Room sensor (CO2, VOC, temperature, humidity) · BACnet points list

Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet points list

Updated 6 November 2026

Short answer

WRF06 AQ and FTW06 are wall-mounted room sensors with BACnet MS/TP. The interface description lists 39 objects: temperature, humidity and derived values, CO2, VOC and CO2/VOC mix, offsets, scaling limits, unit system and the traffic-light LED settings.

This page lists 39 BACnet objects for the Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors — 31 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.

Manufacturer
Thermokon
Model
WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
Equipment
Room sensor (CO2, VOC, temperature, humidity)
Equipment type
Thermostats, sensors & meters
BACnet objects
39 (31 writable)
Transport
BACnet MS/TP
Firmware
1.1
Default device instance
Offset Device ID (AV 46) + MAC address
Also known as
WRF06 AQ, WRF06 CO2, WRF06 CO2 Temp, WRF06 CO2 Temp_rH, WRF06 CO2+VOC, WRF06 VOC Temp, FTW06, WRF06 AQ BACnet MSTP
Source document
Interface description WRF06 AQ / FTW06 BACnet MS/TP · rev. Rev. A, 04.03.2019
Download CSV 39 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.

BMS integration notes: Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors

Integration in brief

Read AI 0 temperature, AI 1 humidity, AI 5 CO2 and AI 6 VOC (as fitted). The rest are calibration and display settings.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0TemperatureRoom temperatureRead
AI 1Relative humidityRoom relative humidityRead
AI 5CO2Room CO2, ppmRead
AI 6VOCRoom VOC, %Read
AI 7CO2 VOC MixCombined CO2/VOC air quality, %Read

Network setup

Watch out for

Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

39 of 39 shown
Type
Access
Show
Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet Points List
DescriptionStates
AV38Unit systemWrite1=SI, 2=Imperial
AImin1Relative humidity%RHRead
AImin5CO2ppmRead
AImin6VOC%Read
AImin7CO2 VOC Mix%Read
AImin0Temperature°CRead
AI2Absolute humidityg/m³Read
AI3EnthalpykJ/kgRead
AI4Dew point°CRead
AV1Offset relative humidity%RHWrite
AV2Offset CO2ppmWrite
AV3Offset VOC%Write
AV0Offset temperature°CWrite
AV8Relative humidity lower limit%RHWrite
AV9Relative humidity upper limitWrite
AV16CO2 lower limitppmWrite
AV17CO2 upper limitWrite
AV18VOC lower limit%Write
AV19VOC upper limitWrite
AV20CO2 VOC Mix lower limit%Write
AV21CO2 VOC Mix upper limitWrite
AV6Temperature lower limit°CWrite
AV7Temperature upper limitWrite
AV10Absolute humidity lower limitg/m³Write
AV11Absolute humidity upper limitWrite
AV12Enthalpy lower limitkJ/kgWrite
AV13Enthalpy upper limitWrite
AV14Dew point lower limit°CWrite
AV15Dew point upper limitWrite
AV82Percentage of CO2 sensor value in CO2 VOC Mix signal%Write
AV46Offset Device IDWrite
AV47Unconfirmed COVWrite0=not active, 1=active
AV48Reset to defaultWrite
AV62Channel assignment for TLFAvailable sensor values depend on the typeWrite
AV63Traffic light function LED range 1Write0=LED OFF, 1=LED green, 2=LED yellow, 3=LED red
AV64Traffic light function LED range 2Write
AV65Traffic light function LED range 3Write
AV66Traffic light function threshold Range 1→2Write
AV67Traffic light function threshold Range 2→3Write
Object ID lookup: Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors

How many BACnet points does the Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors have?

This list has 39 BACnet objects: 8 analog inputs, 31 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet points are writable?

31 of the 39 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors BACnet documentation?

The source is Interface description WRF06 AQ / FTW06 BACnet MS/TP, revision Rev. A, 04.03.2019, published free by Thermokon at https://www.thermokon.de/downloads/Software/Schnittstellenbeschreibung/BACnet/WRF06_AQ_FTW06-RS485_BACnet_InterfaceDescription.zip.

What are the minimum BACnet points to integrate the Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors?

Start with AI 0 Temperature (Room temperature); AI 1 Relative humidity (Room relative humidity); AI 5 CO2 (Room CO2, ppm); AI 6 VOC (Room VOC, %); AI 7 CO2 VOC Mix (Combined CO2/VOC air quality, %).

How do I check these points on the real WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermokon BACnet points lists

Source: Interface description WRF06 AQ / FTW06 BACnet MS/TP · rev. Rev. A, 04.03.2019. Object names, instances and units are reproduced as published; descriptions are our own.