Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet points list
Updated 4 November 2026
NOVOS 7, NOVOS Touch and thanos EVO are touch-screen room operating units that share one BACnet MS/TP object list. They expose room climate (occupancy, ECO, setpoint, fan stage), up to eight lighting circuits, eight shading channels, eight scenes, display icons and up to four built-in sensors. Configuration is done with Thermokon's uConfig tool and sent to the unit as a file over BACnet.
This page lists 75 BACnet objects for the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.
- Manufacturer
- Thermokon
- Model
- NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units
- Equipment
- Room operating unit / room sensor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 75 (62 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Device Offset ID + MAC address
- Also known as
- NOVOS 7, NOVOS Touch, thanos EVO, NOVOS 7 RS485 BACnet, thanos EVO RS485 BACnet
Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.
BMS integration notes: Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units
Set the bus address and baud rate on the unit (or with the NOVOS app), load the configuration with uConfig, then map the room-climate block (occupancy, setpoint, fan stage) and the sensor AIs into the room controller. Light, shade and scene objects carry the user's button actions for the BMS to act on.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 100 | Occupancy | Room occupancy, settable by user or BMS | Write |
| BV 101 | ECO | ECO (energy-saving) mode | Write |
| AV 103 | Setpoint | Room setpoint; the BMS may overwrite it | Write |
| MV 105 | External Fan Stage | Fan stage written back by the BMS | Write |
| MI 104 | Internal Fan Stage | Fan stage chosen by the user | Read |
| AI 500 | Temperature | Room temperature | Read |
| AI 501 | Relative Humidity | Room humidity (rH variants) | Read |
| AI 505 | CO2 | Room CO2 (CO2 variants) | Read |
| BI 514 | Digital Input | Window or other contact, 1 = closed | Read |
Sensors & values from the BMS
AV 106 lets the BMS replace the room temperature shown on the home screen, and AV 509-512 show up to four BMS values in the monitoring menu.
Network setup
- Bus address 1-247; NOVOS 7 baud 9600-115200, NOVOS Touch/thanos EVO 4800-115200.
- Device instance = Device Offset ID (AV 4180) + MAC address.
- Configuration (circuits, scenes, setpoint limits) is written by uConfig as config.bin through BACnet file transfer (FILE 0) and stored in EEPROM.
Watch out for
- In 'Button' mode the light/shade AVs reset to 110 (no press) after they are read; 'Button (raw)' needs a fast bus or presses are missed.
- The State Message text is written into the Description property of BV 400, not its present value.
Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | x_xxxx BACnet MSTP | Device object; instance = Device Offset ID + MAC address | Read | |||
| BV | 425 | Device Restart | Restart the device | Write | 0=false, 1=true | |
| AV | 4180 | Device Offset ID | Offset added to the MAC address for the device instance | Write | ||
| MV | 4183 | COV Mode | COV notifications off, local or global broadcast | Write | 1=off, 2=Local, 3=Global | |
| FILE | 0 | config.bin | Configuration file transfer (uConfig) | Write | ||
| AV | 1113 | Service Countdown | Hours left until service is due | h | Read | |
| AV | 1114 | Calibration Countdown | Hours left until calibration is due | h | Read | |
| BVmin | 100 | Occupancy | Room occupancy | Write | 0=Unoccupied, 1=Occupied | |
| BVmin | 101 | ECO | ECO mode on/off | Write | 0=disabled, 1=enabled | |
| MV | 102 | ECO Colour | Colour of the ECO icon | Write | 1=transparent, 2=white, 3=black, 4=red, 5=green, 6=blue, 7=yellow | |
| AVmin | 103 | Setpoint | Setpoint set on the device; the BMS can overwrite it | °C | Write | |
| MImin | 104 | Internal Fan Stage | Fan stage set by the user | Read | 1=off, 2=Stage 1, 3=Stage 2, 4=Stage 3, 5=Stage 4, 6=Stage 5, 7=Auto | |
| MVmin | 105 | External Fan Stage | Fan stage written by the BMS (shows the auto stage) | Write | 1=off, 2=Stage 1, 3=Stage 2, 4=Stage 3, 5=Stage 4, 6=Stage 5, 7=AUTO, 8=AUTO off, 9=Auto Stage 1, 10=Auto Stage 2, 11=Auto Stage 3, 12=Auto Stage 4, 13=Auto Stage 5 | |
| AV | 106 | Overwrite Temp. Homescreen | Room temperature shown on the display, from the BMS | °C | Write | |
| BV | 0 | Light 1 | Lighting circuit 1 on/off | Write | 0=off, 1=on | |
| BV | 1 | Light 2 | Lighting circuit 2 on/off | Write | 0=off, 1=on | |
