Room operating unit (buttons, LCD, setpoints) / room sensor · BACnet points list

Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet points list

Updated 6 November 2026

Short answer

WRF08 is a room operating panel with LCD and up to 12 buttons. Its BACnet MS/TP interface lists 61 objects: button states, room temperature, four setpoint offsets and effective setpoints, fan stage and occupancy from the panel, plus values the BMS writes for display (outdoor temperature, external values, base setpoints, fan stage, occupancy), LED and symbol control and lock objects. Configuration is done with file objects and Thermokon software.

This page lists 61 BACnet objects for the Thermokon WRF08 BACnet MS/TP RS485 room operating panel — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.

Manufacturer
Thermokon
Model
WRF08 BACnet MS/TP RS485 room operating panel
Equipment
Room operating unit (buttons, LCD, setpoints) / room sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
61 (37 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Offset_device_id (AV 1) + MAC address
Also known as
WRF08, WRF08 BACnet, WRF08 RS485 BACnet, Thermokon_WRF08_BACnet
Source document
Interface description WRF08 BACnet MS/TP RS485 · Ver 1.04 · rev. 2015-04-22
Download CSV 61 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.

BMS integration notes: Thermokon WRF08 BACnet MS/TP RS485 room operating panel

Integration in brief

Write base_setpoint_1 (AV 1533) and, if used, ext_room_occupancy and ext_fan_coil_stage; read room_temperature (AI 1259), setpoint_effective_1, fan_coil_stage and room_occupancy from the panel.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1540ext_room_occupancyOccupancy shown/set from the BMSWrite
MV 1539ext_fan_coil_stageFan stage from the BMSWrite
AV 1533base_setpoint_1Base setpoint 1Write
AI 1259room_temperatureRoom temperatureRead
AI 1261setpoint_effective_1Effective setpoint 1Read
AI 1260setpoint_offset_1User setpoint offset 1Read
MI 1272fan_coil_stageFan stage selected on the panelRead
BI 1273room_occupancyOccupancy selected on the panelRead

Sensors & values from the BMS

outdoor_temperature (AV 1520) and ext_value_1..4 (AV 1521-1524) take values from the BMS for display on the panel.

