireDamperErrClosingRuntime26Error closing runtime fire damper 26, normally closedRead
BI163bOutFireDamperErrClosingRuntime27Error closing runtime fire damper 27, normally closedRead
BI164bOutFireDamperErrClosingRuntime28Error closing runtime fire damper 28, normally closedRead
BI165bOutFireDamperErrClosingRuntime29Error closing runtime fire damper 29, normally closedRead
BI166bOutFireDamperErrClosingRuntime30Error closing runtime fire damper 30, normally closedRead
BI167bOutFireDamperErrClosingRuntime31Error closing runtime fire damper 31, normally closedRead
BI168bOutFireDamperErrClosingRuntime32Error closing runtime fire damper 32, normally closedRead
BI169bOutFireDamperErrClosingRuntime33Error closing runtime fire damper 33, normally closedRead
BI170bOutFireDamperErrClosingRuntime34Error closing runtime fire damper 34, normally closedRead
BI171bOutFireDamperErrClosingRuntime35Error closing runtime fire damper 35, normally closedRead
BI172bOutFireDamperErrClosingRuntime36Error closing runtime fire damper 36, normally closedRead
BI173bOutFireDamperErrClosingRuntime37Error closing runtime fire damper 37, normally closedRead
BI174bOutFireDamperErrClosingRuntime38Error closing runtime fire damper 38, normally closedRead
BI175bOutFireDamperErrClosingRuntime39Error closing runtime fire damper 39, normally closedRead
BI176bOutFireDamperErrClosingRuntime40Error closing runtime fire damper 40, normally closedRead
BI177bOutFireDamperErrClosingRuntime41Error closing runtime fire damper 41, normally closedRead
BI178bOutFireDamperErrClosingRuntime42Error closing runtime fire damper 42, normally closedRead
BI179bOutFireDamperErrClosingRuntime43Error closing runtime fire damper 43, normally closedRead
BI180bOutFireDamperErrClosingRuntime44Error closing runtime fire damper 44, normally closedRead
BI181bOutFireDamperErrClosingRuntime45Error closing runtime fire damper 45, normally closedRead
BI182bOutFireDamperErrClosingRuntime46Error closing runtime fire damper 46, normally closedRead
BI183bOutFireDamperErrClosingRuntime47Error closing runtime fire damper 47, normally closedRead
BI184bOutFireDamperErrClosingRuntime48Error closing runtime fire damper 48, normally closedRead
BI185bOutFireDamperErrClosingRuntime49Error closing runtime fire damper 49, normally closedRead
BI186bOutFireDamperErrClosingRuntime50Error closing runtime fire damper 50, normally closedRead
BI187bOutFireDamperErrClosingRuntime51Error closing runtime fire damper 51, normally closedRead
BI188bOutFireDamperErrClosingRuntime52Error closing runtime fire damper 52, normally closedRead
BI189bOutFireDamperErrClosingRuntime53Error closing runtime fire damper 53, normally closedRead
BI190bOutFireDamperErrClosingRuntime54Error closing runtime fire damper 54, normally closedRead
BI191bOutFireDamperErrClosingRuntime55Error closing runtime fire damper 55, normally closedRead
BI192bOutFireDamperErrClosingRuntime56Error closing runtime fire damper 56, normally closedRead
BI193bOutFireDamperErrClosingRuntime57Error closing runtime fire damper 57, normally closedRead
BI194bOutFireDamperErrClosingRuntime58Error closing runtime fire damper 58, normally closedRead
BI195bOutFireDamperErrClosingRuntime59Error closing runtime fire damper 59, normally closedRead
BI196bOutFireDamperErrClosingRuntime60Error closing runtime fire damper 60, normally closedRead
BI197bOutFireDamperErrClosingRuntime61Error closing runtime fire damper 61, normally closedRead
BI198bOutFireDamperErrClosingRuntime62Error closing runtime fire damper 62, normally closedRead
BI199bOutFireDamperErrOpeningRuntime1Error Opening runtime fire damper 1, normally closedRead
BI200bOutFireDamperErrOpeningRuntime2Error Opening runtime fire damper 2, normally closedRead
BI201bOutFireDamperErrOpeningRuntime3Error Opening runtime fire damper 3, normally closedRead
BI202bOutFireDamperErrOpeningRuntime4Error Opening runtime fire damper 4, normally closedRead
BI203bOutFireDamperErrOpeningRuntime5Error Opening runtime fire damper 5, normally closedRead
BI204bOutFireDamperErrOpeningRuntime6Error Opening runtime fire damper 6, normally closedRead
BI205bOutFireDamperErrOpeningRuntime7Error Opening runtime fire damper 7, normally closedRead
BI206bOutFireDamperErrOpeningRuntime8Error Opening runtime fire damper 8, normally closedRead
BI207bOutFireDamperErrOpeningRuntime9Error Opening runtime fire damper 9, normally closedRead
BI208bOutFireDamperErrOpeningRuntime10Error Opening runtime fire damper 10, normally closedRead
BI209bOutFireDamperErrOpeningRuntime11Error Opening runtime fire damper 11, normally closedRead
BI210bOutFireDamperErrOpeningRuntime12Error Opening runtime fire damper 12, normally closedRead
BI211bOutFireDamperErrOpeningRuntime13Error Opening runtime fire damper 13, normally closedRead
BI212bOutFireDamperErrOpeningRuntime14Error Opening runtime fire damper 14, normally closedRead
BI213bOutFireDamperErrOpeningRuntime15Error Opening runtime fire damper 15, normally closedRead
BI214bOutFireDamperErrOpeningRuntime16Error Opening runtime fire damper 16, normally closedRead
BI215bOutFireDamperErrOpeningRuntime17Error Opening runtime fire damper 17, normally closedRead
BI216bOutFireDamperErrOpeningRuntime18Error Opening runtime fire damper 18, normally closedRead
BI217bOutFireDamperErrOpeningRuntime19Error Opening runtime fire damper 19, normally closedRead
BI218bOutFireDamperErrOpeningRuntime20Error Opening runtime fire damper 20, normally closedRead
BI219bOutFireDamperErrOpeningRuntime21Error Opening runtime fire damper 21, normally closedRead
BI220bOutFireDamperErrOpeningRuntime22Error Opening runtime fire damper 22, normally closedRead
BI221bOutFireDamperErrOpeningRuntime23Error Opening runtime fire damper 23, normally closedRead
BI222bOutFireDamperErrOpeningRuntime24Error Opening runtime fire damper 24, normally closedRead
BI223bOutFireDamperErrOpeningRuntime25Error Opening runtime fire damper 25, normally closedRead
BI224bOutFireDamperErrOpeningRuntime26Error Opening runtime fire damper 26, normally closedRead
BI225bOutFireDamperErrOpeningRuntime27Error Opening runtime fire damper 27, normally closedRead
BI226bOutFireDamperErrOpeningRuntime28Error Opening runtime fire damper 28, normally closedRead
BI227bOutFireDamperErrOpeningRuntime29Error Opening runtime fire damper 29, normally closedRead