| BV | 2 | Light 3 | Lighting circuit 3 on/off | Write | 0=off, 1=on | |
| BV | 3 | Light 4 | Lighting circuit 4 on/off | Write | 0=off, 1=on | |
| BV | 4 | Light 5 | Lighting circuit 5 on/off | Write | 0=off, 1=on | |
| BV | 5 | Light 6 | Lighting circuit 6 on/off | Write | 0=off, 1=on | |
| BV | 6 | Light 7 | Lighting circuit 7 on/off | Write | 0=off, 1=on | |
| BV | 7 | Light 8 | Lighting circuit 8 on/off | Write | 0=off, 1=on | |
| BV | 8 | Scene 1 | Scene 1 | Write | 0=off, 1=on | |
| BV | 9 | Scene 2 | Scene 2 | Write | 0=off, 1=on | |
| BV | 10 | Scene 3 | Scene 3 | Write | 0=off, 1=on | |
| BV | 11 | Scene 4 | Scene 4 | Write | 0=off, 1=on | |
| BV | 12 | Scene 5 | Scene 5 | Write | 0=off, 1=on | |
| BV | 13 | Scene 6 | Scene 6 | Write | 0=off, 1=on | |
| BV | 14 | Scene 7 | Scene 7 | Write | 0=off, 1=on | |
| BV | 15 | Scene 8 | Scene 8 | Write | 0=off, 1=on | |
| BV | 16 | Show Icon Dewpoint | Show the dewpoint icon | Write | 0=false, 1=true | |
| BV | 17 | Show Icon Window open | Show the window open icon | Write | 0=false, 1=true | |
| BV | 22 | Show Icon Heating | Show the heating icon | Write | 0=false, 1=true | |
| BV | 23 | Show Icon Cooling | Show the cooling icon | Write | 0=false, 1=true | |
| BV | 24 | Show Icon Movement | Show the movement icon | Write | 0=false, 1=true | |
| BV | 26 | Show Icon Warning | Show the warning icon | Write | 0=false, 1=true | |
| BV | 400 | State Message | Show a status text (object description) on the home screen | Write | 0=off, 1=on | |
| BV | 424 | Display OFF | Switch the display off | Write | 0=false, 1=true | |
| AV | 200 | Value Light 1 | Dimming value or button action, light 1 | % | Write | |
| AV | 201 | Value Light 2 | Dimming value or button action, light 2 | % | Write | |
| AV | 202 | Value Light 3 | Dimming value or button action, light 3 | % | Write | |
| AV | 203 | Value Light 4 | Dimming value or button action, light 4 | % | Write | |
| AV | 204 | Value Light 5 | Dimming value or button action, light 5 | % | Write | |
| AV | 205 | Value Light 6 | Dimming value or button action, light 6 | % | Write | |
| AV | 206 | Value Light 7 | Dimming value or button action, light 7 | % | Write | |
| AV | 207 | Value Light 8 | Dimming value or button action, light 8 | % | Write | |
| AV | 300 | Value Shutter/Blind 1 | Position or button action, shade 1 | % | Write | |
| AV | 301 | Angle Blind 1 | Slat angle, blind 1 | ° | Write | |
| AV | 302 | Value Shutter/Blind 2 | Position or button action, shade 2 | % | Write | |
| AV | 303 | Angle Blind 2 | Slat angle, blind 2 | ° | Write | |
| AV | 304 | Value Shutter/Blind 3 | Position or button action, shade 3 | % | Write | |
| AV | 305 | Angle Blind 3 | Slat angle, blind 3 | ° | Write | |
| AV | 306 | Value Shutter/Blind 4 | Position or button action, shade 4 | % | Write | |
| AV | 307 | Angle Blind 4 | Slat angle, blind 4 | ° | Write | |
| AV | 308 | Value Shutter/Blind 5 | Position or button action, shade 5 | % | Write | |
| AV | 309 | Angle Blind 5 | Slat angle, blind 5 | ° | Write | |
| AV | 310 | Value Shutter/Blind 6 | Position or button action, shade 6 | % | Write | |
| AV | 311 | Angle Blind 6 | Slat angle, blind 6 | ° | Write | |
| AV | 312 | Value Shutter/Blind 7 | Position or button action, shade 7 | % | Write | |
| AV | 313 | Angle Blind 7 | Slat angle, blind 7 | ° | Write | |
| AV | 314 | Value Shutter/Blind 8 | Position or button action, shade 8 | % | Write | |
| AV | 315 | Angle Blind 8 | Slat angle, blind 8 | ° | Write | |
| AImin | 500 | Temperature | Room temperature | °C | Read | |
| AImin | 501 | Relative Humidity | Room relative humidity | % | Read | |
| AI | 502 | Absolute Humidity | Absolute humidity | g/m³ | Read | |
| AI | 503 | Enthalpy | Enthalpy | kJ/kg | Read | |
| AI | 504 | Dewpoint | Dew point | °C | Read | |
| AImin | 505 | CO2 | CO2 concentration | ppm | Read | |
| AI | 506 | VOC | VOC level | % | Read | |
| AI | 507 | CO2 VOC Mix | Combined CO2/VOC air quality index | % | Read | |
| AV | 509 | External 1 | Value from the BMS shown in the monitoring menu | Write | ||
| AV | 510 | External 2 | Value from the BMS shown in the monitoring menu | Write | ||
| AV | 511 | External 3 | Value from the BMS shown in the monitoring menu | Write | ||
| AV | 512 | External 4 | Value from the BMS shown in the monitoring menu | Write | ||
| BImin | 514 | Digital Input | Contact on terminal 7 | Read | 0=open, 1=closed |
No points match these filters.
