Networked room thermostat · BACnet points list

Daikin AppStat BACnet Thermostat (DAPPS) BACnet points list

Updated 28 October 2026

Short answer

The Daikin AppStat is a programmable BACnet thermostat for light commercial rooftop units and heat pumps. It joins a BACnet MS/TP trunk (the PICS ticks MS/TP master only) and exposes about 70 objects: sensor inputs, staging outputs, setpoint and configuration AVs, status BVs, occupancy/system/fan mode MSVs and three PID loop objects. Several instances change meaning between rooftop and heat pump configurations.

This page lists 72 BACnet objects for the Daikin AppStat BACnet Thermostat (DAPPS) — 36 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.

Manufacturer
Daikin
Model
AppStat BACnet Thermostat (DAPPS)
Equipment
Networked room thermostat
Equipment type
Thermostats, sensors & meters
BACnet objects
72 (36 writable)
Transport
BACnet MS/TP
Firmware
Application APP0.0.1.1, firmware R1.0.0.15 (PICS)
Also known as
DAPPS, AppStat, BACnet AppStat, Daikin BACnet thermostat, 250803, DG-DAPPS
Source document
BACnet Design Guide - BACnet Thermostat Protocol Information (Table 5: BACnet Standard Objects) · DG-DAPPS · rev. 10/19
Download CSV 72 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin AppStat BACnet Thermostat (DAPPS)

Integration in brief

Set Device ID, MAC address and baud on the thermostat's Communication menu (level 2 password); it resets after each change. The BMS then commands Occupied_Mode and System_Mode, writes the occupied setpoints and reads space temperature, discharge air temperature, heat/cool mode and fan proof. The internal schedule is a BACnet schedule object that a workstation can edit.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Occupied_ModeOccupancy command: occupied, standby, unoccupiedCommand
MV 2System_ModeSystem mode: off, auto, cool, heatCommand
MV 3Fan_ModeFan command: Auto or OnCommand
AV 5Occ_Cl_StptOccupied cooling setpointCommand
AV 6Occ_Ht_StptOccupied heating setpointCommand
BO 1FanFan start/stop output (1 = on)Read
BV 8ModeCurrent heat or cool modeRead
AV 1Space_TempSpace temperature used for controlRead
AV 20Discharge_TempDischarge air temperatureRead
BV 14Fan_StatusFan proof alarm (0 = alarm)Read

Enable & remote start

There is no separate enable point. Occupied_Mode (MV 1), System_Mode (MV 2) and Fan_Mode (MV 3) are commandable and act directly; Occ_Schedule (BV 5) reflects the schedule. Local overrides from the keypad show in Local_Ovrd (BV 28) and Stpt_Hold (BV 36).

Network setup

Watch out for

Daikin AppStat BACnet Thermostat (DAPPS) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

