Zoning system / zone thermostat BACnet interface · BACnet points list

Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet points list

Updated 4 November 2026

Short answer

The DZK BACnet Interface plugs onto the DZK main control board and exposes the zoning system on BACnet IP (Ethernet or Wi-Fi) or BACnet MS/TP. The object list is fixed for six zones: per-zone on/off, heat and cool setpoints, room temperature, humidity, demands and damper step, plus the system mode, user mode and indoor unit status. One interface is needed per DZK system.

This page lists 86 BACnet objects for the Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.

Manufacturer
Daikin
Model
DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit
Equipment
Zoning system / zone thermostat BACnet interface
Equipment type
Thermostats, sensors & meters
BACnet objects
86 (26 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1000
Also known as
DZK-BACNET-HUB4, DZK-4, Daikin Zoning Kit BACnet, DZK BACnet Interface
Source document
DZK-4 Integration manual (DZK BACnet Interface) · rev. Rev. 1
Download CSV 86 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Daikin’s current documentation and the live device before use. Not official Daikin information. Terms of use.

BMS integration notes: Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit

Integration in brief

Set BACnet IP or MS/TP and the device ID in the configuration app, then use DZK operation mode (MO 0) and user mode (MO 1) for the system, and Zx ON/OFF plus the zone heat and cool setpoints per zone. Read zone temperatures, IU status, IU speed and the error objects for monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 1DZK user mode1 stop, 2 comfort, 3 unoccupied, 5 eco, 6 vacationWrite
MO 0DZK operation mode1 auto, 2 cool, 3 heat, 4 dry, 5 emergency heatWrite
BV 3Z1 ON/OFFZone 1 on/off (repeat for zones 2-6)Write
AV 1Z1 Heat Set pointZone 1 heating setpointWrite
AV 2Z1 Cool Set pointZone 1 cooling setpointWrite
BI 0IU Status ON/OFFIndoor unit runningRead
AI 0Z1 Room TemperatureZone 1 room temperatureRead
MI 0IU speedIndoor unit fan step: low, medium, highRead
MI 1IU errorsIndoor unit error; hex value = Daikin codeRead
MI 2DZK errorZoning system error (bus, interface, P1P2)Read