Object ID lookup: Thermokon NOVOS 7 / thanos EVO BACnet point IDs by name
BV425Device RestartAV4180Device Offset IDMV4183COV ModeFILE0config.binAV1113Service CountdownAV1114Calibration CountdownBV100OccupancyBV101ECOMV102ECO ColourAV103SetpointMI104Internal Fan StageMV105External Fan StageAV106Overwrite Temp. HomescreenBV0Light 1BV1Light 2BV2Light 3BV3Light 4BV4Light 5BV5Light 6BV6Light 7BV7Light 8BV8Scene 1BV9Scene 2BV10Scene 3BV11Scene 4BV12Scene 5BV13Scene 6BV14Scene 7BV15Scene 8BV16Show Icon DewpointBV17Show Icon Window openBV22Show Icon HeatingBV23Show Icon CoolingBV24Show Icon MovementBV26Show Icon WarningBV400State MessageBV424Display OFFAV200Value Light 1AV201Value Light 2AV202Value Light 3AV203Value Light 4AV204Value Light 5AV205Value Light 6AV206Value Light 7AV207Value Light 8AV300Value Shutter/Blind 1AV301Angle Blind 1AV302Value Shutter/Blind 2AV303Angle Blind 2AV304Value Shutter/Blind 3AV305Angle Blind 3AV306Value Shutter/Blind 4AV307Angle Blind 4AV308Value Shutter/Blind 5AV309Angle Blind 5AV310Value Shutter/Blind 6AV311Angle Blind 6AV312Value Shutter/Blind 7AV313Angle Blind 7AV314Value Shutter/Blind 8AV315Angle Blind 8AI500TemperatureAI501Relative HumidityAI502Absolute HumidityAI503EnthalpyAI504DewpointAI505CO2AI506VOCAI507CO2 VOC MixAV509External 1AV510External 2AV511External 3AV512External 4BI514Digital Input
Integration notes
- Object list from the NOVOS 7 / NOVOS Touch / thanos EVO operating manual, rev A (13.07.2020), section 5 (pages 19-25). The section heading says 'Modbus Register-Specification' but the tables list BACnet objects. Object names are printed in square brackets; the brackets are dropped here.
- NOVOS Touch and thanos EVO are functionally identical and differ only in design.
- The Value Light and Value Shutter/Blind AVs carry 0-100 % or a button code (110 = no press, 111/112 = short/long up, 113/114 = short/long down, 115/116 = pressed up/down), depending on how the channel is configured in uConfig.
- Which sensor AIs are present depends on the variant (temperature, humidity, CO2, VOC). The manual has no access column; R/W here is inferred from the descriptions.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units
How many BACnet points does the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units have?
This list has 75 BACnet objects: 8 analog inputs, 33 analog values, 1 binary input, 27 binary values, 1 device, 1 file, 1 multi-state input, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet points are writable?
62 of the 75 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet documentation?
The source is Operating Manual NOVOS 7 / NOVOS Touch / thanos EVO - RS485 BACnet data point list, revision Rev. A, 13.07.2020, published free by Thermokon at https://www.thermokon.de/direct/alterra-base/mimes/get/3f7260a25eb0435a3.
What are the minimum BACnet points to integrate the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units?
Start with BV 100 Occupancy (Room occupancy, settable by user or BMS); BV 101 ECO (ECO (energy-saving) mode); AV 103 Setpoint (Room setpoint; the BMS may overwrite it); MV 105 External Fan Stage (Fan stage written back by the BMS); MI 104 Internal Fan Stage (Fan stage chosen by the user); AI 500 Temperature (Room temperature); AI 501 Relative Humidity (Room humidity (rH variants)); AI 505 CO2 (Room CO2 (CO2 variants)); BI 514 Digital Input (Window or other contact, 1 = closed).
