- Home
- BACnet points lists
- Daikin
- DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit
Zoning system / zone thermostat BACnet interface · BACnet points list
Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet points list
Updated 4 November 2026
The DZK BACnet Interface plugs onto the DZK main control board and exposes the zoning system on BACnet IP (Ethernet or Wi-Fi) or BACnet MS/TP. The object list is fixed for six zones: per-zone on/off, heat and cool setpoints, room temperature, humidity, demands and damper step, plus the system mode, user mode and indoor unit status. One interface is needed per DZK system.
This page lists 86 BACnet objects for the Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.
- Manufacturer
- Daikin
- Model
- DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit
- Equipment
- Zoning system / zone thermostat BACnet interface
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 86 (26 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1000
- Also known as
- DZK-BACNET-HUB4, DZK-4, Daikin Zoning Kit BACnet, DZK BACnet Interface
Reference only, provided as-is: verify against Daikin’s current documentation and the live device before use. Not official Daikin information. Terms of use.
BMS integration notes: Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit
Set BACnet IP or MS/TP and the device ID in the configuration app, then use DZK operation mode (MO 0) and user mode (MO 1) for the system, and Zx ON/OFF plus the zone heat and cool setpoints per zone. Read zone temperatures, IU status, IU speed and the error objects for monitoring.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MO 1 | DZK user mode | 1 stop, 2 comfort, 3 unoccupied, 5 eco, 6 vacation | Write |
| MO 0 | DZK operation mode | 1 auto, 2 cool, 3 heat, 4 dry, 5 emergency heat | Write |
| BV 3 | Z1 ON/OFF | Zone 1 on/off (repeat for zones 2-6) | Write |
| AV 1 | Z1 Heat Set point | Zone 1 heating setpoint | Write |
| AV 2 | Z1 Cool Set point | Zone 1 cooling setpoint | Write |
| BI 0 | IU Status ON/OFF | Indoor unit running | Read |
| AI 0 | Z1 Room Temperature | Zone 1 room temperature | Read |
| MI 0 | IU speed | Indoor unit fan step: low, medium, high | Read |
| MI 1 | IU errors | Indoor unit error; hex value = Daikin code | Read |
| MI 2 | DZK error | Zoning system error (bus, interface, P1P2) | Read |
Network setup
- BACnet IP defaults: device ID 1000, UDP port 47808, DHCP (static default 192.168.0.100).
- BACnet MS/TP: MAC 0-127, device ID 0-4194302 and baud rate are set in the app; select the MS/TP integration port.
- One DZK BACnet interface per DZK control board.
Watch out for
- In VRV heat pump systems the operating mode of a DZK on a slave indoor unit can be limited by the master indoor unit's mode.
- The DZK address and group address (AV 13, 14) are learned at indoor unit start-up; if the DZK powers up after the indoor unit they may need a refresh from the controller.
- IU Set Point (AV 0) is calculated by the zoning system and is read only; change the zone setpoints instead.
Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 0 | IU Status ON/OFF | Indoor unit on/off status | Read | 0 = Deactivated, 1 = Activated | |
| BI | 1 | DZK system input alarm | System alarm input | Read | 0 = Deactivated, 1 = Activated | |
| BV | 0 | DZK Global Fan | Global ventilation status | Read | 0 = Deactivated, 1 = Activated | |
| BV | 1 | DZK Aux Heat1 | Auxiliary heat stage 1 status | Read | 0 = Deactivated, 1 = Activated | |
| BV | 2 | DZK Aux Heat2 | Auxiliary heat stage 2 status | Read | 0 = Deactivated, 1 = Activated | |
| BVmin | 3 | Z1 ON/OFF | Zone 1 on/off | Write | 0 = Off, 1 = On | |
| BV | 4 | Z1 Local Ventilation | Zone 1 local ventilation enable | Write | 0 = Disable, 1 = Enable | |
| BV | 5 | Z1 Vacation override | Zone 1 vacation override timer active | Read | 0 = Disable, 1 = Enable | |
