 "manufacturer": "TROX",
 "manufacturer_slug": "trox",
 "model": "X-CUBE Control BACnet data point list",
 "model_slug": "x-cube-control",
 "aliases": [
  "X-CUBE",
  "TROX X-CUBE",
  "X-CUBE Control",
  "BACnet DPL",
  "BACnet EDE XCUBE"
 ],
 "equipment_type": "Air handling unit controller",
 "applies_to": "TROX X-CUBE central air handling units with the factory X-CUBE Control system.",
 "summary": "TROX X-CUBE air handlers are controlled by a factory PLC (X-CUBE Control) that connects to a BMS over BACnet IP. TROX publishes the maximum data point list as an EDE-style table: 17 BMS write objects (heartbeat, reset, system mode, standby, external outdoor temperature and fan/temperature/humidity setpoints), about 100 analog inputs for temperatures, humidities, pressures, airflows, valve/damper/fan positions and filter data, and over 600 binary inputs for alarms, fire dampers, fans and heat recovery. Which objects are live depends on the unit's actual configuration.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": 200,
 "access_inferred": false,
 "notes": [
  "This is the maximum list; objects for components a unit doesn't have (extra fans, dampers, fire dampers, KVS run-around coil) stay unused.",
  "BMS write objects are the AO/BO block (BO-1..4, AO-5..17); everything else is read-only.",
  "Units come from the EDE unit-code column (BACnet engineering unit enums: 62=°C, 98=%, 53=Pa, 135=m³/h, 29=%RH, 28=g/kg, 96=ppm, 48=W, 71=h).",
  "Binary inputs reference state-text table 1, which is not printed in this document.",
  "Fan setpoints AO-8/9 carry no engineering unit in the list.",
  "The device instance 200 and device name TROX_856581 come from the example EDE and will differ per unit."
 ],
 "source": {
  "title": "BACnet EDE-File XCUBE (BACnet DPL)",
  "doc_number": "V003",
  "revision_date": "2014-10",
  "url": "https://www.trox.de/en/downloads/ad12a8c8fa3e2cc5/bacnet.pdf"
 },
 "integration": {
  "summary": "Write AO-5 eInSystemMode = 2 (auto) and keep BO-7 bInSPStandby false so the unit runs, toggle BO-1 bInHeartBeat2PLC so the PLC sees the BMS, and set the supply/extract fan and temperature/humidity setpoints in AO-8..17. Read back AI-89 eOutPVOperationMode, AI-1 eOutEventNotification and the main temperatures, and use BO-2 to reset errors. The list marks the objects that must be set in green; those are the AO/BO block.",
  "minimum_points": [
   {
    "ref": "AO 5",
    "name": "eInSystemMode",
    "why": "Operation mode command: 0 off, 1 manual, 2 auto"
   },
   {
    "ref": "BO 7",
    "name": "bInSPStandby",
    "why": "Standby when true; must be false for auto run"
   },
   {
    "ref": "AO 8",
    "name": "fInSPFanSUP",
    "why": "Supply fan setpoint"
   },
   {
    "ref": "AO 14",
    "name": "fInSPTempSUPMin",
    "why": "Minimum supply air temperature setpoint"
   },
   {
    "ref": "BO 1",
    "name": "bInHeartBeat2PLC",
    "why": "BMS-to-PLC heartbeat"
   },
   {
    "ref": "BO 2",
    "name": "bInResetErrors",
    "why": "Resets all errors"
   },
   {
    "ref": "AI 89",
    "name": "eOutPVOperationMode",
    "why": "Actual operating mode"
   },
   {
    "ref": "AI 3",
    "name": "fOutPVTempSUP",
    "why": "Supply air temperature"
   },
   {
    "ref": "AI 4",
    "name": "fOutPVTempETA",
    "why": "Extract air temperature"
   },
   {
    "ref": "AI 1",
    "name": "eOutEventNotification",
    "why": "No error / warning / critical error"
   }
  ],
  "enable": "AO-5 eInSystemMode sets the operation mode (0=unit off, 1=manual, 2=auto); the unit runs in auto only when eInSystemMode is 2, BO-7 bInSPStandby is false and there is no critical error.",
  "heartbeat": "BO-1 bInHeartBeat2PLC is the heartbeat from the BMS to the unit PLC and BI-0 bOutHeartbeat2BMS is the PLC's heartbeat back to the BMS. The list does not state a timeout or what the unit does if the BMS heartbeat stops.",
  "remote_sensors": "A BMS outdoor temperature can be written to AO-6 fInMeasTempOutdoor. No source-select or timeout object is listed for it.",
  "setup": [
   "BACnet IP; the EDE example uses device instance 200 (device object name TROX_856581), which is unit specific."
  ],
  "gotchas": [
   "Fan and temperature setpoints have default 0 and full float range in the list; write sensible values before enabling auto.",
   "BO-4 bInTestFireDampers starts a test of all fire dampers.",
   "Many alarm BIs are described as 'normally closed' contacts; check polarity during commissioning.",
   "Humidity setpoints (AO-12/13, 16/17) are in g/kg (absolute), while humidity readings are %RH."
  ]
 },
 "points": [
  {
   "type": "DEV",
   "instance": 200,
   "name": "TROX_856581",
   "description": "Informational object",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "FILE",
   "instance": 0,
   "name": "CurrentConfig.xml",
   "description": "Informational object",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "FILE",
   "instance": 1,
   "name": "BACnetOnline_1010010.wbp",
   "description": "Informational object",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "Other",
   "instance": 0,
   "name": "IO",
   "description": "Informational object",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "bInHeartBeat2PLC",
   "description": "Heart beat from BMS to the local PLC",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "bInResetErrors",
   "description": "reset all errors",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "bInLight",
   "description": "Switch on/off",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "bInTestFireDampers",
   "description": "starts test of all fire dampers",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "eInSystemMode",
   "description": "set the units operation mode",
   "units": "",
   "access": "C",
   "states": "0=units off, 1=manual mode, 2=auto"
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "fInMeasTempOutdoor",
   "description": "present value outdoor temperature",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 7,
   "name": "bInSPStandby",
   "description": "Puts the unit in standby when true",
   "units": "",
   "access": "C",
   "states": "true=standby, false=auto if eInSystemMode=2"
  },
  {
   "type": "AO",
   "instance": 8,
   "name": "fInSPFanSUP",
   "description": "setpoint of the supply air fan",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 9,
   "name": "fInSPFanETA",
   "description": "setpoint of the extract air fan",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 10,
   "name": "fInSPTempMin",
   "description": "setpoint of the minimal air temperature",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 11,
   "name": "fInSPTempMax",
   "description": "setpoint of the maximal air temperature",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 12,
   "name": "fInSPHumMin",
   "description": "setpoint of the minimal air humidity",
   "units": "g/kg",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 13,
   "name": "fInSPHumMax",
   "description": "setpoint of the maximal air humidity",
   "units": "g/kg",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 14,
   "name": "fInSPTempSUPMin",
   "description": "setpoint of the minimal supply air temperature",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 15,
   "name": "fInSPTempSUPMax",
   "description": "setpoint of the maximal supply air temperature",
   "units": "°C",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 16,
   "name": "fInSPHumSUPMin",
   "description": "setpoint of the minimal supply air humidity",
   "units": "g/kg",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 17,
   "name": "fInSPHumSUPMax",
   "description": "setpoint of the maximal supply air humidity",
   "units": "g/kg",
   "access": "C",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "bOutHeartbeat2BMS",
   "description": "heart beat from to local plc to the BMS",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "bOutLight",
   "description": "true if the light is on otherwise false",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "bOutExtLock",
   "description": "false if the unit have been lock over an external signal otherwise",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "bOutExtAlarm1",
   "description": "State of the extern alarm number 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "bOutExtAlarm2",
   "description": "State of the extern alarm number 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "bOutExtAlarm3",
   "description": "State of the extern alarm number 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "bOutExtAlarm4",
   "description": "State of the extern alarm number 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "bOutExtAlarm5",
   "description": "State of the extern alarm number 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "bOutExtAlarm6",
   "description": "State of the extern alarm number 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "bOutExtAlarm7",
   "description": "State of the extern alarm number 7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "bOutExtAlarm8",
   "description": "State of the extern alarm number 8",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "bOutExtAlarm9",
   "description": "State of the extern alarm number 9",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "bOutExtAlarm10",
   "description": "State of the extern alarm number 10",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "bOutFireDamperClosed1",
   "description": "contact fire damper 1 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "bOutFireDamperClosed2",
   "description": "contact fire damper 2 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "bOutFireDamperClosed3",
   "description": "contact fire damper 3 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "bOutFireDamperClosed4",
   "description": "contact fire damper 4 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "bOutFireDamperClosed5",
   "description": "contact fire damper 5 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "bOutFireDamperClosed6",
   "description": "contact fire damper 6 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "bOutFireDamperClosed7",
   "description": "contact fire damper 7 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "bOutFireDamperClosed8",
   "description": "contact fire damper 8 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "bOutFireDamperClosed9",
   "description": "contact fire damper 9 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "bOutFireDamperClosed10",
   "description": "contact fire damper 10 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "bOutFireDamperClosed11",
   "description": "contact fire damper 11 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "bOutFireDamperClosed12",
   "description": "contact fire damper 12 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "bOutFireDamperClosed13",
   "description": "contact fire damper 13 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "bOutFireDamperClosed14",
   "description": "contact fire damper 14 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "bOutFireDamperClosed15",
   "description": "contact fire damper 15 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "bOutFireDamperClosed16",
   "description": "contact fire damper 16 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "bOutFireDamperClosed17",
   "description": "contact fire damper 17 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "bOutFireDamperClosed18",
   "description": "contact fire damper 18 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "bOutFireDamperClosed19",
   "description": "contact fire damper 19 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "bOutFireDamperClosed20",
   "description": "contact fire damper 20 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "bOutFireDamperClosed21",
   "description": "contact fire damper 21 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "bOutFireDamperClosed22",
   "description": "contact fire damper 22 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "bOutFireDamperClosed23",
   "description": "contact fire damper 23 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "bOutFireDamperClosed24",
   "description": "contact fire damper 24 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "bOutFireDamperClosed25",
   "description": "contact fire damper 25 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "bOutFireDamperClosed26",
   "description": "contact fire damper 26 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 39,
   "name": "bOutFireDamperClosed27",
   "description": "contact fire damper 27 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "bOutFireDamperClosed28",
   "description": "contact fire damper 28 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "bOutFireDamperClosed29",
   "description": "contact fire damper 29 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 42,
   "name": "bOutFireDamperClosed30",
   "description": "contact fire damper 30 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "bOutFireDamperClosed31",
   "description": "contact fire damper 31 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "bOutFireDamperClosed32",
   "description": "contact fire damper 32 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 45,
   "name": "bOutFireDamperClosed33",
   "description": "contact fire damper 33 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 46,
   "name": "bOutFireDamperClosed34",
   "description": "contact fire damper 34 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 47,
   "name": "bOutFireDamperClosed35",
   "description": "contact fire damper 35 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 48,
   "name": "bOutFireDamperClosed36",
   "description": "contact fire damper 36 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 49,
   "name": "bOutFireDamperClosed37",
   "description": "contact fire damper 37 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 50,
   "name": "bOutFireDamperClosed38",
   "description": "contact fire damper 38 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 51,
   "name": "bOutFireDamperClosed39",
   "description": "contact fire damper 39 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 52,
   "name": "bOutFireDamperClosed40",
   "description": "contact fire damper 40 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 53,
   "name": "bOutFireDamperClosed41",
   "description": "contact fire damper 41 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 54,
