- TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)
VAV / static pressure controller · BACnet points list
TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP) BACnet points list
Updated 6 November 2026
The BUPNF product data sheet includes the BACnet MS/TP object list of its VRU-...-BAC control electronics: 39 objects (Device not counted). The BMS writes the relative setpoint to AO 1 (flow, pressure or damper position, depending on MV 2 ApplicationSel), can force states with MO 1, and reads airflow, differential pressure, damper position and five status objects.
This page lists 39 BACnet objects for the TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.
- Manufacturer
- TROX
- Model
- TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)
- Equipment
- VAV / static pressure controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 39 (13 writable)
- Transport
- BACnet MS/TP
- Firmware
- Firmware 10.02.0000, application 01.02.0001
- Default device instance
- 1
- Also known as
- BUPNF, TROX UNIVERSAL static, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-D3-M/B TR, VRU-M1-M/B TR, VRU-M1R-M/B TR
Reference only, provided as-is: verify against TROX’s current documentation and the live device before use. Not official TROX information. Terms of use.
BMS integration notes: TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)
Set MV 122 SpSource to Bus (factory setting is Analogue), then write AO 1 SpRel as a percentage between Min and Max; what it controls (airflow or pressure) follows MV 2 ApplicationSel. Read AI 19 airflow or AI 18 pressure, AI 1 damper position and BI 101 SummaryStatus. Set AV 130 if the unit should react to a lost BMS.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 1 | SpRel | Flow, pressure or position setpoint | Command |
| MV 122 | SpSource | Must be Bus (2); factory setting is Analogue | Write |
| AI 19 | AbsFlow_UnitSel | Measured airflow | Read |
| AI 18 | DeltaP_UnitSel | Measured differential pressure | Read |
| AI 1 | RelPos | Damper position feedback | Read |
| BI 101 | SummaryStatus | Overall OK / not OK alarm | Read |
Enable & remote start
MV 122 SpSource: 2 = Bus makes AO 1 SpRel active; 1 = Analogue (factory setting) uses the analogue input and AO 1 is ignored.
Heartbeat & communication loss
AV 130 BusWatchdog (0-3600 s, factory 0 = off). When set, the unit watches AO 1 and MO 1 for changes and resets the timer on each change; MI 110 StatusDevice shows when bus timeout monitoring has tripped. With SpSource = Analogue only MO 1 is watched.
Sensors & values from the BMS
Sensor 1 (AI 20 / BI 20) is configured with MV 220 Sens1Type; with RmPCasacade active it is the 0-10 V room cascade input.
Network setup
- Default device instance 1.
- MS/TP baud rates 9600, 19200, 38400, 76800 and 115200.
Watch out for
- Min must stay below Max; Max range is 20-100 %.
- MV 102 OperationMode only matters for VRU-M1R-BAC room pressure control.
TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | RelPos | Damper blade position | % | Read | |
| AI | 2 | AbsPos | Absolute position over the rotation range | ° | Read | |
| AI | 6 | SpAnalogue | Analogue setpoint (when SpSource = analogue) | % | Read | |
| AI | 9 | RelDeltaP | Differential pressure, % of DeltaPnom_Pa | % | Read | |
| AI | 10 | RelFlow | Airflow, % of Vnom_m3h | % | Read | |
| AI | 12 | AbsFlow_m3h | Absolute airflow | m³/h | Read | |
| AImin | 18 | DeltaP_UnitSel | Differential pressure in the unit set by MV 127 | Read | ||
| AImin | 19 | AbsFlow_UnitSel | Airflow in the unit set by MV 121 | Read | ||
| AI | 20 | Sens1Analogue | Sensor 1 value (0-10 V or resistance) | Read | ||
| AI | 29 | DeltaP_Pa | Absolute differential pressure | Pa | Read | |
| AOmin | 1 | SpRel | Relative setpoint (flow, pressure or position) when SpSource = bus | % | Command | |
| AV | 97 | Min | Minimum setpoint qvmin / dpmin | % | Write | |