BI228bOutFireDamperErrOpeningRuntime30Error Opening runtime fire damper 30, normally closedRead
BI229bOutFireDamperErrOpeningRuntime31Error Opening runtime fire damper 31, normally closedRead
BI230bOutFireDamperErrOpeningRuntime32Error Opening runtime fire damper 32, normally closedRead
BI231bOutFireDamperErrOpeningRuntime33Error Opening runtime fire damper 33, normally closedRead
BI232bOutFireDamperErrOpeningRuntime34Error Opening runtime fire damper 34, normally closedRead
BI233bOutFireDamperErrOpeningRuntime35Error Opening runtime fire damper 35, normally closedRead
BI234bOutFireDamperErrOpeningRuntime36Error Opening runtime fire damper 36, normally closedRead
BI235bOutFireDamperErrOpeningRuntime37Error Opening runtime fire damper 37, normally closedRead
BI236bOutFireDamperErrOpeningRuntime38Error Opening runtime fire damper 38, normally closedRead
BI237bOutFireDamperErrOpeningRuntime39Error Opening runtime fire damper 39, normally closedRead
BI238bOutFireDamperErrOpeningRuntime40Error Opening runtime fire damper 40, normally closedRead
BI239bOutFireDamperErrOpeningRuntime41Error Opening runtime fire damper 41, normally closedRead
BI240bOutFireDamperErrOpeningRuntime42Error Opening runtime fire damper 42, normally closedRead
BI241bOutFireDamperErrOpeningRuntime43Error Opening runtime fire damper 43, normally closedRead
BI242bOutFireDamperErrOpeningRuntime44Error Opening runtime fire damper 44, normally closedRead
BI243bOutFireDamperErrOpeningRuntime45Error Opening runtime fire damper 45, normally closedRead
BI244bOutFireDamperErrOpeningRuntime46Error Opening runtime fire damper 46, normally closedRead
BI245bOutFireDamperErrOpeningRuntime47Error Opening runtime fire damper 47, normally closedRead
BI246bOutFireDamperErrOpeningRuntime48Error Opening runtime fire damper 48, normally closedRead
BI247bOutFireDamperErrOpeningRuntime49Error Opening runtime fire damper 49, normally closedRead
BI248bOutFireDamperErrOpeningRuntime50Error Opening runtime fire damper 50, normally closedRead
BI249bOutFireDamperErrOpeningRuntime51Error Opening runtime fire damper 51, normally closedRead
BI250bOutFireDamperErrOpeningRuntime52Error Opening runtime fire damper 52, normally closedRead
BI251bOutFireDamperErrOpeningRuntime53Error Opening runtime fire damper 53, normally closedRead
BI252bOutFireDamperErrOpeningRuntime54Error Opening runtime fire damper 54, normally closedRead
BI253bOutFireDamperErrOpeningRuntime55Error Opening runtime fire damper 55, normally closedRead
BI254bOutFireDamperErrOpeningRuntime56Error Opening runtime fire damper 56, normally closedRead
BI255bOutFireDamperErrOpeningRuntime57Error Opening runtime fire damper 57, normally closedRead
BI256bOutFireDamperErrOpeningRuntime58Error Opening runtime fire damper 58, normally closedRead
BI257bOutFireDamperErrOpeningRuntime59Error Opening runtime fire damper 59, normally closedRead
BI258bOutFireDamperErrOpeningRuntime60Error Opening runtime fire damper 60, normally closedRead
BI259bOutFireDamperErrOpeningRuntime61Error Opening runtime fire damper 61, normally closedRead
BI260bOutFireDamperErrOpeningRuntime62Error Opening runtime fire damper 62, normally closedRead
BI261bOutFireDamperErrPosIndicator1Error end switch fire damper 1, normally closedRead
BI262bOutFireDamperErrPosIndicator2Error end switch fire damper 2, normally closedRead
BI263bOutFireDamperErrPosIndicator3Error end switch fire damper 3, normally closedRead
BI264bOutFireDamperErrPosIndicator4Error end switch fire damper 4, normally closedRead
BI265bOutFireDamperErrPosIndicator5Error end switch fire damper 5, normally closedRead
BI266bOutFireDamperErrPosIndicator6Error end switch fire damper 6, normally closedRead
BI267bOutFireDamperErrPosIndicator7Error end switch fire damper 7, normally closedRead
BI268bOutFireDamperErrPosIndicator8Error end switch fire damper 8, normally closedRead
BI269bOutFireDamperErrPosIndicator9Error end switch fire damper 9, normally closedRead
BI270bOutFireDamperErrPosIndicator10Error end switch fire damper 10, normally closedRead
BI271bOutFireDamperErrPosIndicator11Error end switch fire damper 11, normally closedRead
BI272bOutFireDamperErrPosIndicator12Error end switch fire damper 12, normally closedRead
BI273bOutFireDamperErrPosIndicator13Error end switch fire damper 13, normally closedRead
BI274bOutFireDamperErrPosIndicator14Error end switch fire damper 14, normally closedRead
BI275bOutFireDamperErrPosIndicator15Error end switch fire damper 15, normally closedRead
BI276bOutFireDamperErrPosIndicator16Error end switch fire damper 16, normally closedRead
BI277bOutFireDamperErrPosIndicator17Error end switch fire damper 17, normally closedRead
BI278bOutFireDamperErrPosIndicator18Error end switch fire damper 18, normally closedRead
BI279bOutFireDamperErrPosIndicator19Error end switch fire damper 19, normally closedRead
BI280bOutFireDamperErrPosIndicator20Error end switch fire damper 20, normally closedRead
BI281bOutFireDamperErrPosIndicator21Error end switch fire damper 21, normally closedRead
BI282bOutFireDamperErrPosIndicator22Error end switch fire damper 22, normally closedRead
BI283bOutFireDamperErrPosIndicator23Error end switch fire damper 23, normally closedRead
BI284bOutFireDamperErrPosIndicator24Error end switch fire damper 24, normally closedRead
BI285bOutFireDamperErrPosIndicator25Error end switch fire damper 25, normally closedRead
BI286bOutFireDamperErrPosIndicator26Error end switch fire damper 26, normally closedRead
BI287bOutFireDamperErrPosIndicator27Error end switch fire damper 27, normally closedRead
BI288bOutFireDamperErrPosIndicator28Error end switch fire damper 28, normally closedRead
BI289bOutFireDamperErrPosIndicator29Error end switch fire damper 29, normally closedRead
BI290bOutFireDamperErrPosIndicator30Error end switch fire damper 30, normally closedRead
BI291bOutFireDamperErrPosIndicator31Error end switch fire damper 31, normally closedRead
BI292bOutFireDamperErrPosIndicator32Error end switch fire damper 32, normally closedRead
BI293bOutFireDamperErrPosIndicator33Error end switch fire damper 33, normally closedRead
BI294bOutFireDamperErrPosIndicator34Error end switch fire damper 34, normally closedRead
BI295bOutFireDamperErrPosIndicator35Error end switch fire damper 35, normally closedRead
BI296bOutFireDamperErrPosIndicator36Error end switch fire damper 36, normally closedRead