   "name": "bOutFireDamperClosed42",
   "description": "contact fire damper 42 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 55,
   "name": "bOutFireDamperClosed43",
   "description": "contact fire damper 43 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 56,
   "name": "bOutFireDamperClosed44",
   "description": "contact fire damper 44 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 57,
   "name": "bOutFireDamperClosed45",
   "description": "contact fire damper 45 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 58,
   "name": "bOutFireDamperClosed46",
   "description": "contact fire damper 46 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 59,
   "name": "bOutFireDamperClosed47",
   "description": "contact fire damper 47 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 60,
   "name": "bOutFireDamperClosed48",
   "description": "contact fire damper 48 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 61,
   "name": "bOutFireDamperClosed49",
   "description": "contact fire damper 49 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 62,
   "name": "bOutFireDamperClosed50",
   "description": "contact fire damper 50 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 63,
   "name": "bOutFireDamperClosed51",
   "description": "contact fire damper 51 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 64,
   "name": "bOutFireDamperClosed52",
   "description": "contact fire damper 52 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 65,
   "name": "bOutFireDamperClosed53",
   "description": "contact fire damper 53 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 66,
   "name": "bOutFireDamperClosed54",
   "description": "contact fire damper 54 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 67,
   "name": "bOutFireDamperClosed55",
   "description": "contact fire damper 55 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 68,
   "name": "bOutFireDamperClosed56",
   "description": "contact fire damper 56 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 69,
   "name": "bOutFireDamperClosed57",
   "description": "contact fire damper 57 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 70,
   "name": "bOutFireDamperClosed58",
   "description": "contact fire damper 58 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 71,
   "name": "bOutFireDamperClosed59",
   "description": "contact fire damper 59 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 72,
   "name": "bOutFireDamperClosed60",
   "description": "contact fire damper 60 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 73,
   "name": "bOutFireDamperClosed61",
   "description": "contact fire damper 61 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 74,
   "name": "bOutFireDamperClosed62",
   "description": "contact fire damper 62 closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 75,
   "name": "bOutFireDamperOpened1",
   "description": "contact fire damper 1 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 76,
   "name": "bOutFireDamperOpened2",
   "description": "contact fire damper 2 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 77,
   "name": "bOutFireDamperOpened3",
   "description": "contact fire damper 3 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 78,
   "name": "bOutFireDamperOpened4",
   "description": "contact fire damper 4 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 79,
   "name": "bOutFireDamperOpened5",
   "description": "contact fire damper 5 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 80,
   "name": "bOutFireDamperOpened6",
   "description": "contact fire damper 6 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 81,
   "name": "bOutFireDamperOpened7",
   "description": "contact fire damper 7 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 82,
   "name": "bOutFireDamperOpened8",
   "description": "contact fire damper 8 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 83,
   "name": "bOutFireDamperOpened9",
   "description": "contact fire damper 9 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 84,
   "name": "bOutFireDamperOpened10",
   "description": "contact fire damper 10 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 85,
   "name": "bOutFireDamperOpened11",
   "description": "contact fire damper 11 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 86,
   "name": "bOutFireDamperOpened12",
   "description": "contact fire damper 12 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 87,
   "name": "bOutFireDamperOpened13",
   "description": "contact fire damper 13 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 88,
   "name": "bOutFireDamperOpened14",
   "description": "contact fire damper 14 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 89,
   "name": "bOutFireDamperOpened15",
   "description": "contact fire damper 15 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 90,
   "name": "bOutFireDamperOpened16",
   "description": "contact fire damper 16 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 91,
   "name": "bOutFireDamperOpened17",
   "description": "contact fire damper 17 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 92,
   "name": "bOutFireDamperOpened18",
   "description": "contact fire damper 18 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 93,
   "name": "bOutFireDamperOpened19",
   "description": "contact fire damper 19 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 94,
   "name": "bOutFireDamperOpened20",
   "description": "contact fire damper 20 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 95,
   "name": "bOutFireDamperOpened21",
   "description": "contact fire damper 21 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 96,
   "name": "bOutFireDamperOpened22",
   "description": "contact fire damper 22 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 97,
   "name": "bOutFireDamperOpened23",
   "description": "contact fire damper 23 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 98,
   "name": "bOutFireDamperOpened24",
   "description": "contact fire damper 24 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 99,
   "name": "bOutFireDamperOpened25",
   "description": "contact fire damper 25 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "bOutFireDamperOpened26",
   "description": "contact fire damper 26 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 101,
   "name": "bOutFireDamperOpened27",
   "description": "contact fire damper 27 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 102,
   "name": "bOutFireDamperOpened28",
   "description": "contact fire damper 28 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 103,
   "name": "bOutFireDamperOpened29",
   "description": "contact fire damper 29 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "bOutFireDamperOpened30",
   "description": "contact fire damper 30 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "bOutFireDamperOpened31",
   "description": "contact fire damper 31 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 106,
   "name": "bOutFireDamperOpened32",
   "description": "contact fire damper 32 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 107,
   "name": "bOutFireDamperOpened33",
   "description": "contact fire damper 33 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 108,
   "name": "bOutFireDamperOpened34",
   "description": "contact fire damper 34 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 109,
   "name": "bOutFireDamperOpened35",
   "description": "contact fire damper 35 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 110,
   "name": "bOutFireDamperOpened36",
   "description": "contact fire damper 36 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 111,
   "name": "bOutFireDamperOpened37",
   "description": "contact fire damper 37 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 112,
   "name": "bOutFireDamperOpened38",
   "description": "contact fire damper 38 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 113,
   "name": "bOutFireDamperOpened39",
   "description": "contact fire damper 39 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 114,
   "name": "bOutFireDamperOpened40",
   "description": "contact fire damper 40 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 115,
   "name": "bOutFireDamperOpened41",
   "description": "contact fire damper 41 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 116,
   "name": "bOutFireDamperOpened42",
   "description": "contact fire damper 42 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 117,
   "name": "bOutFireDamperOpened43",
   "description": "contact fire damper 43 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 118,
   "name": "bOutFireDamperOpened44",
   "description": "contact fire damper 44 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 119,
   "name": "bOutFireDamperOpened45",
   "description": "contact fire damper 45 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 120,
   "name": "bOutFireDamperOpened46",
   "description": "contact fire damper 46 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 121,
   "name": "bOutFireDamperOpened47",
   "description": "contact fire damper 47 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 122,
   "name": "bOutFireDamperOpened48",
   "description": "contact fire damper 48 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 123,
   "name": "bOutFireDamperOpened49",
   "description": "contact fire damper 49 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 124,
   "name": "bOutFireDamperOpened50",
   "description": "contact fire damper 50 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 125,
   "name": "bOutFireDamperOpened51",
   "description": "contact fire damper 51 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 126,
   "name": "bOutFireDamperOpened52",
   "description": "contact fire damper 52 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 127,
   "name": "bOutFireDamperOpened53",
   "description": "contact fire damper 53 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 128,
   "name": "bOutFireDamperOpened54",
   "description": "contact fire damper 54 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 129,
   "name": "bOutFireDamperOpened55",
   "description": "contact fire damper 55 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 130,
   "name": "bOutFireDamperOpened56",
   "description": "contact fire damper 56 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 131,
   "name": "bOutFireDamperOpened57",
   "description": "contact fire damper 57 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 132,
   "name": "bOutFireDamperOpened58",
   "description": "contact fire damper 58 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 133,
   "name": "bOutFireDamperOpened59",
   "description": "contact fire damper 59 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 134,
   "name": "bOutFireDamperOpened60",
   "description": "contact fire damper 60 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 135,
   "name": "bOutFireDamperOpened61",
   "description": "contact fire damper 61 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 136,
   "name": "bOutFireDamperOpened62",
   "description": "contact fire damper 62 Opened",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 137,
   "name": "bOutFireDamperErrClosingRuntime1",
   "description": "Error closing runtime fire damper 1, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 138,
   "name": "bOutFireDamperErrClosingRuntime2",
   "description": "Error closing runtime fire damper 2, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 139,
   "name": "bOutFireDamperErrClosingRuntime3",
   "description": "Error closing runtime fire damper 3, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 140,
   "name": "bOutFireDamperErrClosingRuntime4",
   "description": "Error closing runtime fire damper 4, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 141,
   "name": "bOutFireDamperErrClosingRuntime5",
   "description": "Error closing runtime fire damper 5, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 142,
   "name": "bOutFireDamperErrClosingRuntime6",
   "description": "Error closing runtime fire damper 6, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 143,
   "name": "bOutFireDamperErrClosingRuntime7",
   "description": "Error closing runtime fire damper 7, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 144,
   "name": "bOutFireDamperErrClosingRuntime8",
   "description": "Error closing runtime fire damper 8, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 145,
   "name": "bOutFireDamperErrClosingRuntime9",
   "description": "Error closing runtime fire damper 9, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 146,
   "name": "bOutFireDamperErrClosingRuntime10",
   "description": "Error closing runtime fire damper 10, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 147,
   "name": "bOutFireDamperErrClosingRuntime11",
   "description": "Error closing runtime fire damper 11, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 148,
   "name": "bOutFireDamperErrClosingRuntime12",
   "description": "Error closing runtime fire damper 12, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 149,
   "name": "bOutFireDamperErrClosingRuntime13",
   "description": "Error closing runtime fire damper 13, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 150,
   "name": "bOutFireDamperErrClosingRuntime14",
   "description": "Error closing runtime fire damper 14, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 151,
   "name": "bOutFireDamperErrClosingRuntime15",
   "description": "Error closing runtime fire damper 15, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 152,
   "name": "bOutFireDamperErrClosingRuntime16",
   "description": "Error closing runtime fire damper 16, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 153,
   "name": "bOutFireDamperErrClosingRuntime17",
   "description": "Error closing runtime fire damper 17, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 154,
   "name": "bOutFireDamperErrClosingRuntime18",
   "description": "Error closing runtime fire damper 18, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 155,
   "name": "bOutFireDamperErrClosingRuntime19",
   "description": "Error closing runtime fire damper 19, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 156,
   "name": "bOutFireDamperErrClosingRuntime20",