| AV | 98 | Max | Maximum setpoint qvmax / dpmax | % | Write | |
| AV | 112 | Vnom_m3h | Nominal airflow | m³/h | Read | |
| AV | 119 | Vnom_UnitSel | Nominal airflow in the unit set by MV 121 | Read | ||
| AV | 120 | SystemAltitude | System altitude above sea level | m | Write | |
| AV | 122 | DeltaPnom_Pa | Nominal differential pressure or max. pressure limit | Pa | Read | |
| AV | 129 | DeltaPnom_UnitSel | Nominal differential pressure in the unit set by MV 127 | Read | ||
| AV | 130 | BusWatchdog | Bus timeout monitoring time, 0 = off (factory) | s | Write | |
| BI | 20 | Sens1Switch | Switch status at the sensor input | Read | 0=Inactive, 1=Active | |
| BI | 99 | BusTermination | 120 ohm terminating resistor activated via service tool | Read | 0=Deactivated, 1=Activated | |
| BImin | 101 | SummaryStatus | Condensed status of MI 103/104/106/109/110 | Read | 0=OK, 1=Not OK | |
| MV | 10 | RmPCasacade | Room pressure cascade (sensor 1 as cascade input) | Read | 1=Inactive, 2=Active, 3=Active fast (M1R only) | |
| MI | 100 | InternalActivity | Internal status | Read | 1=None, 3=Adaption, 4=Synchronisation | |
| MI | 103 | StatusSensor | Differential pressure sensor status | Read | 1=OK, 2=dP sensor not OK, 3=dP sensor outside of measuring range, 4=dP sensor incorrectly connected | |
| MI | 104 | StatusFlow | Airflow status (3 if no airflow within 600 s) | Read | 1=OK, 3=No airflow detected | |
| MI | 106 | StatusActuator | Actuator status | Read | 1=OK, 2=Actuator cannot be moved, 3=Gear release active, 4=Mechanical travel exceeded, 5=Actuator not suitable for application | |
| MI | 109 | StatusPressure | Pressure status (3 if not reached within 180 s) | Read | 1=OK, 3=Pressure not reached | |
| MI | 110 | StatusDevice | Bus timeout monitoring status (per AV 130) | Read | 1=OK, 2=Bus timeout monitoring activated | |
| MO | 1 | Override | Forced command over the setpoint | Command | 1=None, 2=OPEN, 3=CLOSED, 4=qvmin/dpmin, 6=qvmax/dpmax | |
| MV | 2 | ApplicationSel | Application of the controller | Read | 1=Flow control, 2=Pressure control, 3=Room pressure control, 4=Flow measurement | |
| MV | 100 | ControlMode | Control mode | Read | 1=PosCtrl, 2=FlowCtrl | |
| MV | 102 | OperationMode | Negative or positive pressure (VRU-M1R-BAC only) | Write | 1=Negative pressure, 2=Positive pressure | |
| MV | 120 | Command | Trigger test functions | Write | 1=None, 2=Adaption, 4=Reset | |
| MV | 121 | UnitSelAirFlow | Airflow unit for AI 19 and AV 119 | Write | 2=m³/h, 3=l/s, 7=cfm | |
| MVmin | 122 | SpSource | Setpoint source | Write | 1=Analogue (0-10 V, 2-10 V), 2=Bus (Modbus, BACnet, MP-Bus) | |
| MV | 127 | UnitSelPressure | Pressure unit for AI 18 and AV 129 | Write | 1=Pascal, 3=Water column | |
| MV | 128 | UnitSelTemp | Temperature unit for AI 20 | Write | 1=K, 2=°C, 3=°F | |
| MV | 220 | Sens1Type | Sensor type at the sensor input | Write | 1=None, 2=Active sensor (hybrid mode), 3=Passive sensor, 5=Switch |
No points match these filters.
Object ID lookup: TROX UNIVERSAL static BUPNF duct pressure controller point IDs by name
AI1RelPosAI2AbsPosAI6SpAnalogueAI9RelDeltaPAI10RelFlowAI12AbsFlow_m3hAI18DeltaP_UnitSelAI19AbsFlow_UnitSelAI20Sens1AnalogueAI29DeltaP_PaAO1SpRelAV97MinAV98MaxAV112Vnom_m3hAV119Vnom_UnitSelAV120SystemAltitudeAV122DeltaPnom_PaAV129DeltaPnom_UnitSelAV130BusWatchdogBI20Sens1SwitchBI99BusTerminationBI101SummaryStatusMV10RmPCasacadeMI100InternalActivityMI103StatusSensorMI104StatusFlowMI106StatusActuatorMI109StatusPressureMI110StatusDeviceMO1OverrideMV2ApplicationSelMV100ControlModeMV102OperationModeMV120CommandMV121UnitSelAirFlowMV122SpSourceMV127UnitSelPressureMV128UnitSelTempMV220Sens1Type
Integration notes
- The PICS names the product VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC; the object list follows the Belimo VAV-Universal VRU numbering, so it shares firmware with that Belimo product.
