Duct / room sensor (temperature, humidity, CO2, VOC, pressure) · BACnet points list
Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...) BACnet points list
Updated 6 November 2026
The USE-BACnet option gives Thermokon's sensor families a BACnet MS/TP interface. The description lists 107 objects: measured values (temperature, humidity and derived values, CO2, VOC, differential pressure and airflow, illuminance, atmospheric pressure, extra inputs), offsets, upper/lower scaling limits, channel assignment, airflow formula settings, service counters and LCD/traffic-light settings.
This page lists 107 BACnet objects for the Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...) — 84 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.
- Manufacturer
- Thermokon
- Model
- USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)
- Equipment
- Duct / room sensor (temperature, humidity, CO2, VOC, pressure)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 107 (84 writable)
- Transport
- BACnet MS/TP
- Firmware
- 2.5
- Default device instance
- Offset Device ID (AV 46) + MAC address
- Also known as
- USE BACnet, USE-RS485 BACnet, FTA+ BACnet, FTK+ BACnet, LK+ CO2 BACnet, LK+ VOC BACnet, DPA+ BACnet, DPA+ Flow BACnet, LI65+ BACnet, LDF+ BACnet, RDF+ BACnet, WK02+ BACnet
- Source document
- Description for USE-BACnet MS/TP · rev. Rev. F, 19.08.2021
Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.
BMS integration notes: Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)
Read the measured values the sensor type provides (AI 0 temperature, AI 1 humidity, AI 5 CO2, AI 8 differential pressure, AI 9 airflow ...). Offsets, limits and channel settings are commissioning values.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 0 | Temperature 1 | Temperature | Read |
| AI 1 | Relative humidity | Relative humidity | Read |
| AI 5 | CO2 | CO2, ppm | Read |
| AI 6 | VOC | VOC, % | Read |
| AI 8 | Differential pressure 1 | Differential pressure 1, Pa | Read |
| AI 9 | Volumetric flow 1 | Airflow 1 (unit per AV 41) | Read |
Network setup
- MAC address 1-127 and baud rate (9600, 19200, 38400, 76800) are set on DIP switches; 8N1 framing.
- Device ID = Offset Device ID (AV 46) + MAC address.
Watch out for
- Imperial pressure offsets are written in 1/1000 inWC.
- AV 85/86 zero the differential pressure sensors when set to 1.
Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 38 | Selection of unit systems | Write | 1=SI, 2=Imperial | ||
| AImin | 1 | Relative humidity | %RH | Read | ||
| AImin | 5 | CO2 | ppm | Read | ||
| AImin | 6 | VOC | % | Read | ||
| AI | 7 | CO2 VOC Mix | % | Read | ||
| AI | 18 | Input 1 (switch contact) | Read | |||
| AI | 19 | Input 2 (switch contact) | Read | |||
| AI | 20 | Condensate raw value 0…4095 | Read | |||
| AI | 21 | Condensate relay state | Read | |||
| AImin | 0 | Temperature 1 | °C | Read | ||
| AI | 2 | Absolute humidity | g/m³ | Read | ||
| AI | 3 | Enthalpy | kJ/kg | Read | ||
| AI | 4 | Dewpoint | °C | Read | ||
| AImin | 8 | Differential pressure 1 | Pa | Read | ||
| AImin | 9 | Volumetric flow 1 | In m³/s when AV 41 is set to 2 | m³/h | Read | |
| AI | 10 | Differential pressure 2 | Pa | Read | ||
| AI | 11 | Volumetric flow 2 | In m³/s when AV 43 is set to 2 | m³/h | Read | |
| AI | 12 | Temperature 2 | °C | Read | ||
| AI | 13 | Illumination 1 | lx | Read | ||
| AI | 14 | Illumination 2 | Read | |||
| AI | 15 | Atmospheric pressure | hPa | Read | ||
| AI | 16 | Input 1 (Temperature NTC10k) | °C | Read | ||
| AI | 17 | Input 2 (Temperature NTC10k) | Read | |||
| AV | 1 | Offset relative humidty | %RH | Write | ||
| AV | 2 | Offset CO2 | ppm | Write | ||
| AV | 3 | Offset VOC | % | Write | ||
| AV | 70 | Offset Illumination 2 | Write | |||
| AV | 0 | Offset Temperature 1 | °C | Write | ||
| AV | 4 | Offset Differential Pressure 1 | Pa | Write | ||
| AV | 5 | Offset Differential Pressure 2 | Pa | Write | ||
| AV | 68 | Offset Temperature 2 | °C | Write | ||
| AV | 69 | Offset Illumination 1 | lx | Write | ||
| AV | 73 | Offset Atmospheric Pressure | hPa | Write | ||
| AV | 8 | Relative humidity lower limit | %RH | Write | ||
| AV | 9 | Relative humidity upper limit | Write | |||
| AV | 16 | CO2 lower limit | ppm | Write | ||
| AV | 17 | CO2 upper limit | Write | |||
| AV | 18 | VOC lower limit | % | Write | ||
| AV | 19 | VOC upper limit | Write | |||
| AV | 20 | CO2 VOC Mix lower limit | % | Write | ||
| AV | 21 | CO2 VOC Mix upper limit | Write | |||
