Easy BACnet
  1. Home
  2. BACnet points lists
  3. TROX
  4. TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)

Fire and smoke damper control module · BACnet points list

TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The MB-BAC-WA1/4 module connects up to 4 fire or smoke dampers to BACnet MS/TP (or Modbus RTU). Per channel it has an operating-mode object, a safe position, an open/close command, position feedback, an alarm object and run-time and heartbeat timers; a test object starts a damper test for all channels. 38 objects in total; the object names are factory defaults and can be renamed.

This page lists 38 BACnet objects for the TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) — 29 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.

Manufacturer
TROX
Model
TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)
Equipment
Fire and smoke damper control module
Equipment type
Other equipment
BACnet objects
38 (29 writable)
Transport
BACnet MS/TP
Firmware
1.0
Default device instance
32900 + address switch
Also known as
MB-BAC-WA1/4, TROXNETCOM, MB-BAC-WA1-4
Source document
TROXNETCOM functional module MB-BAC-WA1/4 - Installation, commissioning and maintenance manual · A00000068978 V2 · rev. 2026-04
Download CSV 38 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TROX’s current documentation and the live device before use. Not official TROX information. Terms of use.

BMS integration notes: TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)

Integration in brief

Set each channel mode in Damper1..4 (MV 1-4) and its safe position, then drive motorised dampers with ActuDrive (open/close) and read ActuPos and Alarm. Write OK (1) to an Alarm object to reset it. If RcvHrtBt is set, the BMS must rewrite ActuDrive within that time.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 9ActuDrive1Open/close command, damper 1Write
BV 1TestStarts a damper test runWrite
MV 13ActuPos1Damper 1 position: open, close, runningRead
BV 2FireChainFire chain relay stateRead
MV 21Alarm1Channel 1 alarm; write 1 (OK) to resetWrite

Enable & remote start

A channel is only active once its Damper object (MV 1-4) is set from Inactive (1, factory) to an operating mode.

Heartbeat & communication loss

RcvHrtBt1..4 (AV 9-12, factory 0 = off) sets the maximum time between writes to ActuDrive. If it is exceeded the channel reports Update_Error and the damper goes to its safe position; the error stays latched until reset.

