Room controller (fan coil, radiator, chilled ceiling) · BACnet points list

Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers BACnet points list

Updated 4 November 2026

Short answer

WRF06 RC and WRF07 RC are wall-mounted room controllers with a built-in PI controller, setpoint knob, buttons and up to two outputs (0-10 V, relay, triac or 6-way valve), plus up to four digital inputs. Everything is configured over BACnet MS/TP: device type, PI parameters, fan stages, button, LED and input functions. The BMS can command occupancy, mode and fan stage, override the outputs and drive the LEDs.

This page lists 138 BACnet objects for the Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers — 94 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.

Manufacturer
Thermokon
Model
WRF06 RC / WRF07 RC BACnet MS/TP room controllers
Equipment
Room controller (fan coil, radiator, chilled ceiling)
Equipment type
VAV boxes & fan coils
BACnet objects
138 (94 writable)
Transport
BACnet MS/TP
Firmware
1.0.0 or later (BV 114 needs 1.1.0, writable device name 3.0.6)
Default device instance
Offset Device ID (AV 100) + MAC address
Also known as
WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP, WRF07 RC, WRF06 RC, WRF07 BACnet MSTP
Source document
Description for WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP · rev. Rev. E, 30.01.2026
Download CSV 138 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.

BMS integration notes: Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers

Integration in brief

Set the MAC address and baud rate on the DIP switches, then set the device type (MV 100) and controller parameters. From the BMS, command occupancy with BV 3, the mode with MV 0 (needed for change-over) and the fan stage with MV 1, write the base setpoint (AV 1), and read room temperature, active setpoint and the controller outputs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 3Occupancy OverrideOccupancy command, 1 = occupiedWrite
BV 1PI-Ctr. EnableEnable the room controllerWrite
MV 0PI-Ctr. Mode OverrideMode: off, heat, cool or automaticWrite
AV 1Base SetpointBase room setpointWrite
MV 1Fan StageFan stage 0-3 or automaticWrite
AI 7PI-Controller ModeCurrent controller modeRead
AI 0TemperatureRoom temperatureRead
AI 5Setpoint AbsoluteActive setpointRead
AI 8PI-Controller Y HeatHeating demand, %Read
AI 9PI-Controller Y CoolCooling demand, %Read

Enable & remote start

PI-Ctr. Enable (BV 1) turns the built-in controller on; Occupancy Override (BV 3) sets occupied/unoccupied, and PI-Ctr. Mode Override (MV 0) sets off/heat/cool/automatic. In change-over operation (BV 112) the heat/cool mode must be given through MV 0.

Sensors & values from the BMS

Energy hold-off (BV 0) and dew-point (BV 2) can be set from the BMS as well as from wired inputs. The outputs can be overridden with AO 0 and AO 1 (0-10 V); writing -1 returns them to automatic.