BI297bOutFireDamperErrPosIndicator37Error end switch fire damper 37, normally closedRead
BI298bOutFireDamperErrPosIndicator38Error end switch fire damper 38, normally closedRead
BI299bOutFireDamperErrPosIndicator39Error end switch fire damper 39, normally closedRead
BI300bOutFireDamperErrPosIndicator40Error end switch fire damper 40, normally closedRead
BI301bOutFireDamperErrPosIndicator41Error end switch fire damper 41, normally closedRead
BI302bOutFireDamperErrPosIndicator42Error end switch fire damper 42, normally closedRead
BI303bOutFireDamperErrPosIndicator43Error end switch fire damper 43, normally closedRead
BI304bOutFireDamperErrPosIndicator44Error end switch fire damper 44, normally closedRead
BI305bOutFireDamperErrPosIndicator45Error end switch fire damper 45, normally closedRead
BI306bOutFireDamperErrPosIndicator46Error end switch fire damper 46, normally closedRead
BI307bOutFireDamperErrPosIndicator47Error end switch fire damper 47, normally closedRead
BI308bOutFireDamperErrPosIndicator48Error end switch fire damper 48, normally closedRead
BI309bOutFireDamperErrPosIndicator49Error end switch fire damper 49, normally closedRead
BI310bOutFireDamperErrPosIndicator50Error end switch fire damper 50, normally closedRead
BI311bOutFireDamperErrPosIndicator51Error end switch fire damper 51, normally closedRead
BI312bOutFireDamperErrPosIndicator52Error end switch fire damper 52, normally closedRead
BI313bOutFireDamperErrPosIndicator53Error end switch fire damper 53, normally closedRead
BI314bOutFireDamperErrPosIndicator54Error end switch fire damper 54, normally closedRead
BI315bOutFireDamperErrPosIndicator55Error end switch fire damper 55, normally closedRead
BI316bOutFireDamperErrPosIndicator56Error end switch fire damper 56, normally closedRead
BI317bOutFireDamperErrPosIndicator57Error end switch fire damper 57, normally closedRead
BI318bOutFireDamperErrPosIndicator58Error end switch fire damper 58, normally closedRead
BI319bOutFireDamperErrPosIndicator59Error end switch fire damper 59, normally closedRead
BI320bOutFireDamperErrPosIndicator60Error end switch fire damper 60, normally closedRead
BI321bOutFireDamperErrPosIndicator61Error end switch fire damper 61, normally closedRead
BI322bOutFireDamperErrPosIndicator62Error end switch fire damper 62, normally closedRead
BI323bOutFireDamperErr1Error triggered fire damper 1, normally closedRead
BI324bOutFireDamperErr2Error triggered fire damper 2, normally closedRead
BI325bOutFireDamperErr3Error triggered fire damper 3, normally closedRead
BI326bOutFireDamperErr4Error triggered fire damper 4, normally closedRead
BI327bOutFireDamperErr5Error triggered fire damper 5, normally closedRead
BI328bOutFireDamperErr6Error triggered fire damper 6, normally closedRead
BI329bOutFireDamperErr7Error triggered fire damper 7, normally closedRead
BI330bOutFireDamperErr8Error triggered fire damper 8, normally closedRead
BI331bOutFireDamperErr9Error triggered fire damper 9, normally closedRead
BI332bOutFireDamperErr10Error triggered fire damper 10, normally closedRead
BI333bOutFireDamperErr11Error triggered fire damper 11, normally closedRead
BI334bOutFireDamperErr12Error triggered fire damper 12, normally closedRead
BI335bOutFireDamperErr13Error triggered fire damper 13, normally closedRead
BI336bOutFireDamperErr14Error triggered fire damper 14, normally closedRead
BI337bOutFireDamperErr15Error triggered fire damper 15, normally closedRead
BI338bOutFireDamperErr16Error triggered fire damper 16, normally closedRead
BI339bOutFireDamperErr17Error triggered fire damper 17, normally closedRead
BI340bOutFireDamperErr18Error triggered fire damper 18, normally closedRead
BI341bOutFireDamperErr19Error triggered fire damper 19, normally closedRead
BI342bOutFireDamperErr20Error triggered fire damper 20, normally closedRead
BI343bOutFireDamperErr21Error triggered fire damper 21, normally closedRead
BI344bOutFireDamperErr22Error triggered fire damper 22, normally closedRead
BI345bOutFireDamperErr23Error triggered fire damper 23, normally closedRead
BI346bOutFireDamperErr24Error triggered fire damper 24, normally closedRead
BI347bOutFireDamperErr25Error triggered fire damper 25, normally closedRead
BI348bOutFireDamperErr26Error triggered fire damper 26, normally closedRead
BI349bOutFireDamperErr27Error triggered fire damper 27, normally closedRead
BI350bOutFireDamperErr28Error triggered fire damper 28, normally closedRead
BI351bOutFireDamperErr29Error triggered fire damper 29, normally closedRead
BI352bOutFireDamperErr30Error triggered fire damper 30, normally closedRead
BI353bOutFireDamperErr31Error triggered fire damper 31, normally closedRead
BI354bOutFireDamperErr32Error triggered fire damper 32, normally closedRead
BI355bOutFireDamperErr33Error triggered fire damper 33, normally closedRead
BI356bOutFireDamperErr34Error triggered fire damper 34, normally closedRead
BI357bOutFireDamperErr35Error triggered fire damper 35, normally closedRead
BI358bOutFireDamperErr36Error triggered fire damper 36, normally closedRead
BI359bOutFireDamperErr37Error triggered fire damper 37, normally closedRead
BI360bOutFireDamperErr38Error triggered fire damper 38, normally closedRead
BI361bOutFireDamperErr39Error triggered fire damper 39, normally closedRead
BI362bOutFireDamperErr40Error triggered fire damper 40, normally closedRead
BI363bOutFireDamperErr41Error triggered fire damper 41, normally closedRead
BI364bOutFireDamperErr42Error triggered fire damper 42, normally closedRead
BI365bOutFireDamperErr43Error triggered fire damper 43, normally closedRead
BI366bOutFireDamperErr44Error triggered fire damper 44, normally closedRead
BI367bOutFireDamperErr45Error triggered fire damper 45, normally closedRead
BI368bOutFireDamperErr46Error triggered fire damper 46, normally closedRead
BI369bOutFireDamperErr47Error triggered fire damper 47, normally closedRead
BI370bOutFireDamperErr48Error triggered fire damper 48, normally closedRead
BI371bOutFireDamperErr49Error triggered fire damper 49, normally closedRead
BI372bOutFireDamperErr50Error triggered fire damper 50, normally closedRead
BI373bOutFireDamperErr51Error triggered fire damper 51, normally closedRead
BI374bOutFireDamperErr52Error triggered fire damper 52, normally closedRead
BI375bOutFireDamperErr53Error triggered fire damper 53, normally closedRead
BI376bOutFireDamperErr54Error triggered fire damper 54, normally closedRead