- Several objects go Out_Of_Service depending on MV 2 ApplicationSel, MV 122 SpSource or MV 220 Sens1Type (see the status-flag notes in the data sheet).
- SpSource leaves the factory set to Analogue; set it to Bus before writing AO 1.
- The object name RmPCasacade (MV 10) is spelled this way in the data sheet.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)
How many BACnet points does the TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP) have?
This list has 39 BACnet objects: 10 analog inputs, 1 analog output, 8 analog values, 3 binary inputs, 6 multi-state inputs, 1 multi-state output, 10 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP) BACnet points are writable?
13 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP) BACnet documentation?
The source is TROX UNIVERSAL static BUPNF - Product data sheet (PD-01/2024), revision 2024-01, published free by TROX at https://cdn.trox.de/9fc405e75348e839/11320132561f/BUPNF_PD_2024_01_17_DE_en.pdf.
What are the minimum BACnet points to integrate the TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)?
Start with AO 1 SpRel (Flow, pressure or position setpoint); MV 122 SpSource (Must be Bus (2); factory setting is Analogue); AI 19 AbsFlow_UnitSel (Measured airflow); AI 18 DeltaP_UnitSel (Measured differential pressure); AI 1 RelPos (Damper position feedback); BI 101 SummaryStatus (Overall OK / not OK alarm).
How do I enable BMS control of the TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)?
MV 122 SpSource: 2 = Bus makes AO 1 SpRel active; 1 = Analogue (factory setting) uses the analogue input and AO 1 is ignored.
Does the TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
AV 130 BusWatchdog (0-3600 s, factory 0 = off). When set, the unit watches AO 1 and MO 1 for changes and resets the timer on each change; MI 110 StatusDevice shows when bus timeout monitoring has tripped. With SpSource = Analogue only MO 1 is watched.
Can the BMS supply sensor values to the TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)?
Sensor 1 (AI 20 / BI 20) is configured with MV 220 Sens1Type; with RmPCasacade active it is the 0-10 V room cascade input.
How do I check these points on the real TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More TROX BACnet points lists
- VAV box controller (compact, built-in damper drive)
TROX BM0-D8 VAV control component (BACnet MS/TP)
TROX VAV terminal units fitted with the BM0-D8 compact control component (LMV/NMV-D3-M/B-X TR actuators).
Also known as: BM0-D8, BM0, LMV-D3-M/B-X TR, NMV-D3-M/B-X TR, ..MV-D3-M/B-X, ..MV-D3-M/B-FX, TROX VAV Compact - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM with room management function (RMF) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM with room management function (RMF), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code TAM-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM with room management function (RMF) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM with room management function (RMF), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code TAM-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM without room management function (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM without room management function, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code TAM - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM without room management function (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM without room management function, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code TAM - Laboratory VAV airflow controller
TROX EASYLAB TCU3 all EASYLAB applications (combined list) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as all EASYLAB applications (combined list), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code ELAB - Laboratory VAV airflow controller
TROX EASYLAB TCU3 all EASYLAB applications (combined list) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as all EASYLAB applications (combined list), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code ELAB - Laboratory VAV controller (fume cupboard)
TROX EASYLAB TCU3 fume cupboard controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as fume cupboard controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code FH - Laboratory VAV controller (fume cupboard)
TROX EASYLAB TCU3 fume cupboard controller (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as fume cupboard controller, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code FH - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller with room management function (RMF) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller with room management function (RMF), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code LAB-RMF / CLR-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller with room management function (RMF) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller with room management function (RMF), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code LAB-RMF / CLR-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller without room management function (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller without room management function, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code LAB / CLR - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller without room management function (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller without room management function, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code LAB / CLR - Laboratory VAV airflow controller
TROX EASYLAB TCU3 single extract or supply air controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as single extract or supply air controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code EC / SC - Laboratory VAV airflow controller
TROX EASYLAB TCU3 single extract or supply air controller (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as single extract or supply air controller, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code EC / SC - Decentralised ventilation unit / zone controller
TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)
TROX FSL decentralised (single-room) ventilation units with the FSL-CONTROL II / X-AIRCONTROL controller and the EM-BAC-MOD-01 XAC BACnet MS/TP card.