Network setup

Watch out for

Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

138 of 138 shown
Type
Multi-stateOther
Access
Show
Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers BACnet Points List
DescriptionStates
DEVWRF07 BACnet MSTPDevice object; instance = Offset Device ID + MAC addressRead
AImin0TemperatureRoom temperature°CRead
AI1Relative HumidityRoom relative humidity (rH variants)%rHRead
AI2Absolute HumidtyAbsolute humidityg/m³Read
AI3EnthalpyEnthalpykJ/kgRead
AI4DewpointDew point°CRead
AImin5Setpoint AbsoluteActive setpoint°CRead
AI6Setpoint AdjustmentSetpoint shift from the knob°CRead
AImin7PI-Controller ModeController mode (1 off, 2 heating, 3 cooling, 4/5 auto heat/cool)Read
AImin8PI-Controller Y HeatHeating control variable%Read
AImin9PI-Controller Y CoolCooling control variable%Read
AI10Output 1 ValueOutput 1 signalVRead
AI11Output 2 ValueOutput 2 signalVRead
AI12Digital Input 1 CounterPulse count on input 1; reset to 0 when readRead
AI13Digital Input 2 CounterPulse count on input 2; reset to 0 when readRead
AI14Digital Input 3 CounterPulse count on input 3; reset to 0 when readRead
AI15Digital Input 4 CounterPulse count on input 4; reset to 0 when readRead
BI0OccupancyOccupancy stateRead0=unoccupied, 1=occupied
BI1Button 1Button 1 live stateRead0=released, 1=pressed
BI2Button 2Button 2 live stateRead0=released, 1=pressed
BI3Button 3Button 3 live stateRead0=released, 1=pressed
BI4Button 4Button 4 live stateRead0=released, 1=pressed
BI5Button 5Button 5 live stateRead0=released, 1=pressed
BI6Button 6Button 6 live stateRead0=released, 1=pressed
BI7Button 7Button 7 live stateRead0=released, 1=pressed
BI8Button 1 (saved)Button 1 press latched until readRead0=released, 1=pressed
BI9Button 2 (saved)Button 2 press latched until readRead0=released, 1=pressed
BI10Button 3 (saved)Button 3 press latched until readRead0=released, 1=pressed
BI11Button 4 (saved)Button 4 press latched until readRead0=released, 1=pressed
BI12Button 5 (saved)Button 5 press latched until readRead0=released, 1=pressed
BI13Button 6 (saved)Button 6 press latched until readRead0=released, 1=pressed
BI14Button 7 (saved)Button 7 press latched until readRead0=released, 1=pressed
BI15Switch Position 1Switch position 1Read0=released, 1=pressed
BI16Switch Position 2Switch position 2Read0=released, 1=pressed
BI17Switch Position 1 (saved)Switch position 1, latched until readRead0=released, 1=pressed
BI18Switch Position 2 (saved)Switch position 2, latched until readRead0=released, 1=pressed
BI19Digital Input 1Digital input 1Read0=false, 1=true
BI20Digital Input 2Digital input 2Read0=false, 1=true
BI21Digital Input 3Digital input 3Read0=false, 1=true
BI22Digital Input 4Digital input 4Read0=false, 1=true
BI23Digital Input 1 (saved)Digital input 1, latched until readRead0=false, 1=true
BI24Digital Input 2 (saved)Digital input 2, latched until readRead0=false, 1=true
BI25Digital Input 3 (saved)Digital input 3, latched until readRead0=false, 1=true
BI26Digital Input 4 (saved)Digital input 4, latched until readRead0=false, 1=true
AV0Setpoint Adjustment RangeSetpoint adjustment range of the knob°CWrite
AVmin1Base SetpointBase setpoint°CWrite
AV100Offset Device IDOffset added to the MAC address for the device instanceWrite
AV101Temperature OffsetTemperature sensor correction°CWrite
AV102Rel. Humidity OffsetHumidity sensor correction%rHWrite
AV103Base Setpoint after ResetBase setpoint used after a restart°CWrite
AV104Setpoint Adjustment Range After ResetAdjustment range used after a restart°CWrite
AV105Setpoint Unoccupied AdjustmentNight setback/setup when unoccupied°CWrite
AV106Occupancy Party TimeParty (temporary occupancy) timesWrite
AV107PI-Ctr. Dead BandDead band between heating and cooling°CWrite
AV108PI-Ctr. xp HeatHeating proportional band°CWrite
AV109PI-Ctr. Tn HeatHeating integral timeminWrite
AV110PI-Ctr. Y-min HeatMinimum heating output%Write
AV111PI-Ctr. Y-max HeatMaximum heating output%Write
AV112PI-Ctr. PWM-cycle HeatHeating PWM cycle timesWrite
AV113PI-Ctr. xp CoolCooling proportional band°CWrite
AV114PI-Ctr. Tn CoolCooling integral timeminWrite
AV115PI-Ctr. Y-min CoolMinimum cooling output%Write
AV116PI-Ctr. Y-max CoolMaximum cooling output%Write
AV117PI-Ctr. PWM-cycle CoolCooling PWM cycle timesWrite
AV118PI-Ctr. Frost ProtectionFrost protection setpoint°CWrite
AV119Fan Stage 1 Threshold Y HeatHeating control variable that starts fan stage 1%Write
AV120Fan Stage 2 Threshold Y HeatHeating control variable that starts fan stage 2%Write
AV121Fan Stage 3 Threshold Y HeatHeating control variable that starts fan stage 3%Write
AV122Fan Stage 1 Threshold Y CoolCooling control variable that starts fan stage 1%Write
AV123Fan Stage 2 Threshold Y CoolCooling control variable that starts fan stage 2%Write
AV124Fan Stage 3 Threshold Y CoolCooling control variable that starts fan stage 3%Write
AV125Fan Stage 1 Output VoltageFan output voltage for stage 1VWrite
AV126Fan Stage 2 Output VoltageFan output voltage for stage 2VWrite
AV127Fan Stage 3 Output VoltageFan output voltage for stage 3VWrite
BV0PI-Ctr. Energy Hold OffEnergy hold-off (e.g. window open) activeWrite0=false, 1=true
BVmin1PI-Ctr. EnableEnable the room controllerWrite0=false, 1=true
BV2PI-Ctr. DewpointDew point alarm (stops cooling)Write0=false, 1=true
BVmin3Occupancy OverrideOccupancy command from the BMSWrite0=unoccupied, 1=occupied
BV100Unit-SystemUnit systemWrite0=Imperial, 1=SI
BV101COV Enable - TemperatureCOV reporting for temperatureWrite0=disable, 1=enable
BV102COV Enable - rel. HumidityCOV reporting for rel. humidityWrite0=disable, 1=enable
BV103COV Enable - abs. HumidityCOV reporting for abs. humidityWrite0=disable, 1=enable
BV104COV Enable - EnthalpyCOV reporting for enthalpyWrite0=disable, 1=enable
