  4. NOVOS 3 / NOVOS 5 RS485 BACnet room operating units

Room operating unit / room sensor · BACnet points list

Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units BACnet points list

Updated 4 November 2026

Short answer

NOVOS 3 and NOVOS 5 are wall-mounted room sensors and operating units with a BACnet MS/TP interface. They measure temperature and, depending on the variant, humidity, CO2 and VOC, and offer occupancy, setpoint and fan-stage inputs for the room controller in the BMS. Only the main operating values are BACnet objects; the rest is set through a configuration file written with Thermokon's uConfig tool.

This page lists 32 BACnet objects for the Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.

Manufacturer
Thermokon
Model
NOVOS 3 / NOVOS 5 RS485 BACnet room operating units
Equipment
Room operating unit / room sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
32 (21 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Device Offset ID + MAC address
Also known as
NOVOS 3 RS485 BACnet, NOVOS 5 LCD RS485 BACnet, NOVOS 3 x, NOVOS 5 x, NOVOS 5 LCD
Source document
Description of RS485 BACnet Interface NOVOS 3 / NOVOS 5 · rev. Rev. D, 18.06.2026
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.

BMS integration notes: Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units

Integration in brief

Set the MAC address and baud rate with the DIP switches, and the Device Offset ID if needed. Read the sensor AIs and the occupancy, setpoint and fan-stage objects and feed them to the room controller in the BMS; write the LED and icon objects to show states back to the user.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 100OccupancyRoom occupied (button), also writable from the BMSWrite
AV 103SetpointRoom setpoint set on the unitWrite
MV 104Fan StageFan stage selected on the unitRead
AI 500TemperatureRoom temperatureRead
AI 501Relative HumidityRoom humidity (rH variants)Read
AI 505CO2Room CO2 (CO2 variants)Read
BI 514Digital InputWindow or other contact, 1 = closedRead

Network setup

Watch out for

Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

32 of 32 shown
Type
Access
Show
Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units BACnet Points List
DescriptionStates
DEVx_Novos 3/5 BACnet MSTPDevice object; instance = Device Offset ID + MAC addressRead
MO1041Device ResetRestart the deviceWrite1=running, 2=Reset, 3=Reboot
AV4180Device Offset IDOffset added to the MAC address for the device instanceWrite
MV4183COV ModeCOV notifications off, local or global broadcastWrite1=off, 2=Local, 3=Global
FILE0config.binConfiguration file transfer (uConfig)Write
BVmin100OccupancyRoom occupancy (toggled by the button)Write0=Unoccupied, 1=Occupied
AVmin103SetpointEffective room setpoint°CWrite
MVmin104Fan StageCurrently active fan stageRead1=off, 2=Stage 1, 3=Stage 2, 4=Stage 3, 5=Stage 4, 6=Stage 5, 7=Auto
MV105Auto Fan StageFan stage shown when the fan is in AutoWrite1=Auto, 2=Auto 0, 3=Auto 1, 4=Auto 2, 5=Auto 3, 6=Auto 4, 7=Auto 5
MV426LED StateButton LED on/off or occupancy indicationWrite1=off, 2=on, 3=Occupancy
MV427LED ColorButton LED colourWrite1=white, 2=black, 3=red, 4=green, 5=blue, 6=yellow, 7=magenta, 8=cyan
AImin500TemperatureRoom temperature°CRead
AImin501Relative HumidityRoom relative humidity%Read
AI502Absolute HumidityAbsolute humidityg/m³Read
AI503EnthalpyEnthalpykJ/kgRead
AI504DewpointDew point°CRead
AImin505CO2CO2 concentrationppmRead
AI506VOCVOC level%Read
AI507CO2 / VOC MixCombined CO2/VOC air quality index%Read
BImin514Digital InputPotential-free contact statusRead0=open, 1=closed
BV16Show Icon CondensationShow the condensation icon on the LCDWrite0=off, 1=on
BV17Show Icon Window openShow the window open icon on the LCDWrite0=off, 1=on
BV18Show Icon CalibrationShow the calibration icon on the LCDWrite0=off, 1=on
BV19Show Icon Communication ErrorShow the communication error icon on the LCDWrite0=off, 1=on
BV20Show Icon Communication ModeShow the communication mode icon on the LCDWrite0=off, 1=on
BV21Show Icon ECOShow the eco icon on the LCDWrite0=off, 1=on
BV22Show Icon HeatingShow the heating icon on the LCDWrite0=off, 1=on
BV23Show Icon CoolingShow the cooling icon on the LCDWrite0=off, 1=on
BV24Show Icon MovementShow the movement icon on the LCDWrite0=off, 1=on
BV25Show Icon OccupancyShow the occupancy icon on the LCDWrite0=off, 1=on
BV26Show Icon WarningShow the warning icon on the LCDWrite0=off, 1=on
BV27Show Icon ServiceShow the service icon on the LCDWrite0=off, 1=on
Object ID lookup: Thermokon NOVOS 3/5 BACnet point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the NOVOS 3 / NOVOS 5 RS485 BACnet room operating units and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units

How many BACnet points does the Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units have?

This list has 32 BACnet objects: 8 analog inputs, 2 analog values, 1 binary input, 13 binary values, 1 device, 1 file, 1 multi-state output, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units BACnet points are writable?

21 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units BACnet documentation?

The source is Description of RS485 BACnet Interface NOVOS 3 / NOVOS 5, revision Rev. D, 18.06.2026, published free by Thermokon at https://www.thermokon.de/direct/alterra-base/mimes/get/3f7260a25eb0435a3.

What are the minimum BACnet points to integrate the Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units?

Start with BV 100 Occupancy (Room occupied (button), also writable from the BMS); AV 103 Setpoint (Room setpoint set on the unit); MV 104 Fan Stage (Fan stage selected on the unit); AI 500 Temperature (Room temperature); AI 501 Relative Humidity (Room humidity (rH variants)); AI 505 CO2 (Room CO2 (CO2 variants)); BI 514 Digital Input (Window or other contact, 1 = closed).

How do I check these points on the real NOVOS 3 / NOVOS 5 RS485 BACnet room operating units?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermokon BACnet points lists

Source: Description of RS485 BACnet Interface NOVOS 3 / NOVOS 5 · rev. Rev. D, 18.06.2026. Object names, instances and units are reproduced as published; descriptions are our own.