| AV | 6 | Temperature 1 lower limit | °C | Write | ||
| AV | 7 | Temperature 1 upper limit | Write | |||
| AV | 10 | Absolute humidity lower limit | g/m³ | Write | ||
| AV | 11 | Absolute humidity upper limit | Write | |||
| AV | 12 | Enthalpy lower limit | kJ/kg | Write | ||
| AV | 13 | Enthalpy upper limit | Write | |||
| AV | 14 | Dew point lower limit | °C | Write | ||
| AV | 15 | Dew point upper limit | Write | |||
| AV | 22 | Volumetric flow 1 lower limit | In m³/s when AV 41 is set to 2 | m³/h | Write | |
| AV | 23 | Volumetric flow 1 upper limit | In m³/s when AV 41 is set to 2 | Write | ||
| AV | 24 | Volumetric flow 2 lower limit | In m³/s when AV 43 is set to 2 | Write | ||
| AV | 25 | Volumetric flow 2 upper limit | In m³/s when AV 43 is set to 2 | Write | ||
| AV | 74 | Temperature 2 lower limit | °C | Write | ||
| AV | 75 | Temperature 2 upper limit | Write | |||
| AV | 76 | Atmospheric pressure lower limit | hPa | Write | ||
| AV | 77 | Atmospheric pressure upper limit | Write | |||
| AV | 26 | Channel number Temperature 1 | Write | |||
| AV | 27 | Channel number Relative humidity | Write | |||
| AV | 28 | Channel number Absolute humidity | Write | |||
| AV | 29 | Channel number Enthalpy | Write | |||
| AV | 30 | Channel number Dew point | Write | |||
| AV | 31 | Channel number CO2 | Write | |||
| AV | 32 | Channel number VOC | Write | |||
| AV | 33 | Channel number CO2 VOC Mix | Write | |||
| AV | 34 | Channel number Differential pressure 1 | Write | |||
| AV | 35 | Channel number Volumetric flow 1 | Write | |||
| AV | 36 | Channel number Differential pressure 2 | For devices with 2 pressure sensors | Write | ||
| AV | 37 | Channel number Volumetric flow 2 | For devices with 2 pressure sensors | Write | ||
| AV | 78 | Channel number Temperature 2 | Write | |||
| AV | 79 | Channel number Illumination 1 | Write | |||
| AV | 80 | Channel number Illumination 1 | Write | |||
| AV | 81 | Channel number Atmospheric Pressure 1 | Write | |||
| AV | 82 | Percentage value of the CO2 value in the CO2 VOC Mix Signal | % | Write | ||
| AV | 83 | BETA-Value NTC 1 | Write | |||
| AV | 39 | Height (above sea level) | m | Write | ||
| AV | 40 | k-value volumetric flow 1 | Fan maker's conversion factor for the airflow calculation | Write | ||
| AV | 41 | Calculation formula volumetric flow 1 | Selection of calculation formula (depending on fan manufacturer) | Write | ||
| AV | 42 | k-value volumetric flow 2 | Fan maker's conversion factor for the airflow calculation | Write | ||
| AV | 43 | Calculation formula volumetric flow 2 | Selection of calculation formula (depending on fan manufacturer) | Write | ||
| AV | 44 | Response time volumetric flow 1 | s | Write | ||
| AV | 45 | Response time volumetric flow 1 | s | Write | ||
| AV | 84 | BETA-Value NTC 2 | Write | |||
| AV | 85 | Zeroing differential pressure 1 | Write | 0=no zeroing, 1=start zeroing | ||
| AV | 86 | Zeroing differential pressure 2 | Write | |||
| AV | 46 | Offset Device ID | Write | |||
| AV | 47 | Unconfirmed COV | Write | 0=deactivated, 1=activated | ||
| AV | 48 | Minimal output voltage | V | Write | ||
| AV | 49 | Elapsed hour counter | h | Read | ||
| AV | 50 | Service Countdown | Countdown to the next service, hours | Write | ||
| AV | 51 | Calibration Countdown | Countdown to the next calibration, hours | Write | ||
| AV | 52 | LCD ON/OFF | Write | 0=ON, 1=OFF | ||
| AV | 53 | LCD Brightness | % | Write | ||
| AV | 54 | LCD Rotation | Write | |||
| AV | 55 | LCD activate traffic-light function | Write | 0=deactivated, 1=activated | ||
| AV | 56 | LCD Service symbol enabled | Write | 0=disabled, 1=enabled | ||
| AV | 57 | LCD Calibration symbol enabled | Write | |||
| AV | 58 | LCD Channel 1 display/ do not display | Write | 0=do not display, 1=display | ||
| AV | 59 | LCD Channel 2 display/do not display | Write | |||
| AV | 60 | LCD Channel 3 display/do not display | Write | |||
| AV | 61 | LCD Channel 4 display/do not display | Write | |||
| AV | 62 | Channel assignment for traffic-light function | Write | |||
| AV | 63 | Traffic-light function Colour range 1 | Write | 0=off, 1=green, 2=yellow, 3=red, 4=blue, 5=magenta, 6=cyan, 7=white | ||
| AV | 64 | Traffic-light function Colour range 2 | Write | |||
| AV | 65 | Traffic-light function Colour range 3 | Write | |||
| AV | 66 | Traffic-light threshold Range 1→2 | Write | |||
| AV | 67 | Traffic-light threshold Range 2→3 | Write |
No points match these filters.