BI377bOutFireDamperErr55Error triggered fire damper 55, normally closedRead
BI378bOutFireDamperErr56Error triggered fire damper 56, normally closedRead
BI379bOutFireDamperErr57Error triggered fire damper 57, normally closedRead
BI380bOutFireDamperErr58Error triggered fire damper 58, normally closedRead
BI381bOutFireDamperErr59Error triggered fire damper 59, normally closedRead
BI382bOutFireDamperErr60Error triggered fire damper 60, normally closedRead
BI383bOutFireDamperErr61Error triggered fire damper 61, normally closedRead
BI384bOutFireDamperErr62Error triggered fire damper 62, normally closedRead
BI385bOutSmokeDetectorErr1Error triggered smoke detector 1, normally closedRead
BI386bOutSmokeDetectorErr2Error triggered smoke detector 2, normally closedRead
BI387bOutSmokeDetectorErr3Error triggered smoke detector 3, normally closedRead
BI388bOutSmokeDetectorErr4Error triggered smoke detector 4, normally closedRead
BI389bOutSmokeDetectorErr5Error triggered smoke detector 5, normally closedRead
BI390bOutSmokeDetectorDirty1Error triggered smoke detector 1 is dirty, normally closedRead
BI391bOutSmokeDetectorDirty2Error triggered smoke detector 2 is dirty, normally closedRead
BI392bOutSmokeDetectorDirty3Error triggered smoke detector 3 is dirty, normally closedRead
BI393bOutSmokeDetectorDirty4Error triggered smoke detector 4 is dirty, normally closedRead
BI394bOutSmokeDetectorDirty5Error triggered smoke detector 5 is dirty, normally closedRead
AI0fOutPVTempOutdoorpresent value outdoor temperature°CRead
AImin1eOutEventNotificationUnit error summaryRead0=no error, 1=warnings, 2=at least one critical error
BI395bOutVoltageErrorvoltage error, normaly closedRead
BI396bOutMainFuseErrormain fuse error, normaly closedRead
BI397bOutFireAlarmfire alarm, normaly closedRead
BI398bOutFrostProtectionerror frost protection, normaly closedRead
BI399bOutModbuslineErrorerror modbus line, normaly closedRead
AI2fOutPVTempODApresent value outdoor air temperature°CRead
AImin3fOutPVTempSUPpresent value supply air temperature°CRead
AImin4fOutPVTempETApresent value extracted air temperature°CRead
AI5fOutPVTempEHApresent value exhauts air temperature°CRead
AI6fOutPVHumODApresent value outdoor air humidity%RHRead
AI7fOutPVHumSUPpresent value supply air humidity%RHRead
AI8fOutPVHumETApresent value extracted air humidity%RHRead
AI9fOutPVHumEHApresent value exhauts air humidity%RHRead
AI10fOutPVPressureSUPpresent value supply duct pressurePaRead
AI11fOutPVPressureETApresent value exhaust duct pressurePaRead
AI12fOutPV_VOCpresent value voc concentrationppmRead
AI13fOutPV_CO2present value CO2 concentrationppmRead
BI400bOutCoolerMotorProtectionerror motor protection cooler pump, normaly closedRead
BI401bOutCoolerValveComErrmodbus communication error witth the cooler valve, normaly closedRead
BI402bOutCoolerCtrlPumpONcontrolled value to switch on/off the cooler pumpRead
AI14fOutCoolerPVValvePoscurrent position of the cooler valve%Read
AI15fOutCoolerCtrlValvePoscontrolled value of the cooler valve%Read
AI16fOutCoolerPVIntletTemppresent value of the cooler inlet temperature°CRead
BI403bOutPreheaterMotorProtectionerror motor protection preheater pump, normaly closedRead
BI404bOutPreheaterValveComErrmodbus communication error witth the preheater valve, normaly closedRead
BI405bOutPreheaterCtrlPumpONcontrolled value to switch on/off the preheater pumpRead
AI17fOutPreheaterPVValvePoscurrent position of the preheater valve%Read
AI18fOutPreheaterCtrlValvePoscontrolled value of the preheater valve%Read
AI19fOutPreheaterPVReturnTemppresent value of the preheater return temperature°CRead
BI406bOutReheaterMotorProtectionerror motor protection reheater pump, normaly closedRead
BI407bOutReheaterValveComErrmodbus communication error witth the reheater valve, normaly closedRead
BI408bOutReheaterCtrlPumpONcontrolled value to switch on/off the reheater pumpRead
AI20fOutReheaterPVValvePoscurrent position of the reheater valve%Read
AI21fOutReheaterCtrlValvePoscontrolled value of the reheater valve%Read
AI22fOutReheaterPVReturnTemppresent value of the reheater return temperature°CRead
BI409bOutDamperODAComErrmodbus communication error witth the outdoor air damper, normaly closedRead
BI410bOutDamperSUPComErrmodbus communication error witth the supply air damper, normaly closedRead
BI411bOutDamperETAComErrmodbus communication error witth the extracted air damper, normaly closedRead
BI412bOutDamperEHAComErrmodbus communication error witth the exhaust air damper, normaly closedRead
BI413bOutDamperFanSUPComErrmodbus communication error witth the supply air fan damper, normaly closedRead
BI414bOutDamperFanETAComErrmodbus communication error witth the extracted air fan damper, normaly closedRead
BI415bOutDamperODAComErr2modbus communication error witth the second outdoor air damper, normaly closedRead
BI416bOutDamperSUPComErr2modbus communication error witth the second supply air damper, normaly closedRead
BI417bOutDamperETAComErr2modbus communication error witth the second extracted air damper, normaly closedRead
BI418bOutDamperEHAComErr2modbus communication error witth the second exhaust air damper, normaly closedRead
BI419bOutDamperFanSUPComErr2modbus communication error witth the second supply air fan damper, normaly closedRead
BI420bOutDamperFanETAComErr2modbus communication error witth the second extracted air fan damper, normaly closedRead
BI421bOutDamperRCAComErrmodbus communication error with the recovery air damper, normaly closedRead
BI422bOutDamperRCAComErr2modbus communication error with the second recovery air damper, normaly closedRead
AI23fOutDamperODAPVPoscurrent position of the outdoor air damper%Read
AI24fOutDamperSUPPVPoscurrent position of the supply air damper%Read
AI25fOutDamperETAPVPoscurrent position of the extract air damper%Read
AI26fOutDamperEHAPVPoscurrent position of the exhaust air damper%Read
AI27fOutDamperODAPVPos2current position of the second outdoor air damper%Read
AI28fOutDamperSUPPVPos2current position of the second supply air damper%Read
AI29fOutDamperETAPVPos2current position of the second extract air damper%Read
AI30fOutDamperEHAPVPos2current position of the second exhaust air damper%Read
AI31fOutDamperFanSUPPVPoscurrent position of the supply air fan damper%Read
AI32fOutDamperFanETAPVPoscurrent position of the extract air fan damper%Read
