- WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
Room sensor (CO2, VOC, temperature, humidity) · BACnet points list
Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet points list
Updated 6 November 2026
WRF06 AQ and FTW06 are wall-mounted room sensors with BACnet MS/TP. The interface description lists 39 objects: temperature, humidity and derived values, CO2, VOC and CO2/VOC mix, offsets, scaling limits, unit system and the traffic-light LED settings.
This page lists 39 BACnet objects for the Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors — 31 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.
- Manufacturer
- Thermokon
- Model
- WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
- Equipment
- Room sensor (CO2, VOC, temperature, humidity)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 39 (31 writable)
- Transport
- BACnet MS/TP
- Firmware
- 1.1
- Default device instance
- Offset Device ID (AV 46) + MAC address
- Also known as
- WRF06 AQ, WRF06 CO2, WRF06 CO2 Temp, WRF06 CO2 Temp_rH, WRF06 CO2+VOC, WRF06 VOC Temp, FTW06, WRF06 AQ BACnet MSTP
Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.
BMS integration notes: Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
Read AI 0 temperature, AI 1 humidity, AI 5 CO2 and AI 6 VOC (as fitted). The rest are calibration and display settings.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 0 | Temperature | Room temperature | Read |
| AI 1 | Relative humidity | Room relative humidity | Read |
| AI 5 | CO2 | Room CO2, ppm | Read |
| AI 6 | VOC | Room VOC, % | Read |
| AI 7 | CO2 VOC Mix | Combined CO2/VOC air quality, % | Read |
Network setup
- MAC address 1-127 and baud rate (9600, 19200, 38400, 76800) are set on DIP switches; 8N1 framing.
- Device ID = Offset Device ID (AV 46) + MAC address.
Watch out for
- AV 48 = 9999 restores factory settings.
Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 38 | Unit system | Write | 1=SI, 2=Imperial | ||
| AImin | 1 | Relative humidity | %RH | Read | ||
| AImin | 5 | CO2 | ppm | Read | ||
| AImin | 6 | VOC | % | Read | ||
| AImin | 7 | CO2 VOC Mix | % | Read | ||
| AImin | 0 | Temperature | °C | Read | ||
| AI | 2 | Absolute humidity | g/m³ | Read | ||
| AI | 3 | Enthalpy | kJ/kg | Read | ||
| AI | 4 | Dew point | °C | Read | ||
| AV | 1 | Offset relative humidity | %RH | Write | ||
| AV | 2 | Offset CO2 | ppm | Write | ||
| AV | 3 | Offset VOC | % | Write | ||
| AV | 0 | Offset temperature | °C | Write | ||
| AV | 8 | Relative humidity lower limit | %RH | Write | ||
| AV | 9 | Relative humidity upper limit | Write | |||
| AV | 16 | CO2 lower limit | ppm | Write | ||
| AV | 17 | CO2 upper limit | Write | |||
| AV | 18 | VOC lower limit | % | Write | ||
| AV | 19 | VOC upper limit | Write | |||
| AV | 20 | CO2 VOC Mix lower limit | % | Write | ||
| AV | 21 | CO2 VOC Mix upper limit | Write | |||
| AV | 6 | Temperature lower limit | °C | Write | ||
| AV | 7 | Temperature upper limit | Write | |||
| AV | 10 | Absolute humidity lower limit | g/m³ | Write | ||
| AV | 11 | Absolute humidity upper limit | Write | |||
| AV | 12 | Enthalpy lower limit | kJ/kg | Write | ||
| AV | 13 | Enthalpy upper limit | Write | |||
| AV | 14 | Dew point lower limit | °C | Write | ||
| AV | 15 | Dew point upper limit | Write | |||
| AV | 82 | Percentage of CO2 sensor value in CO2 VOC Mix signal | % | Write | ||
| AV | 46 | Offset Device ID | Write | |||
| AV | 47 | Unconfirmed COV | Write | 0=not active, 1=active | ||
| AV | 48 | Reset to default | Write | |||
| AV | 62 | Channel assignment for TLF | Available sensor values depend on the type | Write | ||
| AV | 63 | Traffic light function LED range 1 | Write | 0=LED OFF, 1=LED green, 2=LED yellow, 3=LED red | ||
| AV | 64 | Traffic light function LED range 2 | Write | |||
| AV | 65 | Traffic light function LED range 3 | Write | |||
| AV | 66 | Traffic light function threshold Range 1→2 | Write | |||
| AV | 67 | Traffic light function threshold Range 2→3 | Write |
No points match these filters.
Object ID lookup: Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors point IDs by name
AV38Unit systemAI1Relative humidityAI5CO2AI6VOCAI7CO2 VOC MixAI0TemperatureAI2Absolute humidityAI3EnthalpyAI4Dew pointAV1Offset relative humidityAV2Offset CO2AV3Offset VOCAV0Offset temperatureAV8Relative humidity lower limitAV9Relative humidity upper limitAV16CO2 lower limitAV17CO2 upper limitAV18VOC lower limitAV19VOC upper limitAV20CO2 VOC Mix lower limitAV21CO2 VOC Mix upper limitAV6Temperature lower limitAV7Temperature upper limitAV10Absolute humidity lower limitAV11Absolute humidity upper limitAV12Enthalpy lower limitAV13Enthalpy upper limitAV14Dew point lower limitAV15Dew point upper limitAV82Percentage of CO2 sensor value in CO2 VOC Mix signalAV46Offset Device IDAV47Unconfirmed COVAV48Reset to defaultAV62Channel assignment for TLFAV63Traffic light function LED range 1AV64Traffic light function LED range 2AV65Traffic light function LED range 3AV66Traffic light function threshold Range 1→2AV67Traffic light function threshold Range 2→3
Integration notes
- The description gives each object an ID, access and description but no object name; the description is used as the name here.
