- FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)
Decentralised ventilation unit / zone controller · BACnet points list
TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP) BACnet points list
Updated 6 November 2026
FSL-CONTROL II single-room ventilation units connect to BACnet MS/TP through the EM-BAC-MOD-01 XAC expansion card. The PICS in the FSL-CONTROL II manual lists 47 objects (AV 1-18, BV 1-20, MV 1-9): BMS presets for operating mode, occupancy, fan stage, changeover, fire and window inputs, BMS-fed temperatures, humidity and VOC values, plus feedback, alarms and hardware status messages.
This page lists 47 BACnet objects for the TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.
- Manufacturer
- TROX
- Model
- FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)
- Equipment
- Decentralised ventilation unit / zone controller
- Equipment type
- Other equipment
- BACnet objects
- 47 (18 writable)
- Transport
- BACnet MS/TP
- Firmware
- EM-BAC-MOD-01 XAC 1.0; data point list valid from X-AIRCONTROL V1.14
- Default device instance
- 32900 + address switch
- Also known as
- FSL-CONTROL II, X-AIRCONTROL, EM-BAC-MOD-01 XAC, A00000020207, Schoolair, FSL decentralised ventilation
Reference only, provided as-is: verify against TROX’s current documentation and the live device before use. Not official TROX information. Terms of use.
BMS integration notes: TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)
Preset the operating mode with MV 4 Mode (occupied/unoccupied/boost/standby) or MV 2 ApplicMode, set the fan stage with MV 8 and the heat/cool changeover with MV 7, and feed BV 2 Fire and BV 3 Window if the BMS handles them. Read MV 5 ActMode, AV 7 ActRoomTemp, AV 14 EffectSetpt and the alarm BVs (BV 7, BV 8, BV 11-17).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 4 | Mode | Occupancy preset: occupied, unoccupied, boost, standby | Write |
| MV 8 | FanSpeed | Fan stage preset: off, level 1-5 or auto | Write |
| AV 5 | TempOffset | Relative room setpoint offset, °C | Write |
| BV 2 | Fire | Fire protection switch-off from the BMS | Write |
| MV 5 | ActMode | Actual operating mode | Read |
| AV 7 | ActRoomTemp | Room air temperature | Read |
| AV 14 | EffectSetpt | Effective room temperature setpoint | Read |
| BV 7 | FAlarm | Frost protection alarm | Read |
| BV 8 | Alarm1 | Alarm/error message | Read |
Enable & remote start
MV 4 Mode is the operating mode default from the central BMS; 5 = NUL means no preset. MV 2 ApplicMode presets the HVAC mode (1 = HVAC_NUL, inactive).
Sensors & values from the BMS
AV 1 OutsideTemp, AV 6 RoomTemp, AV 8 RelHumid, AV 10 VOC_Room and AV 12 VOC_Outside take values written by the BMS; the Act* objects show what the controller uses.
Network setup
- Default device instance 32900 + the network address on hex switches X/Y.
- Baud rate 9600, 19200, 38400 or 76800 on DIP switches 2 and 3; select BACnet or Modbus with the slide switch on the interface card.
- Max_Master default 127, Max_Info_Frames default 1.
Watch out for
- BV 7, BV 8, BV 9 and BV 11-17 support unsolicited COV, set by MV 1 COV-Mode.
- A written temperature of 327.67 is treated as invalid.
TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | OutsideTemp | Outdoor air temperature from the BMS | °C | Write | |
| AV | 2 | ActOutsideTemp | Actual outdoor air temperature (feedback) | °C | Read | |
| AV | 3 | RoomTemp_Set | °C | Write | ||
| AV | 4 | SetptOffset | Temperature offset (feedback) | °C | Read | |
| AVmin | 5 | TempOffset | Relative room setpoint offset from the BMS | °C | Write | |
| AV | 6 | RoomTemp | Room temperature from the BMS | °C | Write | |
| AVmin | 7 | ActRoomTemp | Actual room air temperature | °C | Read | |
| AV | 8 | RelHumid | Relative humidity from the BMS | %RH | Write | |
| AV | 9 | ActRelHumid | Relative humidity (feedback) | %RH | Read | |
| AV | 10 | VOC_Room | Room VOC value from the BMS | ppm | Write | |
| AV | 11 | ActVOC_Room | Actual VOC value | ppm | Read | |
| AV | 12 | VOC_Outside | Outdoor air VOC value from the BMS | ppm | Write | |
| AV | 13 | DischAirTemp | Supply air actual temperature | °C | Read | |
| AVmin | 14 | EffectSetpt | Effective room temperature setpoint | °C | Read | |
| AV | 15 | RTemp | Return temperature | °C | Read | |
| AV | 16 | Sum_Sup | Total supply air flow rate | l/s | Read | |
| AV | 17 | Sum_Exh | Total extract air flow rate | l/s | Read | |
| AV | 18 | SystemDevices | Number of system devices | Read | ||
| BV | 1 | StartPCM | Write | 0=Off, 1=On | ||
| BVmin | 2 | Fire | Emergency switch-off for fire protection | Write | 0=Normal, 1=Fire | |
| BV | 3 | Window | Switch-off from window contact | Write | 0=Close, 1=Open | |
| BV | 4 | ExtraTime | Extension of operating time | Write | 0=Inactive, 1=Active | |
| BV | 5 | ActExtraTime | Feedback: operating time extension active | Read | 0=Inactive, 1=Active | |
| BV | 6 | ActWindow | Feedback: window contact | Read | 0=Close, 1=Open | |
| BVmin | 7 | FAlarm | Frost protection alarm | Read | 0=Normal, 1=Frostalarm | |
| BVmin | 8 | Alarm1 | Alarm/error message | Read | 0=Normal, 1=Alarm1 | |
| BV | 9 | Alarm2 | Read | 0=Normal, 1=Alarm2 | ||
| BV | 10 | Release | Read | 0=Off, 1=On | ||
| BV | 11 | Status_PowerSupply | Hardware message: power supply | Read | 0=Normal, 1=LowPower | |
| BV | 12 | Status_EMFSLIO | Hardware message: EM-FSLIO communication | Read | 0=Normal, 1=ComFail | |
| BV | 13 | Status_Fan | Hardware message: fan | Read | 0=Normal, 1=FanBlocked | |
| BV | 14 | Status_Sensor | Hardware message: sensor | Read | 0=Normal, 1=SensorFail | |
| BV | 15 | Status_Filter | Hardware message: filter | Read | 0=Normal, 1=FilterAlarm | |
| BV | 16 | Status_FlowControl | Hardware message: flow control | Read | 0=Normal, 1=FlowAlarm | |
| BV | 17 | Status_Damper | Hardware message: damper | Read | 0=Normal, 1=CalibrationFail | |
| BV | 18 | ActFire | Feedback: fire switch-off | Read | 0=Normal, 1=Fire | |
| BV | 19 | FanForce | Write | 0=Inactive, 1=Active | ||
| BV | 20 | ActFanForce | Feedback of FanForce | Read | 0=Inactive, 1=Active | |
