- Home
- BACnet points lists
- Thermokon
- WRF04 BACnet MS/TP RS485 room operating unit
Room sensor / operating unit · BACnet points list
Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet points list
Updated 6 November 2026
WRF04 is a wall-mounted room unit with BACnet MS/TP. The interface description lists 26 objects including the device object: room temperature, setpoint potentiometer, button, digital inputs and rotary switch, two 0-10 V outputs, offsets, setpoint scaling and LED behaviour.
This page lists 25 BACnet objects for the Thermokon WRF04 BACnet MS/TP RS485 room operating unit — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.
- Manufacturer
- Thermokon
- Model
- WRF04 BACnet MS/TP RS485 room operating unit
- Equipment
- Room sensor / operating unit
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 25 (19 writable)
- Transport
- BACnet MS/TP
- Firmware
- 1.0.0
- Default device instance
- DeviceOffsetID (AV 0, default 100) + MAC address
- Also known as
- WRF04, WRF04 BACnet, WRF04_BACnet, WRF04-RS485-BACnet
Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.
BMS integration notes: Thermokon WRF04 BACnet MS/TP RS485 room operating unit
Read the temperature, the setpoint potentiometer and the button/digital inputs; the BMS can drive the two 0-10 V outputs and the LED.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 0 | Temperature | Room temperature | Read |
| AI 1 | Set point | Setpoint potentiometer value | Read |
| BI 0 | Button | Button state | Read |
| MI 0 | RotarySwitch | Rotary switch position 1-5 | Read |
Network setup
- Baud rate 9600, 19200, 38400, 57600 or 76800 and MAC address are set on DIP switches.
- Device ID = DeviceOffsetID (default 100) + MAC address; the device restarts after either is changed.
Watch out for
- Device profile is B-SA with only ReadProperty and WriteProperty.
Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 0 | Temperature | Room temperature (unit per BV 2) | °C/°F | Read | |
| AImin | 1 | Set point | Setpoint potentiometer (unit/range per AV 2-6) | Read | ||
| BImin | 0 | Button | Status of the button | Read | 0=Inactive, 1=Active | |
| BI | 1 | DigitalInput1 | Status of digital input 1 | Read | 0=Inactive, 1=Active | |
| BI | 2 | DigitalInput2 | Status of digital input 2 | Read | 0=Inactive, 1=Active | |
| MImin | 0 | RotarySwitch | Rotary switch position 1-5 | Read | ||
| AO | 0 | AnalogOutput1 | Analogue output 1, 0-100 % = 0-10 V | % | Write | |
| AO | 1 | AnalogOutput2 | Analogue output 2, 0-100 % = 0-10 V | % | Write | |
| AV | 0 | DeviceOffsetID | Added to the MAC address to form the device ID | Write | ||
| AV | 1 | TempOffset | Temperature correction | °C/°F | Write | |
| AV | 2 | SetpUnit | Unit of the setpoint object | Write | 0=no unit, 1=%, 2=°C, 3=°F, 4=Kelvin, 5=% relative humidity, 6=° angle | |
| AV | 3 | SetpMIN | Lower setpoint limit after device reset (default 0) | Write | ||
| AV | 4 | SetpMAX | Upper setpoint limit after device reset (default 100) | Write | ||
| AV | 5 | SetpMIN | Lower setpoint limit, changeable in operation | Write | ||
| AV | 6 | SetpMAX | Upper setpoint limit, changeable in operation | Write | ||
| AV | 7 | ButtonCounter | Button press counter | Write | ||
| AV | 8 | DigInp1Counter | Digital input 1 rising-edge counter | Write | ||
| AV | 9 | DigInput2Counter | Digital input 2 rising-edge counter | Write | ||
| BV | 0 | LEDState | LED status | Write | 0=Inactive, 1=Active | |
| BV | 1 | LockLEDState | Active: LED toggle via button and digital inputs locked | Write | 0=Inactive, 1=Active | |
| BV | 2 | TempUnit | Temperature unit | Write | 0=°C, 1=°F | |
| BV | 3 | LEDStateReset | LED status after device reset | Write | 0=Inactive, 1=Active | |
| BV | 4 | ToggleLEDbyButton | Button press toggles the LED | Write | 0=Inactive, 1=Active | |
| BV | 5 | ToggleLEDbyDigInput1 | Rising edge on DI1 toggles the LED | Write | 0=Inactive, 1=Active | |
| BV | 6 | ToggleLEDbyDigInput2 | Rising edge on DI2 toggles the LED | Write | 0=Inactive, 1=Active |
No points match these filters.
Object ID lookup: Thermokon WRF04 BACnet MS/TP RS485 room operating unit point IDs by name
AI0TemperatureAI1Set pointBI0ButtonBI1DigitalInput1BI2DigitalInput2MI0RotarySwitchAO0AnalogOutput1AO1AnalogOutput2AV0DeviceOffsetIDAV1TempOffsetAV2SetpUnitAV3SetpMINAV4SetpMAXAV5SetpMINAV6SetpMAXAV7ButtonCounterAV8DigInp1CounterAV9DigInput2CounterBV0LEDStateBV1LockLEDStateBV2TempUnitBV3LEDStateResetBV4ToggleLEDbyButtonBV5ToggleLEDbyDigInput1BV6ToggleLEDbyDigInput2
Integration notes
- Objects marked # in the description (device offset, offsets, setpoint unit/limits after reset, TempUnit, LED configuration) keep their values after a reset; the # is not part of the name.