| BV | 6 | Z1 Unoccupied override | Zone 1 unoccupied override timer active | Read | 0 = Deactivated, 1 = Activated | |
| BV | 7 | Z2 ON/OFF | Zone 2 on/off | Write | 0 = Off, 1 = On | |
| BV | 8 | Z2 Local ventilation | Zone 2 local ventilation enable | Write | 0 = Disable, 1 = Enable | |
| BV | 9 | Z2 Vacation override | Zone 2 vacation override timer active | Read | 0 = Disable, 1 = Enable | |
| BV | 10 | Z2 Unoccupied override | Zone 2 unoccupied override timer active | Read | 0 = Deactivated, 1 = Activated | |
| BV | 11 | Z3 ON/OFF | Zone 3 on/off | Write | 0 = Off, 1 = On | |
| BV | 12 | Z3 Local ventilation | Zone 3 local ventilation enable | Write | 0 = Disable, 1 = Enable | |
| BV | 13 | Z3 Vacation override | Zone 3 vacation override timer active | Read | 0 = Disable, 1 = Enable | |
| BV | 14 | Z3 Unoccupied override | Zone 3 unoccupied override timer active | Read | 0 = Deactivated, 1 = Activated | |
| BV | 15 | Z4 ON/OFF | Zone 4 on/off | Write | 0 = Off, 1 = On | |
| BV | 16 | Z4 Local ventilation | Zone 4 local ventilation enable | Write | 0 = Disable, 1 = Enable | |
| BV | 17 | Z4 Vacation override | Zone 4 vacation override timer active | Read | 0 = Disable, 1 = Enable | |
| BV | 18 | Z4 Unoccupied override | Zone 4 unoccupied override timer active | Read | 0 = Deactivated, 1 = Activated | |
| BV | 19 | Z5 ON/OFF | Zone 5 on/off | Write | 0 = Off, 1 = On | |
| BV | 20 | Z5 Local ventilation | Zone 5 local ventilation enable | Write | 0 = Disable, 1 = Enable | |
| BV | 21 | Z5 Vacation override | Zone 5 vacation override timer active | Read | 0 = Disable, 1 = Enable | |
| BV | 22 | Z5 Unoccupied override | Zone 5 unoccupied override timer active | Read | 0 = Deactivated, 1 = Activated | |
| BV | 23 | Z6 ON/OFF | Zone 6 on/off | Write | 0 = Off, 1 = On | |
| BV | 24 | Z6 Local ventilation | Zone 6 local ventilation enable | Write | 0 = Disable, 1 = Enable | |
| BV | 25 | Z6 Vacation override | Zone 6 vacation override timer active | Read | 0 = Disable, 1 = Enable | |
| BV | 26 | Z6 Unoccupied override | Zone 6 unoccupied override timer active | Read | 0 = Deactivated, 1 = Activated | |
| BV | 27 | DZK/BACnet Interface communication error | Interface lost contact with DZK control board | Read | 0 = Deactivated, 1 = Activated | |
| AImin | 0 | Z1 Room Temperature | Zone 1 room temperature, 50-95 °F (10-35 °C) | °F/°C | Read | |
| AI | 1 | Z2 Room Temperature | Zone 2 room temperature, 50-95 °F (10-35 °C) | °F/°C | Read | |
| AI | 2 | Z3 Room Temperature | Zone 3 room temperature, 50-95 °F (10-35 °C) | °F/°C | Read | |
| AI | 3 | Z4 Room Temperature | Zone 4 room temperature, 50-95 °F (10-35 °C) | °F/°C | Read | |
| AI | 4 | Z5 Room Temperature | Zone 5 room temperature, 50-95 °F (10-35 °C) | °F/°C | Read | |
| AI | 5 | Z6 Room Temperature | Zone 6 room temperature, 50-95 °F (10-35 °C) | °F/°C | Read | |
| AV | 0 | IU Set Point | Setpoint the zoning system sends to the indoor unit, 64-86 °F | °F/°C | Read | |
| AVmin | 1 | Z1 Heat Set point | Zone 1 heating setpoint, 59-86 °F (15-30 °C) | °F/°C | Write | |
| AVmin | 2 | Z1 Cool Set point | Zone 1 cooling setpoint, 64-86 °F (18-30 °C) | °F/°C | Write | |
| AV | 3 | Z2 Heat Set point | Zone 2 heating setpoint, 59-86 °F (15-30 °C) | °F/°C | Write | |
| AV | 4 | Z2 Cool Set point | Zone 2 cooling setpoint, 64-86 °F (18-30 °C) | °F/°C | Write | |
| AV | 5 | Z3 Heat Set point | Zone 3 heating setpoint, 59-86 °F (15-30 °C) | °F/°C | Write | |
| AV | 6 | Z3 Cool Set point | Zone 3 cooling setpoint, 64-86 °F (18-30 °C) | °F/°C | Write | |
| AV | 7 | Z4 Heat Set point | Zone 4 heating setpoint, 59-86 °F (15-30 °C) | °F/°C | Write | |
| AV | 8 | Z4 Cool Set point | Zone 4 cooling setpoint, 64-86 °F (18-30 °C) | °F/°C | Write | |
| AV | 9 | Z5 Heat Set point | Zone 5 heating setpoint, 59-86 °F (15-30 °C) | °F/°C | Write | |
