Room operating unit (buttons, LCD, setpoints) / room sensor · BACnet points list
Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet points list
Updated 6 November 2026
WRF08 is a room operating panel with LCD and up to 12 buttons. Its BACnet MS/TP interface lists 61 objects: button states, room temperature, four setpoint offsets and effective setpoints, fan stage and occupancy from the panel, plus values the BMS writes for display (outdoor temperature, external values, base setpoints, fan stage, occupancy), LED and symbol control and lock objects. Configuration is done with file objects and Thermokon software.
This page lists 61 BACnet objects for the Thermokon WRF08 BACnet MS/TP RS485 room operating panel — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.
- Manufacturer
- Thermokon
- Model
- WRF08 BACnet MS/TP RS485 room operating panel
- Equipment
- Room operating unit (buttons, LCD, setpoints) / room sensor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 61 (37 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Offset_device_id (AV 1) + MAC address
- Also known as
- WRF08, WRF08 BACnet, WRF08 RS485 BACnet, Thermokon_WRF08_BACnet
Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.
BMS integration notes: Thermokon WRF08 BACnet MS/TP RS485 room operating panel
Write base_setpoint_1 (AV 1533) and, if used, ext_room_occupancy and ext_fan_coil_stage; read room_temperature (AI 1259), setpoint_effective_1, fan_coil_stage and room_occupancy from the panel.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 1540 | ext_room_occupancy | Occupancy shown/set from the BMS | Write |
| MV 1539 | ext_fan_coil_stage | Fan stage from the BMS | Write |
| AV 1533 | base_setpoint_1 | Base setpoint 1 | Write |
| AI 1259 | room_temperature | Room temperature | Read |
| AI 1261 | setpoint_effective_1 | Effective setpoint 1 | Read |
| AI 1260 | setpoint_offset_1 | User setpoint offset 1 | Read |
| MI 1272 | fan_coil_stage | Fan stage selected on the panel | Read |
| BI 1273 | room_occupancy | Occupancy selected on the panel | Read |
Sensors & values from the BMS
outdoor_temperature (AV 1520) and ext_value_1..4 (AV 1521-1524) take values from the BMS for display on the panel.
Network setup
- Device ID = Offset_device_id (AV 1) + MAC address (0-127); MAC address and baud rate are set on the device.
Watch out for
- lock_buttons, lock_occupancy, lock_fan_coil and lock_setpoint (BV 2269-2272) disable operation on the panel.
Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | Offset_device_id | This value plus the set MAC (0-127) corresponds to the device ID | Write | ||
| MV | 1 | COV-Mode | COV mode | Write | Off, Local broadcast, Global broadcast | |
| FILE | 1 | Configuration register file | Configuration properties (for the configuration software) | Write | ||
| FILE | 2 | Input registers file | Readable objects (for the configuration software) | Read | ||
| FILE | 3 | Holding registers file | Read/write objects (for the configuration software) | Write | ||
| FILE | 4 | Configuration coils file | Configuration bits (for the configuration software) | Write | ||
| FILE | 5 | Coils file | Read/write binary objects (for the configuration software) | Write | ||
| BI | 1001 | pushbutton_01 | Current state of button 1 | Read | ||
| BI | 1002 | pushbutton_02 | Current state of button 2 | Read | ||
| BI | 1003 | pushbutton_03 | Current state of button 3 | Read | ||
| BI | 1004 | pushbutton_04 | Current state of button 4 | Read | ||
| BI | 1005 | pushbutton_05 | Current state of button 5 | Read | ||
| BI | 1006 | pushbutton_06 | Current state of button 6 | Read | ||
| BI | 1007 | pushbutton_07 | Current state of button 7 | Read | ||
| BI | 1008 | pushbutton_08 | Current state of button 8 | Read | ||
| BI | 1009 | pushbutton_09 | Current state of button 9 | Read | ||
| BI | 1010 | pushbutton_10 | Current state of button 10 | Read | ||
| BI | 1011 | pushbutton_11 | Current state of button 11 | Read | ||
| BI | 1012 | pushbutton_12 | Current state of button 12 | Read | ||
| AImin | 1259 | room_temperature | Room temperature | °C | Read | |
| AImin | 1260 | setpoint_offset_1 | Offset set point 1 | °C | Read | |
| AImin | 1261 | setpoint_effective_1 | Effective set point 1 | °C | Read | |
| AI | 1262 | setpoint_offset_2 | Offset set point 2 | °C | Read | |
| AI | 1263 | setpoint_effective_2 | Effective set point 2 | °C | Read | |
| AI | 1264 | setpoint_offset_3 | Offset set point 3 | °C | Read | |
| AI | 1265 | setpoint_effective_3 | Effective set point 3 | °C | Read | |
