- TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)
VAV room airflow controller · BACnet points list
TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP) BACnet points list
Updated 11 November 2026
TROX UNIVERSAL lab and room airflow controllers connect to BACnet MS/TP (or Modbus RTU) through the EM-BAC-MOD-01 expansion module. This is TROX's EDE file for the room airflow controller (order code RS / RE): 42 value objects (16 AV, 25 BV, 1 MV). The MS/TP module has a much smaller object set than the EM-IP (BACnet IP) module, and some instance numbers differ.
This page lists 42 BACnet objects for the TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TROX’s own free documentation, linked below.
- Manufacturer
- TROX
- Model
- TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)
- Equipment
- VAV room airflow controller
- Equipment type
- VAV boxes & fan coils
- BACnet objects
- 42 (8 writable)
- Transport
- BACnet MS/TP
- Firmware
- EM-BAC-MOD EDE V4.1
- Default device instance
- 32900 + network address
- Also known as
- TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code RS / RE
Reference only, provided as-is: verify against TROX’s current documentation and the live device before use. Not official TROX information. Terms of use.
BMS integration notes: TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)
This application takes no mode preset over BACnet; the BMS mainly reads airflow, damper and alarm values. Read MV 4 RoomModeAct, AV 2 VolflowAct, AV 3 VolTotalExh, BV 1 LocalAlarm.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 4 | RoomModeAct | Current operating mode of the room | Read |
| AV 2 | VolflowAct | Measured airflow, l/s | Read |
| AV 10 | DampPos | Damper position, % | Read |
| BV 1 | LocalAlarm | Alarm on this controller | Read |
Sensors & values from the BMS
AV 22 VolflowExh and AV 23 VolflowSup let the BMS feed extract and supply airflows of other equipment into the room balance.
Network setup
- Default device instance is 32900 plus the network address set on hex switches X/Y.
- MS/TP baud rate (9600, 19200, 38400 or 76800) is set on DIP switches 2 and 3; DIP 1 selects EASYLAB TCU3 or another controller.
- Max_Master defaults to 127 and Max_Info_Frames to 1.
Watch out for
- If the network interface fails the airflow controller keeps controlling; only data exchange with the BMS stops.
TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| MVmin | 4 | RoomModeAct | room mode, current state | Read | 1=No preset, 2=Standard Mode, 3=Low Mode, 4=High Mode, 5=Shut off Mode, 6=Open Mode | |
| AV | 1 | VolflowSet | volume flow, set value | l/s | Read | |
| AVmin | 2 | VolflowAct | volume flow, current value | l/s | Read | |
| AV | 3 | VolTotalExh | volume flow, total extract air value | l/s | Read | |
| AV | 4 | VolTotalSup | volume flow, total supply air value | l/s | Read | |
| AVmin | 10 | DampPos | damper, current position of the device | % | Read | |
| AV | 13 | DampPosMax_RE | damper, max. position of all room extractors | % | Read | |
| AV | 14 | DampPosMin_RE | damper, min. position of all room extractors | % | Read | |
| AV | 15 | DampPosMax_TE | damper, max. position of all extractors (FH + EC + RE) | % | Read | |
| AV | 16 | DampPosMin_TE | damper, min. position of all extractors (FH + EC + RE) | % | Read | |
| AV | 17 | DampPosMax_RS | damper, max. position of all room suppliers | % | Read | |
| AV | 18 | DampPosMin_RS | damper, min. position of all room suppliers | % | Read | |
| AV | 21 | SystemDevices | total number of system devices | Read | ||
| AV | 22 | VolflowExh | extract airflow input from an external device | l/s | Write | |