| AV | 10 | Z5 Cool Set point | Zone 5 cooling setpoint, 64-86 °F (18-30 °C) | °F/°C | Write | |
| AV | 11 | Z6 Heat Set point | Zone 6 heating setpoint, 59-86 °F (15-30 °C) | °F/°C | Write | |
| AV | 12 | Z6 Cool Set point | Zone 6 cooling setpoint, 64-86 °F (18-30 °C) | °F/°C | Write | |
| AV | 13 | DZK address (DK AirNet address) | Indoor unit DIII AirNet address, 0-255 | Read | ||
| AV | 14 | DZK group address (DK group address) | Indoor unit group address, 0-255 | Read | ||
| AV | 15 | Z1 cooling demand (%) | Zone 1 cooling demand | % | Read | |
| AV | 16 | Z1 heating demand (%) | Zone 1 heating demand | % | Read | |
| AV | 17 | Z1 aux heating demand (%) | Zone 1 auxiliary heating demand | % | Read | |
| AV | 18 | Z2 cooling demand (%) | Zone 2 cooling demand | % | Read | |
| AV | 19 | Z2 heating demand (%) | Zone 2 heating demand | % | Read | |
| AV | 20 | Z2 aux heating demand (%) | Zone 2 auxiliary heating demand | % | Read | |
| AV | 21 | Z3 cooling demand (%) | Zone 3 cooling demand | % | Read | |
| AV | 22 | Z3 heating demand (%) | Zone 3 heating demand | % | Read | |
| AV | 23 | Z3 aux heating demand (%) | Zone 3 auxiliary heating demand | % | Read | |
| AV | 24 | Z4 cooling demand (%) | Zone 4 cooling demand | % | Read | |
| AV | 25 | Z4 heating demand (%) | Zone 4 heating demand | % | Read | |
| AV | 26 | Z4 aux heating demand (%) | Zone 4 auxiliary heating demand | % | Read | |
| AV | 27 | Z5 cooling demand (%) | Zone 5 cooling demand | % | Read | |
| AV | 28 | Z5 heating demand (%) | Zone 5 heating demand | % | Read | |
| AV | 29 | Z5 aux heating demand (%) | Zone 5 auxiliary heating demand | % | Read | |
| AV | 30 | Z6 cooling demand (%) | Zone 6 cooling demand | % | Read | |
| AV | 31 | Z6 heating demand (%) | Zone 6 heating demand | % | Read | |
| AV | 32 | Z6 aux heating demand (%) | Zone 6 auxiliary heating demand | % | Read | |
| AV | 33 | Z1 humidity | Zone 1 relative humidity | % | Read | |
| AV | 34 | Z2 humidity | Zone 2 relative humidity | % | Read | |
| AV | 35 | Z3 humidity | Zone 3 relative humidity | % | Read | |
| AV | 36 | Z4 humidity | Zone 4 relative humidity | % | Read | |
| AV | 37 | Z5 humidity | Zone 5 relative humidity | % | Read | |
| AV | 38 | Z6 humidity | Zone 6 relative humidity | % | Read | |
| MImin | 0 | IU speed | Indoor unit fan speed step | Read | 1 = Speed Low, 2 = Speed Medium, 3 = Speed High (number of speeds depends on IU model) | |
| MImin | 1 | IU errors | Indoor unit error; value in hex gives the Daikin malfunction code | Read | ||
| MImin | 2 | DZK error | Zoning system error | Read | 1 = Error 9: DZK internal bus fault, 2 = Error 10: BACnet interface board fault, 3 = Error 11: P1P2 communication error | |
| MOmin | 0 | DZK operation mode | System operating mode | Write | 1 = Auto, 2 = Cold, 3 = Heat, 4 = Dry, 5 = Emergency heat | |
| MOmin | 1 | DZK user mode | System user mode | Write | 1 = Stop, 2 = Comfort, 3 = Unoccupied, 4 = Night time, 5 = Eco, 6 = Vacation | |
| MV | 0 | Z1 opening step damper | Zone 1 modulating damper step | Read | 1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100% | |
| MV | 1 | Z2 opening step damper | Zone 2 modulating damper step | Read | 1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100% | |
| MV | 2 | Z3 opening step damper | Zone 3 modulating damper step | Read | 1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100% | |
| MV | 3 | Z4 opening step damper | Zone 4 modulating damper step | Read | 1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100% | |
| MV | 4 | Z5 opening step damper | Zone 5 modulating damper step | Read | 1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100% | |
| MV | 5 | Z6 opening step damper | Zone 6 modulating damper step | Read | 1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100% |
No points match these filters.
