VAV box controller (compact, built-in damper drive) · BACnet points list

TROX BM0-D8 VAV control component (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

BM0-D8 is a compact VAV actuator-controller TROX fits to its VAV terminal units. It ships in Modbus RTU mode and can be switched to BACnet MS/TP with a service tool. The BACnet object list has 23 objects: relative setpoint (AO 1), override (MO 1), airflow and damper readings, min/max limits, a bus watchdog and status objects.

This page lists 23 BACnet objects for the TROX BM0-D8 VAV control component (BACnet MS/TP) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.

Manufacturer
TROX
Model
BM0-D8 VAV control component (BACnet MS/TP)
Equipment
VAV box controller (compact, built-in damper drive)
Equipment type
VAV boxes & fan coils
BACnet objects
23 (10 writable)
Transport
BACnet MS/TP
Firmware
BTL:0002 B:0001 (Modbus module V1.0)
Also known as
BM0-D8, BM0, LMV-D3-M/B-X TR, NMV-D3-M/B-X TR, ..MV-D3-M/B-X, ..MV-D3-M/B-FX, TROX VAV Compact
Source document
Control component BM0-D8 - Installation, operation and maintenance manual · CD10129 V2 · rev. 2026-07
Download CSV 23 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TROX’s current documentation and the live device before use. Not official TROX information. Terms of use.

BMS integration notes: TROX BM0-D8 VAV control component (BACnet MS/TP)

Integration in brief

Switch the unit to BACnet MS/TP, keep MV 122 SpSource at Bus, and write the setpoint to AO 1 SpRel (0-100 % between qvmin and qvmax); MO 1 Override forces open/closed/qvmin/qvmid/qvmax. Read AI 10 or AI 19 for airflow, AI 1 for damper position and BI 101 for faults. Turn on AV 130 Bus Watchdog if the unit should fall back when the BMS stops writing.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1SpRelAirflow setpoint between Min. and Max.Command
AI 19AbsFlow_UnitSelMeasured airflowRead
AI 1RelPosDamper position feedbackRead
BI 101SummaryStatusOverall OK / not OK alarmRead

Enable & remote start

MV 122 SpSource selects the setpoint source: 2 = Bus (factory setting), 1 = Analogue, in which case AO 1 goes out of service.

Heartbeat & communication loss

AV 130 Bus Watchdog (0-3600 s, factory 0 = off). When set, writes to AO 1 SpRel or MO 1 Override reset the timer; if it expires the AO 1 Relinquish_Default applies (factory 0 = qvmin) and MI 110 StatusDevice shows bus failure. In hybrid mode only MO 1 writes are monitored.

Network setup

Watch out for

TROX BM0-D8 VAV control component (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

23 of 23 shown
Type
Binary
Access
Show
TROX BM0-D8 VAV control component (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1RelPosDamper blade position%Read
AI2AbsPosAbsolute position°Read
AI6SpAnalogueAnalogue setpoint (when SpSource = Analogue)%Read
AI10RelFlowRelative airflow%Read
AImin19AbsFlow_UnitSelAbsolute airflow in the unit set by MV 121Read
AI20Sens1AnalogueSensor 1 analogue valuemVRead
AOmin1SpRelRelative setpoint between qvmin and qvmax (bus control)%Command
AV97Min.Minimum setpoint qvmin%Write
AV98Max.Maximum setpoint qvmax%Write
AV104Vnom_UnitSelNominal airflow in the unit set by MV 121Read
AV130Bus WatchdogTime until bus failure monitoring trips, 0 = offsWrite
BI20Sens1SwitchSwitch status at the sensor inputRead0=Switch not active
BI99BusTermination120 ohm terminating resistor switched on via service toolRead0=Switch not active
BImin101SummaryStatusSummary status (MI 106 and MI 110)Read0=no error
MI100InternalActivityActivity statusRead1=none, 2=Test, 3=Adaptation
MI106StatusActuatorActuator statusRead1=OK, 2=Actuator cannot be moved, 3=Gear disengagement active, 4=Mechanical travel exceeded
MI110StatusDeviceGeneral device statusRead1=OK, 2=Bus failure monitoring activated
MO1OverrideForced command over the setpointCommand1=none, 2=OPEN, 3=CLOSED, 4=qvmin, 5=qvmid, 6=qvmax
MV120CommandTrigger test functionsWrite1=none, 2=Adaptation, 3=Test, 4=Reset
MV121UnitSelFlowAirflow unit for AI 19 and AV 104Write1=m³/s, 2=m³/h, 3=l/s, 4=l/min, 5=l/h, 6=gpm, 7=cfm
MV122SpSourceSetpoint sourceWrite1=Analogue (0-10 V, 2-10 V), 2=Bus (Modbus, BACnet, MP-Bus)
MV123ControlModeControl modeWrite1=Position control (OpenLoop), 2=Volume flow control
MV220Sens1TypeSensor type at the analogue inputWrite1=none, 2=active sensor (hybrid mode), 5=switch
Object ID lookup: TROX BM0-D8 VAV control component point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BM0-D8 VAV control component (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TROX BM0-D8 VAV control component (BACnet MS/TP)

How many BACnet points does the TROX BM0-D8 VAV control component (BACnet MS/TP) have?

This list has 23 BACnet objects: 6 analog inputs, 1 analog output, 4 analog values, 3 binary inputs, 3 multi-state inputs, 1 multi-state output, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TROX BM0-D8 VAV control component (BACnet MS/TP) BACnet points are writable?

10 of the 23 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TROX BM0-D8 VAV control component (BACnet MS/TP) BACnet documentation?

The source is Control component BM0-D8 - Installation, operation and maintenance manual (CD10129 V2), revision 2026-07, published free by TROX at https://www.trox.de/en/downloads/18aceabac41d9f56/BM0-D8_IOM_CD10129_V2_2026_07_GB_en.pdf.

What are the minimum BACnet points to integrate the TROX BM0-D8 VAV control component (BACnet MS/TP)?

Start with AO 1 SpRel (Airflow setpoint between Min. and Max); AI 19 AbsFlow_UnitSel (Measured airflow); AI 1 RelPos (Damper position feedback); BI 101 SummaryStatus (Overall OK / not OK alarm).

How do I enable BMS control of the TROX BM0-D8 VAV control component (BACnet MS/TP)?

MV 122 SpSource selects the setpoint source: 2 = Bus (factory setting), 1 = Analogue, in which case AO 1 goes out of service.

Does the TROX BM0-D8 VAV control component (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

AV 130 Bus Watchdog (0-3600 s, factory 0 = off). When set, writes to AO 1 SpRel or MO 1 Override reset the timer; if it expires the AO 1 Relinquish_Default applies (factory 0 = qvmin) and MI 110 StatusDevice shows bus failure. In hybrid mode only MO 1 writes are monitored.

How do I check these points on the real BM0-D8 VAV control component (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TROX BACnet points lists

Source: Control component BM0-D8 - Installation, operation and maintenance manual · CD10129 V2 · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.