Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet points list

Updated 4 November 2026

Short answer

NOVOS 7, NOVOS Touch and thanos EVO are touch-screen room operating units that share one BACnet MS/TP object list. They expose room climate (occupancy, ECO, setpoint, fan stage), up to eight lighting circuits, eight shading channels, eight scenes, display icons and up to four built-in sensors. Configuration is done with Thermokon's uConfig tool and sent to the unit as a file over BACnet.

This page lists 75 BACnet objects for the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermokon’s own free documentation, linked below.

Manufacturer
Thermokon
Model
NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units
Equipment
Room operating unit / room sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
75 (62 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Device Offset ID + MAC address
Also known as
NOVOS 7, NOVOS Touch, thanos EVO, NOVOS 7 RS485 BACnet, thanos EVO RS485 BACnet
Source document
Operating Manual NOVOS 7 / NOVOS Touch / thanos EVO - RS485 BACnet data point list · rev. Rev. A, 13.07.2020
Download CSV 75 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermokon’s current documentation and the live device before use. Not official Thermokon information. Terms of use.

BMS integration notes: Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units

Integration in brief

Set the bus address and baud rate on the unit (or with the NOVOS app), load the configuration with uConfig, then map the room-climate block (occupancy, setpoint, fan stage) and the sensor AIs into the room controller. Light, shade and scene objects carry the user's button actions for the BMS to act on.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 100OccupancyRoom occupancy, settable by user or BMSWrite
BV 101ECOECO (energy-saving) modeWrite
AV 103SetpointRoom setpoint; the BMS may overwrite itWrite
MV 105External Fan StageFan stage written back by the BMSWrite
MI 104Internal Fan StageFan stage chosen by the userRead
AI 500TemperatureRoom temperatureRead
AI 501Relative HumidityRoom humidity (rH variants)Read
AI 505CO2Room CO2 (CO2 variants)Read
BI 514Digital InputWindow or other contact, 1 = closedRead

Sensors & values from the BMS

AV 106 lets the BMS replace the room temperature shown on the home screen, and AV 509-512 show up to four BMS values in the monitoring menu.