AI33fOutDamperFanSUPPVPos2current position of the second supply air fan damper%Read
AI34fOutDamperFanETAPVPos2current position of the second extract air fan damper%Read
AI35fOutDamperRCAPVPoscurrent position of the recovery air damper%Read
AI36fOutDamperRCAPVPos2current position of the second recovery air damper%Read
AI37fOutDamperODACtrlPoscontrolled value of the outdoor air damper position%Read
AI38fOutDamperSUPCtrlPoscontrolled value of the supply air damper position%Read
AI39fOutDamperETACtrlPoscontrolled value of the extract air damper position%Read
AI40fOutDamperEHACtrlPoscontrolled value of the exhaust air damper position%Read
AI41fOutDamperODACtrlPos2controlled value of the second outdoor air damper position%Read
AI42fOutDamperSUPCtrlPos2controlled value of the second supply air damper position%Read
AI43fOutDamperETACtrlPos2controlled value of the second extract air damper position%Read
AI44fOutDamperEHACtrlPos2controlled value of the second exhaust air damper position%Read
AI45fOutDamperFanSUPCtrlPoscontrolled value of the supply air fan damper position%Read
AI46fOutDamperFanETACtrlPoscontrolled value of the extract air fan damper position%Read
AI47fOutDamperFanSUPCtrlPos2controlled value of the second supply air fan damper position%Read
AI48fOutDamperFanETACtrlPos2controlled value of the second extract air fan damper position%Read
AI49fOutDamperRCACtrlPoscontrolled value of the recovery air damper position%Read
AI50fOutDamperRCACtrlPos2controlled value of the second recovery air damper position%Read
BI423bOutFanSUPMotorProtectionerror motor protection supply air fan, normaly closedRead
BI424bOutFanSUPMotorProtection2error motor protection of the second supply air fan, normaly closedRead
BI425bOutFanETAMotorProtectionerror motor protection extract air fan, normaly closedRead
BI426bOutFanETAMotorProtection2error motor protection of the second extract air fan, normaly closedRead
BI427bOutFanSUPRepairSwitcherror repair switch supply air fan, normaly closedRead
BI428bOutFanSUPRepairSwitch2error repair switch of the second supply air fan, normaly closedRead
BI429bOutFanSUPRepairSwitch3error repair switch of the supply air fan 3, normaly closedRead
BI430bOutFanSUPRepairSwitch4error repair switch of the supply air fan 4, normaly closedRead
BI431bOutFanSUPRepairSwitch5error repair switch of the supply air fan 5, normaly closedRead
BI432bOutFanSUPRepairSwitch6error repair switch of the supply air fan 6, normaly closedRead
BI433bOutFanSUPRepairSwitch7error repair switch of the supply air fan 7, normaly closedRead
BI434bOutFanSUPRepairSwitch8error repair switch of the supply air fan 8, normaly closedRead
BI435bOutFanSUPRepairSwitch9error repair switch of the supply air fan 9, normaly closedRead
BI436bOutFanSUPRepairSwitch10error repair switch of the supply air fan 10, normaly closedRead
BI437bOutFanSUPRepairSwitch11error repair switch of the supply air fan 11, normaly closedRead
BI438bOutFanSUPRepairSwitch12error repair switch of the supply air fan 12, normaly closedRead
BI439bOutFanSUPRepairSwitch13error repair switch of the supply air fan 13, normaly closedRead
BI440bOutFanSUPRepairSwitch14error repair switch of the supply air fan 14, normaly closedRead
BI441bOutFanSUPRepairSwitch15error repair switch of the supply air fan 15, normaly closedRead
BI442bOutFanSUPRepairSwitch16error repair switch of the supply air fan 16, normaly closedRead
BI443bOutFanETARepairSwitcherror repair switch extract air fan, normaly closedRead
BI444bOutFanETARepairSwitch2error repair switch of the second extract air fan, normaly closedRead
BI445bOutFanETARepairSwitch3error repair switch of the extract air fan 3, normaly closedRead
BI446bOutFanETARepairSwitch4error repair switch of the extract air fan 4, normaly closedRead
BI447bOutFanETARepairSwitch5error repair switch of the extract air fan 5, normaly closedRead
BI448bOutFanETARepairSwitch6error repair switch of the extract air fan 6, normaly closedRead
BI449bOutFanETARepairSwitch7error repair switch of the extract air fan 7, normaly closedRead
BI450bOutFanETARepairSwitch8error repair switch of the extract air fan 8, normaly closedRead
BI451bOutFanETARepairSwitch9error repair switch of the extract air fan 9, normaly closedRead
BI452bOutFanETARepairSwitch10error repair switch of the extract air fan 10, normaly closedRead
BI453bOutFanETARepairSwitch11error repair switch of the extract air fan 11, normaly closedRead
BI454bOutFanETARepairSwitch12error repair switch of the extract air fan 12, normaly closedRead
BI455bOutFanETARepairSwitch13error repair switch of the extract air fan 13, normaly closedRead
BI456bOutFanETARepairSwitch14error repair switch of the extract air fan 14, normaly closedRead
BI457bOutFanETARepairSwitch15error repair switch of the extract air fan 15, normaly closedRead
BI458bOutFanETARepairSwitch16error repair switch of the extract air fan 16, normaly closedRead
BI459bOutFanSUPComErrmodbus communication error with the supply air fan, normaly closedRead
BI460bOutFanSUPComErr2modbus communication error with the second supply air fan, normaly closedRead
BI461bOutFanSUPComErr3modbus communication error with the supply air fan 3, normaly closedRead
BI462bOutFanSUPComErr4modbus communication error with the supply air fan 4, normaly closedRead
BI463bOutFanSUPComErr5modbus communication error with the supply air fan 5, normaly closedRead
BI464bOutFanSUPComErr6modbus communication error with the supply air fan 6, normaly closedRead
BI465bOutFanSUPComErr7modbus communication error with the supply air fan 7, normaly closedRead
BI466bOutFanSUPComErr8modbus communication error with the supply air fan 8, normaly closedRead
BI467bOutFanSUPComErr9modbus communication error with the supply air fan 9, normaly closedRead
BI468bOutFanSUPComErr10modbus communication error with the supply air fan 10, normaly closedRead
BI469bOutFanSUPComErr11modbus communication error with the supply air fan 11, normaly closedRead
BI470bOutFanSUPComErr12modbus communication error with the supply air fan 12, normaly closedRead
BI471bOutFanSUPComErr13modbus communication error with the supply air fan 13, normaly closedRead
BI472bOutFanSUPComErr14modbus communication error with the supply air fan 14, normaly closedRead
BI473bOutFanSUPComErr15modbus communication error with the supply air fan 15, normaly closedRead