Can the BMS supply sensor values to the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units?
AV 106 lets the BMS replace the room temperature shown on the home screen, and AV 509-512 show up to four BMS values in the monitoring menu.
How do I check these points on the real NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Thermokon BACnet points lists
- Room sensor / operating unit
Thermokon FTW04 BACnet MS/TP RS485 room humidity/temperature unit
Thermokon FTW04 BACnet MS/TP RS485 room units (temperature, humidity, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: FTW04, FTW04 BACnet, FTW04_BACnet, FTW04-RS485-BACnet - Room thermostat / fan coil controller
Thermokon JOY BACnet room thermostats / fan coil controllers (5DO, ECAO2DO, HCAO2DO, EC3AO, HC3AO)
Thermokon JOY wall thermostats with RS485 BACnet MS/TP for fan coils, heating/cooling valves and 6-way valves, in 230 V and 24 V versions with optional CO2 and humidity sensors.
Also known as: JOY FC5DO BACnet, JOY ECAO2DO BACnet, JOY HCAO2DO BACnet, JOY EC3AO BACnet, JOY HC3AO BACnet, JOY HC AO2DO 24V RS485 BACnet, JOY RS485 BACnet - Room operating unit / room sensor
Thermokon NOVOS 3 / NOVOS 5 RS485 BACnet room operating units
Thermokon NOVOS 3 and NOVOS 5 (LCD) wall units with RS485 BACnet MS/TP, in temperature, CO2, humidity and VOC sensor variants.
Also known as: NOVOS 3 RS485 BACnet, NOVOS 5 LCD RS485 BACnet, NOVOS 3 x, NOVOS 5 x, NOVOS 5 LCD - Duct / room sensor (temperature, humidity, CO2, VOC, pressure)
Thermokon USE-BACnet MS/TP option for Thermokon sensors (FTA+, LK+, DPA+, LI65+ ...)
Thermokon sensors fitted with the USE-BACnet MS/TP RS485 option board (FTA+, FTK+, LK+, DPA+, LI65+, LDF+, RDF+, WK02+ and their LCD versions).
Also known as: USE BACnet, USE-RS485 BACnet, FTA+ BACnet, FTK+ BACnet, LK+ CO2 BACnet, LK+ VOC BACnet, DPA+ BACnet, DPA+ Flow BACnet, LI65+ BACnet, LDF+ BACnet, RDF+ BACnet, WK02+ BACnet - Room sensor / operating unit
Thermokon WRF04 BACnet MS/TP RS485 room operating unit
Thermokon WRF04 BACnet MS/TP RS485 room units (temperature, optional setpoint, button, rotary switch, LED, 2 digital inputs, 2 analogue outputs).
Also known as: WRF04, WRF04 BACnet, WRF04_BACnet, WRF04-RS485-BACnet - Room sensor (CO2, VOC, temperature, humidity)
Thermokon WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors
Thermokon WRF06 AQ room air quality sensors (CO2, VOC, temperature, humidity variants) and FTW06 room humidity/temperature sensors with RS485 BACnet MS/TP.
Also known as: WRF06 AQ, WRF06 CO2, WRF06 CO2 Temp, WRF06 CO2 Temp_rH, WRF06 CO2+VOC, WRF06 VOC Temp, FTW06, WRF06 AQ BACnet MSTP - Room controller (fan coil, radiator, chilled ceiling)
Thermokon WRF06 RC / WRF07 RC BACnet MS/TP room controllers
Thermokon WRF06 RC and WRF07 RC wall-mounted room controllers with RS485 BACnet MS/TP, including the humidity (x rH) variants.
Also known as: WRF06 RC BACnet MS/TP, WRF06 RC (x) BACnet MS/TP, WRF07 RC (x) BACnet MS/TP, WRF07 RC, WRF06 RC, WRF07 BACnet MSTP - Room operating unit (buttons, LCD, setpoints) / room sensor
Thermokon WRF08 BACnet MS/TP RS485 room operating panel
Thermokon WRF08 room operating panels with LCD, up to 12 buttons, room temperature sensor and BACnet MS/TP over RS485.
Also known as: WRF08, WRF08 BACnet, WRF08 RS485 BACnet, Thermokon_WRF08_BACnet
Source: Operating Manual NOVOS 7 / NOVOS Touch / thanos EVO - RS485 BACnet data point list · rev. Rev. A, 13.07.2020. Object names, instances and units are reproduced as published; descriptions are our own.