| MV | 1 | COV-Mode | How unsolicited COV notifications are sent | Write | 1=Disabled, 2=Local Broadcast, 3=Global Broadcast | |
| MV | 2 | ApplicMode | Operating mode default setting | Write | 1=HVAC_NUL, 2=HVAC_AUTO, 3=HVAC_HEAT, 4=HVAC_MRNG_WRMUP, 5=HVAC_COOL, 6=HVAC_NIGHT_PURGE, 7=HVAC_PRE_COOL, 8=HVAC_OFF, 9=HVAC_TEST, 10=HVAC_EMERG_HEAT, 11=HVAC_FAN_ONLY, 12=HVAC_FREE_COOL, 13=HVAC_MAXHEAT, 14=HVAC_ECONOMY, 15=HVAC_DEHUMID | |
| MV | 3 | ActApplicMode | Feedback: actual operating state | Read | 1=HVAC_NUL, 2=HVAC_AUTO, 3=HVAC_HEAT, 4=HVAC_MRNG_WRMUP, 5=HVAC_COOL, 6=HVAC_NIGHT_PURGE, 7=HVAC_PRE_COOL, 8=HVAC_OFF, 9=HVAC_TEST, 10=HVAC_EMERG_HEAT, 11=HVAC_FAN_ONLY, 12=HVAC_FREE_COOL, 13=HVAC_MAXHEAT, 14=HVAC_ECONOMY, 15=HVAC_DEHUMID | |
| MVmin | 4 | Mode | Operating mode default setting by the central BMS | Write | 1=OCCUPIED, 2=UNOCCUPIED, 3=BOOST, 4=STANDBY, 5=NUL | |
| MVmin | 5 | ActMode | Actual operating mode | Read | 1=OCCUPIED, 2=UNOCCUPIED, 3=BOOST, 4=STANDBY, 5=NUL | |
| MV | 6 | OccSensor | Operating mode default from a PIR sensor | Write | 1=OCCUPIED, 2=UNOCCUPIED, 3=BOOST, 4=STANDBY, 5=NUL | |
| MV | 7 | ChangeOver | Changeover between heating and cooling | Write | 1=Off, 2=COOLING, 3=HEATING | |
| MVmin | 8 | FanSpeed | Default setting of fan stage | Write | 1=Off, 2=LEVEL1, 3=LEVEL2, 4=LEVEL3, 5=LEVEL4, 6=LEVEL5, 7=AUTO | |
| MV | 9 | ActFanSpeed | Feedback: actual fan stage (hand or auto) | Read | 1=Off (hand), 2=LEVEL1, 3=LEVEL2, 4=LEVEL3, 5=LEVEL4, 6=LEVEL5, 7=Off (auto), 8=LEVEL1, 9=LEVEL2, 10=LEVEL3, 11=LEVEL4, 12=LEVEL5 |
No points match these filters.
Object ID lookup: TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC point IDs by name
AV1OutsideTempAV2ActOutsideTempAV3RoomTemp_SetAV4SetptOffsetAV5TempOffsetAV6RoomTempAV7ActRoomTempAV8RelHumidAV9ActRelHumidAV10VOC_RoomAV11ActVOC_RoomAV12VOC_OutsideAV13DischAirTempAV14EffectSetptAV15RTempAV16Sum_SupAV17Sum_ExhAV18SystemDevicesBV1StartPCMBV2FireBV3WindowBV4ExtraTimeBV5ActExtraTimeBV6ActWindowBV7FAlarmBV8Alarm1BV9Alarm2BV10ReleaseBV11Status_PowerSupplyBV12Status_EMFSLIOBV13Status_FanBV14Status_SensorBV15Status_FilterBV16Status_FlowControlBV17Status_DamperBV18ActFireBV19FanForceBV20ActFanForceMV1COV-ModeMV2ApplicModeMV3ActApplicModeMV4ModeMV5ActModeMV6OccSensorMV7ChangeOverMV8FanSpeedMV9ActFanSpeed
Integration notes
- Object names, units and state texts come from the EM-BAC-MOD-01 XAC PICS tables; descriptions follow the manual's data point list where it has one.
- The data point list gives the same functions for LON and Modbus; only the BACnet objects are listed here.
- Temperature defaults of 327.67 mean "invalid / not set".
- BV 11-17 are the individual hardware messages (power supply, EM-FSLIO, fan, sensor, filter, flow control, damper).
- StartPCM, Alarm2, Release, FanForce and RoomTemp_Set are not described in the manual.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)
How many BACnet points does the TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP) have?