BI474bOutFanSUPComErr16modbus communication error with the supply air fan 16, normaly closedRead
BI475bOutFanETAComErrmodbus communication error with the extract air fan, normaly closedRead
BI476bOutFanETAComErr2modbus communication error with the second extract air fan, normaly closedRead
BI477bOutFanETAComErr3modbus communication error with the extract air fan 3, normaly closedRead
BI478bOutFanETAComErr4modbus communication error with the extract air fan 4, normaly closedRead
BI479bOutFanETAComErr5modbus communication error with the extract air fan 5, normaly closedRead
BI480bOutFanETAComErr6modbus communication error with the extract air fan 6, normaly closedRead
BI481bOutFanETAComErr7modbus communication error with the extract air fan 7, normaly closedRead
BI482bOutFanETAComErr8modbus communication error with the extract air fan 8, normaly closedRead
BI483bOutFanETAComErr9modbus communication error with the extract air fan 9, normaly closedRead
BI484bOutFanETAComErr10modbus communication error with the extract air fan 10, normaly closedRead
BI485bOutFanETAComErr11modbus communication error with the extract air fan 11, normaly closedRead
BI486bOutFanETAComErr12modbus communication error with the extract air fan 12, normaly closedRead
BI487bOutFanETAComErr13modbus communication error with the extract air fan 13, normaly closedRead
BI488bOutFanETAComErr14modbus communication error with the extract air fan 14, normaly closedRead
BI489bOutFanETAComErr15modbus communication error with the extract air fan 15, normaly closedRead
BI490bOutFanETAComErr16modbus communication error with the extract air fan 16, normaly closedRead
BI491bOutFanSUPInErrinternal supply air fan error, normaly closedRead
BI492bOutFanSUPInErr2internal error on the second supply air fan, normaly closedRead
BI493bOutFanSUPInErr3internal error on the supply air fan 3, normaly closedRead
BI494bOutFanSUPInErr4internal error on the supply air fan 4, normaly closedRead
BI495bOutFanSUPInErr5internal error on the supply air fan 5, normaly closedRead
BI496bOutFanSUPInErr6internal error on the supply air fan 6, normaly closedRead
BI497bOutFanSUPInErr7internal error on the supply air fan 7, normaly closedRead
BI498bOutFanSUPInErr8internal error on the supply air fan 8, normaly closedRead
BI499bOutFanSUPInErr9internal error on the supply air fan 9, normaly closedRead
BI500bOutFanSUPInErr10internal error on the supply air fan 10, normaly closedRead
BI501bOutFanSUPInErr11internal error on the supply air fan 11, normaly closedRead
BI502bOutFanSUPInErr12internal error on the supply air fan 12, normaly closedRead
BI503bOutFanSUPInErr13internal error on the supply air fan 13, normaly closedRead
BI504bOutFanSUPInErr14internal error on the supply air fan 14, normaly closedRead
BI505bOutFanSUPInErr15internal error on the supply air fan 15, normaly closedRead
BI506bOutFanSUPInErr16internal error on the supply air fan 16, normaly closedRead
BI507bOutFanETAInErrinternal extract air fan error, normaly closedRead
BI508bOutFanETAInErr2internal error on the second extract air fan, normaly closedRead
BI509bOutFanETAInErr3internal error on the extract air fan 3, normaly closedRead
BI510bOutFanETAInErr4internal error on the extract air fan 4, normaly closedRead
BI511bOutFanETAInErr5internal error on the extract air fan 5, normaly closedRead
BI512bOutFanETAInErr6internal error on the extract air fan 6, normaly closedRead
BI513bOutFanETAInErr7internal error on the extract air fan 7, normaly closedRead
BI514bOutFanETAInErr8internal error on the extract air fan 8, normaly closedRead
BI515bOutFanETAInErr9internal error on the extract air fan 9, normaly closedRead
BI516bOutFanETAInErr10internal error on the extract air fan 10, normaly closedRead
BI517bOutFanETAInErr11internal error on the extract air fan 11, normaly closedRead
BI518bOutFanETAInErr12internal error on the extract air fan 12, normaly closedRead
BI519bOutFanETAInErr13internal error on the extract air fan 13, normaly closedRead
BI520bOutFanETAInErr14internal error on the extract air fan 14, normaly closedRead
BI521bOutFanETAInErr15internal error on the extract air fan 15, normaly closedRead
BI522bOutFanETAInErr16internal error on the extract air fan 16, normaly closedRead
BI523bOutFanSUPDpComErrmodbus communication error with the pressure transmitter of the supply air fanRead
BI524bOutFanSUPDpComErr2modbus communication error with the pressure transmitter of the second supply airRead
BI525bOutFanETADpComErrmodbus communication error with the pressure transmitter of the extract air fanRead
BI526bOutFanETADpComErr2modbus communication error with the pressure transmitter of the second extract airRead
BI527bOutFanSUPCtrlONcontrolled value to switch on/off the supply air fanRead
BI528bOutFanSUPCtrlON2controlled value to switch on/off the second supply air fanRead
BI529bOutFanSUPCtrlON3controlled value to switch on/off the supply air fan 3Read
BI530bOutFanSUPCtrlON4controlled value to switch on/off the supply air fan 4Read
BI531bOutFanSUPCtrlON5controlled value to switch on/off the supply air fan 5Read
BI532bOutFanSUPCtrlON6controlled value to switch on/off the supply air fan 6Read
BI533bOutFanSUPCtrlON7controlled value to switch on/off the supply air fan 7Read
BI534bOutFanSUPCtrlON8controlled value to switch on/off the supply air fan 8Read
BI535bOutFanSUPCtrlON9controlled value to switch on/off the supply air fan 9Read
BI536bOutFanSUPCtrlON10controlled value to switch on/off the supply air fan 10Read
BI537bOutFanSUPCtrlON11controlled value to switch on/off the supply air fan 11Read
BI538bOutFanSUPCtrlON12controlled value to switch on/off the supply air fan 12Read
BI539bOutFanSUPCtrlON13controlled value to switch on/off the supply air fan 13Read
BI540bOutFanSUPCtrlON14controlled value to switch on/off the supply air fan 14Read
BI541bOutFanSUPCtrlON15controlled value to switch on/off the supply air fan 15Read
BI542bOutFanSUPCtrlON16controlled value to switch on/off the supply air fan 16Read
BI543bOutFanETACtrlONcontrolled value to switch on/off the extract air fanRead
BI544bOutFanETACtrlON2controlled value to switch on/off the second extract air fanRead
BI545bOutFanETACtrlON3controlled value to switch on/off the extract air fan 3Read
BI546bOutFanETACtrlON4controlled value to switch on/off the extract air fan 4Read
BI547bOutFanETACtrlON5controlled value to switch on/off the extract air fan 5Read