Network setup

Watch out for

Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

86 of 86 shown
Type
Access
Show
Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet Points List
DescriptionStates
BImin0IU Status ON/OFFIndoor unit on/off statusRead0 = Deactivated, 1 = Activated
BI1DZK system input alarmSystem alarm inputRead0 = Deactivated, 1 = Activated
BV0DZK Global FanGlobal ventilation statusRead0 = Deactivated, 1 = Activated
BV1DZK Aux Heat1Auxiliary heat stage 1 statusRead0 = Deactivated, 1 = Activated
BV2DZK Aux Heat2Auxiliary heat stage 2 statusRead0 = Deactivated, 1 = Activated
BVmin3Z1 ON/OFFZone 1 on/offWrite0 = Off, 1 = On
BV4Z1 Local VentilationZone 1 local ventilation enableWrite0 = Disable, 1 = Enable
BV5Z1 Vacation overrideZone 1 vacation override timer activeRead0 = Disable, 1 = Enable
BV6Z1 Unoccupied overrideZone 1 unoccupied override timer activeRead0 = Deactivated, 1 = Activated
BV7Z2 ON/OFFZone 2 on/offWrite0 = Off, 1 = On
BV8Z2 Local ventilationZone 2 local ventilation enableWrite0 = Disable, 1 = Enable
BV9Z2 Vacation overrideZone 2 vacation override timer activeRead0 = Disable, 1 = Enable
BV10Z2 Unoccupied overrideZone 2 unoccupied override timer activeRead0 = Deactivated, 1 = Activated
BV11Z3 ON/OFFZone 3 on/offWrite0 = Off, 1 = On
BV12Z3 Local ventilationZone 3 local ventilation enableWrite0 = Disable, 1 = Enable
BV13Z3 Vacation overrideZone 3 vacation override timer activeRead0 = Disable, 1 = Enable
BV14Z3 Unoccupied overrideZone 3 unoccupied override timer activeRead0 = Deactivated, 1 = Activated
BV15Z4 ON/OFFZone 4 on/offWrite0 = Off, 1 = On
BV16Z4 Local ventilationZone 4 local ventilation enableWrite0 = Disable, 1 = Enable
BV17Z4 Vacation overrideZone 4 vacation override timer activeRead0 = Disable, 1 = Enable
BV18Z4 Unoccupied overrideZone 4 unoccupied override timer activeRead0 = Deactivated, 1 = Activated
BV19Z5 ON/OFFZone 5 on/offWrite0 = Off, 1 = On
BV20Z5 Local ventilationZone 5 local ventilation enableWrite0 = Disable, 1 = Enable
BV21Z5 Vacation overrideZone 5 vacation override timer activeRead0 = Disable, 1 = Enable
BV22Z5 Unoccupied overrideZone 5 unoccupied override timer activeRead0 = Deactivated, 1 = Activated
BV23Z6 ON/OFFZone 6 on/offWrite0 = Off, 1 = On
BV24Z6 Local ventilationZone 6 local ventilation enableWrite0 = Disable, 1 = Enable
BV25Z6 Vacation overrideZone 6 vacation override timer activeRead0 = Disable, 1 = Enable
BV26Z6 Unoccupied overrideZone 6 unoccupied override timer activeRead0 = Deactivated, 1 = Activated
BV27DZK/BACnet Interface communication errorInterface lost contact with DZK control boardRead0 = Deactivated, 1 = Activated
AImin0Z1 Room TemperatureZone 1 room temperature, 50-95 °F (10-35 °C)°F/°CRead
AI1Z2 Room TemperatureZone 2 room temperature, 50-95 °F (10-35 °C)°F/°CRead
AI2Z3 Room TemperatureZone 3 room temperature, 50-95 °F (10-35 °C)°F/°CRead
AI3Z4 Room TemperatureZone 4 room temperature, 50-95 °F (10-35 °C)°F/°CRead
AI4Z5 Room TemperatureZone 5 room temperature, 50-95 °F (10-35 °C)°F/°CRead
AI5Z6 Room TemperatureZone 6 room temperature, 50-95 °F (10-35 °C)°F/°CRead
AV0IU Set PointSetpoint the zoning system sends to the indoor unit, 64-86 °F°F/°CRead
AVmin1Z1 Heat Set pointZone 1 heating setpoint, 59-86 °F (15-30 °C)°F/°CWrite
AVmin2Z1 Cool Set pointZone 1 cooling setpoint, 64-86 °F (18-30 °C)°F/°CWrite
AV3Z2 Heat Set pointZone 2 heating setpoint, 59-86 °F (15-30 °C)°F/°CWrite
AV4Z2 Cool Set pointZone 2 cooling setpoint, 64-86 °F (18-30 °C)°F/°CWrite
AV5Z3 Heat Set pointZone 3 heating setpoint, 59-86 °F (15-30 °C)°F/°CWrite
AV6Z3 Cool Set pointZone 3 cooling setpoint, 64-86 °F (18-30 °C)°F/°CWrite
AV7Z4 Heat Set pointZone 4 heating setpoint, 59-86 °F (15-30 °C)°F/°CWrite
AV8Z4 Cool Set pointZone 4 cooling setpoint, 64-86 °F (18-30 °C)°F/°CWrite
AV9Z5 Heat Set pointZone 5 heating setpoint, 59-86 °F (15-30 °C)°F/°CWrite
AV10Z5 Cool Set pointZone 5 cooling setpoint, 64-86 °F (18-30 °C)°F/°CWrite
AV11Z6 Heat Set pointZone 6 heating setpoint, 59-86 °F (15-30 °C)°F/°CWrite
AV12Z6 Cool Set pointZone 6 cooling setpoint, 64-86 °F (18-30 °C)°F/°CWrite
AV13DZK address (DK AirNet address)Indoor unit DIII AirNet address, 0-255Read
AV14DZK group address (DK group address)Indoor unit group address, 0-255Read
AV15Z1 cooling demand (%)Zone 1 cooling demand%Read
AV16Z1 heating demand (%)Zone 1 heating demand%Read
AV17Z1 aux heating demand (%)Zone 1 auxiliary heating demand%Read
AV18Z2 cooling demand (%)Zone 2 cooling demand%Read
AV19Z2 heating demand (%)Zone 2 heating demand%Read
AV20Z2 aux heating demand (%)Zone 2 auxiliary heating demand%Read
AV21Z3 cooling demand (%)Zone 3 cooling demand%Read
AV22Z3 heating demand (%)Zone 3 heating demand%Read
AV23Z3 aux heating demand (%)Zone 3 auxiliary heating demand%Read
AV24Z4 cooling demand (%)Zone 4 cooling demand%Read
AV25Z4 heating demand (%)Zone 4 heating demand%Read
AV26Z4 aux heating demand (%)Zone 4 auxiliary heating demand%Read
AV27Z5 cooling demand (%)Zone 5 cooling demand%Read
AV28Z5 heating demand (%)Zone 5 heating demand%Read
AV29Z5 aux heating demand (%)Zone 5 auxiliary heating demand%Read
AV30Z6 cooling demand (%)Zone 6 cooling demand%Read
AV31Z6 heating demand (%)Zone 6 heating demand%Read
AV32Z6 aux heating demand (%)Zone 6 auxiliary heating demand%Read
AV33Z1 humidityZone 1 relative humidity%Read
AV34Z2 humidityZone 2 relative humidity%Read
AV35Z3 humidityZone 3 relative humidity%Read
AV36Z4 humidityZone 4 relative humidity%Read
AV37Z5 humidityZone 5 relative humidity%Read
AV38Z6 humidityZone 6 relative humidity%Read
MImin0IU speedIndoor unit fan speed stepRead1 = Speed Low, 2 = Speed Medium, 3 = Speed High (number of speeds depends on IU model)
MImin1IU errorsIndoor unit error; value in hex gives the Daikin malfunction codeRead
MImin2DZK errorZoning system errorRead1 = Error 9: DZK internal bus fault, 2 = Error 10: BACnet interface board fault, 3 = Error 11: P1P2 communication error
MOmin0DZK operation modeSystem operating modeWrite1 = Auto, 2 = Cold, 3 = Heat, 4 = Dry, 5 = Emergency heat
MOmin1DZK user modeSystem user modeWrite1 = Stop, 2 = Comfort, 3 = Unoccupied, 4 = Night time, 5 = Eco, 6 = Vacation
MV0Z1 opening step damperZone 1 modulating damper stepRead1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%
MV1Z2 opening step damperZone 2 modulating damper stepRead1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%
MV2Z3 opening step damperZone 3 modulating damper stepRead1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%
MV3Z4 opening step damperZone 4 modulating damper stepRead1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%
MV4Z5 opening step damperZone 5 modulating damper stepRead1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%
MV5Z6 opening step damperZone 6 modulating damper stepRead1 = 0%, 2 = 25%, 3 = 50%, 4 = 75%, 5 = 100%
Object ID lookup: Daikin DZK BACnet HUB4 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit

How many BACnet points does the Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit have?

This list has 86 BACnet objects: 6 analog inputs, 39 analog values, 2 binary inputs, 28 binary values, 3 multi-state inputs, 2 multi-state outputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet points are writable?

26 of the 86 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit BACnet documentation?

The source is DZK-4 Integration manual (DZK BACnet Interface), revision Rev. 1, published free by Daikin at https://daikincomfort.com/docs/default-source/dzk-zoning-kit/um-dzk-bacnet-hub4.pdf.

What are the minimum BACnet points to integrate the Daikin DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit?

Start with MO 1 DZK user mode (1 stop, 2 comfort, 3 unoccupied, 5 eco, 6 vacation); MO 0 DZK operation mode (1 auto, 2 cool, 3 heat, 4 dry, 5 emergency heat); BV 3 Z1 ON/OFF (Zone 1 on/off (repeat for zones 2-6)); AV 1 Z1 Heat Set point (Zone 1 heating setpoint); AV 2 Z1 Cool Set point (Zone 1 cooling setpoint); BI 0 IU Status ON/OFF (Indoor unit running); AI 0 Z1 Room Temperature (Zone 1 room temperature); MI 0 IU speed (Indoor unit fan step: low, medium, high); MI 1 IU errors (Indoor unit error; hex value = Daikin code); MI 2 DZK error (Zoning system error (bus, interface, P1P2)).

How do I check these points on the real DZK BACnet Interface (DZK-BACNET-HUB4) for the Daikin Zoning Kit?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin BACnet points lists

Source: DZK-4 Integration manual (DZK BACnet Interface) · rev. Rev. 1. Object names, instances and units are reproduced as published; descriptions are our own.