   "description": "Error closing runtime fire damper 20, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 157,
   "name": "bOutFireDamperErrClosingRuntime21",
   "description": "Error closing runtime fire damper 21, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 158,
   "name": "bOutFireDamperErrClosingRuntime22",
   "description": "Error closing runtime fire damper 22, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 159,
   "name": "bOutFireDamperErrClosingRuntime23",
   "description": "Error closing runtime fire damper 23, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 160,
   "name": "bOutFireDamperErrClosingRuntime24",
   "description": "Error closing runtime fire damper 24, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 161,
   "name": "bOutFireDamperErrClosingRuntime25",
   "description": "Error closing runtime fire damper 25, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 162,
   "name": "bOutFireDamperErrClosingRuntime26",
   "description": "Error closing runtime fire damper 26, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 163,
   "name": "bOutFireDamperErrClosingRuntime27",
   "description": "Error closing runtime fire damper 27, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 164,
   "name": "bOutFireDamperErrClosingRuntime28",
   "description": "Error closing runtime fire damper 28, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 165,
   "name": "bOutFireDamperErrClosingRuntime29",
   "description": "Error closing runtime fire damper 29, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 166,
   "name": "bOutFireDamperErrClosingRuntime30",
   "description": "Error closing runtime fire damper 30, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 167,
   "name": "bOutFireDamperErrClosingRuntime31",
   "description": "Error closing runtime fire damper 31, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 168,
   "name": "bOutFireDamperErrClosingRuntime32",
   "description": "Error closing runtime fire damper 32, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 169,
   "name": "bOutFireDamperErrClosingRuntime33",
   "description": "Error closing runtime fire damper 33, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 170,
   "name": "bOutFireDamperErrClosingRuntime34",
   "description": "Error closing runtime fire damper 34, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 171,
   "name": "bOutFireDamperErrClosingRuntime35",
   "description": "Error closing runtime fire damper 35, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 172,
   "name": "bOutFireDamperErrClosingRuntime36",
   "description": "Error closing runtime fire damper 36, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 173,
   "name": "bOutFireDamperErrClosingRuntime37",
   "description": "Error closing runtime fire damper 37, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 174,
   "name": "bOutFireDamperErrClosingRuntime38",
   "description": "Error closing runtime fire damper 38, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 175,
   "name": "bOutFireDamperErrClosingRuntime39",
   "description": "Error closing runtime fire damper 39, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 176,
   "name": "bOutFireDamperErrClosingRuntime40",
   "description": "Error closing runtime fire damper 40, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 177,
   "name": "bOutFireDamperErrClosingRuntime41",
   "description": "Error closing runtime fire damper 41, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 178,
   "name": "bOutFireDamperErrClosingRuntime42",
   "description": "Error closing runtime fire damper 42, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 179,
   "name": "bOutFireDamperErrClosingRuntime43",
   "description": "Error closing runtime fire damper 43, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 180,
   "name": "bOutFireDamperErrClosingRuntime44",
   "description": "Error closing runtime fire damper 44, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 181,
   "name": "bOutFireDamperErrClosingRuntime45",
   "description": "Error closing runtime fire damper 45, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 182,
   "name": "bOutFireDamperErrClosingRuntime46",
   "description": "Error closing runtime fire damper 46, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 183,
   "name": "bOutFireDamperErrClosingRuntime47",
   "description": "Error closing runtime fire damper 47, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 184,
   "name": "bOutFireDamperErrClosingRuntime48",
   "description": "Error closing runtime fire damper 48, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 185,
   "name": "bOutFireDamperErrClosingRuntime49",
   "description": "Error closing runtime fire damper 49, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 186,
   "name": "bOutFireDamperErrClosingRuntime50",
   "description": "Error closing runtime fire damper 50, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 187,
   "name": "bOutFireDamperErrClosingRuntime51",
   "description": "Error closing runtime fire damper 51, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 188,
   "name": "bOutFireDamperErrClosingRuntime52",
   "description": "Error closing runtime fire damper 52, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 189,
   "name": "bOutFireDamperErrClosingRuntime53",
   "description": "Error closing runtime fire damper 53, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 190,
   "name": "bOutFireDamperErrClosingRuntime54",
   "description": "Error closing runtime fire damper 54, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 191,
   "name": "bOutFireDamperErrClosingRuntime55",
   "description": "Error closing runtime fire damper 55, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 192,
   "name": "bOutFireDamperErrClosingRuntime56",
   "description": "Error closing runtime fire damper 56, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 193,
   "name": "bOutFireDamperErrClosingRuntime57",
   "description": "Error closing runtime fire damper 57, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 194,
   "name": "bOutFireDamperErrClosingRuntime58",
   "description": "Error closing runtime fire damper 58, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 195,
   "name": "bOutFireDamperErrClosingRuntime59",
   "description": "Error closing runtime fire damper 59, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 196,
   "name": "bOutFireDamperErrClosingRuntime60",
   "description": "Error closing runtime fire damper 60, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 197,
   "name": "bOutFireDamperErrClosingRuntime61",
   "description": "Error closing runtime fire damper 61, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 198,
   "name": "bOutFireDamperErrClosingRuntime62",
   "description": "Error closing runtime fire damper 62, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 199,
   "name": "bOutFireDamperErrOpeningRuntime1",
   "description": "Error Opening runtime fire damper 1, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 200,
   "name": "bOutFireDamperErrOpeningRuntime2",
   "description": "Error Opening runtime fire damper 2, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 201,
   "name": "bOutFireDamperErrOpeningRuntime3",
   "description": "Error Opening runtime fire damper 3, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 202,
   "name": "bOutFireDamperErrOpeningRuntime4",
   "description": "Error Opening runtime fire damper 4, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 203,
   "name": "bOutFireDamperErrOpeningRuntime5",
   "description": "Error Opening runtime fire damper 5, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 204,
   "name": "bOutFireDamperErrOpeningRuntime6",
   "description": "Error Opening runtime fire damper 6, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 205,
   "name": "bOutFireDamperErrOpeningRuntime7",
   "description": "Error Opening runtime fire damper 7, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 206,
   "name": "bOutFireDamperErrOpeningRuntime8",
   "description": "Error Opening runtime fire damper 8, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 207,
   "name": "bOutFireDamperErrOpeningRuntime9",
   "description": "Error Opening runtime fire damper 9, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 208,
   "name": "bOutFireDamperErrOpeningRuntime10",
   "description": "Error Opening runtime fire damper 10, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 209,
   "name": "bOutFireDamperErrOpeningRuntime11",
   "description": "Error Opening runtime fire damper 11, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 210,
   "name": "bOutFireDamperErrOpeningRuntime12",
   "description": "Error Opening runtime fire damper 12, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 211,
   "name": "bOutFireDamperErrOpeningRuntime13",
   "description": "Error Opening runtime fire damper 13, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 212,
   "name": "bOutFireDamperErrOpeningRuntime14",
   "description": "Error Opening runtime fire damper 14, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 213,
   "name": "bOutFireDamperErrOpeningRuntime15",
   "description": "Error Opening runtime fire damper 15, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 214,
   "name": "bOutFireDamperErrOpeningRuntime16",
   "description": "Error Opening runtime fire damper 16, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 215,
   "name": "bOutFireDamperErrOpeningRuntime17",
   "description": "Error Opening runtime fire damper 17, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 216,
   "name": "bOutFireDamperErrOpeningRuntime18",
   "description": "Error Opening runtime fire damper 18, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 217,
   "name": "bOutFireDamperErrOpeningRuntime19",
   "description": "Error Opening runtime fire damper 19, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 218,
   "name": "bOutFireDamperErrOpeningRuntime20",
   "description": "Error Opening runtime fire damper 20, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 219,
   "name": "bOutFireDamperErrOpeningRuntime21",
   "description": "Error Opening runtime fire damper 21, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 220,
   "name": "bOutFireDamperErrOpeningRuntime22",
   "description": "Error Opening runtime fire damper 22, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 221,
   "name": "bOutFireDamperErrOpeningRuntime23",
   "description": "Error Opening runtime fire damper 23, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 222,
   "name": "bOutFireDamperErrOpeningRuntime24",
   "description": "Error Opening runtime fire damper 24, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 223,
   "name": "bOutFireDamperErrOpeningRuntime25",
   "description": "Error Opening runtime fire damper 25, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 224,
   "name": "bOutFireDamperErrOpeningRuntime26",
   "description": "Error Opening runtime fire damper 26, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 225,
   "name": "bOutFireDamperErrOpeningRuntime27",
   "description": "Error Opening runtime fire damper 27, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 226,
   "name": "bOutFireDamperErrOpeningRuntime28",
   "description": "Error Opening runtime fire damper 28, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 227,
   "name": "bOutFireDamperErrOpeningRuntime29",
   "description": "Error Opening runtime fire damper 29, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 228,
   "name": "bOutFireDamperErrOpeningRuntime30",
   "description": "Error Opening runtime fire damper 30, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 229,
   "name": "bOutFireDamperErrOpeningRuntime31",
   "description": "Error Opening runtime fire damper 31, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 230,
   "name": "bOutFireDamperErrOpeningRuntime32",
   "description": "Error Opening runtime fire damper 32, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 231,
   "name": "bOutFireDamperErrOpeningRuntime33",
   "description": "Error Opening runtime fire damper 33, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 232,
   "name": "bOutFireDamperErrOpeningRuntime34",
   "description": "Error Opening runtime fire damper 34, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 233,
   "name": "bOutFireDamperErrOpeningRuntime35",
   "description": "Error Opening runtime fire damper 35, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 234,
   "name": "bOutFireDamperErrOpeningRuntime36",
   "description": "Error Opening runtime fire damper 36, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 235,
   "name": "bOutFireDamperErrOpeningRuntime37",
   "description": "Error Opening runtime fire damper 37, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 236,
   "name": "bOutFireDamperErrOpeningRuntime38",
   "description": "Error Opening runtime fire damper 38, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 237,
   "name": "bOutFireDamperErrOpeningRuntime39",
   "description": "Error Opening runtime fire damper 39, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 238,
   "name": "bOutFireDamperErrOpeningRuntime40",
   "description": "Error Opening runtime fire damper 40, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 239,
   "name": "bOutFireDamperErrOpeningRuntime41",
   "description": "Error Opening runtime fire damper 41, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 240,
   "name": "bOutFireDamperErrOpeningRuntime42",
   "description": "Error Opening runtime fire damper 42, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 241,
   "name": "bOutFireDamperErrOpeningRuntime43",
   "description": "Error Opening runtime fire damper 43, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 242,
   "name": "bOutFireDamperErrOpeningRuntime44",
   "description": "Error Opening runtime fire damper 44, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 243,
   "name": "bOutFireDamperErrOpeningRuntime45",
   "description": "Error Opening runtime fire damper 45, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 244,
   "name": "bOutFireDamperErrOpeningRuntime46",
   "description": "Error Opening runtime fire damper 46, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 245,
   "name": "bOutFireDamperErrOpeningRuntime47",
   "description": "Error Opening runtime fire damper 47, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 246,