This list has 47 BACnet objects: 18 analog values, 20 binary values, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP) BACnet points are writable?
18 of the 47 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP) BACnet documentation?
The source is FSL-CONTROL II single room control system - installation and commissioning manual (BACnet MS/TP PICS and X-AIRCONTROL data point list) (A00000046303 V6), revision 2018-04, published free by TROX at https://www.trox.de/en/downloads/89ec5e20ea361fa7/SM_2018_04_A00000046303_FSL-CONTROL_II_V6_GB_en_web.pdf.
What are the minimum BACnet points to integrate the TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)?
Start with MV 4 Mode (Occupancy preset: occupied, unoccupied, boost, standby); MV 8 FanSpeed (Fan stage preset: off, level 1-5 or auto); AV 5 TempOffset (Relative room setpoint offset, °C); BV 2 Fire (Fire protection switch-off from the BMS); MV 5 ActMode (Actual operating mode); AV 7 ActRoomTemp (Room air temperature); AV 14 EffectSetpt (Effective room temperature setpoint); BV 7 FAlarm (Frost protection alarm); BV 8 Alarm1 (Alarm/error message).
How do I enable BMS control of the TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)?
MV 4 Mode is the operating mode default from the central BMS; 5 = NUL means no preset. MV 2 ApplicMode presets the HVAC mode (1 = HVAC_NUL, inactive).
Can the BMS supply sensor values to the TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)?
AV 1 OutsideTemp, AV 6 RoomTemp, AV 8 RelHumid, AV 10 VOC_Room and AV 12 VOC_Outside take values written by the BMS; the Act* objects show what the controller uses.
How do I check these points on the real FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More TROX BACnet points lists
- VAV box controller (compact, built-in damper drive)
TROX BM0-D8 VAV control component (BACnet MS/TP)
TROX VAV terminal units fitted with the BM0-D8 compact control component (LMV/NMV-D3-M/B-X TR actuators).
Also known as: BM0-D8, BM0, LMV-D3-M/B-X TR, NMV-D3-M/B-X TR, ..MV-D3-M/B-X, ..MV-D3-M/B-FX, TROX VAV Compact - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM with room management function (RMF) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM with room management function (RMF), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code TAM-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM with room management function (RMF) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM with room management function (RMF), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code TAM-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM without room management function (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM without room management function, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code TAM - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM without room management function (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM without room management function, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code TAM - Laboratory VAV airflow controller
TROX EASYLAB TCU3 all EASYLAB applications (combined list) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as all EASYLAB applications (combined list), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code ELAB - Laboratory VAV airflow controller
TROX EASYLAB TCU3 all EASYLAB applications (combined list) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as all EASYLAB applications (combined list), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code ELAB - Laboratory VAV controller (fume cupboard)
TROX EASYLAB TCU3 fume cupboard controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as fume cupboard controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code FH - Laboratory VAV controller (fume cupboard)
TROX EASYLAB TCU3 fume cupboard controller (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as fume cupboard controller, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code FH - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller with room management function (RMF) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller with room management function (RMF), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code LAB-RMF / CLR-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller with room management function (RMF) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller with room management function (RMF), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code LAB-RMF / CLR-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller without room management function (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller without room management function, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code LAB / CLR - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller without room management function (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller without room management function, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code LAB / CLR - Laboratory VAV airflow controller
TROX EASYLAB TCU3 single extract or supply air controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as single extract or supply air controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code EC / SC - Laboratory VAV airflow controller
TROX EASYLAB TCU3 single extract or supply air controller (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as single extract or supply air controller, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code EC / SC - Decentralised ventilation unit controller
TROX FSL-CONTROL III decentralised ventilation controller (software 8.0)
TROX FSL decentralised (single-room) ventilation units with the FSL-CONTROL III controller, software version 8.0.