| AV | 23 | VolflowSup | supply airflow input from an external device | l/s | Write | |
| AV | 30 | DampPosMax_TS | damper, max. position of all suppliers (SC + RS) | % | Read | |
| AV | 31 | DampPosMin_TS | damper, min. position of all suppliers (SC + RS) | % | Read | |
| BVmin | 1 | LocalAlarm | local alarm | Read | 0=Normal, 1=Alarm | |
| BV | 6 | DI1 | digital input 1 | Read | 0=Off, 1=On | |
| BV | 7 | DI2 | digital input 2 | Read | 0=Off, 1=On | |
| BV | 8 | DI3 | digital input 3 | Read | 0=Off, 1=On | |
| BV | 9 | DI4 | digital input 4 | Read | 0=Off, 1=On | |
| BV | 10 | DI5 | digital input 5 | Read | 0=Off, 1=On | |
| BV | 11 | DI6 | digital input 6 | Read | 0=Off, 1=On | |
| BV | 12 | DO1 | digital output 1 | Read | 0=Off, 1=On | |
| BV | 13 | DO2 | digital output 2 | Read | 0=Off, 1=On | |
| BV | 14 | DO3 | digital output 3 | Read | 0=Off, 1=On | |
| BV | 15 | DO4 | digital output 4 | Read | 0=Off, 1=On | |
| BV | 16 | DO5 | digital output 5 | Read | 0=Off, 1=On | |
| BV | 17 | DO6 | digital output 6 | Read | 0=Off, 1=On | |
| BV | 19 | DO1_Set | digital output 1 set | Write | 0=Inactive, 1=Active | |
| BV | 20 | DO2_Set | digital output 2 set | Write | 0=Inactive, 1=Active | |
| BV | 21 | DO3_Set | digital output 3 set | Write | 0=Inactive, 1=Active | |
| BV | 22 | DO4_Set | digital output 4 set | Write | 0=Inactive, 1=Active | |
| BV | 23 | DO5_Set | digital output 5 set | Write | 0=Inactive, 1=Active | |
| BV | 24 | DO6_Set | digital output 6 set | Write | 0=Inactive, 1=Active | |
| BV | 25 | DO1_SetByLocal | digital output 1 feedback | Read | 0=External, 1=Local | |
| BV | 26 | DO2_SetByLocal | digital output 2 feedback | Read | 0=External, 1=Local | |
| BV | 27 | DO3_SetByLocal | digital output 3 feedback | Read | 0=External, 1=Local | |
| BV | 28 | DO4_SetByLocal | digital output 4 feedback | Read | 0=External, 1=Local | |
| BV | 29 | DO5_SetByLocal | digital output 5 feedback | Read | 0=External, 1=Local | |
| BV | 30 | DO6_SetByLocal | digital output 6 feedback | Read | 0=External, 1=Local |
No points match these filters.
Object ID lookup: TROX UNIVERSAL Room EM-BAC-MOD-01 point IDs by name
MV4RoomModeActAV1VolflowSetAV2VolflowActAV3VolTotalExhAV4VolTotalSupAV10DampPosAV13DampPosMax_REAV14DampPosMin_REAV15DampPosMax_TEAV16DampPosMin_TEAV17DampPosMax_RSAV18DampPosMin_RSAV21SystemDevicesAV22VolflowExhAV23VolflowSupAV30DampPosMax_TSAV31DampPosMin_TSBV1LocalAlarmBV6DI1BV7DI2BV8DI3BV9DI4BV10DI5BV11DI6BV12DO1BV13DO2BV14DO3BV15DO4BV16DO5BV17DO6BV19DO1_SetBV20DO2_SetBV21DO3_SetBV22DO4_SetBV23DO5_SetBV24DO6_SetBV25DO1_SetByLocalBV26DO2_SetByLocalBV27DO3_SetByLocalBV28DO4_SetByLocalBV29DO5_SetByLocalBV30DO6_SetByLocal
Integration notes
- The module holds the objects of all applications; objects outside this application stay unused.
- Units come from the EDE unit-code column; airflows are in l/s.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)
How many BACnet points does the TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP) have?
This list has 42 BACnet objects: 16 analog values, 25 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP) BACnet points are writable?
8 of the 42 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP) BACnet documentation?
The source is EM-BAC-MOD EDE files V4.1 (EM-BAC-MOD_EDE-complete-V4_1) (TCU3_EDE_files_U_RR_V4_1), published free by TROX at https://www.trox.de/en/downloads/42fe282430305ce7/EM-BAC-MOD_EDE-complete-V4_1.zip.
What are the minimum BACnet points to integrate the TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)?
Start with MV 4 RoomModeAct (Current operating mode of the room); AV 2 VolflowAct (Measured airflow, l/s); AV 10 DampPos (Damper position, %); BV 1 LocalAlarm (Alarm on this controller).