Object ID lookup: Daikin DZK BACnet HUB4 point IDs by name
BI0IU Status ON/OFFBI1DZK system input alarmBV0DZK Global FanBV1DZK Aux Heat1BV2DZK Aux Heat2BV3Z1 ON/OFFBV4Z1 Local VentilationBV5Z1 Vacation overrideBV6Z1 Unoccupied overrideBV7Z2 ON/OFFBV8Z2 Local ventilationBV9Z2 Vacation overrideBV10Z2 Unoccupied overrideBV11Z3 ON/OFFBV12Z3 Local ventilationBV13Z3 Vacation overrideBV14Z3 Unoccupied overrideBV15Z4 ON/OFFBV16Z4 Local ventilationBV17Z4 Vacation overrideBV18Z4 Unoccupied overrideBV19Z5 ON/OFFBV20Z5 Local ventilationBV21Z5 Vacation overrideBV22Z5 Unoccupied overrideBV23Z6 ON/OFFBV24Z6 Local ventilationBV25Z6 Vacation overrideBV26Z6 Unoccupied overrideBV27DZK/BACnet Interface communication errorAI0Z1 Room TemperatureAI1Z2 Room TemperatureAI2Z3 Room TemperatureAI3Z4 Room TemperatureAI4Z5 Room TemperatureAI5Z6 Room TemperatureAV0IU Set PointAV1Z1 Heat Set pointAV2Z1 Cool Set pointAV3Z2 Heat Set pointAV4Z2 Cool Set pointAV5Z3 Heat Set pointAV6Z3 Cool Set pointAV7Z4 Heat Set pointAV8Z4 Cool Set pointAV9Z5 Heat Set pointAV10Z5 Cool Set pointAV11Z6 Heat Set pointAV12Z6 Cool Set pointAV13DZK address (DK AirNet address)AV14DZK group address (DK group address)AV15Z1 cooling demand (%)AV16Z1 heating demand (%)AV17Z1 aux heating demand (%)AV18Z2 cooling demand (%)AV19Z2 heating demand (%)AV20Z2 aux heating demand (%)AV21Z3 cooling demand (%)AV22Z3 heating demand (%)AV23Z3 aux heating demand (%)AV24Z4 cooling demand (%)AV25Z4 heating demand (%)AV26Z4 aux heating demand (%)AV27Z5 cooling demand (%)AV28Z5 heating demand (%)AV29Z5 aux heating demand (%)AV30Z6 cooling demand (%)AV31Z6 heating demand (%)AV32Z6 aux heating demand (%)AV33Z1 humidityAV34Z2 humidityAV35Z3 humidityAV36Z4 humidityAV37Z5 humidityAV38Z6 humidityMI0IU speedMI1IU errorsMI2DZK errorMO0DZK operation modeMO1DZK user modeMV0Z1 opening step damperMV1Z2 opening step damperMV2Z3 opening step damperMV3Z4 opening step damperMV4Z5 opening step damperMV5Z6 opening step damper
Integration notes
- Objects for zones that do not exist report Out_Of_Service TRUE; only use values where Out_Of_Service is FALSE.