BI548bOutFanETACtrlON6controlled value to switch on/off the extract air fan 6Read
BI549bOutFanETACtrlON7controlled value to switch on/off the extract air fan 7Read
BI550bOutFanETACtrlON8controlled value to switch on/off the extract air fan 8Read
BI551bOutFanETACtrlON9controlled value to switch on/off the extract air fan 9Read
BI552bOutFanETACtrlON10controlled value to switch on/off the extract air fan 10Read
BI553bOutFanETACtrlON11controlled value to switch on/off the extract air fan 11Read
BI554bOutFanETACtrlON12controlled value to switch on/off the extract air fan 12Read
BI555bOutFanETACtrlON13controlled value to switch on/off the extract air fan 13Read
BI556bOutFanETACtrlON14controlled value to switch on/off the extract air fan 14Read
BI557bOutFanETACtrlON15controlled value to switch on/off the extract air fan 15Read
BI558bOutFanETACtrlON16controlled value to switch on/off the extract air fan 16Read
AI51fOutFanSUPCtrlSpeedcontrolled value of the supply air fan speed%Read
AI52fOutFanSUPCtrlSpeed2controlled value of the second supply air fan speed%Read
AI53fOutFanETACtrlSpeedcontrolled value of the extract air fan speed%Read
AI54fOutFanETACtrlSpeed2controlled value of the second extract air fan speed%Read
AI55fOutFanSUPPVdppresent value supply air fan differential pressurePaRead
AI56fOutFanSUPPVdp2present value second supply air fan differential pressurePaRead
AI57fOutFanETAPVdppresent value extract air fan differential pressurePaRead
AI58fOutFanETAPVdp2present value second extract air fan differential pressurePaRead
AI59fOutFanSUPPVAirflowpresent value supply airflowm³/hRead
AI60fOutFanSUPPVAirflow2present value supply airflow provided by the second fanm³/hRead
AI61fOutFanETAPVAirflowpresent value extract airflowm³/hRead
AI62fOutFanETAPVAirflow2present value extract airflow provided by the second fanm³/hRead
BI559bOutFilterODAChangeErrerror outdoor air filter change required, normaly closedRead
BI560bOutFilterSUPChangeErrerror supply air filter change requiredRead
BI561bOutFilterETAChangeErrerror extract air filter change requiredRead
BI562bOutFilterODADpComErrcommunication error pressure sensor outdoor air filter, normaly closedRead
BI563bOutFilterSUPDpComErrcommunication error pressure sensor suppply air filterRead
BI564bOutFilterETADpComErrcommunication error pressure sensor extract air filterRead
AI63tOutFitlerODAHoldingTimeholding time outdoor air filterhRead
AI64tOutFitlerSUPHoldingTimeholding time supply air filterhRead
AI65tOutFitlerETAHoldingTimeholding time extract air filterhRead
AI66tOutFitlerODAOperationTimeoperation time outdoor air filterhRead
AI67tOutFitlerSUPOperationTimeoperation time supply air filterhRead
AI68tOutFitlerETAOperationTimeoperation time extract air filterhRead
AI69fOutFilterODAPVdppresent value outdoor air filter differential pressurePaRead
AI70fOutFilterSUPPVdppresent value supply air filter differential pressurePaRead
AI71fOutFilterETAPVdppresent value extract air filter differential pressurePaRead
BI565bOutFilterODAChangeErr2error second outdoor air filter change required, normaly closedRead
BI566bOutFilterSUPChangeErr2error second supply air filter change requiredRead
BI567bOutFilterETAChangeErr2error second extract air filter change requiredRead
BI568bOutFilterODADpComErr2communication error pressure sensor second outdoor air filter, normaly closedRead
BI569bOutFilterSUPDpComErr2communication error pressure sensor second supply air filterRead
BI570bOutFilterETADpComErr2communication error pressure sensor second extract air filterRead
AI72tOutFitlerODAHoldingTime2holding time second outdoor air filterhRead
AI73tOutFitlerSUPHoldingTime2holding time second supply air filterhRead
AI74tOutFitlerETAHoldingTime2holding time second extract air filterhRead
AI75tOutFitlerODAOperationTime2operation time second outdoor air filterhRead
AI76tOutFitlerSUPOperationTime2operation time second supply air filterhRead
AI77tOutFitlerETAOperationTime2operation time second extract air filterhRead
AI78fOutFilterODAPVdp2present value second outdoor air filter differential pressurePaRead
AI79fOutFilterSUPPVdp2present value second supply air filter differential pressurePaRead
AI80fOutFilterETAPVdp2present value second extract air filter differential pressurePaRead
BI571bOutPlateHexDamperComErrmodbus communication error with the plate heat exchanger damper, normaly closedRead
BI572bOutPlateHexDamperComErr2modbus communication error with the second plate heat exchanger damper, normaly closedRead
BI573bOutPlateHexDpComErrmodbus communication error with the plate heat exchanger differential pressure sensor, normalyRead
AI81fOutPlatehexPVdppresent value plate heat exchanger differential pressurePaRead
AI82fOutPlatehexDamperCtrlPoscontrolled value bypass plate heat exchanger%Read
AI83fOutPlatehexDamperCtrlPos2controlled value of the second bypass plate heat exchanger%Read
AI84fOutPlatehexDamperPVPoscurrent position bypass plate heat exchanger%Read
AI85fOutPlatehexDamperPVPos2current position second bypass plate heat exchanger%Read
BI574bOutRotHexInErrinternal error of the heat recovery wheel, normaly closedRead
BI575bOutRotHexComErrmodbus communication error with the heat recovery wheel, normaly closedRead
BI576bOutRotHexCtrlRelcontrolled value to release the heat recovery wheel, normaly closedRead
AI86fOutRothexCtrlcontrolled value heat recovery wheel speed%Read
BI577bOutComErrSenHumODAmodbus communication error with the outdoor air humidity sensor, normaly closedRead
BI578bOutComErrSenHumSUPmodbus communication error with the supply air humidity sensor, normaly closedRead
BI579bOutComErrSenHumETAmodbus communication error with the extract air humidity sensor, normaly closedRead
BI580bOutComErrSenHumEHAmodbus communication error with the exhaust air humidity sensor, normaly closedRead
BI581bOutComErrSenTempODAmodbus communication error with the outdoor air temperature sensor, normaly closedRead
BI582bOutComErrSenTempSUPmodbus communication error with the supply air temperature sensor, normaly closedRead
BI583bOutComErrSenTempETAmodbus communication error with the extract air temperature sensor, normaly closedRead
BI584bOutComErrSenTempEHAmodbus communication error with the exhaust air temperature sensor, normaly closedRead
BI585bOutComErrSenDpSUPmodbus communication error with the supply air pressure sensor, normaly closedRead