- Setpoint, button, rotary switch and LED objects only apply to variants that have those parts.
- The description has no access column; inputs are listed read-only and values/outputs writable.
- Two objects are printed with the same name SetpMIN (and SetpMAX): one is the limit after reset, the other the limit used in operation.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRF04 BACnet MS/TP RS485 room operating unit and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Thermokon WRF04 BACnet MS/TP RS485 room operating unit
How many BACnet points does the Thermokon WRF04 BACnet MS/TP RS485 room operating unit have?
This list has 25 BACnet objects: 2 analog inputs, 2 analog outputs, 10 analog values, 3 binary inputs, 7 binary values, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet points are writable?
19 of the 25 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet documentation?
The source is Interface Description WRF04/FTW04 BACnet MS/TP, revision Rev. A, 17.05.2013, published free by Thermokon at https://www.thermokon.de/downloads/Software/Schnittstellenbeschreibung/BACnet/WRF04_FTW04-RS485_BACnet_InterfaceDescription.zip.
What are the minimum BACnet points to integrate the Thermokon WRF04 BACnet MS/TP RS485 room operating unit?
Start with AI 0 Temperature (Room temperature); AI 1 Set point (Setpoint potentiometer value); BI 0 Button (Button state); MI 0 RotarySwitch (Rotary switch position 1-5).
How do I check these points on the real WRF04 BACnet MS/TP RS485 room operating unit?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Thermokon BACnet points lists
- Room sensor / operating unit
Thermokon FTW04 BACnet MS/TP RS485 room humidity/temperature unit
Thermokon FTW04 BACnet MS/TP RS485 room units (temperature, humidity, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: FTW04, FTW04 BACnet, FTW04_BACnet, FTW04-RS485-BACnet - Room thermostat / fan coil controller
Thermokon JOY BACnet room thermostats / fan coil controllers (5DO, ECAO2DO, HCAO2DO, EC3AO, HC3AO)
Thermokon JOY wall thermostats with RS485 BACnet MS/TP for fan coils, heating/cooling valves and 6-way valves, in 230 V and 24 V versions with optional CO2 and humidity sensors.
Also known as: JOY FC5DO BACnet, JOY ECAO2DO BACnet, JOY HCAO2DO BACnet, JOY EC3AO BACnet, JOY HC3AO BACnet, JOY HC AO2DO 24V RS485 BACnet, JOY RS485 BACnet - Room operating unit / room sensor
Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units
Thermokon NOVOS 3 and NOVOS 5 (LCD) wall units with RS485 BACnet MS/TP, in temperature, CO2, humidity and VOC sensor variants.
Also known as: NOVOS 3 RS485 BACnet, NOVOS 5 LCD RS485 BACnet, NOVOS 3 x, NOVOS 5 x, NOVOS 5 LCD - Room operating unit / room sensor
Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units
Thermokon NOVOS 7, NOVOS Touch and thanos EVO touch-screen room operating units with RS485 BACnet MS/TP.
Also known as: NOVOS 7, NOVOS Touch, thanos EVO, NOVOS 7 RS485 BACnet, thanos EVO RS485 BACnet - Duct / room sensor (temperature, humidity, CO2, VOC, pressure)
Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)
Thermokon sensors fitted with the USE-BACnet MS/TP RS485 option board (FTA+, FTK+, LK+, DPA+, LI65+, LDF+, RDF+, WK02+ and their LCD versions).
Also known as: USE BACnet, USE-RS485 BACnet, FTA+ BACnet, FTK+ BACnet, LK+ CO2 BACnet, LK+ VOC BACnet, DPA+ BACnet, DPA+ Flow BACnet, LI65+ BACnet, LDF+ BACnet, RDF+ BACnet, WK02+ BACnet - Room sensor (CO2, VOC, temperature, humidity)
Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
Thermokon WRF06 AQ room air quality sensors (CO2, VOC, temperature, humidity variants) and FTW06 room humidity/temperature sensors with RS485 BACnet MS/TP.
Also known as: WRF06 AQ, WRF06 CO2, WRF06 CO2 Temp, WRF06 CO2 Temp_rH, WRF06 CO2+VOC, WRF06 VOC Temp, FTW06, WRF06 AQ BACnet MSTP - Room controller (fan coil, radiator, chilled ceiling)
Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers
Thermokon WRF06 RC and WRF07 RC wall-mounted room controllers with RS485 BACnet MS/TP, including the humidity (x rH) variants.
Also known as: WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP, WRF07 RC, WRF06 RC, WRF07 BACnet MSTP - Room operating unit (buttons, LCD, setpoints) / room sensor
Thermokon WRF08 BACnet MS/TP RS485 room operating panel
Thermokon WRF08 room operating panels with LCD, up to 12 buttons, room temperature sensor and BACnet MS/TP over RS485.
Also known as: WRF08, WRF08 BACnet, WRF08 RS485 BACnet, Thermokon_WRF08_BACnet
Source: Interface Description WRF04/FTW04 BACnet MS/TP · rev. Rev. A, 17.05.2013. Object names, instances and units are reproduced as published; descriptions are our own.