   "name": "bOutFireDamperErrOpeningRuntime48",
   "description": "Error Opening runtime fire damper 48, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 247,
   "name": "bOutFireDamperErrOpeningRuntime49",
   "description": "Error Opening runtime fire damper 49, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 248,
   "name": "bOutFireDamperErrOpeningRuntime50",
   "description": "Error Opening runtime fire damper 50, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 249,
   "name": "bOutFireDamperErrOpeningRuntime51",
   "description": "Error Opening runtime fire damper 51, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 250,
   "name": "bOutFireDamperErrOpeningRuntime52",
   "description": "Error Opening runtime fire damper 52, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 251,
   "name": "bOutFireDamperErrOpeningRuntime53",
   "description": "Error Opening runtime fire damper 53, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 252,
   "name": "bOutFireDamperErrOpeningRuntime54",
   "description": "Error Opening runtime fire damper 54, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 253,
   "name": "bOutFireDamperErrOpeningRuntime55",
   "description": "Error Opening runtime fire damper 55, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 254,
   "name": "bOutFireDamperErrOpeningRuntime56",
   "description": "Error Opening runtime fire damper 56, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 255,
   "name": "bOutFireDamperErrOpeningRuntime57",
   "description": "Error Opening runtime fire damper 57, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 256,
   "name": "bOutFireDamperErrOpeningRuntime58",
   "description": "Error Opening runtime fire damper 58, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 257,
   "name": "bOutFireDamperErrOpeningRuntime59",
   "description": "Error Opening runtime fire damper 59, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 258,
   "name": "bOutFireDamperErrOpeningRuntime60",
   "description": "Error Opening runtime fire damper 60, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 259,
   "name": "bOutFireDamperErrOpeningRuntime61",
   "description": "Error Opening runtime fire damper 61, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 260,
   "name": "bOutFireDamperErrOpeningRuntime62",
   "description": "Error Opening runtime fire damper 62, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 261,
   "name": "bOutFireDamperErrPosIndicator1",
   "description": "Error end switch fire damper 1, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 262,
   "name": "bOutFireDamperErrPosIndicator2",
   "description": "Error end switch fire damper 2, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 263,
   "name": "bOutFireDamperErrPosIndicator3",
   "description": "Error end switch fire damper 3, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 264,
   "name": "bOutFireDamperErrPosIndicator4",
   "description": "Error end switch fire damper 4, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 265,
   "name": "bOutFireDamperErrPosIndicator5",
   "description": "Error end switch fire damper 5, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 266,
   "name": "bOutFireDamperErrPosIndicator6",
   "description": "Error end switch fire damper 6, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 267,
   "name": "bOutFireDamperErrPosIndicator7",
   "description": "Error end switch fire damper 7, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 268,
   "name": "bOutFireDamperErrPosIndicator8",
   "description": "Error end switch fire damper 8, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 269,
   "name": "bOutFireDamperErrPosIndicator9",
   "description": "Error end switch fire damper 9, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 270,
   "name": "bOutFireDamperErrPosIndicator10",
   "description": "Error end switch fire damper 10, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 271,
   "name": "bOutFireDamperErrPosIndicator11",
   "description": "Error end switch fire damper 11, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 272,
   "name": "bOutFireDamperErrPosIndicator12",
   "description": "Error end switch fire damper 12, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 273,
   "name": "bOutFireDamperErrPosIndicator13",
   "description": "Error end switch fire damper 13, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 274,
   "name": "bOutFireDamperErrPosIndicator14",
   "description": "Error end switch fire damper 14, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 275,
   "name": "bOutFireDamperErrPosIndicator15",
   "description": "Error end switch fire damper 15, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 276,
   "name": "bOutFireDamperErrPosIndicator16",
   "description": "Error end switch fire damper 16, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 277,
   "name": "bOutFireDamperErrPosIndicator17",
   "description": "Error end switch fire damper 17, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 278,
   "name": "bOutFireDamperErrPosIndicator18",
   "description": "Error end switch fire damper 18, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 279,
   "name": "bOutFireDamperErrPosIndicator19",
   "description": "Error end switch fire damper 19, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 280,
   "name": "bOutFireDamperErrPosIndicator20",
   "description": "Error end switch fire damper 20, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 281,
   "name": "bOutFireDamperErrPosIndicator21",
   "description": "Error end switch fire damper 21, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 282,
   "name": "bOutFireDamperErrPosIndicator22",
   "description": "Error end switch fire damper 22, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 283,
   "name": "bOutFireDamperErrPosIndicator23",
   "description": "Error end switch fire damper 23, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 284,
   "name": "bOutFireDamperErrPosIndicator24",
   "description": "Error end switch fire damper 24, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 285,
   "name": "bOutFireDamperErrPosIndicator25",
   "description": "Error end switch fire damper 25, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 286,
   "name": "bOutFireDamperErrPosIndicator26",
   "description": "Error end switch fire damper 26, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 287,
   "name": "bOutFireDamperErrPosIndicator27",
   "description": "Error end switch fire damper 27, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 288,
   "name": "bOutFireDamperErrPosIndicator28",
   "description": "Error end switch fire damper 28, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 289,
   "name": "bOutFireDamperErrPosIndicator29",
   "description": "Error end switch fire damper 29, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 290,
   "name": "bOutFireDamperErrPosIndicator30",
   "description": "Error end switch fire damper 30, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 291,
   "name": "bOutFireDamperErrPosIndicator31",
   "description": "Error end switch fire damper 31, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 292,
   "name": "bOutFireDamperErrPosIndicator32",
   "description": "Error end switch fire damper 32, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 293,
   "name": "bOutFireDamperErrPosIndicator33",
   "description": "Error end switch fire damper 33, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 294,
   "name": "bOutFireDamperErrPosIndicator34",
   "description": "Error end switch fire damper 34, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 295,
   "name": "bOutFireDamperErrPosIndicator35",
   "description": "Error end switch fire damper 35, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 296,
   "name": "bOutFireDamperErrPosIndicator36",
   "description": "Error end switch fire damper 36, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 297,
   "name": "bOutFireDamperErrPosIndicator37",
   "description": "Error end switch fire damper 37, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 298,
   "name": "bOutFireDamperErrPosIndicator38",
   "description": "Error end switch fire damper 38, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 299,
   "name": "bOutFireDamperErrPosIndicator39",
   "description": "Error end switch fire damper 39, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 300,
   "name": "bOutFireDamperErrPosIndicator40",
   "description": "Error end switch fire damper 40, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 301,
   "name": "bOutFireDamperErrPosIndicator41",
   "description": "Error end switch fire damper 41, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 302,
   "name": "bOutFireDamperErrPosIndicator42",
   "description": "Error end switch fire damper 42, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 303,
   "name": "bOutFireDamperErrPosIndicator43",
   "description": "Error end switch fire damper 43, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 304,
   "name": "bOutFireDamperErrPosIndicator44",
   "description": "Error end switch fire damper 44, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 305,
   "name": "bOutFireDamperErrPosIndicator45",
   "description": "Error end switch fire damper 45, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 306,
   "name": "bOutFireDamperErrPosIndicator46",
   "description": "Error end switch fire damper 46, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 307,
   "name": "bOutFireDamperErrPosIndicator47",
   "description": "Error end switch fire damper 47, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 308,
   "name": "bOutFireDamperErrPosIndicator48",
   "description": "Error end switch fire damper 48, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 309,
   "name": "bOutFireDamperErrPosIndicator49",
   "description": "Error end switch fire damper 49, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 310,
   "name": "bOutFireDamperErrPosIndicator50",
   "description": "Error end switch fire damper 50, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 311,
   "name": "bOutFireDamperErrPosIndicator51",
   "description": "Error end switch fire damper 51, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 312,
   "name": "bOutFireDamperErrPosIndicator52",
   "description": "Error end switch fire damper 52, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 313,
   "name": "bOutFireDamperErrPosIndicator53",
   "description": "Error end switch fire damper 53, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 314,
   "name": "bOutFireDamperErrPosIndicator54",
   "description": "Error end switch fire damper 54, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 315,
   "name": "bOutFireDamperErrPosIndicator55",
   "description": "Error end switch fire damper 55, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 316,
   "name": "bOutFireDamperErrPosIndicator56",
   "description": "Error end switch fire damper 56, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 317,
   "name": "bOutFireDamperErrPosIndicator57",
   "description": "Error end switch fire damper 57, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 318,
   "name": "bOutFireDamperErrPosIndicator58",
   "description": "Error end switch fire damper 58, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 319,
   "name": "bOutFireDamperErrPosIndicator59",
   "description": "Error end switch fire damper 59, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 320,
   "name": "bOutFireDamperErrPosIndicator60",
   "description": "Error end switch fire damper 60, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 321,
   "name": "bOutFireDamperErrPosIndicator61",
   "description": "Error end switch fire damper 61, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 322,
   "name": "bOutFireDamperErrPosIndicator62",
   "description": "Error end switch fire damper 62, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 323,
   "name": "bOutFireDamperErr1",
   "description": "Error triggered fire damper 1, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 324,
   "name": "bOutFireDamperErr2",
   "description": "Error triggered fire damper 2, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 325,
   "name": "bOutFireDamperErr3",
   "description": "Error triggered fire damper 3, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 326,
   "name": "bOutFireDamperErr4",
   "description": "Error triggered fire damper 4, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 327,
   "name": "bOutFireDamperErr5",
   "description": "Error triggered fire damper 5, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 328,
   "name": "bOutFireDamperErr6",
   "description": "Error triggered fire damper 6, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 329,
   "name": "bOutFireDamperErr7",
   "description": "Error triggered fire damper 7, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 330,
   "name": "bOutFireDamperErr8",
   "description": "Error triggered fire damper 8, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 331,
   "name": "bOutFireDamperErr9",
   "description": "Error triggered fire damper 9, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 332,
   "name": "bOutFireDamperErr10",
   "description": "Error triggered fire damper 10, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 333,
   "name": "bOutFireDamperErr11",
   "description": "Error triggered fire damper 11, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 334,
   "name": "bOutFireDamperErr12",
   "description": "Error triggered fire damper 12, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 335,
   "name": "bOutFireDamperErr13",
   "description": "Error triggered fire damper 13, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 336,
   "name": "bOutFireDamperErr14",
   "description": "Error triggered fire damper 14, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 337,
   "name": "bOutFireDamperErr15",
   "description": "Error triggered fire damper 15, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 338,
   "name": "bOutFireDamperErr16",
   "description": "Error triggered fire damper 16, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 339,
   "name": "bOutFireDamperErr17",
   "description": "Error triggered fire damper 17, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 340,