| AI | 1266 | setpoint_offset_4 | Offset set point 4 | °C | Read | |
| AI | 1267 | setpoint_effective_4 | Effective set point 4 | °C | Read | |
| MImin | 1272 | fan_coil_stage | Fan coil stage | Read | ||
| BImin | 1273 | room_occupancy | Room occupancy | Read | ||
| AV | 1520 | outdoor_temperature | Outdoor temperature | °C | Write | |
| AV | 1521 | ext_value_1 | External value 1 | Write | ||
| AV | 1522 | ext_value_2 | External value 2 | Write | ||
| AV | 1523 | ext_value_3 | External value 3 | Write | ||
| AV | 1524 | ext_value_4 | External value 4 | Write | ||
| AV | 1527 | ext_setpoint_offset_1 | Set point 1 offset | °C | Write | |
| AV | 1528 | ext_setpoint_offset_2 | Set point 2 offset | °C | Write | |
| AV | 1529 | ext_setpoint_offset_3 | Set point 3 offset | °C | Write | |
| AV | 1530 | ext_setpoint_offset_4 | Set point 4 offset | °C | Write | |
| AVmin | 1533 | base_setpoint_1 | Basic set point 1 | °C | Write | |
| AV | 1534 | base_setpoint_2 | Basic set point 2 | °C | Write | |
| AV | 1535 | base_setpoint_3 | Basic set point 3 | °C | Write | |
| AV | 1536 | base_setpoint_4 | Basic set point 4 | °C | Write | |
| MVmin | 1539 | ext_fan_coil_stage | External fan coil stage | Write | ||
| BVmin | 1540 | ext_room_occupancy | External room occupancy | Write | ||
| BV | 2257 | led_button_12 | LED of button 12 on/off | Write | ||
| BV | 2258 | led_button_11 | LED of button 11 on/off | Write | ||
| BV | 2259 | led_button_10 | LED of button 10 on/off | Write | ||
| BV | 2260 | led_button_9 | LED of button 9 on/off | Write | ||
| BV | 2261 | led_button_8 | LED of button 8 on/off | Write | ||
| BV | 2262 | led_button_7 | LED of button 7 on/off | Write | ||
| BV | 2263 | led_button_6 | LED of button 6 on/off | Write | ||
| BV | 2264 | led_button_5 | LED of button 5 on/off | Write | ||
| BV | 2265 | symbol_fault | Symbol fault on/off | Write | ||
| BV | 2266 | symbol_heating | Symbol heating on/off | Write | ||
| BV | 2267 | symbol_cooling | Symbol cooling on/off | Write | ||
| BV | 2268 | symbol_window | Symbol window on/off | Write | ||
| BV | 2269 | lock_buttons | Deactivate Button actuation | Write | ||
| BV | 2270 | lock_occupancy | Deactivate Room occupancy | Write | ||
| BV | 2271 | lock_fan_coil | Deactivate Fan speed | Write | ||
| BV | 2272 | lock_setpoint | Deactivate Set point | Write |
No points match these filters.
Object ID lookup: Thermokon WRF08 BACnet MS/TP RS485 room operating panel point IDs by name
AV1Offset_device_idMV1COV-ModeFILE1Configuration register fileFILE2Input registers fileFILE3Holding registers fileFILE4Configuration coils fileFILE5Coils fileBI1001pushbutton_01BI1002pushbutton_02BI1003pushbutton_03BI1004pushbutton_04BI1005pushbutton_05BI1006pushbutton_06BI1007pushbutton_07BI1008pushbutton_08BI1009pushbutton_09BI1010pushbutton_10BI1011pushbutton_11BI1012pushbutton_12AI1259room_temperatureAI1260setpoint_offset_1AI1261setpoint_effective_1AI1262setpoint_offset_2AI1263setpoint_effective_2AI1264setpoint_offset_3AI1265setpoint_effective_3AI1266setpoint_offset_4AI1267setpoint_effective_4MI1272fan_coil_stageBI1273room_occupancyAV1520outdoor_temperatureAV1521ext_value_1AV1522ext_value_2AV1523ext_value_3AV1524ext_value_4AV1527ext_setpoint_offset_1AV1528ext_setpoint_offset_2AV1529ext_setpoint_offset_3AV1530ext_setpoint_offset_4AV1533base_setpoint_1AV1534base_setpoint_2AV1535base_setpoint_3AV1536base_setpoint_4MV1539ext_fan_coil_stageBV1540ext_room_occupancyBV2257led_button_12BV2258led_button_11BV2259led_button_10BV2260led_button_9BV2261led_button_8BV2262led_button_7BV2263led_button_6BV2264led_button_5BV2265symbol_faultBV2266symbol_heatingBV2267symbol_coolingBV2268symbol_windowBV2269lock_buttonsBV2270lock_occupancyBV2271lock_fan_coilBV2272lock_setpoint
Integration notes
- Access follows the specification: section 5.2.2 lists the read-only objects and 5.2.3 the readable and writeable ones; the basic-settings objects are described as writeable.
- Units are not printed; temperature and setpoint objects are shown in °C.
- Button functions, LED functions, display options and setpoint ranges are configuration registers in the file objects (FI 1-5), not separate BACnet objects.
- COV-Mode (MV 1) states are listed as printed, without numbers.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRF08 BACnet MS/TP RS485 room operating panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Thermokon WRF08 BACnet MS/TP RS485 room operating panel
How many BACnet points does the Thermokon WRF08 BACnet MS/TP RS485 room operating panel have?