BV105COV Enable - DewpointCOV reporting for dewpointWrite0=disable, 1=enable
BV106COV Enable - SetpointCOV reporting for setpointWrite0=disable, 1=enable
BV107COV Enable - OccupancyCOV reporting for occupancyWrite0=disable, 1=enable
BV108COV Enable - ButtonsCOV reporting for buttonsWrite0=disable, 1=enable
BV109COV Enable - SwitchCOV reporting for switchWrite0=disable, 1=enable
BV110COV Enable - InputsCOV reporting for inputsWrite0=disable, 1=enable
BV111PI-Ctr. Y-Min. if Y>0Apply minimum output only when demand is above 0Write0=false, 1=true
BV112PI-CTR. Change OverChange-over (2-pipe) operationWrite0=false, 1=true
BV113Occupancy after ResetOccupancy state after a restartWrite0=unoccupied, 1=occupied
BV114Disable State LEDs (STA, RXD, TXD, ERR)Turn off the bus status LEDs (fw 1.1.0+)Write0=LEDs not disabled, 1=LEDs disabled
MVmin0PI-Ctr. Mode OverrideController mode command (heat/cool in change-over)Writeoff, heat, cool, automatic
MVmin1Fan StageFan stageWriteStage 0 (Fan OFF), Stage 1 (manual), Stage 2 (manual), Stage 3 (manual), automatic
MV100Device TypeOutput configuration of the controllerWriteAO2V, DO2R, DO2T, OVR, OVT, 4DI, 6WV, 6WV_INV, 6WV_DN15, 6WV_DN20
MV101PI-Ctr. Mode after ResetController mode after a restartWriteoff, heat, cool, automatic
MV102Setpoint VisualizationWhich setpoint the display showsWriteAlways Heat-Setpoint, Heat- and Cool-Setpoint
MV103Button 1 FunctionFunction of button 1WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV104Button 2 FunctionFunction of button 2WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV105Button 3 FunctionFunction of button 3WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV106Button 4 FunctionFunction of button 4WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV107Button 5 FunctionFunction of button 5WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV108Button 6 FunctionFunction of button 6WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV109Button 7 FunctionFunction of button 7WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV110Button 8 FunctionFunction of button 8WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV111Button 9 FunctionFunction of button 9WriteContact, Pulse Unoccupied, Pulse Occupied, Toggle Occupancy, Contact Occupied, Pulse Party Time, Fan Stage UP, Fan Stage DOWN, Fan Stage Loop
MV112LED 1 FunctionFunction of LED 1WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV113LED 2 FunctionFunction of LED 2WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV114LED 3 FunctionFunction of LED 3WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV115LED 4 FunctionFunction of LED 4WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV116LED 5 FunctionFunction of LED 5WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV117LED 6 FunctionFunction of LED 6WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV118LED 7 FunctionFunction of LED 7WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV119LED 8 FunctionFunction of LED 8WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV120LED 9 FunctionFunction of LED 9WriteBus Controlled, Occupancy, PI Controller Active, PI Controller Heating, PI Controller Cooling, Fan Stage 0, Fan Stage 1, Fan Stage 2, Fan Stage 3, Fan AUTO
MV121Input 1 FunctionFunction of digital input 1WriteNC Contact, NC Dewpoint, NC Window, NC Occupancy, NC PI Ctr. Auto/Off, NC PI Ctr. Heat/Cool, NO Contact, NO Dewpoint, NO Window, NO Occupancy, NO PI Ctr. Auto/Off, NO PI Ctr. Heat/Cool
MV122Input 2 FunctionFunction of digital input 2WriteNC Contact, NC Dewpoint, NC Window, NC Occupancy, NC PI Ctr. Auto/Off, NC PI Ctr. Heat/Cool, NO Contact, NO Dewpoint, NO Window, NO Occupancy, NO PI Ctr. Auto/Off, NO PI Ctr. Heat/Cool
MV123Input 3 FunctionFunction of digital input 3WriteNC Contact, NC Dewpoint, NC Window, NC Occupancy, NC PI Ctr. Auto/Off, NC PI Ctr. Heat/Cool, NO Contact, NO Dewpoint, NO Window, NO Occupancy, NO PI Ctr. Auto/Off, NO PI Ctr. Heat/Cool
MV124Input 4 FunctionFunction of digital input 4WriteNC Contact, NC Dewpoint, NC Window, NC Occupancy, NC PI Ctr. Auto/Off, NC PI Ctr. Heat/Cool, NO Contact, NO Dewpoint, NO Window, NO Occupancy, NO PI Ctr. Auto/Off, NO PI Ctr. Heat/Cool
MV125Input 1 Counter ModeCounting mode of input 1WriteEdge, Pulse
MV126Input 2 Counter ModeCounting mode of input 2WriteEdge, Pulse
MV127Input 3 Counter ModeCounting mode of input 3WriteEdge, Pulse
MV128Input 4 Counter ModeCounting mode of input 4WriteEdge, Pulse
MV129Number of Fan StagesFan stages and manual/automatic operationWrite0 (Fan OFF), 1 (manual), 2 (manual), 3 (manual), 0 (Fan OFF), 1 (automatic), 2 (automatic), 3 (automatic)
MV130Fan Stage after ResetFan stage after a restartWrite0 (Fan OFF), 1 (manual), 2 (manual), 3 (manual), automatic
MV131Min. Fan StageLowest fan stage selectableWrite0, 1, 2, 3
AO0Output 1 Value OverrideOverride output 1, 0-10 V; -1 = automaticVWrite
AO1Output 2 Value OverrideOverride output 2, 0-10 V; -1 = automaticVWrite
BO0LED 1LED 1 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
BO1LED 2LED 2 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
BO2LED 3LED 3 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
BO3LED 4LED 4 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
BO4LED 5LED 5 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
BO5LED 6LED 6 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
BO6LED 7LED 7 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
BO7LED 8LED 8 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
BO8LED 9LED 9 on/off (when set to bus controlled)WriteFalse=LED off, True=LED on
Object ID lookup: Thermokon WRF06/WRF07 RC BACnet point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRF06 RC / WRF07 RC BACnet MS/TP room controllers and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers

How many BACnet points does the Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers have?

This list has 138 BACnet objects: 16 analog inputs, 2 analog outputs, 30 analog values, 27 binary inputs, 9 binary outputs, 19 binary values, 1 device, 34 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers BACnet points are writable?

94 of the 138 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers BACnet documentation?

The source is Description for WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP, revision Rev. E, 30.01.2026, published free by Thermokon at https://www.thermokon.de/direct/alterra-base/mimes/get/e39d6620bf738dd3a.

What are the minimum BACnet points to integrate the Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers?

Start with BV 3 Occupancy Override (Occupancy command, 1 = occupied); BV 1 PI-Ctr. Enable (Enable the room controller); MV 0 PI-Ctr. Mode Override (Mode: off, heat, cool or automatic); AV 1 Base Setpoint (Base room setpoint); MV 1 Fan Stage (Fan stage 0-3 or automatic); AI 7 PI-Controller Mode (Current controller mode); AI 0 Temperature (Room temperature); AI 5 Setpoint Absolute (Active setpoint); AI 8 PI-Controller Y Heat (Heating demand, %); AI 9 PI-Controller Y Cool (Cooling demand, %).

How do I enable BMS control of the Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers?

PI-Ctr. Enable (BV 1) turns the built-in controller on; Occupancy Override (BV 3) sets occupied/unoccupied, and PI-Ctr. Mode Override (MV 0) sets off/heat/cool/automatic. In change-over operation (BV 112) the heat/cool mode must be given through MV 0.

Can the BMS supply sensor values to the Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers?

Energy hold-off (BV 0) and dew-point (BV 2) can be set from the BMS as well as from wired inputs. The outputs can be overridden with AO 0 and AO 1 (0-10 V); writing -1 returns them to automatic.

How do I check these points on the real WRF06 RC / WRF07 RC BACnet MS/TP room controllers?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermokon BACnet points lists

Source: Description for WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP · rev. Rev. E, 30.01.2026. Object names, instances and units are reproduced as published; descriptions are our own.