Room sensor / operating unit · BACnet points list

Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet points list

Updated 6 November 2026

Short answer

WRF04 is a wall-mounted room unit with BACnet MS/TP. The interface description lists 26 objects including the device object: room temperature, setpoint potentiometer, button, digital inputs and rotary switch, two 0-10 V outputs, offsets, setpoint scaling and LED behaviour.

This page lists 25 BACnet objects for the Thermokon WRF04 BACnet MS/TP RS485 room operating unit — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.

Manufacturer
Thermokon
Model
WRF04 BACnet MS/TP RS485 room operating unit
Equipment
Room sensor / operating unit
Equipment type
Thermostats, sensors & meters
BACnet objects
25 (19 writable)
Transport
BACnet MS/TP
Firmware
1.0.0
Default device instance
DeviceOffsetID (AV 0, default 100) + MAC address
Also known as
WRF04, WRF04 BACnet, WRF04_BACnet, WRF04-RS485-BACnet
Source document
Interface Description WRF04/FTW04 BACnet MS/TP · rev. Rev. A, 17.05.2013
Download CSV 25 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.

BMS integration notes: Thermokon WRF04 BACnet MS/TP RS485 room operating unit

Integration in brief

Read the temperature, the setpoint potentiometer and the button/digital inputs; the BMS can drive the two 0-10 V outputs and the LED.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0TemperatureRoom temperatureRead
AI 1Set pointSetpoint potentiometer valueRead
BI 0ButtonButton stateRead
MI 0RotarySwitchRotary switch position 1-5Read

Network setup

Watch out for

Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

25 of 25 shown
Type
Multi-state
Access
Show
Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet Points List
DescriptionStates
AImin0TemperatureRoom temperature (unit per BV 2)°C/°FRead
AImin1Set pointSetpoint potentiometer (unit/range per AV 2-6)Read
BImin0ButtonStatus of the buttonRead0=Inactive, 1=Active
BI1DigitalInput1Status of digital input 1Read0=Inactive, 1=Active
BI2DigitalInput2Status of digital input 2Read0=Inactive, 1=Active
MImin0RotarySwitchRotary switch position 1-5Read
AO0AnalogOutput1Analogue output 1, 0-100 % = 0-10 V%Write
AO1AnalogOutput2Analogue output 2, 0-100 % = 0-10 V%Write
AV0DeviceOffsetIDAdded to the MAC address to form the device IDWrite
AV1TempOffsetTemperature correction°C/°FWrite
AV2SetpUnitUnit of the setpoint objectWrite0=no unit, 1=%, 2=°C, 3=°F, 4=Kelvin, 5=% relative humidity, 6=° angle
AV3SetpMINLower setpoint limit after device reset (default 0)Write
AV4SetpMAXUpper setpoint limit after device reset (default 100)Write
AV5SetpMINLower setpoint limit, changeable in operationWrite
AV6SetpMAXUpper setpoint limit, changeable in operationWrite
AV7ButtonCounterButton press counterWrite
AV8DigInp1CounterDigital input 1 rising-edge counterWrite
AV9DigInput2CounterDigital input 2 rising-edge counterWrite
BV0LEDStateLED statusWrite0=Inactive, 1=Active
BV1LockLEDStateActive: LED toggle via button and digital inputs lockedWrite0=Inactive, 1=Active
BV2TempUnitTemperature unitWrite0=°C, 1=°F
BV3LEDStateResetLED status after device resetWrite0=Inactive, 1=Active
BV4ToggleLEDbyButtonButton press toggles the LEDWrite0=Inactive, 1=Active
BV5ToggleLEDbyDigInput1Rising edge on DI1 toggles the LEDWrite0=Inactive, 1=Active
BV6ToggleLEDbyDigInput2Rising edge on DI2 toggles the LEDWrite0=Inactive, 1=Active
Object ID lookup: Thermokon WRF04 BACnet MS/TP RS485 room operating unit point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRF04 BACnet MS/TP RS485 room operating unit and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermokon WRF04 BACnet MS/TP RS485 room operating unit

How many BACnet points does the Thermokon WRF04 BACnet MS/TP RS485 room operating unit have?

This list has 25 BACnet objects: 2 analog inputs, 2 analog outputs, 10 analog values, 3 binary inputs, 7 binary values, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet points are writable?

19 of the 25 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermokon WRF04 BACnet MS/TP RS485 room operating unit BACnet documentation?

The source is Interface Description WRF04/FTW04 BACnet MS/TP, revision Rev. A, 17.05.2013, published free by Thermokon at https://www.thermokon.de/downloads/Software/Schnittstellenbeschreibung/BACnet/WRF04_FTW04-RS485_BACnet_InterfaceDescription.zip.

What are the minimum BACnet points to integrate the Thermokon WRF04 BACnet MS/TP RS485 room operating unit?

Start with AI 0 Temperature (Room temperature); AI 1 Set point (Setpoint potentiometer value); BI 0 Button (Button state); MI 0 RotarySwitch (Rotary switch position 1-5).

How do I check these points on the real WRF04 BACnet MS/TP RS485 room operating unit?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermokon BACnet points lists

Source: Interface Description WRF04/FTW04 BACnet MS/TP · rev. Rev. A, 17.05.2013. Object names, instances and units are reproduced as published; descriptions are our own.