This list has 61 BACnet objects: 9 analog inputs, 14 analog values, 13 binary inputs, 17 binary values, 5 files, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet points are writable?
37 of the 61 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet documentation?
The source is Interface description WRF08 BACnet MS/TP RS485 (Ver 1.04), revision 2015-04-22, published free by Thermokon at https://www.thermokon.de/downloads/Software/Schnittstellenbeschreibung/BACnet/WRF08-RS485_BACnet_Manual.zip.
What are the minimum BACnet points to integrate the Thermokon WRF08 BACnet MS/TP RS485 room operating panel?
Start with BV 1540 ext_room_occupancy (Occupancy shown/set from the BMS); MV 1539 ext_fan_coil_stage (Fan stage from the BMS); AV 1533 base_setpoint_1 (Base setpoint 1); AI 1259 room_temperature (Room temperature); AI 1261 setpoint_effective_1 (Effective setpoint 1); AI 1260 setpoint_offset_1 (User setpoint offset 1); MI 1272 fan_coil_stage (Fan stage selected on the panel); BI 1273 room_occupancy (Occupancy selected on the panel).
Can the BMS supply sensor values to the Thermokon WRF08 BACnet MS/TP RS485 room operating panel?
outdoor_temperature (AV 1520) and ext_value_1..4 (AV 1521-1524) take values from the BMS for display on the panel.
How do I check these points on the real WRF08 BACnet MS/TP RS485 room operating panel?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Thermokon BACnet points lists
- Room sensor / operating unit
Thermokon FTW04 BACnet MS/TP RS485 room humidity/temperature unit
Thermokon FTW04 BACnet MS/TP RS485 room units (temperature, humidity, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: FTW04, FTW04 BACnet, FTW04_BACnet, FTW04-RS485-BACnet - Room thermostat / fan coil controller
Thermokon JOY BACnet room thermostats / fan coil controllers (5DO, ECAO2DO, HCAO2DO, EC3AO, HC3AO)
Thermokon JOY wall thermostats with RS485 BACnet MS/TP for fan coils, heating/cooling valves and 6-way valves, in 230 V and 24 V versions with optional CO2 and humidity sensors.
Also known as: JOY FC5DO BACnet, JOY ECAO2DO BACnet, JOY HCAO2DO BACnet, JOY EC3AO BACnet, JOY HC3AO BACnet, JOY HC AO2DO 24V RS485 BACnet, JOY RS485 BACnet - Room operating unit / room sensor
Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units
Thermokon NOVOS 3 and NOVOS 5 (LCD) wall units with RS485 BACnet MS/TP, in temperature, CO2, humidity and VOC sensor variants.
Also known as: NOVOS 3 RS485 BACnet, NOVOS 5 LCD RS485 BACnet, NOVOS 3 x, NOVOS 5 x, NOVOS 5 LCD - Room operating unit / room sensor
Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units
Thermokon NOVOS 7, NOVOS Touch and thanos EVO touch-screen room operating units with RS485 BACnet MS/TP.
Also known as: NOVOS 7, NOVOS Touch, thanos EVO, NOVOS 7 RS485 BACnet, thanos EVO RS485 BACnet - Duct / room sensor (temperature, humidity, CO2, VOC, pressure)
Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)
Thermokon sensors fitted with the USE-BACnet MS/TP RS485 option board (FTA+, FTK+, LK+, DPA+, LI65+, LDF+, RDF+, WK02+ and their LCD versions).
Also known as: USE BACnet, USE-RS485 BACnet, FTA+ BACnet, FTK+ BACnet, LK+ CO2 BACnet, LK+ VOC BACnet, DPA+ BACnet, DPA+ Flow BACnet, LI65+ BACnet, LDF+ BACnet, RDF+ BACnet, WK02+ BACnet - Room sensor / operating unit
Thermokon WRF04 BACnet MS/TP RS485 room operating unit
Thermokon WRF04 BACnet MS/TP RS485 room units (temperature, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: WRF04, WRF04 BACnet, WRF04_BACnet, WRF04-RS485-BACnet - Room sensor (CO2, VOC, temperature, humidity)
Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
Thermokon WRF06 AQ room air quality sensors (CO2, VOC, temperature, humidity variants) and FTW06 room humidity/temperature sensors with RS485 BACnet MS/TP.
Also known as: WRF06 AQ, WRF06 CO2, WRF06 CO2 Temp, WRF06 CO2 Temp_rH, WRF06 CO2+VOC, WRF06 VOC Temp, FTW06, WRF06 AQ BACnet MSTP - Room controller (fan coil, radiator, chilled ceiling)
Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers
Thermokon WRF06 RC and WRF07 RC wall-mounted room controllers with RS485 BACnet MS/TP, including the humidity (x rH) variants.
Also known as: WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP, WRF07 RC, WRF06 RC, WRF07 BACnet MSTP
Source: Interface description WRF08 BACnet MS/TP RS485 · Ver 1.04 · rev. 2015-04-22. Object names, instances and units are reproduced as published; descriptions are our own.