Network setup

Watch out for

Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

61 of 61 shown
Type
Other
Access
Show
Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet Points List
DescriptionStates
AV1Offset_device_idThis value plus the set MAC (0-127) corresponds to the device IDWrite
MV1COV-ModeCOV modeWriteOff, Local broadcast, Global broadcast
FILE1Configuration register fileConfiguration properties (for the configuration software)Write
FILE2Input registers fileReadable objects (for the configuration software)Read
FILE3Holding registers fileRead/write objects (for the configuration software)Write
FILE4Configuration coils fileConfiguration bits (for the configuration software)Write
FILE5Coils fileRead/write binary objects (for the configuration software)Write
BI1001pushbutton_01Current state of button 1Read
BI1002pushbutton_02Current state of button 2Read
BI1003pushbutton_03Current state of button 3Read
BI1004pushbutton_04Current state of button 4Read
BI1005pushbutton_05Current state of button 5Read
BI1006pushbutton_06Current state of button 6Read
BI1007pushbutton_07Current state of button 7Read
BI1008pushbutton_08Current state of button 8Read
BI1009pushbutton_09Current state of button 9Read
BI1010pushbutton_10Current state of button 10Read
BI1011pushbutton_11Current state of button 11Read
BI1012pushbutton_12Current state of button 12Read
AImin1259room_temperatureRoom temperature°CRead
AImin1260setpoint_offset_1Offset set point 1°CRead
AImin1261setpoint_effective_1Effective set point 1°CRead
AI1262setpoint_offset_2Offset set point 2°CRead
AI1263setpoint_effective_2Effective set point 2°CRead
AI1264setpoint_offset_3Offset set point 3°CRead
AI1265setpoint_effective_3Effective set point 3°CRead
AI1266setpoint_offset_4Offset set point 4°CRead
AI1267setpoint_effective_4Effective set point 4°CRead
MImin1272fan_coil_stageFan coil stageRead
BImin1273room_occupancyRoom occupancyRead
AV1520outdoor_temperatureOutdoor temperature°CWrite
AV1521ext_value_1External value 1Write
AV1522ext_value_2External value 2Write
AV1523ext_value_3External value 3Write
AV1524ext_value_4External value 4Write
AV1527ext_setpoint_offset_1Set point 1 offset°CWrite
AV1528ext_setpoint_offset_2Set point 2 offset°CWrite
AV1529ext_setpoint_offset_3Set point 3 offset°CWrite
AV1530ext_setpoint_offset_4Set point 4 offset°CWrite
AVmin1533base_setpoint_1Basic set point 1°CWrite
AV1534base_setpoint_2Basic set point 2°CWrite
AV1535base_setpoint_3Basic set point 3°CWrite
AV1536base_setpoint_4Basic set point 4°CWrite
MVmin1539ext_fan_coil_stageExternal fan coil stageWrite
BVmin1540ext_room_occupancyExternal room occupancyWrite
BV2257led_button_12LED of button 12 on/offWrite
BV2258led_button_11LED of button 11 on/offWrite
BV2259led_button_10LED of button 10 on/offWrite
BV2260led_button_9LED of button 9 on/offWrite
BV2261led_button_8LED of button 8 on/offWrite
BV2262led_button_7LED of button 7 on/offWrite
BV2263led_button_6LED of button 6 on/offWrite
BV2264led_button_5LED of button 5 on/offWrite
BV2265symbol_faultSymbol fault on/offWrite
BV2266symbol_heatingSymbol heating on/offWrite
BV2267symbol_coolingSymbol cooling on/offWrite
BV2268symbol_windowSymbol window on/offWrite
BV2269lock_buttonsDeactivate Button actuationWrite
BV2270lock_occupancyDeactivate Room occupancyWrite
BV2271lock_fan_coilDeactivate Fan speedWrite
BV2272lock_setpointDeactivate Set pointWrite
Object ID lookup: Thermokon WRF08 BACnet MS/TP RS485 room operating panel point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRF08 BACnet MS/TP RS485 room operating panel and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermokon WRF08 BACnet MS/TP RS485 room operating panel

How many BACnet points does the Thermokon WRF08 BACnet MS/TP RS485 room operating panel have?

This list has 61 BACnet objects: 9 analog inputs, 14 analog values, 13 binary inputs, 17 binary values, 5 files, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet points are writable?

37 of the 61 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Thermokon WRF08 BACnet MS/TP RS485 room operating panel BACnet documentation?

The source is Interface description WRF08 BACnet MS/TP RS485 (Ver 1.04), revision 2015-04-22, published free by Thermokon at https://www.thermokon.de/downloads/Software/Schnittstellenbeschreibung/BACnet/WRF08-RS485_BACnet_Manual.zip.

What are the minimum BACnet points to integrate the Thermokon WRF08 BACnet MS/TP RS485 room operating panel?

Start with BV 1540 ext_room_occupancy (Occupancy shown/set from the BMS); MV 1539 ext_fan_coil_stage (Fan stage from the BMS); AV 1533 base_setpoint_1 (Base setpoint 1); AI 1259 room_temperature (Room temperature); AI 1261 setpoint_effective_1 (Effective setpoint 1); AI 1260 setpoint_offset_1 (User setpoint offset 1); MI 1272 fan_coil_stage (Fan stage selected on the panel); BI 1273 room_occupancy (Occupancy selected on the panel).

Can the BMS supply sensor values to the Thermokon WRF08 BACnet MS/TP RS485 room operating panel?

outdoor_temperature (AV 1520) and ext_value_1..4 (AV 1521-1524) take values from the BMS for display on the panel.

How do I check these points on the real WRF08 BACnet MS/TP RS485 room operating panel?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermokon BACnet points lists

Source: Interface description WRF08 BACnet MS/TP RS485 · Ver 1.04 · rev. 2015-04-22. Object names, instances and units are reproduced as published; descriptions are our own.