- Which measured values exist depends on the variant (the document has a table per type).
- Units follow AV 38 (1 = SI, 2 = Imperial); SI units are shown.
- Not the WRF06 RC room controller, which has its own list.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
How many BACnet points does the Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors have?
This list has 39 BACnet objects: 8 analog inputs, 31 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet points are writable?
31 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet documentation?
The source is Interface description WRF06 AQ / FTW06 BACnet MS/TP, revision Rev. A, 04.03.2019, published free by Thermokon at https://www.thermokon.de/downloads/Software/Schnittstellenbeschreibung/BACnet/WRF06_AQ_FTW06-RS485_BACnet_InterfaceDescription.zip.
What are the minimum BACnet points to integrate the Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors?
Start with AI 0 Temperature (Room temperature); AI 1 Relative humidity (Room relative humidity); AI 5 CO2 (Room CO2, ppm); AI 6 VOC (Room VOC, %); AI 7 CO2 VOC Mix (Combined CO2/VOC air quality, %).
How do I check these points on the real WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Thermokon BACnet points lists
- Room sensor / operating unit
Thermokon FTW04 BACnet MS/TP RS485 room humidity/temperature unit
Thermokon FTW04 BACnet MS/TP RS485 room units (temperature, humidity, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: FTW04, FTW04 BACnet, FTW04_BACnet, FTW04-RS485-BACnet - Room thermostat / fan coil controller
Thermokon JOY BACnet room thermostats / fan coil controllers (5DO, ECAO2DO, HCAO2DO, EC3AO, HC3AO)
Thermokon JOY wall thermostats with RS485 BACnet MS/TP for fan coils, heating/cooling valves and 6-way valves, in 230 V and 24 V versions with optional CO2 and humidity sensors.
Also known as: JOY FC5DO BACnet, JOY ECAO2DO BACnet, JOY HCAO2DO BACnet, JOY EC3AO BACnet, JOY HC3AO BACnet, JOY HC AO2DO 24V RS485 BACnet, JOY RS485 BACnet - Room operating unit / room sensor
Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units
Thermokon NOVOS 3 and NOVOS 5 (LCD) wall units with RS485 BACnet MS/TP, in temperature, CO2, humidity and VOC sensor variants.
Also known as: NOVOS 3 RS485 BACnet, NOVOS 5 LCD RS485 BACnet, NOVOS 3 x, NOVOS 5 x, NOVOS 5 LCD - Room operating unit / room sensor
Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units
Thermokon NOVOS 7, NOVOS Touch and thanos EVO touch-screen room operating units with RS485 BACnet MS/TP.
Also known as: NOVOS 7, NOVOS Touch, thanos EVO, NOVOS 7 RS485 BACnet, thanos EVO RS485 BACnet - Duct / room sensor (temperature, humidity, CO2, VOC, pressure)
Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)
Thermokon sensors fitted with the USE-BACnet MS/TP RS485 option board (FTA+, FTK+, LK+, DPA+, LI65+, LDF+, RDF+, WK02+ and their LCD versions).
Also known as: USE BACnet, USE-RS485 BACnet, FTA+ BACnet, FTK+ BACnet, LK+ CO2 BACnet, LK+ VOC BACnet, DPA+ BACnet, DPA+ Flow BACnet, LI65+ BACnet, LDF+ BACnet, RDF+ BACnet, WK02+ BACnet - Room sensor / operating unit
Thermokon WRF04 BACnet MS/TP RS485 room operating unit
Thermokon WRF04 BACnet MS/TP RS485 room units (temperature, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: WRF04, WRF04 BACnet, WRF04_BACnet, WRF04-RS485-BACnet - Room controller (fan coil, radiator, chilled ceiling)
Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers
Thermokon WRF06 RC and WRF07 RC wall-mounted room controllers with RS485 BACnet MS/TP, including the humidity (x rH) variants.
Also known as: WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP, WRF07 RC, WRF06 RC, WRF07 BACnet MSTP - Room operating unit (buttons, LCD, setpoints) / room sensor
Thermokon WRF08 BACnet MS/TP RS485 room operating panel
Thermokon WRF08 room operating panels with LCD, up to 12 buttons, room temperature sensor and BACnet MS/TP over RS485.
Also known as: WRF08, WRF08 BACnet, WRF08 RS485 BACnet, Thermokon_WRF08_BACnet
Source: Interface description WRF06 AQ / FTW06 BACnet MS/TP · rev. Rev. A, 04.03.2019. Object names, instances and units are reproduced as published; descriptions are our own.