Object ID lookup: Thermokon USE-BACnet MS/TP option for Thermokon sensors point IDs by name
AV38Selection of unit systemsAI1Relative humidityAI5CO2AI6VOCAI7CO2 VOC MixAI18Input 1 (switch contact)AI19Input 2 (switch contact)AI20Condensate raw value 0…4095AI21Condensate relay stateAI0Temperature 1AI2Absolute humidityAI3EnthalpyAI4DewpointAI8Differential pressure 1AI9Volumetric flow 1AI10Differential pressure 2AI11Volumetric flow 2AI12Temperature 2AI13Illumination 1AI14Illumination 2AI15Atmospheric pressureAI16Input 1 (Temperature NTC10k)AI17Input 2 (Temperature NTC10k)AV1Offset relative humidtyAV2Offset CO2AV3Offset VOCAV70Offset Illumination 2AV0Offset Temperature 1AV4Offset Differential Pressure 1AV5Offset Differential Pressure 2AV68Offset Temperature 2AV69Offset Illumination 1AV73Offset Atmospheric PressureAV8Relative humidity lower limitAV9Relative humidity upper limitAV16CO2 lower limitAV17CO2 upper limitAV18VOC lower limitAV19VOC upper limitAV20CO2 VOC Mix lower limitAV21CO2 VOC Mix upper limitAV6Temperature 1 lower limitAV7Temperature 1 upper limitAV10Absolute humidity lower limitAV11Absolute humidity upper limitAV12Enthalpy lower limitAV13Enthalpy upper limitAV14Dew point lower limitAV15Dew point upper limitAV22Volumetric flow 1 lower limitAV23Volumetric flow 1 upper limitAV24Volumetric flow 2 lower limitAV25Volumetric flow 2 upper limitAV74Temperature 2 lower limitAV75Temperature 2 upper limitAV76Atmospheric pressure lower limitAV77Atmospheric pressure upper limitAV26Channel number Temperature 1AV27Channel number Relative humidityAV28Channel number Absolute humidityAV29Channel number EnthalpyAV30Channel number Dew pointAV31Channel number CO2AV32Channel number VOCAV33Channel number CO2 VOC MixAV34Channel number Differential pressure 1AV35Channel number Volumetric flow 1AV36Channel number Differential pressure 2AV37Channel number Volumetric flow 2AV78Channel number Temperature 2AV79Channel number Illumination 1AV80Channel number Illumination 1AV81Channel number Atmospheric Pressure 1AV82Percentage value of the CO2 value in the CO2 VOC Mix SignalAV83BETA-Value NTC 1AV39Height (above sea level)AV40k-value volumetric flow 1AV41Calculation formula volumetric flow 1AV42k-value volumetric flow 2AV43Calculation formula volumetric flow 2AV44Response time volumetric flow 1AV45Response time volumetric flow 1AV84BETA-Value NTC 2AV85Zeroing differential pressure 1AV86Zeroing differential pressure 2AV46Offset Device IDAV47Unconfirmed COVAV48Minimal output voltageAV49Elapsed hour counterAV50Service CountdownAV51Calibration CountdownAV52LCD ON/OFFAV53LCD BrightnessAV54LCD RotationAV55LCD activate traffic-light functionAV56LCD Service symbol enabledAV57LCD Calibration symbol enabledAV58LCD Channel 1 display/ do not displayAV59LCD Channel 2 display/do not displayAV60LCD Channel 3 display/do not displayAV61LCD Channel 4 display/do not displayAV62Channel assignment for traffic-light functionAV63Traffic-light function Colour range 1AV64Traffic-light function Colour range 2AV65Traffic-light function Colour range 3AV66Traffic-light threshold Range 1→2AV67Traffic-light threshold Range 2→3
Integration notes
- The description gives each object an ID, access and description but no object name; the description is used as the name here.