Can the BMS supply sensor values to the TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)?
AV 22 VolflowExh and AV 23 VolflowSup let the BMS feed extract and supply airflows of other equipment into the room balance.
How do I check these points on the real TROX UNIVERSAL room airflow controller (EM-BAC-MOD-01, BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More TROX BACnet points lists
- VAV box controller (compact, built-in damper drive)
TROX BM0-D8 VAV control component (BACnet MS/TP)
TROX VAV terminal units fitted with the BM0-D8 compact control component (LMV/NMV-D3-M/B-X TR actuators).
Also known as: BM0-D8, BM0, LMV-D3-M/B-X TR, NMV-D3-M/B-X TR, ..MV-D3-M/B-X, ..MV-D3-M/B-FX, TROX VAV Compact - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM with room management function (RMF) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM with room management function (RMF), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code TAM-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM with room management function (RMF) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM with room management function (RMF), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code TAM-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM without room management function (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM without room management function, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code TAM - Laboratory VAV airflow controller
TROX EASYLAB TCU3 adapter module TAM without room management function (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as adapter module TAM without room management function, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code TAM - Laboratory VAV airflow controller
TROX EASYLAB TCU3 all EASYLAB applications (combined list) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as all EASYLAB applications (combined list), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code ELAB - Laboratory VAV airflow controller
TROX EASYLAB TCU3 all EASYLAB applications (combined list) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as all EASYLAB applications (combined list), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code ELAB - Laboratory VAV controller (fume cupboard)
TROX EASYLAB TCU3 fume cupboard controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as fume cupboard controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code FH - Laboratory VAV controller (fume cupboard)
TROX EASYLAB TCU3 fume cupboard controller (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as fume cupboard controller, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code FH - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller with room management function (RMF) (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller with room management function (RMF), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code LAB-RMF / CLR-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller with room management function (RMF) (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller with room management function (RMF), fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code LAB-RMF / CLR-RMF - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller without room management function (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller without room management function, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code LAB / CLR - Laboratory VAV airflow controller
TROX EASYLAB TCU3 room supply/extract controller without room management function (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as room supply/extract controller without room management function, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code LAB / CLR - Laboratory VAV airflow controller
TROX EASYLAB TCU3 single extract or supply air controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX EASYLAB TCU3 controllers set up as single extract or supply air controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: EASYLAB TCU3 EM-BAC-MOD-01, EM-BAC-MOD-01, TCU3, TROX EASYLAB, order code EC / SC - Laboratory VAV airflow controller
TROX EASYLAB TCU3 single extract or supply air controller (EM-IP, BACnet IP)
TROX EASYLAB TCU3 controllers set up as single extract or supply air controller, fitted with the EM-IP expansion module.
Also known as: EASYLAB TCU3 EM-IP, EM-IP, TCU3, TROX EASYLAB, order code EC / SC - Decentralised ventilation unit / zone controller
TROX FSL-CONTROL II / X-AIRCONTROL with EM-BAC-MOD-01 XAC (BACnet MS/TP)
TROX FSL decentralised (single-room) ventilation units with the FSL-CONTROL II / X-AIRCONTROL controller and the EM-BAC-MOD-01 XAC BACnet MS/TP card.
Also known as: FSL-CONTROL II, X-AIRCONTROL, EM-BAC-MOD-01 XAC, A00000020207, Schoolair, FSL decentralised ventilation - Decentralised ventilation unit controller
TROX FSL-CONTROL III decentralised ventilation controller (software 8.0)
TROX FSL decentralised (single-room) ventilation units with the FSL-CONTROL III controller, software version 8.0.
Also known as: FSL-CONTROL III, FSL-C-III, Schoolair, FSL decentralised ventilation, M172 - Fan coil unit controller
TROX TITAN FCU403 fan coil controller (config FCU403 TRX)
Fan coil units supplied by TROX with the Titan Products FCU4 controller running configuration FCU403 TRX and the graphical RDU.