   "name": "bOutFireDamperErr18",
   "description": "Error triggered fire damper 18, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 341,
   "name": "bOutFireDamperErr19",
   "description": "Error triggered fire damper 19, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 342,
   "name": "bOutFireDamperErr20",
   "description": "Error triggered fire damper 20, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 343,
   "name": "bOutFireDamperErr21",
   "description": "Error triggered fire damper 21, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 344,
   "name": "bOutFireDamperErr22",
   "description": "Error triggered fire damper 22, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 345,
   "name": "bOutFireDamperErr23",
   "description": "Error triggered fire damper 23, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 346,
   "name": "bOutFireDamperErr24",
   "description": "Error triggered fire damper 24, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 347,
   "name": "bOutFireDamperErr25",
   "description": "Error triggered fire damper 25, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 348,
   "name": "bOutFireDamperErr26",
   "description": "Error triggered fire damper 26, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 349,
   "name": "bOutFireDamperErr27",
   "description": "Error triggered fire damper 27, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 350,
   "name": "bOutFireDamperErr28",
   "description": "Error triggered fire damper 28, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 351,
   "name": "bOutFireDamperErr29",
   "description": "Error triggered fire damper 29, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 352,
   "name": "bOutFireDamperErr30",
   "description": "Error triggered fire damper 30, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 353,
   "name": "bOutFireDamperErr31",
   "description": "Error triggered fire damper 31, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 354,
   "name": "bOutFireDamperErr32",
   "description": "Error triggered fire damper 32, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 355,
   "name": "bOutFireDamperErr33",
   "description": "Error triggered fire damper 33, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 356,
   "name": "bOutFireDamperErr34",
   "description": "Error triggered fire damper 34, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 357,
   "name": "bOutFireDamperErr35",
   "description": "Error triggered fire damper 35, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 358,
   "name": "bOutFireDamperErr36",
   "description": "Error triggered fire damper 36, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 359,
   "name": "bOutFireDamperErr37",
   "description": "Error triggered fire damper 37, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 360,
   "name": "bOutFireDamperErr38",
   "description": "Error triggered fire damper 38, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 361,
   "name": "bOutFireDamperErr39",
   "description": "Error triggered fire damper 39, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 362,
   "name": "bOutFireDamperErr40",
   "description": "Error triggered fire damper 40, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 363,
   "name": "bOutFireDamperErr41",
   "description": "Error triggered fire damper 41, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 364,
   "name": "bOutFireDamperErr42",
   "description": "Error triggered fire damper 42, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 365,
   "name": "bOutFireDamperErr43",
   "description": "Error triggered fire damper 43, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 366,
   "name": "bOutFireDamperErr44",
   "description": "Error triggered fire damper 44, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 367,
   "name": "bOutFireDamperErr45",
   "description": "Error triggered fire damper 45, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 368,
   "name": "bOutFireDamperErr46",
   "description": "Error triggered fire damper 46, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 369,
   "name": "bOutFireDamperErr47",
   "description": "Error triggered fire damper 47, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 370,
   "name": "bOutFireDamperErr48",
   "description": "Error triggered fire damper 48, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 371,
   "name": "bOutFireDamperErr49",
   "description": "Error triggered fire damper 49, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 372,
   "name": "bOutFireDamperErr50",
   "description": "Error triggered fire damper 50, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 373,
   "name": "bOutFireDamperErr51",
   "description": "Error triggered fire damper 51, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 374,
   "name": "bOutFireDamperErr52",
   "description": "Error triggered fire damper 52, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 375,
   "name": "bOutFireDamperErr53",
   "description": "Error triggered fire damper 53, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 376,
   "name": "bOutFireDamperErr54",
   "description": "Error triggered fire damper 54, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 377,
   "name": "bOutFireDamperErr55",
   "description": "Error triggered fire damper 55, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 378,
   "name": "bOutFireDamperErr56",
   "description": "Error triggered fire damper 56, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 379,
   "name": "bOutFireDamperErr57",
   "description": "Error triggered fire damper 57, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 380,
   "name": "bOutFireDamperErr58",
   "description": "Error triggered fire damper 58, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 381,
   "name": "bOutFireDamperErr59",
   "description": "Error triggered fire damper 59, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 382,
   "name": "bOutFireDamperErr60",
   "description": "Error triggered fire damper 60, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 383,
   "name": "bOutFireDamperErr61",
   "description": "Error triggered fire damper 61, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 384,
   "name": "bOutFireDamperErr62",
   "description": "Error triggered fire damper 62, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 385,
   "name": "bOutSmokeDetectorErr1",
   "description": "Error triggered smoke detector 1, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 386,
   "name": "bOutSmokeDetectorErr2",
   "description": "Error triggered smoke detector 2, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 387,
   "name": "bOutSmokeDetectorErr3",
   "description": "Error triggered smoke detector 3, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 388,
   "name": "bOutSmokeDetectorErr4",
   "description": "Error triggered smoke detector 4, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 389,
   "name": "bOutSmokeDetectorErr5",
   "description": "Error triggered smoke detector 5, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 390,
   "name": "bOutSmokeDetectorDirty1",
   "description": "Error triggered smoke detector 1 is dirty, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 391,
   "name": "bOutSmokeDetectorDirty2",
   "description": "Error triggered smoke detector 2 is dirty, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 392,
   "name": "bOutSmokeDetectorDirty3",
   "description": "Error triggered smoke detector 3 is dirty, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 393,
   "name": "bOutSmokeDetectorDirty4",
   "description": "Error triggered smoke detector 4 is dirty, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 394,
   "name": "bOutSmokeDetectorDirty5",
   "description": "Error triggered smoke detector 5 is dirty, normally closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "fOutPVTempOutdoor",
   "description": "present value outdoor temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "eOutEventNotification",
   "description": "Unit error summary",
   "units": "",
   "access": "R",
   "states": "0=no error, 1=warnings, 2=at least one critical error"
  },
  {
   "type": "BI",
   "instance": 395,
   "name": "bOutVoltageError",
   "description": "voltage error, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 396,
   "name": "bOutMainFuseError",
   "description": "main fuse error, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 397,
   "name": "bOutFireAlarm",
   "description": "fire alarm, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 398,
   "name": "bOutFrostProtection",
   "description": "error frost protection, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 399,
   "name": "bOutModbuslineError",
   "description": "error modbus line, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "fOutPVTempODA",
   "description": "present value outdoor air temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "fOutPVTempSUP",
   "description": "present value supply air temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "fOutPVTempETA",
   "description": "present value extracted air temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "fOutPVTempEHA",
   "description": "present value exhauts air temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "fOutPVHumODA",
   "description": "present value outdoor air humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "fOutPVHumSUP",
   "description": "present value supply air humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "fOutPVHumETA",
   "description": "present value extracted air humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "fOutPVHumEHA",
   "description": "present value exhauts air humidity",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "fOutPVPressureSUP",
   "description": "present value supply duct pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "fOutPVPressureETA",
   "description": "present value exhaust duct pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "fOutPV_VOC",
   "description": "present value voc concentration",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "fOutPV_CO2",
   "description": "present value CO2 concentration",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 400,
   "name": "bOutCoolerMotorProtection",
   "description": "error motor protection cooler pump, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 401,
   "name": "bOutCoolerValveComErr",
   "description": "modbus communication error witth the cooler valve, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 402,
   "name": "bOutCoolerCtrlPumpON",
   "description": "controlled value to switch on/off the cooler pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "fOutCoolerPVValvePos",
   "description": "current position of the cooler valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "fOutCoolerCtrlValvePos",
   "description": "controlled value of the cooler valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "fOutCoolerPVIntletTemp",
   "description": "present value of the cooler inlet temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 403,
   "name": "bOutPreheaterMotorProtection",
   "description": "error motor protection preheater pump, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 404,
   "name": "bOutPreheaterValveComErr",
   "description": "modbus communication error witth the preheater valve, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 405,
   "name": "bOutPreheaterCtrlPumpON",
   "description": "controlled value to switch on/off the preheater pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "fOutPreheaterPVValvePos",
   "description": "current position of the preheater valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "fOutPreheaterCtrlValvePos",
   "description": "controlled value of the preheater valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "fOutPreheaterPVReturnTemp",
   "description": "present value of the preheater return temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 406,
   "name": "bOutReheaterMotorProtection",
   "description": "error motor protection reheater pump, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 407,
   "name": "bOutReheaterValveComErr",
   "description": "modbus communication error witth the reheater valve, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 408,
   "name": "bOutReheaterCtrlPumpON",
   "description": "controlled value to switch on/off the reheater pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "fOutReheaterPVValvePos",
   "description": "current position of the reheater valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "fOutReheaterCtrlValvePos",
   "description": "controlled value of the reheater valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "fOutReheaterPVReturnTemp",
   "description": "present value of the reheater return temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 409,
   "name": "bOutDamperODAComErr",
   "description": "modbus communication error witth the outdoor air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 410,
   "name": "bOutDamperSUPComErr",
   "description": "modbus communication error witth the supply air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 411,
   "name": "bOutDamperETAComErr",
   "description": "modbus communication error witth the extracted air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 412,
   "name": "bOutDamperEHAComErr",
   "description": "modbus communication error witth the exhaust air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 413,
   "name": "bOutDamperFanSUPComErr",
   "description": "modbus communication error witth the supply air fan damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 414,
   "name": "bOutDamperFanETAComErr",
   "description": "modbus communication error witth the extracted air fan damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 415,
   "name": "bOutDamperODAComErr2",
   "description": "modbus communication error witth the second outdoor air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 416,
   "name": "bOutDamperSUPComErr2",
   "description": "modbus communication error witth the second supply air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 417,
   "name": "bOutDamperETAComErr2",
   "description": "modbus communication error witth the second extracted air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 418,