Network setup

Watch out for

TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

38 of 38 shown
Type
AnalogBinaryMulti-state
Access
Show
TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) BACnet Points List
DescriptionStates
BVmin1TestStarts, stops and signals a damper test runWrite0=No_Test_Active, 1=Test_Active
BVmin2FireChainFire chain relay stateRead0=Relay_Off, 1=Relay_On
AV1DriveTime1Max. opening time of damper 1, 0 = off (default 240)sWrite
AV2DriveTime2Max. opening time of damper 2, 0 = off (default 240)sWrite
AV3DriveTime3Max. opening time of damper 3, 0 = off (default 240)sWrite
AV4DriveTime4Max. opening time of damper 4, 0 = off (default 240)sWrite
AV5TurnOffTime1Max. closing time of damper 1, 0 = off (default 35)sWrite
AV6TurnOffTime2Max. closing time of damper 2, 0 = off (default 35)sWrite
AV7TurnOffTime3Max. closing time of damper 3, 0 = off (default 35)sWrite
AV8TurnOffTime4Max. closing time of damper 4, 0 = off (default 35)sWrite
AV9RcvHrtBt1Max. time between ActuDrive1 writes, 0 = offsWrite
AV10RcvHrtBt2Max. time between ActuDrive2 writes, 0 = offsWrite
AV11RcvHrtBt3Max. time between ActuDrive3 writes, 0 = offsWrite
AV12RcvHrtBt4Max. time between ActuDrive4 writes, 0 = offsWrite
MV1Damper1Operating mode of channel 1Write1=Inactive, 2=Motorized_Damper, 3=Limit_Switches_Open_and_Closed, 4=Only_Limit_Switch_Open, 5=Only_Limit_Switch_Closed
MV2Damper2Operating mode of channel 2Write1=Inactive, 2=Motorized_Damper, 3=Limit_Switches_Open_and_Closed, 4=Only_Limit_Switch_Open, 5=Only_Limit_Switch_Closed
MV3Damper3Operating mode of channel 3Write1=Inactive, 2=Motorized_Damper, 3=Limit_Switches_Open_and_Closed, 4=Only_Limit_Switch_Open, 5=Only_Limit_Switch_Closed
MV4Damper4Operating mode of channel 4Write1=Inactive, 2=Motorized_Damper, 3=Limit_Switches_Open_and_Closed, 4=Only_Limit_Switch_Open, 5=Only_Limit_Switch_Closed
MV5SafetyPos1Safe position of damper 1 on errorWrite1=open, 2=close
MV6SafetyPos2Safe position of damper 2 on errorWrite1=open, 2=close
MV7SafetyPos3Safe position of damper 3 on errorWrite1=open, 2=close
MV8SafetyPos4Safe position of damper 4 on errorWrite1=open, 2=close
MVmin9ActuDrive1Open/close command for damper 1Write1=open, 2=close
MV10ActuDrive2Open/close command for damper 2Write1=open, 2=close
MV11ActuDrive3Open/close command for damper 3Write1=open, 2=close
MV12ActuDrive4Open/close command for damper 4Write1=open, 2=close
MVmin13ActuPos1Position of damper 1 from limit switchesRead1=open, 2=close, 3=running
MV14ActuPos2Position of damper 2 from limit switchesRead1=open, 2=close, 3=running
MV15ActuPos3Position of damper 3 from limit switchesRead1=open, 2=close, 3=running
MV16ActuPos4Position of damper 4 from limit switchesRead1=open, 2=close, 3=running
MV17ActuPos1aPosition of second damper on channel 1Read1=open, 2=close
MV18ActuPos2aPosition of second damper on channel 2Read1=open, 2=close
MV19ActuPos3aPosition of second damper on channel 3Read1=open, 2=close
MV20ActuPos4aPosition of second damper on channel 4Read1=open, 2=close
MVmin21Alarm1Alarm state of channel 1; write OK (1) to resetWrite1=OK, 2=System_Error, 3=Runtime_Error, 4=Manipulation, 5=Update_Error, 6=Alarm, 7=Alarm_a
MV22Alarm2Alarm state of channel 2; write OK (1) to resetWrite1=OK, 2=System_Error, 3=Runtime_Error, 4=Manipulation, 5=Update_Error, 6=Alarm, 7=Alarm_a
MV23Alarm3Alarm state of channel 3; write OK (1) to resetWrite1=OK, 2=System_Error, 3=Runtime_Error, 4=Manipulation, 5=Update_Error, 6=Alarm, 7=Alarm_a
MV24Alarm4Alarm state of channel 4; write OK (1) to resetWrite1=OK, 2=System_Error, 3=Runtime_Error, 4=Manipulation, 5=Update_Error, 6=Alarm, 7=Alarm_a
Object ID lookup: TROX TROXNETCOM MB-BAC-WA1/4 fire damper module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)

How many BACnet points does the TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) have?

This list has 38 BACnet objects: 12 analog values, 2 binary values, 24 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) BACnet points are writable?

29 of the 38 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) BACnet documentation?

The source is TROXNETCOM functional module MB-BAC-WA1/4 - Installation, commissioning and maintenance manual (A00000068978 V2), revision 2026-04, published free by TROX at https://www.trox.de/en/downloads/345d50c92eb87aec/MB-BAC-WA1-4_ICM_A00000068978_V2_2026_04_GB_en.pdf.

What are the minimum BACnet points to integrate the TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)?

Start with MV 9 ActuDrive1 (Open/close command, damper 1); BV 1 Test (Starts a damper test run); MV 13 ActuPos1 (Damper 1 position: open, close, running); BV 2 FireChain (Fire chain relay state); MV 21 Alarm1 (Channel 1 alarm; write 1 (OK) to reset).

How do I enable BMS control of the TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)?

A channel is only active once its Damper object (MV 1-4) is set from Inactive (1, factory) to an operating mode.

Does the TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

RcvHrtBt1..4 (AV 9-12, factory 0 = off) sets the maximum time between writes to ActuDrive. If it is exceeded the channel reports Update_Error and the damper goes to its safe position; the error stays latched until reset.

How do I check these points on the real TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TROX BACnet points lists

Source: TROXNETCOM functional module MB-BAC-WA1/4 - Installation, commissioning and maintenance manual · A00000068978 V2 · rev. 2026-04. Object names, instances and units are reproduced as published; descriptions are our own.