Also known as: FCU403, FCU4, FCU403 TRX, Titan FCU4, FCU403 TP1193E, Graphical RDU V2 - VAV room airflow controller
TROX UNIVERSAL all TROX UNIVERSAL applications (combined list) (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as all TROX UNIVERSAL applications (combined list), fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code TU* - VAV room airflow controller
TROX UNIVERSAL all TROX UNIVERSAL applications (combined list) (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as all TROX UNIVERSAL applications (combined list), fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code TU* - VAV room / duct pressure controller
TROX UNIVERSAL duct pressure controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as duct pressure controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PDS / PDE - VAV room airflow controller
TROX UNIVERSAL room airflow controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code RS / RE - VAV room airflow controller
TROX UNIVERSAL room airflow controller, master (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, master, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code RS/M / RE/M - VAV room airflow controller
TROX UNIVERSAL room airflow controller, master (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room airflow controller, master, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code RS/M / RE/M - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code PRS / PRE / PDS / PDE - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller, master (EM-BAC-MOD-01, BACnet MS/TP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, master, fitted with the EM-BAC-MOD-01 expansion module.
Also known as: TROX UNIVERSAL EM-BAC-MOD-01, EM-BAC-MOD-01, TROX UNIVERSAL, order code PRS/M / PRE/M / PDS/M / PDE/M, TROX UNIVERSAL PD master - VAV room / duct pressure controller
TROX UNIVERSAL room or duct pressure controller, master (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room or duct pressure controller, master, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PRS/M / PRE/M / PDS/M / PDE/M, TROX UNIVERSAL PD master - VAV room / duct pressure controller
TROX UNIVERSAL room pressure controller (EM-IP, BACnet IP)
TROX TROX UNIVERSAL controllers set up as room pressure controller, fitted with the EM-IP expansion module.
Also known as: TROX UNIVERSAL EM-IP, EM-IP, TROX UNIVERSAL, order code PRS / PRE - VAV / static pressure controller
TROX UNIVERSAL static BUPNF duct pressure controller (VRU-...-BAC, BACnet MS/TP)
TROX UNIVERSAL static BUPNF controllers (VRU-D3/M1/M1R-BAC control electronics) for airflow, duct pressure and room pressure control.
Also known as: BUPNF, TROX UNIVERSAL static, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-D3-M/B TR, VRU-M1-M/B TR, VRU-M1R-M/B TR - Fire and smoke damper control module
TROX TROXNETCOM MB-BAC-WA1/2 fire damper module (BACnet MS/TP)
TROX TROXNETCOM MB-BAC-WA1/2 modules that drive and monitor up to 2 fire or smoke extract dampers (motorised or limit-switch only).
Also known as: MB-BAC-WA1/2, MB-BAC-WA1B3, TROXNETCOM, MB-BAC-WA1-2 - Fire and smoke damper control module
TROX TROXNETCOM MB-BAC-WA1/4 fire damper module (BACnet MS/TP)
TROX TROXNETCOM MB-BAC-WA1/4 modules that drive and monitor up to 4 fire or smoke extract dampers (motorised or limit-switch only).
Also known as: MB-BAC-WA1/4, TROXNETCOM, MB-BAC-WA1-4 - VAV zone controller (master for up to 25 zone modules)
TROX X-AIRCONTROL Master zone controller (TROX Auranor, BACnet IP)
TROX Auranor X-AIRCONTROL VAV zone control systems: one Master with up to 25 Zone Modules, linked to an AHU.
Also known as: X-AIRCONTROL, X-AIRCONTROL Master, TROX Auranor X-AIRCONTROL, 67501-06/15, X-AIRCONTROL ZoneModule - Air handling unit controller
TROX X-CUBE Control BACnet data point list
TROX X-CUBE central air handling units with the factory X-CUBE Control system.
Also known as: X-CUBE, TROX X-CUBE, X-CUBE Control, BACnet DPL, BACnet EDE XCUBE - VAV box controller (compact, built-in damper drive)
TROX XDMB0 compact VAV control component (TVE, BACnet MS/TP)
TROX TVE and TVE-Q VAV terminal units fitted with the XDMB0 compact control component.
Also known as: XDMB0, TVE XDMB0, TVE-Q, Compact XDMB0
Source: EM-BAC-MOD EDE files V4.1 (EM-BAC-MOD_EDE-complete-V4_1) · TCU3_EDE_files_U_RR_V4_1. Object names, instances and units are reproduced as published; descriptions are our own.