   "name": "bOutDamperEHAComErr2",
   "description": "modbus communication error witth the second exhaust air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 419,
   "name": "bOutDamperFanSUPComErr2",
   "description": "modbus communication error witth the second supply air fan damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 420,
   "name": "bOutDamperFanETAComErr2",
   "description": "modbus communication error witth the second extracted air fan damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 421,
   "name": "bOutDamperRCAComErr",
   "description": "modbus communication error with the recovery air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 422,
   "name": "bOutDamperRCAComErr2",
   "description": "modbus communication error with the second recovery air damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "fOutDamperODAPVPos",
   "description": "current position of the outdoor air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "fOutDamperSUPPVPos",
   "description": "current position of the supply air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "fOutDamperETAPVPos",
   "description": "current position of the extract air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "fOutDamperEHAPVPos",
   "description": "current position of the exhaust air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "fOutDamperODAPVPos2",
   "description": "current position of the second outdoor air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "fOutDamperSUPPVPos2",
   "description": "current position of the second supply air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "fOutDamperETAPVPos2",
   "description": "current position of the second extract air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "fOutDamperEHAPVPos2",
   "description": "current position of the second exhaust air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "fOutDamperFanSUPPVPos",
   "description": "current position of the supply air fan damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "fOutDamperFanETAPVPos",
   "description": "current position of the extract air fan damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "fOutDamperFanSUPPVPos2",
   "description": "current position of the second supply air fan damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "fOutDamperFanETAPVPos2",
   "description": "current position of the second extract air fan damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "fOutDamperRCAPVPos",
   "description": "current position of the recovery air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "fOutDamperRCAPVPos2",
   "description": "current position of the second recovery air damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "fOutDamperODACtrlPos",
   "description": "controlled value of the outdoor air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "fOutDamperSUPCtrlPos",
   "description": "controlled value of the supply air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "fOutDamperETACtrlPos",
   "description": "controlled value of the extract air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "fOutDamperEHACtrlPos",
   "description": "controlled value of the exhaust air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "fOutDamperODACtrlPos2",
   "description": "controlled value of the second outdoor air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "fOutDamperSUPCtrlPos2",
   "description": "controlled value of the second supply air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "fOutDamperETACtrlPos2",
   "description": "controlled value of the second extract air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "fOutDamperEHACtrlPos2",
   "description": "controlled value of the second exhaust air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "fOutDamperFanSUPCtrlPos",
   "description": "controlled value of the supply air fan damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "fOutDamperFanETACtrlPos",
   "description": "controlled value of the extract air fan damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "fOutDamperFanSUPCtrlPos2",
   "description": "controlled value of the second supply air fan damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "fOutDamperFanETACtrlPos2",
   "description": "controlled value of the second extract air fan damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "fOutDamperRCACtrlPos",
   "description": "controlled value of the recovery air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "fOutDamperRCACtrlPos2",
   "description": "controlled value of the second recovery air damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 423,
   "name": "bOutFanSUPMotorProtection",
   "description": "error motor protection supply air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 424,
   "name": "bOutFanSUPMotorProtection2",
   "description": "error motor protection of the second supply air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 425,
   "name": "bOutFanETAMotorProtection",
   "description": "error motor protection extract air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 426,
   "name": "bOutFanETAMotorProtection2",
   "description": "error motor protection of the second extract air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 427,
   "name": "bOutFanSUPRepairSwitch",
   "description": "error repair switch supply air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 428,
   "name": "bOutFanSUPRepairSwitch2",
   "description": "error repair switch of the second supply air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 429,
   "name": "bOutFanSUPRepairSwitch3",
   "description": "error repair switch of the supply air fan 3, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 430,
   "name": "bOutFanSUPRepairSwitch4",
   "description": "error repair switch of the supply air fan 4, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 431,
   "name": "bOutFanSUPRepairSwitch5",
   "description": "error repair switch of the supply air fan 5, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 432,
   "name": "bOutFanSUPRepairSwitch6",
   "description": "error repair switch of the supply air fan 6, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 433,
   "name": "bOutFanSUPRepairSwitch7",
   "description": "error repair switch of the supply air fan 7, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 434,
   "name": "bOutFanSUPRepairSwitch8",
   "description": "error repair switch of the supply air fan 8, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 435,
   "name": "bOutFanSUPRepairSwitch9",
   "description": "error repair switch of the supply air fan 9, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 436,
   "name": "bOutFanSUPRepairSwitch10",
   "description": "error repair switch of the supply air fan 10, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 437,
   "name": "bOutFanSUPRepairSwitch11",
   "description": "error repair switch of the supply air fan 11, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 438,
   "name": "bOutFanSUPRepairSwitch12",
   "description": "error repair switch of the supply air fan 12, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 439,
   "name": "bOutFanSUPRepairSwitch13",
   "description": "error repair switch of the supply air fan 13, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 440,
   "name": "bOutFanSUPRepairSwitch14",
   "description": "error repair switch of the supply air fan 14, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 441,
   "name": "bOutFanSUPRepairSwitch15",
   "description": "error repair switch of the supply air fan 15, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 442,
   "name": "bOutFanSUPRepairSwitch16",
   "description": "error repair switch of the supply air fan 16, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 443,
   "name": "bOutFanETARepairSwitch",
   "description": "error repair switch extract air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 444,
   "name": "bOutFanETARepairSwitch2",
   "description": "error repair switch of the second extract air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 445,
   "name": "bOutFanETARepairSwitch3",
   "description": "error repair switch of the extract air fan 3, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 446,
   "name": "bOutFanETARepairSwitch4",
   "description": "error repair switch of the extract air fan 4, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 447,
   "name": "bOutFanETARepairSwitch5",
   "description": "error repair switch of the extract air fan 5, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 448,
   "name": "bOutFanETARepairSwitch6",
   "description": "error repair switch of the extract air fan 6, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 449,
   "name": "bOutFanETARepairSwitch7",
   "description": "error repair switch of the extract air fan 7, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 450,
   "name": "bOutFanETARepairSwitch8",
   "description": "error repair switch of the extract air fan 8, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 451,
   "name": "bOutFanETARepairSwitch9",
   "description": "error repair switch of the extract air fan 9, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 452,
   "name": "bOutFanETARepairSwitch10",
   "description": "error repair switch of the extract air fan 10, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 453,
   "name": "bOutFanETARepairSwitch11",
   "description": "error repair switch of the extract air fan 11, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 454,
   "name": "bOutFanETARepairSwitch12",
   "description": "error repair switch of the extract air fan 12, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 455,
   "name": "bOutFanETARepairSwitch13",
   "description": "error repair switch of the extract air fan 13, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 456,
   "name": "bOutFanETARepairSwitch14",
   "description": "error repair switch of the extract air fan 14, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 457,
   "name": "bOutFanETARepairSwitch15",
   "description": "error repair switch of the extract air fan 15, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 458,
   "name": "bOutFanETARepairSwitch16",
   "description": "error repair switch of the extract air fan 16, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 459,
   "name": "bOutFanSUPComErr",
   "description": "modbus communication error with the supply air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 460,
   "name": "bOutFanSUPComErr2",
   "description": "modbus communication error with the second supply air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 461,
   "name": "bOutFanSUPComErr3",
   "description": "modbus communication error with the supply air fan 3, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 462,
   "name": "bOutFanSUPComErr4",
   "description": "modbus communication error with the supply air fan 4, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 463,
   "name": "bOutFanSUPComErr5",
   "description": "modbus communication error with the supply air fan 5, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 464,
   "name": "bOutFanSUPComErr6",
   "description": "modbus communication error with the supply air fan 6, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 465,
   "name": "bOutFanSUPComErr7",
   "description": "modbus communication error with the supply air fan 7, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 466,
   "name": "bOutFanSUPComErr8",
   "description": "modbus communication error with the supply air fan 8, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 467,
   "name": "bOutFanSUPComErr9",
   "description": "modbus communication error with the supply air fan 9, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 468,
   "name": "bOutFanSUPComErr10",
   "description": "modbus communication error with the supply air fan 10, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 469,
   "name": "bOutFanSUPComErr11",
   "description": "modbus communication error with the supply air fan 11, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 470,
   "name": "bOutFanSUPComErr12",
   "description": "modbus communication error with the supply air fan 12, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 471,
   "name": "bOutFanSUPComErr13",
   "description": "modbus communication error with the supply air fan 13, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 472,
   "name": "bOutFanSUPComErr14",
   "description": "modbus communication error with the supply air fan 14, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 473,
   "name": "bOutFanSUPComErr15",
   "description": "modbus communication error with the supply air fan 15, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 474,
   "name": "bOutFanSUPComErr16",
   "description": "modbus communication error with the supply air fan 16, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 475,
   "name": "bOutFanETAComErr",
   "description": "modbus communication error with the extract air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 476,
   "name": "bOutFanETAComErr2",
   "description": "modbus communication error with the second extract air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 477,
   "name": "bOutFanETAComErr3",
   "description": "modbus communication error with the extract air fan 3, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 478,
   "name": "bOutFanETAComErr4",
   "description": "modbus communication error with the extract air fan 4, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 479,
   "name": "bOutFanETAComErr5",
   "description": "modbus communication error with the extract air fan 5, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 480,
   "name": "bOutFanETAComErr6",
   "description": "modbus communication error with the extract air fan 6, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 481,
   "name": "bOutFanETAComErr7",
   "description": "modbus communication error with the extract air fan 7, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 482,
   "name": "bOutFanETAComErr8",
   "description": "modbus communication error with the extract air fan 8, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 483,
   "name": "bOutFanETAComErr9",
   "description": "modbus communication error with the extract air fan 9, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 484,