BI586bOutComErrSenDpETAmodbus communication error with the extract air pressure sensor, normaly closedRead
BI587bOutComErrSenCO2modbus communication error with the CO2 sensor, normaly closedRead
BI588bOutComErrSenVOCmodbus communication error with the VOC sensor, normaly closedRead
AI87fOutSPTempSUPcurrent set point of the supply air temperature°CRead
AI88fOutSPTempETAcurrent set point of the extract or room air temperature°CRead
AImin89eOutPVOperationModecurrent operation mode of the air handling unitRead0=off, 1=standby, 2=control, 3=freeze protection, 4=deicing, 5=startup, 6=shutdown, 7=manual, 8=nightpurge, 9=intermittent Operation, 10=cooling protection, 11=fire protection
BI589bOutKVS2BrinePressure1Pressure step 1 triggered 0=Off, 1=OnRead0=Off, 1=On
BI590bOutKVS2BrinePressure2Pressure step 2 triggered 0=Off, 1=OnRead0=Off, 1=On
BI591bOutKVS2MsgAutoPumpOffauto pump stop PRIO=2Read
BI592bOutKVS2MsgBrinePressureCriticalcritical brine pressure PRIO=3Read
BI593bOutKVS2MsgBrinePressureLowbrine pressure have to be checked PRIO=2Read
BI594bOutKVS2MsgFrostFeedCoilalarm feed coil frosting Prio=3Read
BI595bOutKVS2MsgMinTempInletETAexhaust air heat exchanger is frosting Prio=2Read
BI596bOutKVS2MsgNoFeedfeed doesnt have cooling or heating effects Prio=2Read
BI597bOutKVS2MsgNoRecoveryheat recovery is currently not possible Prio=2Read
BI598bOutKVS2MsgPumpErrorPump errorRead
BI599bOutKVS2ReleasePumpPump releaseRead
BI600bOutKVS2StateCoolingFeedstate of the cooling feed TRUE, if feeding is activeRead
BI601bOutKVS2StateFastModestate of the fast cool- or heating mode TRUE, if activeRead
BI602bOutKVS2StateHeatExchangerOperationstate of the operation signalRead
BI603bOutKVS2StateHeatingFeedstate of the heating feed TRUE, if feeding is activeRead
AI90fOutKVS2CtrlFrostProtectionValvecontrolled value run around coil frost protection valve%Read
AI91fOutKVS2CtrlPowerValvecontrolled value run around coil power valve%Read
AI92fOutKVS2CtrlPumpcontrolled value run around coil pump%Read
AI93fOutKVS2BrineVolumeFlowpresent value brine volume flowm³/hRead
AI94fOutKVS2TempETAIncurrent value inlet temperature of exhaust air heat exchanger°CRead
AI95fOutKVS2TempETAOutcurrent value return temperature exhaust air heat exchanger°CRead
AI96fOutKVS2TempPreFeedcurrent value brine temperature°CRead
AI97fOutKVS2TempSUPIncurrent value inlet temperature of the fresh air heat exchanger°CRead
AI98fOutKVS2TempSUPOutcurrent value outlet temperature of the fresh air heat exchanger°CRead
AI99fOutKVS2ThermalPowerSUPcurrent value thermal power of the fresh air heat exchangerWRead
AI100fOutKVS2ThermalPowerETAcurrent value thermal power of the exhaust air heat exchangerWRead
AI101fOutKVS2ThermalPowerFeedHeatcurrent value thermal power of the heating feedWRead
AI102fOutKVS2ThermalPowerFeedCoolcurrent value thermal power of the cooling feedWRead
BI604bOutIKMsgOilManagementOil management errorRead
BI605bOutIKMsgLowPressureLow pressure errorRead
BI606bOutIKMsgHighPressureHigh pressure errorRead
BI607bOutIKMsgSuperHeatingControllererror super heating controllerRead
BI608bOutIKMsgMotorProtection1error first compressorRead
BI609bOutIKMsgMotorProtection2error second compressorRead
BI610bOutIKMsgMotorProtection3error third compressorRead
BI611bOutIKCtrlPWM1actuating value pwm compressor 1Read
BI612bOutIKCtrlPWM2actuating value pwm compressor 2Read
BI613bOutIKCtrlPWM3actuating value pwm compressor 3Read
BI614bOutIKCtrlSoftStarterOn1actuating value soft starter compressor 1Read
BI615bOutIKCtrlSoftStarterOn2actuating value soft starter compressor 2Read
BI616bOutIKCtrlSoftStarterOn3actuating value soft starter compressor 3Read
BI617bOutIKMsgHighTempHigh compressor end temperature errorRead
BI618bOutIKMsgEAPComErrorerror with EAP-Communication unitRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the X-CUBE Control BACnet data point list and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TROX X-CUBE Control BACnet data point list

How many BACnet points does the TROX X-CUBE Control BACnet data point list have?

This list has 743 BACnet objects: 103 analog inputs, 12 analog outputs, 619 binary inputs, 5 binary outputs, 1 device, 2 files, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TROX X-CUBE Control BACnet data point list BACnet points are writable?

17 of the 743 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TROX X-CUBE Control BACnet data point list BACnet documentation?

The source is BACnet EDE-File XCUBE (BACnet DPL) (V003), revision 2014-10, published free by TROX at https://www.trox.de/en/downloads/ad12a8c8fa3e2cc5/bacnet.pdf.

What are the minimum BACnet points to integrate the TROX X-CUBE Control BACnet data point list?

Start with AO 5 eInSystemMode (Operation mode command: 0 off, 1 manual, 2 auto); BO 7 bInSPStandby (Standby when true; must be false for auto run); AO 8 fInSPFanSUP (Supply fan setpoint); AO 14 fInSPTempSUPMin (Minimum supply air temperature setpoint); BO 1 bInHeartBeat2PLC (BMS-to-PLC heartbeat); BO 2 bInResetErrors (Resets all errors); AI 89 eOutPVOperationMode (Actual operating mode); AI 3 fOutPVTempSUP (Supply air temperature); AI 4 fOutPVTempETA (Extract air temperature); AI 1 eOutEventNotification (No error / warning / critical error).

How do I enable BMS control of the TROX X-CUBE Control BACnet data point list?

AO-5 eInSystemMode sets the operation mode (0=unit off, 1=manual, 2=auto); the unit runs in auto only when eInSystemMode is 2, BO-7 bInSPStandby is false and there is no critical error.

Does the TROX X-CUBE Control BACnet data point list need a BACnet heartbeat or have a communication timeout?

BO-1 bInHeartBeat2PLC is the heartbeat from the BMS to the unit PLC and BI-0 bOutHeartbeat2BMS is the PLC's heartbeat back to the BMS. The list does not state a timeout or what the unit does if the BMS heartbeat stops.

Can the BMS supply sensor values to the TROX X-CUBE Control BACnet data point list?

A BMS outdoor temperature can be written to AO-6 fInMeasTempOutdoor. No source-select or timeout object is listed for it.

How do I check these points on the real X-CUBE Control BACnet data point list?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BACnet EDE-File XCUBE (BACnet DPL) · V003 · rev. 2014-10. Object names, instances and units are reproduced as published; descriptions are our own.