Network setup

Watch out for

Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

75 of 75 shown
Type
Access
Show
Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet Points List
DescriptionStates
DEVx_xxxx BACnet MSTPDevice object; instance = Device Offset ID + MAC addressRead
BV425Device RestartRestart the deviceWrite0=false, 1=true
AV4180Device Offset IDOffset added to the MAC address for the device instanceWrite
MV4183COV ModeCOV notifications off, local or global broadcastWrite1=off, 2=Local, 3=Global
FILE0config.binConfiguration file transfer (uConfig)Write
AV1113Service CountdownHours left until service is duehRead
AV1114Calibration CountdownHours left until calibration is duehRead
BVmin100OccupancyRoom occupancyWrite0=Unoccupied, 1=Occupied
BVmin101ECOECO mode on/offWrite0=disabled, 1=enabled
MV102ECO ColourColour of the ECO iconWrite1=transparent, 2=white, 3=black, 4=red, 5=green, 6=blue, 7=yellow
AVmin103SetpointSetpoint set on the device; the BMS can overwrite it°CWrite
MImin104Internal Fan StageFan stage set by the userRead1=off, 2=Stage 1, 3=Stage 2, 4=Stage 3, 5=Stage 4, 6=Stage 5, 7=Auto
MVmin105External Fan StageFan stage written by the BMS (shows the auto stage)Write1=off, 2=Stage 1, 3=Stage 2, 4=Stage 3, 5=Stage 4, 6=Stage 5, 7=AUTO, 8=AUTO off, 9=Auto Stage 1, 10=Auto Stage 2, 11=Auto Stage 3, 12=Auto Stage 4, 13=Auto Stage 5
AV106Overwrite Temp. HomescreenRoom temperature shown on the display, from the BMS°CWrite
BV0Light 1Lighting circuit 1 on/offWrite0=off, 1=on
BV1Light 2Lighting circuit 2 on/offWrite0=off, 1=on
BV2Light 3Lighting circuit 3 on/offWrite0=off, 1=on
BV3Light 4Lighting circuit 4 on/offWrite0=off, 1=on
BV4Light 5Lighting circuit 5 on/offWrite0=off, 1=on
BV5Light 6Lighting circuit 6 on/offWrite0=off, 1=on
BV6Light 7Lighting circuit 7 on/offWrite0=off, 1=on
BV7Light 8Lighting circuit 8 on/offWrite0=off, 1=on
BV8Scene 1Scene 1Write0=off, 1=on
BV9Scene 2Scene 2Write0=off, 1=on
BV10Scene 3Scene 3Write0=off, 1=on
BV11Scene 4Scene 4Write0=off, 1=on
BV12Scene 5Scene 5Write0=off, 1=on
BV13Scene 6Scene 6Write0=off, 1=on
BV14Scene 7Scene 7Write0=off, 1=on
BV15Scene 8Scene 8Write0=off, 1=on
BV16Show Icon DewpointShow the dewpoint iconWrite0=false, 1=true
BV17Show Icon Window openShow the window open iconWrite0=false, 1=true
BV22Show Icon HeatingShow the heating iconWrite0=false, 1=true
BV23Show Icon CoolingShow the cooling iconWrite0=false, 1=true
BV24Show Icon MovementShow the movement iconWrite0=false, 1=true
BV26Show Icon WarningShow the warning iconWrite0=false, 1=true
BV400State MessageShow a status text (object description) on the home screenWrite0=off, 1=on
BV424Display OFFSwitch the display offWrite0=false, 1=true
AV200Value Light 1Dimming value or button action, light 1%Write
AV201Value Light 2Dimming value or button action, light 2%Write
AV202Value Light 3Dimming value or button action, light 3%Write
AV203Value Light 4Dimming value or button action, light 4%Write
AV204Value Light 5Dimming value or button action, light 5%Write
AV205Value Light 6Dimming value or button action, light 6%Write
AV206Value Light 7Dimming value or button action, light 7%Write
AV207Value Light 8Dimming value or button action, light 8%Write
AV300Value Shutter/Blind 1Position or button action, shade 1%Write
AV301Angle Blind 1Slat angle, blind 1°Write
AV302Value Shutter/Blind 2Position or button action, shade 2%Write
AV303Angle Blind 2Slat angle, blind 2°Write
AV304Value Shutter/Blind 3Position or button action, shade 3%Write
AV305Angle Blind 3Slat angle, blind 3°Write
AV306Value Shutter/Blind 4Position or button action, shade 4%Write
AV307Angle Blind 4Slat angle, blind 4°Write
AV308Value Shutter/Blind 5Position or button action, shade 5%Write
AV309Angle Blind 5Slat angle, blind 5°Write
AV310Value Shutter/Blind 6Position or button action, shade 6%Write
AV311Angle Blind 6Slat angle, blind 6°Write
AV312Value Shutter/Blind 7Position or button action, shade 7%Write
AV313Angle Blind 7Slat angle, blind 7°Write
AV314Value Shutter/Blind 8Position or button action, shade 8%Write
AV315Angle Blind 8Slat angle, blind 8°Write
AImin500TemperatureRoom temperature°CRead
AImin501Relative HumidityRoom relative humidity%Read
AI502Absolute HumidityAbsolute humidityg/m³Read
AI503EnthalpyEnthalpykJ/kgRead
AI504DewpointDew point°CRead
AImin505CO2CO2 concentrationppmRead
AI506VOCVOC level%Read
AI507CO2 VOC MixCombined CO2/VOC air quality index%Read
AV509External 1Value from the BMS shown in the monitoring menuWrite
AV510External 2Value from the BMS shown in the monitoring menuWrite
AV511External 3Value from the BMS shown in the monitoring menuWrite
AV512External 4Value from the BMS shown in the monitoring menuWrite
BImin514Digital InputContact on terminal 7Read0=open, 1=closed
Object ID lookup: Thermokon NOVOS 7 / thanos EVO BACnet point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units

How many BACnet points does the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units have?

This list has 75 BACnet objects: 8 analog inputs, 33 analog values, 1 binary input, 27 binary values, 1 device, 1 file, 1 multi-state input, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet points are writable?

62 of the 75 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units BACnet documentation?

The source is Operating Manual NOVOS 7 / NOVOS Touch / thanos EVO - RS485 BACnet data point list, revision Rev. A, 13.07.2020, published free by Thermokon at https://www.thermokon.de/direct/alterra-base/mimes/get/3f7260a25eb0435a3.

What are the minimum BACnet points to integrate the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units?

Start with BV 100 Occupancy (Room occupancy, settable by user or BMS); BV 101 ECO (ECO (energy-saving) mode); AV 103 Setpoint (Room setpoint; the BMS may overwrite it); MV 105 External Fan Stage (Fan stage written back by the BMS); MI 104 Internal Fan Stage (Fan stage chosen by the user); AI 500 Temperature (Room temperature); AI 501 Relative Humidity (Room humidity (rH variants)); AI 505 CO2 (Room CO2 (CO2 variants)); BI 514 Digital Input (Window or other contact, 1 = closed).

Can the BMS supply sensor values to the Thermokon NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units?

AV 106 lets the BMS replace the room temperature shown on the home screen, and AV 509-512 show up to four BMS values in the monitoring menu.

How do I check these points on the real NOVOS 7 / NOVOS Touch / thanos EVO RS485 BACnet room operating units?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermokon BACnet points lists

Source: Operating Manual NOVOS 7 / NOVOS Touch / thanos EVO - RS485 BACnet data point list · rev. Rev. A, 13.07.2020. Object names, instances and units are reproduced as published; descriptions are our own.