   "name": "bOutFanETAComErr10",
   "description": "modbus communication error with the extract air fan 10, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 485,
   "name": "bOutFanETAComErr11",
   "description": "modbus communication error with the extract air fan 11, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 486,
   "name": "bOutFanETAComErr12",
   "description": "modbus communication error with the extract air fan 12, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 487,
   "name": "bOutFanETAComErr13",
   "description": "modbus communication error with the extract air fan 13, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 488,
   "name": "bOutFanETAComErr14",
   "description": "modbus communication error with the extract air fan 14, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 489,
   "name": "bOutFanETAComErr15",
   "description": "modbus communication error with the extract air fan 15, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 490,
   "name": "bOutFanETAComErr16",
   "description": "modbus communication error with the extract air fan 16, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 491,
   "name": "bOutFanSUPInErr",
   "description": "internal supply air fan error, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 492,
   "name": "bOutFanSUPInErr2",
   "description": "internal error on the second supply air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 493,
   "name": "bOutFanSUPInErr3",
   "description": "internal error on the supply air fan 3, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 494,
   "name": "bOutFanSUPInErr4",
   "description": "internal error on the supply air fan 4, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 495,
   "name": "bOutFanSUPInErr5",
   "description": "internal error on the supply air fan 5, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 496,
   "name": "bOutFanSUPInErr6",
   "description": "internal error on the supply air fan 6, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 497,
   "name": "bOutFanSUPInErr7",
   "description": "internal error on the supply air fan 7, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 498,
   "name": "bOutFanSUPInErr8",
   "description": "internal error on the supply air fan 8, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 499,
   "name": "bOutFanSUPInErr9",
   "description": "internal error on the supply air fan 9, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 500,
   "name": "bOutFanSUPInErr10",
   "description": "internal error on the supply air fan 10, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 501,
   "name": "bOutFanSUPInErr11",
   "description": "internal error on the supply air fan 11, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 502,
   "name": "bOutFanSUPInErr12",
   "description": "internal error on the supply air fan 12, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 503,
   "name": "bOutFanSUPInErr13",
   "description": "internal error on the supply air fan 13, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 504,
   "name": "bOutFanSUPInErr14",
   "description": "internal error on the supply air fan 14, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 505,
   "name": "bOutFanSUPInErr15",
   "description": "internal error on the supply air fan 15, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 506,
   "name": "bOutFanSUPInErr16",
   "description": "internal error on the supply air fan 16, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 507,
   "name": "bOutFanETAInErr",
   "description": "internal extract air fan error, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 508,
   "name": "bOutFanETAInErr2",
   "description": "internal error on the second extract air fan, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 509,
   "name": "bOutFanETAInErr3",
   "description": "internal error on the extract air fan 3, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 510,
   "name": "bOutFanETAInErr4",
   "description": "internal error on the extract air fan 4, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 511,
   "name": "bOutFanETAInErr5",
   "description": "internal error on the extract air fan 5, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 512,
   "name": "bOutFanETAInErr6",
   "description": "internal error on the extract air fan 6, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 513,
   "name": "bOutFanETAInErr7",
   "description": "internal error on the extract air fan 7, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 514,
   "name": "bOutFanETAInErr8",
   "description": "internal error on the extract air fan 8, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 515,
   "name": "bOutFanETAInErr9",
   "description": "internal error on the extract air fan 9, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 516,
   "name": "bOutFanETAInErr10",
   "description": "internal error on the extract air fan 10, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 517,
   "name": "bOutFanETAInErr11",
   "description": "internal error on the extract air fan 11, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 518,
   "name": "bOutFanETAInErr12",
   "description": "internal error on the extract air fan 12, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 519,
   "name": "bOutFanETAInErr13",
   "description": "internal error on the extract air fan 13, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 520,
   "name": "bOutFanETAInErr14",
   "description": "internal error on the extract air fan 14, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 521,
   "name": "bOutFanETAInErr15",
   "description": "internal error on the extract air fan 15, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 522,
   "name": "bOutFanETAInErr16",
   "description": "internal error on the extract air fan 16, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 523,
   "name": "bOutFanSUPDpComErr",
   "description": "modbus communication error with the pressure transmitter of the supply air fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 524,
   "name": "bOutFanSUPDpComErr2",
   "description": "modbus communication error with the pressure transmitter of the second supply air",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 525,
   "name": "bOutFanETADpComErr",
   "description": "modbus communication error with the pressure transmitter of the extract air fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 526,
   "name": "bOutFanETADpComErr2",
   "description": "modbus communication error with the pressure transmitter of the second extract air",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 527,
   "name": "bOutFanSUPCtrlON",
   "description": "controlled value to switch on/off the supply air fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 528,
   "name": "bOutFanSUPCtrlON2",
   "description": "controlled value to switch on/off the second supply air fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 529,
   "name": "bOutFanSUPCtrlON3",
   "description": "controlled value to switch on/off the supply air fan 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 530,
   "name": "bOutFanSUPCtrlON4",
   "description": "controlled value to switch on/off the supply air fan 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 531,
   "name": "bOutFanSUPCtrlON5",
   "description": "controlled value to switch on/off the supply air fan 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 532,
   "name": "bOutFanSUPCtrlON6",
   "description": "controlled value to switch on/off the supply air fan 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 533,
   "name": "bOutFanSUPCtrlON7",
   "description": "controlled value to switch on/off the supply air fan 7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 534,
   "name": "bOutFanSUPCtrlON8",
   "description": "controlled value to switch on/off the supply air fan 8",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 535,
   "name": "bOutFanSUPCtrlON9",
   "description": "controlled value to switch on/off the supply air fan 9",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 536,
   "name": "bOutFanSUPCtrlON10",
   "description": "controlled value to switch on/off the supply air fan 10",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 537,
   "name": "bOutFanSUPCtrlON11",
   "description": "controlled value to switch on/off the supply air fan 11",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 538,
   "name": "bOutFanSUPCtrlON12",
   "description": "controlled value to switch on/off the supply air fan 12",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 539,
   "name": "bOutFanSUPCtrlON13",
   "description": "controlled value to switch on/off the supply air fan 13",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 540,
   "name": "bOutFanSUPCtrlON14",
   "description": "controlled value to switch on/off the supply air fan 14",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 541,
   "name": "bOutFanSUPCtrlON15",
   "description": "controlled value to switch on/off the supply air fan 15",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 542,
   "name": "bOutFanSUPCtrlON16",
   "description": "controlled value to switch on/off the supply air fan 16",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 543,
   "name": "bOutFanETACtrlON",
   "description": "controlled value to switch on/off the extract air fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 544,
   "name": "bOutFanETACtrlON2",
   "description": "controlled value to switch on/off the second extract air fan",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 545,
   "name": "bOutFanETACtrlON3",
   "description": "controlled value to switch on/off the extract air fan 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 546,
   "name": "bOutFanETACtrlON4",
   "description": "controlled value to switch on/off the extract air fan 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 547,
   "name": "bOutFanETACtrlON5",
   "description": "controlled value to switch on/off the extract air fan 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 548,
   "name": "bOutFanETACtrlON6",
   "description": "controlled value to switch on/off the extract air fan 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 549,
   "name": "bOutFanETACtrlON7",
   "description": "controlled value to switch on/off the extract air fan 7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 550,
   "name": "bOutFanETACtrlON8",
   "description": "controlled value to switch on/off the extract air fan 8",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 551,
   "name": "bOutFanETACtrlON9",
   "description": "controlled value to switch on/off the extract air fan 9",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 552,
   "name": "bOutFanETACtrlON10",
   "description": "controlled value to switch on/off the extract air fan 10",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 553,
   "name": "bOutFanETACtrlON11",
   "description": "controlled value to switch on/off the extract air fan 11",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 554,
   "name": "bOutFanETACtrlON12",
   "description": "controlled value to switch on/off the extract air fan 12",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 555,
   "name": "bOutFanETACtrlON13",
   "description": "controlled value to switch on/off the extract air fan 13",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 556,
   "name": "bOutFanETACtrlON14",
   "description": "controlled value to switch on/off the extract air fan 14",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 557,
   "name": "bOutFanETACtrlON15",
   "description": "controlled value to switch on/off the extract air fan 15",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 558,
   "name": "bOutFanETACtrlON16",
   "description": "controlled value to switch on/off the extract air fan 16",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "fOutFanSUPCtrlSpeed",
   "description": "controlled value of the supply air fan speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "fOutFanSUPCtrlSpeed2",
   "description": "controlled value of the second supply air fan speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "fOutFanETACtrlSpeed",
   "description": "controlled value of the extract air fan speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "fOutFanETACtrlSpeed2",
   "description": "controlled value of the second extract air fan speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "fOutFanSUPPVdp",
   "description": "present value supply air fan differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "fOutFanSUPPVdp2",
   "description": "present value second supply air fan differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "fOutFanETAPVdp",
   "description": "present value extract air fan differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "fOutFanETAPVdp2",
   "description": "present value second extract air fan differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "fOutFanSUPPVAirflow",
   "description": "present value supply airflow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "fOutFanSUPPVAirflow2",
   "description": "present value supply airflow provided by the second fan",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "fOutFanETAPVAirflow",
   "description": "present value extract airflow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "fOutFanETAPVAirflow2",
   "description": "present value extract airflow provided by the second fan",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 559,
   "name": "bOutFilterODAChangeErr",
   "description": "error outdoor air filter change required, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 560,
   "name": "bOutFilterSUPChangeErr",
   "description": "error supply air filter change required",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 561,
   "name": "bOutFilterETAChangeErr",
   "description": "error extract air filter change required",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 562,
   "name": "bOutFilterODADpComErr",
   "description": "communication error pressure sensor outdoor air filter, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 563,
   "name": "bOutFilterSUPDpComErr",
   "description": "communication error pressure sensor suppply air filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 564,
   "name": "bOutFilterETADpComErr",
