 "manufacturer": "Thermokon",
 "manufacturer_slug": "thermokon",
 "model": "WRF06 AQ / FTW06 RS485 BACnet MS/TP room sensors",
 "model_slug": "wrf06-aq-ftw06-bacnet-room-sensor",
 "aliases": [
  "WRF06 AQ",
  "WRF06 CO2",
  "WRF06 CO2 Temp",
  "WRF06 CO2 Temp_rH",
  "WRF06 CO2+VOC",
  "WRF06 VOC Temp",
  "FTW06",
  "WRF06 AQ BACnet MSTP"
 ],
 "equipment_type": "Room sensor (CO2, VOC, temperature, humidity)",
 "applies_to": "Thermokon WRF06 AQ room air quality sensors (CO2, VOC, temperature, humidity variants) and FTW06 room humidity/temperature sensors with RS485 BACnet MS/TP.",
 "summary": "WRF06 AQ and FTW06 are wall-mounted room sensors with BACnet MS/TP. The interface description lists 39 objects: temperature, humidity and derived values, CO2, VOC and CO2/VOC mix, offsets, scaling limits, unit system and the traffic-light LED settings.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "1.1",
 "default_device_instance": "Offset Device ID (AV 46) + MAC address",
 "access_inferred": false,
 "notes": [
  "The description gives each object an ID, access and description but no object name; the description is used as the name here.",
  "Which measured values exist depends on the variant (the document has a table per type).",
  "Units follow AV 38 (1 = SI, 2 = Imperial); SI units are shown.",
  "Not the WRF06 RC room controller, which has its own list."
 ],
 "source": {
  "title": "Interface description WRF06 AQ / FTW06 BACnet MS/TP",
  "doc_number": null,
  "revision_date": "Rev. A, 04.03.2019",
  "url": "https://www.thermokon.de/downloads/Software/Schnittstellenbeschreibung/BACnet/WRF06_AQ_FTW06-RS485_BACnet_InterfaceDescription.zip"
 },
 "points": [
  {
   "type": "AV",
   "instance": 38,
   "name": "Unit system",
   "description": "",
   "units": "",
   "access": "W",
   "states": "1=SI, 2=Imperial"
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Relative humidity",
   "description": "",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "CO2",
   "description": "",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "VOC",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "CO2 VOC Mix",
   "description": "",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "Temperature",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Absolute humidity",
   "description": "",
   "units": "g/m³",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Enthalpy",
   "description": "",
   "units": "kJ/kg",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Dew point",
   "description": "",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Offset relative humidity",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Offset CO2",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Offset VOC",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Offset temperature",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Relative humidity lower limit",
   "description": "",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Relative humidity upper limit",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "CO2 lower limit",
   "description": "",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "CO2 upper limit",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "VOC lower limit",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "VOC upper limit",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "CO2 VOC Mix lower limit",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "CO2 VOC Mix upper limit",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Temperature lower limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Temperature upper limit",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Absolute humidity lower limit",
   "description": "",
   "units": "g/m³",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Absolute humidity upper limit",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Enthalpy lower limit",
   "description": "",
   "units": "kJ/kg",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Enthalpy upper limit",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Dew point lower limit",
   "description": "",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Dew point upper limit",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "Percentage of CO2 sensor value in CO2 VOC Mix signal",
   "description": "",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "Offset Device ID",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "Unconfirmed COV",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=not active, 1=active"
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "Reset to default",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "Channel assignment for TLF",
   "description": "Available sensor values depend on the type",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "Traffic light function LED range 1",
   "description": "",
   "units": "",
   "access": "W",
   "states": "0=LED OFF, 1=LED green, 2=LED yellow, 3=LED red"
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "Traffic light function LED range 2",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "Traffic light function LED range 3",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "Traffic light function threshold Range 1→2",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "Traffic light function threshold Range 2→3",
   "description": "",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "integration": {
  "summary": "Read AI 0 temperature, AI 1 humidity, AI 5 CO2 and AI 6 VOC (as fitted). The rest are calibration and display settings.",
  "minimum_points": [
   {
    "ref": "AI 0",
    "name": "Temperature",
    "why": "Room temperature"
   },
   {
    "ref": "AI 1",
    "name": "Relative humidity",
    "why": "Room relative humidity"
   },
   {
    "ref": "AI 5",
    "name": "CO2",
    "why": "Room CO2, ppm"
   },
   {
    "ref": "AI 6",
    "name": "VOC",
    "why": "Room VOC, %"
   },
   {
    "ref": "AI 7",
    "name": "CO2 VOC Mix",
    "why": "Combined CO2/VOC air quality, %"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "MAC address 1-127 and baud rate (9600, 19200, 38400, 76800) are set on DIP switches; 8N1 framing.",
   "Device ID = Offset Device ID (AV 46) + MAC address."
  ],
  "gotchas": [
   "AV 48 = 9999 restores factory settings."
  ]
 },
 "page": "https://easybacnet.com/bacnet-points-lists/thermokon/wrf06-aq-ftw06-bacnet-room-sensor",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}