- Which values exist depends on the sensor type; the data sheet of each product says which are available.
- Units for temperatures, flows and pressures follow AV 38 (1 = SI, 2 = Imperial); SI units are shown.
- The document prints AV 70 twice as "Correction factor Illumination 1" and once as "Offset Illumination 2", and uses AV 82/AV 83 both as channel numbers and as CO2/VOC mix percentage and NTC BETA value; the later sections (consistent with section 1.6) are used here.
- RW* objects are read-only on LI65+, DPA+, LDF+ and RDF+, where the DIP switches set them.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)
How many BACnet points does the Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...) have?
This list has 107 BACnet objects: 22 analog inputs, 85 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...) BACnet points are writable?
84 of the 107 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...) BACnet documentation?
The source is Description for USE-BACnet MS/TP, revision Rev. F, 19.08.2021, published free by Thermokon at https://www.thermokon.de/downloads/Software/Schnittstellenbeschreibung/BACnet/USE-RS485_BACnet_Manual.zip.
What are the minimum BACnet points to integrate the Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)?
Start with AI 0 Temperature 1 (Temperature); AI 1 Relative humidity (Relative humidity); AI 5 CO2 (CO2, ppm); AI 6 VOC (VOC, %); AI 8 Differential pressure 1 (Differential pressure 1, Pa); AI 9 Volumetric flow 1 (Airflow 1 (unit per AV 41)).
How do I check these points on the real USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Thermokon BACnet points lists
- Room sensor / operating unit
Thermokon FTW04 BACnet MS/TP RS485 room humidity/temperature unit
Thermokon FTW04 BACnet MS/TP RS485 room units (temperature, humidity, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: FTW04, FTW04 BACnet, FTW04_BACnet, FTW04-RS485-BACnet - Room thermostat / fan coil controller
Thermokon JOY BACnet room thermostats / fan coil controllers (5DO, ECAO2DO, HCAO2DO, EC3AO, HC3AO)
Thermokon JOY wall thermostats with RS485 BACnet MS/TP for fan coils, heating/cooling valves and 6-way valves, in 230 V and 24 V versions with optional CO2 and humidity sensors.
Also known as: JOY FC5DO BACnet, JOY ECAO2DO BACnet, JOY HCAO2DO BACnet, JOY EC3AO BACnet, JOY HC3AO BACnet, JOY HC AO2DO 24V RS485 BACnet, JOY RS485 BACnet - Room operating unit / room sensor
Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units
Thermokon NOVOS 3 and NOVOS 5 (LCD) wall units with RS485 BACnet MS/TP, in temperature, CO2, humidity and VOC sensor variants.
Also known as: NOVOS 3 RS485 BACnet, NOVOS 5 LCD RS485 BACnet, NOVOS 3 x, NOVOS 5 x, NOVOS 5 LCD - Room operating unit / room sensor
Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units
Thermokon NOVOS 7, NOVOS Touch and thanos EVO touch-screen room operating units with RS485 BACnet MS/TP.
Also known as: NOVOS 7, NOVOS Touch, thanos EVO, NOVOS 7 RS485 BACnet, thanos EVO RS485 BACnet - Room sensor / operating unit
Thermokon WRF04 BACnet MS/TP RS485 room operating unit
Thermokon WRF04 BACnet MS/TP RS485 room units (temperature, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: WRF04, WRF04 BACnet, WRF04_BACnet, WRF04-RS485-BACnet - Room sensor (CO2, VOC, temperature, humidity)
Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
Thermokon WRF06 AQ room air quality sensors (CO2, VOC, temperature, humidity variants) and FTW06 room humidity/temperature sensors with RS485 BACnet MS/TP.
Also known as: WRF06 AQ, WRF06 CO2, WRF06 CO2 Temp, WRF06 CO2 Temp_rH, WRF06 CO2+VOC, WRF06 VOC Temp, FTW06, WRF06 AQ BACnet MSTP - Room controller (fan coil, radiator, chilled ceiling)
Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers
Thermokon WRF06 RC and WRF07 RC wall-mounted room controllers with RS485 BACnet MS/TP, including the humidity (x rH) variants.
Also known as: WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP, WRF07 RC, WRF06 RC, WRF07 BACnet MSTP - Room operating unit (buttons, LCD, setpoints) / room sensor
Thermokon WRF08 BACnet MS/TP RS485 room operating panel
Thermokon WRF08 room operating panels with LCD, up to 12 buttons, room temperature sensor and BACnet MS/TP over RS485.
Also known as: WRF08, WRF08 BACnet, WRF08 RS485 BACnet, Thermokon_WRF08_BACnet
Source: Description for USE-BACnet MS/TP · rev. Rev. F, 19.08.2021. Object names, instances and units are reproduced as published; descriptions are our own.