   "description": "communication error pressure sensor extract air filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "tOutFitlerODAHoldingTime",
   "description": "holding time outdoor air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "tOutFitlerSUPHoldingTime",
   "description": "holding time supply air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "tOutFitlerETAHoldingTime",
   "description": "holding time extract air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "tOutFitlerODAOperationTime",
   "description": "operation time outdoor air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "tOutFitlerSUPOperationTime",
   "description": "operation time supply air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "tOutFitlerETAOperationTime",
   "description": "operation time extract air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "fOutFilterODAPVdp",
   "description": "present value outdoor air filter differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "fOutFilterSUPPVdp",
   "description": "present value supply air filter differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "fOutFilterETAPVdp",
   "description": "present value extract air filter differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 565,
   "name": "bOutFilterODAChangeErr2",
   "description": "error second outdoor air filter change required, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 566,
   "name": "bOutFilterSUPChangeErr2",
   "description": "error second supply air filter change required",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 567,
   "name": "bOutFilterETAChangeErr2",
   "description": "error second extract air filter change required",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 568,
   "name": "bOutFilterODADpComErr2",
   "description": "communication error pressure sensor second outdoor air filter, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 569,
   "name": "bOutFilterSUPDpComErr2",
   "description": "communication error pressure sensor second supply air filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 570,
   "name": "bOutFilterETADpComErr2",
   "description": "communication error pressure sensor second extract air filter",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "tOutFitlerODAHoldingTime2",
   "description": "holding time second outdoor air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "tOutFitlerSUPHoldingTime2",
   "description": "holding time second supply air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "tOutFitlerETAHoldingTime2",
   "description": "holding time second extract air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "tOutFitlerODAOperationTime2",
   "description": "operation time second outdoor air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "tOutFitlerSUPOperationTime2",
   "description": "operation time second supply air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "tOutFitlerETAOperationTime2",
   "description": "operation time second extract air filter",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "fOutFilterODAPVdp2",
   "description": "present value second outdoor air filter differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "fOutFilterSUPPVdp2",
   "description": "present value second supply air filter differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "fOutFilterETAPVdp2",
   "description": "present value second extract air filter differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 571,
   "name": "bOutPlateHexDamperComErr",
   "description": "modbus communication error with the plate heat exchanger damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 572,
   "name": "bOutPlateHexDamperComErr2",
   "description": "modbus communication error with the second plate heat exchanger damper, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 573,
   "name": "bOutPlateHexDpComErr",
   "description": "modbus communication error with the plate heat exchanger differential pressure sensor, normaly",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "fOutPlatehexPVdp",
   "description": "present value plate heat exchanger differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "fOutPlatehexDamperCtrlPos",
   "description": "controlled value bypass plate heat exchanger",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "fOutPlatehexDamperCtrlPos2",
   "description": "controlled value of the second bypass plate heat exchanger",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "fOutPlatehexDamperPVPos",
   "description": "current position bypass plate heat exchanger",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "fOutPlatehexDamperPVPos2",
   "description": "current position second bypass plate heat exchanger",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 574,
   "name": "bOutRotHexInErr",
   "description": "internal error of the heat recovery wheel, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 575,
   "name": "bOutRotHexComErr",
   "description": "modbus communication error with the heat recovery wheel, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 576,
   "name": "bOutRotHexCtrlRel",
   "description": "controlled value to release the heat recovery wheel, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "fOutRothexCtrl",
   "description": "controlled value heat recovery wheel speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 577,
   "name": "bOutComErrSenHumODA",
   "description": "modbus communication error with the outdoor air humidity sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 578,
   "name": "bOutComErrSenHumSUP",
   "description": "modbus communication error with the supply air humidity sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 579,
   "name": "bOutComErrSenHumETA",
   "description": "modbus communication error with the extract air humidity sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 580,
   "name": "bOutComErrSenHumEHA",
   "description": "modbus communication error with the exhaust air humidity sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 581,
   "name": "bOutComErrSenTempODA",
   "description": "modbus communication error with the outdoor air temperature sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 582,
   "name": "bOutComErrSenTempSUP",
   "description": "modbus communication error with the supply air temperature sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 583,
   "name": "bOutComErrSenTempETA",
   "description": "modbus communication error with the extract air temperature sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 584,
   "name": "bOutComErrSenTempEHA",
   "description": "modbus communication error with the exhaust air temperature sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 585,
   "name": "bOutComErrSenDpSUP",
   "description": "modbus communication error with the supply air pressure sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 586,
   "name": "bOutComErrSenDpETA",
   "description": "modbus communication error with the extract air pressure sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 587,
   "name": "bOutComErrSenCO2",
   "description": "modbus communication error with the CO2 sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 588,
   "name": "bOutComErrSenVOC",
   "description": "modbus communication error with the VOC sensor, normaly closed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "fOutSPTempSUP",
   "description": "current set point of the supply air temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "fOutSPTempETA",
   "description": "current set point of the extract or room air temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 89,
   "name": "eOutPVOperationMode",
   "description": "current operation mode of the air handling unit",
   "units": "",
   "access": "R",
   "states": "0=off, 1=standby, 2=control, 3=freeze protection, 4=deicing, 5=startup, 6=shutdown, 7=manual, 8=nightpurge, 9=intermittent Operation, 10=cooling protection, 11=fire protection"
  },
  {
   "type": "BI",
   "instance": 589,
   "name": "bOutKVS2BrinePressure1",
   "description": "Pressure step 1 triggered 0=Off, 1=On",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 590,
   "name": "bOutKVS2BrinePressure2",
   "description": "Pressure step 2 triggered 0=Off, 1=On",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 591,
   "name": "bOutKVS2MsgAutoPumpOff",
   "description": "auto pump stop PRIO=2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 592,
   "name": "bOutKVS2MsgBrinePressureCritical",
   "description": "critical brine pressure PRIO=3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 593,
   "name": "bOutKVS2MsgBrinePressureLow",
   "description": "brine pressure have to be checked PRIO=2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 594,
   "name": "bOutKVS2MsgFrostFeedCoil",
   "description": "alarm feed coil frosting Prio=3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 595,
   "name": "bOutKVS2MsgMinTempInletETA",
   "description": "exhaust air heat exchanger is frosting Prio=2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 596,
   "name": "bOutKVS2MsgNoFeed",
   "description": "feed doesnt have cooling or heating effects Prio=2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 597,
   "name": "bOutKVS2MsgNoRecovery",
   "description": "heat recovery is currently not possible Prio=2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 598,
   "name": "bOutKVS2MsgPumpError",
   "description": "Pump error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 599,
   "name": "bOutKVS2ReleasePump",
   "description": "Pump release",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 600,
   "name": "bOutKVS2StateCoolingFeed",
   "description": "state of the cooling feed TRUE, if feeding is active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 601,
   "name": "bOutKVS2StateFastMode",
   "description": "state of the fast cool- or heating mode TRUE, if active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 602,
   "name": "bOutKVS2StateHeatExchangerOperation",
   "description": "state of the operation signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 603,
   "name": "bOutKVS2StateHeatingFeed",
   "description": "state of the heating feed TRUE, if feeding is active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "fOutKVS2CtrlFrostProtectionValve",
   "description": "controlled value run around coil frost protection valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "fOutKVS2CtrlPowerValve",
   "description": "controlled value run around coil power valve",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "fOutKVS2CtrlPump",
   "description": "controlled value run around coil pump",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "fOutKVS2BrineVolumeFlow",
   "description": "present value brine volume flow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "fOutKVS2TempETAIn",
   "description": "current value inlet temperature of exhaust air heat exchanger",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "fOutKVS2TempETAOut",
   "description": "current value return temperature exhaust air heat exchanger",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "fOutKVS2TempPreFeed",
   "description": "current value brine temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "fOutKVS2TempSUPIn",
   "description": "current value inlet temperature of the fresh air heat exchanger",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "fOutKVS2TempSUPOut",
   "description": "current value outlet temperature of the fresh air heat exchanger",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "fOutKVS2ThermalPowerSUP",
   "description": "current value thermal power of the fresh air heat exchanger",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "fOutKVS2ThermalPowerETA",
   "description": "current value thermal power of the exhaust air heat exchanger",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "fOutKVS2ThermalPowerFeedHeat",
   "description": "current value thermal power of the heating feed",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "fOutKVS2ThermalPowerFeedCool",
   "description": "current value thermal power of the cooling feed",
   "units": "W",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 604,
   "name": "bOutIKMsgOilManagement",
   "description": "Oil management error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 605,
   "name": "bOutIKMsgLowPressure",
   "description": "Low pressure error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 606,
   "name": "bOutIKMsgHighPressure",
   "description": "High pressure error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 607,
   "name": "bOutIKMsgSuperHeatingController",
   "description": "error super heating controller",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 608,
   "name": "bOutIKMsgMotorProtection1",
   "description": "error first compressor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 609,
   "name": "bOutIKMsgMotorProtection2",
   "description": "error second compressor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 610,
   "name": "bOutIKMsgMotorProtection3",
   "description": "error third compressor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 611,
   "name": "bOutIKCtrlPWM1",
   "description": "actuating value pwm compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 612,
   "name": "bOutIKCtrlPWM2",
   "description": "actuating value pwm compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 613,
   "name": "bOutIKCtrlPWM3",
   "description": "actuating value pwm compressor 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 614,
   "name": "bOutIKCtrlSoftStarterOn1",
   "description": "actuating value soft starter compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 615,
   "name": "bOutIKCtrlSoftStarterOn2",
   "description": "actuating value soft starter compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 616,
   "name": "bOutIKCtrlSoftStarterOn3",
   "description": "actuating value soft starter compressor 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 617,
   "name": "bOutIKMsgHighTemp",
   "description": "High compressor end temperature error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 618,
   "name": "bOutIKMsgEAPComError",
   "description": "error with EAP-Communication unit",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/trox/x-cube-control",