- Z1 local ventilation is printed 'Z1 Local Ventilation'; zones 2-6 use 'Local ventilation'.
- Temperature ranges are printed in both °F and °C; the unit follows the system setting.
- IU errors (MI 1): convert the value to hex 0xXY, row = X-1, column = Y, then look up the Daikin malfunction code table in the manual.
- The DZK error states are printed as display codes 1-3 mapping to errors 9, 10 and 11; the detailed text also lists 0 for normal operation.
- Values are refreshed every second; COV subscriptions are supported.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit
How many BACnet points does the Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit have?
This list has 86 BACnet objects: 6 analog inputs, 39 analog values, 2 binary inputs, 28 binary values, 3 multi-state inputs, 2 multi-state outputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet points are writable?
26 of the 86 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet documentation?
The source is DZK-4 Integration manual (DZK BACnet Interface), revision Rev. 1, published free by Daikin at https://daikincomfort.com/docs/default-source/dzk-zoning-kit/um-dzk-bacnet-hub4.pdf.
What are the minimum BACnet points to integrate the Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit?
Start with MO 1 DZK user mode (1 stop, 2 comfort, 3 unoccupied, 5 eco, 6 vacation); MO 0 DZK operation mode (1 auto, 2 cool, 3 heat, 4 dry, 5 emergency heat); BV 3 Z1 ON/OFF (Zone 1 on/off (repeat for zones 2-6)); AV 1 Z1 Heat Set point (Zone 1 heating setpoint); AV 2 Z1 Cool Set point (Zone 1 cooling setpoint); BI 0 IU Status ON/OFF (Indoor unit running); AI 0 Z1 Room Temperature (Zone 1 room temperature); MI 0 IU speed (Indoor unit fan step: low, medium, high); MI 1 IU errors (Indoor unit error; hex value = Daikin code); MI 2 DZK error (Zoning system error (bus, interface, P1P2)).
How do I check these points on the real DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Daikin BACnet points lists
- Networked room thermostat
Daikin AppStat BACnet Thermostat (DAPPS)
Daikin light commercial rooftop units and heat pumps controlled by the BACnet AppStat thermostat.
Also known as: DAPPS, AppStat, BACnet AppStat, Daikin BACnet thermostat, 250803, DG-DAPPS - Rooftop unit controller (light commercial packaged units and heat pumps)
Daikin iLINQ DDC Controller (BACnet MS/TP and BACnet IP)
Daikin light commercial packaged rooftop units (AC with electric or gas heat, or heat pump) fitted with the iLINQ DDC controller.
Also known as: iLINQ, Daikin iLINQ, BDG-ILINQA, iLINQ DDC controller - Split / VRF indoor unit BACnet interface
Daikin DKN Plus Interface AZAI6WSPDKC (BACnet MS/TP)
One Daikin residential, Sky Air or VRV indoor unit connected through a DKN Plus Interface (AZAI6WSPDKC).
Also known as: AZAI6WSPDKC, DKN Plus, DKN Cloud NA, DKN Wi-Fi controller, Daikin DKN Plus BACnet - VRV BACnet gateway
Daikin DMS502B71 Interface for use in BACnet
Daikin VRV and ductless indoor units and ERV (VAM) units on up to four DIII-Net lines (256 groups).
Also known as: DMS502B71, DAM411B51, D-BACS, Daikin VRV BACnet interface, BACnet Interface, EDUS72-749 - VRV BACnet gateway (iTM option)
Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects
VRV and ductless indoor unit groups managed by a Daikin intelligent Touch Manager with the DCM014A51 BACnet server option.
Also known as: DCM014A51, iTM BACnet, intelligent Touch Manager, DCM601A71, DCM601B71, iTM BACnet Server Gateway - VRV BACnet gateway (iTM option)
Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects
VRV outdoor units (main, sub-1 and sub-2 modules) monitored through an iTM with the DCM014A51 BACnet server option.
Also known as: DCM014A51, iTM BACnet outdoor unit, intelligent Touch Manager, DCM601A71, DCM601B71
Source: DZK-4 Integration manual (DZK BACnet Interface) · rev. Rev. 1. Object names, instances and units are reproduced as published; descriptions are our own.