Also known as: FSL-CONTROL II, X-AIRCONTROL, EM-BAC-MOD-01 XAC, A00000020207, Schoolair, FSL decentralised ventilation - Decentralised ventilation unit controller
TROX FSL-CONTROL III decentralised ventilation controller (software 8.0)
TROX FSL decentralised (single-room) ventilation units with the FSL-CONTROL III controller, software version 8.0.
Also known as: FSL-CONTROL III, FSL-C-III, Schoolair, FSL decentralised ventilation, M172 - Fan coil unit controller
TROX TITAN FCU403 fan coil controller (config FCU403 TRX)
Fan coil units supplied by TROX with the Titan Products FCU4 controller running configuration FCU403 TRX and the graphical RDU.
Also known as: FCU403, FCU4, FCU403 TRX, Titan FCU4, FCU403 TP1193E, Graphical RDU V2 - VAV room airflow controller
TROX UNIVERSAL all TROX UNIVERSAL applications (combined list) (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as all TROX UNIVERSAL applications (combined list), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code TU* - VAV room airflow controller
TROX UNIVERSAL all TROX UNIVERSAL applications (combined list) (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as all TROX UNIVERSAL applications (combined list), fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code TU* - VAV room / duct pressure controller
TROX UNIVERSAL duct pressure controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as duct pressure controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PDS / PDE - VAV room airflow controller
TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code RS / RE - VAV room airflow controller
TROX UNIVERSAL room airflow controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code RS / RE - VAV room airflow controller
TROX UNIVERSAL room airflow controller, master (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, master, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code RS/M / RE/M - VAV room airflow controller
TROX UNIVERSAL room airflow controller, master (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, master, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code RS/M / RE/M - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code PRS / PRE / PDS / PDE - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller, master (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, master, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code PRS/M / PRE/M / PDS/M / PDE/M, TROX UNIVERSAL PD master - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller, master (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, master, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PRS/M / PRE/M / PDS/M / PDE/M, TROX UNIVERSAL PD master - VAV room / duct pressure controller
TROX UNIVERSAL room pressure controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room pressure controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PRS / PRE - Fire and smoke damper control module
TROX TROXNETCOM MB-BAC-WA1/2 fire damper module (BACnet MS/TP)
TROX TROXNETCOM MB-BAC-WA1/2 modules that drive and monitor up to 2 fire or smoke extract dampers (motorised or limit-switch only).
Also known as: MB-BAC-WA1/2, MB-BAC-WA1B3, TROXNETCOM, MB-BAC-WA1-2 - Fire and smoke damper control module
TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)
TROX TROXNETCOM MB-BAC-WA1/4 modules that drive and monitor up to 4 fire or smoke extract dampers (motorised or limit-switch only).
Also known as: MB-BAC-WA1/4, TROXNETCOM, MB-BAC-WA1-4 - VAV zone controller (master for up to 25 zone modules)
TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)
TROX Auranor X-AIRCONTROL VAV zone control systems: one Master with up to 25 Zone Modules, linked to an AHU.
Also known as: X-AIRCONTROL, X-AIRCONTROL Master, TROX Auranor X-AIRCONTROL, 67501-06/15, X-AIRCONTROL ZoneModule - Air handling unit controller
TROX X-CUBE Control BACnet data point list
TROX X-CUBE central air handling units with the factory X-CUBE Control system.
Also known as: X-CUBE, TROX X-CUBE, X-CUBE Control, BACnet DPL, BACnet EDE XCUBE - VAV box controller (compact, built-in damper drive)
TROX XDMB0 compact VAV control component (TVE, BACnet MS/TP)
TROX TVE and TVE-Q VAV terminal units fitted with the XDMB0 compact control component.
Also known as: XDMB0, TVE XDMB0, TVE-Q, Compact XDMB0
Source: TROX UNIVERSAL static BUPNF - Product data sheet · PD-01/2024 · rev. 2024-01. Object names, instances and units are reproduced as published; descriptions are our own.