Also known as: FSL-CONTROL III, FSL-C-III, Schoolair, FSL decentralised ventilation, M172 - Fan coil unit controller
TROX TITAN FCU403 fan coil controller (config FCU403 TRX)
Fan coil units supplied by TROX with the Titan Products FCU4 controller running configuration FCU403 TRX and the graphical RDU.
Also known as: FCU403, FCU4, FCU403 TRX, Titan FCU4, FCU403 TP1193E, Graphical RDU V2 - VAV room airflow controller
TROX UNIVERSAL all TROX UNIVERSAL applications (combined list) (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as all TROX UNIVERSAL applications (combined list), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code TU* - VAV room airflow controller
TROX UNIVERSAL all TROX UNIVERSAL applications (combined list) (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as all TROX UNIVERSAL applications (combined list), fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code TU* - VAV room / duct pressure controller
TROX UNIVERSAL duct pressure controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as duct pressure controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PDS / PDE - VAV room airflow controller
TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code RS / RE - VAV room airflow controller
TROX UNIVERSAL room airflow controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code RS / RE - VAV room airflow controller
TROX UNIVERSAL room airflow controller, master (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, master, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code RS/M / RE/M - VAV room airflow controller
TROX UNIVERSAL room airflow controller, master (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, master, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code RS/M / RE/M - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code PRS / PRE / PDS / PDE - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller, master (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, master, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code PRS/M / PRE/M / PDS/M / PDE/M, TROX UNIVERSAL PD master - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller, master (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, master, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PRS/M / PRE/M / PDS/M / PDE/M, TROX UNIVERSAL PD master - VAV room / duct pressure controller
TROX UNIVERSAL room pressure controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room pressure controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PRS / PRE - VAV / static pressure controller
TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)
TROX UNIVERSAL static BUPNF controllers (VRU-D3/M1/M1R-BAC control electronics) for airflow, duct pressure and room pressure control.
Also known as: BUPNF, TROX UNIVERSAL static, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-D3-M/B TR, VRU-M1-M/B TR, VRU-M1R-M/B TR - Fire and smoke damper control module
TROX TROXNETCOM MB-BAC-WA1/2 fire damper module (BACnet MS/TP)
TROX TROXNETCOM MB-BAC-WA1/2 modules that drive and monitor up to 2 fire or smoke extract dampers (motorised or limit-switch only).
Also known as: MB-BAC-WA1/2, MB-BAC-WA1B3, TROXNETCOM, MB-BAC-WA1-2 - Fire and smoke damper control module
TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)
TROX TROXNETCOM MB-BAC-WA1/4 modules that drive and monitor up to 4 fire or smoke extract dampers (motorised or limit-switch only).
Also known as: MB-BAC-WA1/4, TROXNETCOM, MB-BAC-WA1-4 - VAV zone controller (master for up to 25 zone modules)
TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)
TROX Auranor X-AIRCONTROL VAV zone control systems: one Master with up to 25 Zone Modules, linked to an AHU.
Also known as: X-AIRCONTROL, X-AIRCONTROL Master, TROX Auranor X-AIRCONTROL, 67501-06/15, X-AIRCONTROL ZoneModule - Air handling unit controller
TROX X-CUBE Control BACnet data point list
TROX X-CUBE central air handling units with the factory X-CUBE Control system.
Also known as: X-CUBE, TROX X-CUBE, X-CUBE Control, BACnet DPL, BACnet EDE XCUBE - VAV box controller (compact, built-in damper drive)
TROX XDMB0 compact VAV control component (TVE, BACnet MS/TP)
TROX TVE and TVE-Q VAV terminal units fitted with the XDMB0 compact control component.
Also known as: XDMB0, TVE XDMB0, TVE-Q, Compact XDMB0
Source: FSL-CONTROL II single room control system - installation and commissioning manual (BACnet MS/TP PICS and X-AIRCONTROL data point list) · A00000046303 V6 · rev. 2018-04. Object names, instances and units are reproduced as published; descriptions are our own.