72 of 72 shown
Type
Multi-stateOther
Access
Show
Daikin AppStat BACnet Thermostat (DAPPS) BACnet Points List
DescriptionStates
AI1Remote_SNSRemote Room Sensor°FRead
AI2OATOutdoor Air Temperature°FRead
AI3DATDischarge Air Temperature°FRead
AI4Local_SensorSpace Temperature°FRead
AO6Cooling_OutputAnalog Cooling Output (default 0)%Read
AO7Heating_OutputAnalog Heating Output (default 0)%Read
AO8Econ_DamperEconomizer Output (default 0)%Read
BOmin1FanFan Start - StopRead0=OFF, 1=ON
BO2Cool_Stage_1 / Compressor_1Cool stage 1 (rooftop) / compressor stage 1 (heat pump)Read0=OFF, 1=ON
BO3Cool_Stage_2 / Compressor_2Cool stage 2 (rooftop) / compressor stage 2 (heat pump)Read0=OFF, 1=ON
BO4Heat_Stage_1 / Reversing_ValveHeat stage 1 (rooftop) / reversing valve (heat pump)Read0=OFF, 1=ON
BO5Heat_Stage_2Heat Stage 2, rooftop onlyRead0=OFF, 1=ON
AVmin1Space_TempSpace temperature°FRead
AV3Act_Cool_StptActive Cooling Setpoint (default 74°F)°FCommand
AV4Act_Heat_StptActive Heating Setpoint (default 70°F)°FCommand
AVmin5Occ_Cl_StptOccupied Cooling Setpoint (default 74°F)°FCommand
AVmin6Occ_Ht_StptOccupied Heating Setpoint (default 70°F)°FCommand
AV7Unocc_Cl_StptUnoccupied Cooling Setpoint (default 80°F)°FCommand
AV8Unocc_Ht_StptUnoccupied Heating Setpoint (default 64°F)°FCommand
AV9Min_Cl_StptMinimum Cooling Setpoint (default 68°F)°FCommand
AV10Max_Ht_StptMaximum Heating Setpoint (default 76°F)°FCommand
AV11MIN_STPT_DIFFMinimum Setpoint Differential (default 2°F)°FCommand
AV12STBY_OFFSETStandby Offset (default 3°F)°FCommand
AV13DAT STPT / DAT_ResetDischarge air temp setpoint (rooftop) / reset setpoint (heat pump)°FWrite
AV14Min DATMin Discharge Air Temperature (default 55°F)°FWrite
AV15Min_Econ_DamperMinimum Economizer Damper (default 10%)%Write
AV16Econ_Enable_TempEconomizer Enable Temp (default 60°F)°FWrite
AV17Cmp_LockoutCompressor Lockout Temp (default 25°F), heat pump only°FWrite
AV19Outdoor_Temp / WATER_TEMPOutdoor air temp (rooftop) / water temp, 2-pipe (heat pump)°FRead
AVmin20Discharge_TempDischarge Air Temperature°FRead
AV25Fan_Off_DelayFan Off Delay (default 2 mins)minWrite
AV26Min_Off_TimeEquipment Delay (default 5 mins)minWrite
AV27Stage_DelayStage Delay (default 10 mins)minWrite
AV34FAN_SPEEDFan Speed, heat pump onlyWrite
AV38Ovrd_TimeLocal Override Timer (default 60 mins)minWrite
AV52Cool PropCooling Proportional Band (default 2)Write
AV53Heat PropHeat Proportional Band (default 2)Write
AV54Cool IntgCool Integral (default 0)Write
AV55Heat IntgHeat Integral (default 0)Write
BV1Animate_FanAnimate Fan IconRead0=OFF, 1=ON
BV3Animate_Ht_ClAnimation Mode IconRead0=OFF, 1=ON
BV5Occ_ScheduleOccupy ScheduleWrite0=Unoccupied, 1=Occupied
BV7DAT_SensorDAT Sensor PresentWrite0=No, 1=Yes
BVmin8ModeHeat or Cool ModeRead0=Heat, 1=Cool
BV9Fan_NeedCall For FanRead0=Disable, 1=Enable
BV10Cool_Heat_NeedCooling or Heat NeedRead0=Heat, 1=Cool
BV11Speed_Up_ClSpeed up timers x15 (start-up and service only)Write0=Inactive, 1=Active
BV12HEATING_FANFan Active in Heat, rooftop onlyWrite0=OFF, 1=Auto
BV13Occupied_FanFan ON During Occupied ModeWrite0=OFF, 1=ON
BVmin14Fan_StatusFan ProofRead0=Alarm, 1=Normal
BV15Rev_Vlv_PolarityReversing valve action, heat pump only (detail section only)Read0=Active Cooling, 1=Active Heating
BV16Econ_EnableEconomizer EnableWrite0=Disabled, 1=Enabled
BV17Econ_ModeEconomizer ModeRead0=Inactive, 1=Active
BV18CL_VLV_ACTIONCooling Valve Action, rooftop onlyWrite0=Normally Closed, 1=Normally Open
BV19HT_VLV_ACTIONHeating Valve Action, rooftop onlyWrite0=Normally Closed, 1=Normally Open
BV20Cool_Stg_1Cooling Stage 1Read0=OFF, 1=ON
BV21Cool_Stg_2Cooling Stage 2Read0=OFF, 1=ON
BV22Heat_Stg_1Heating Stage 1Read0=OFF, 1=ON
BV23Heat_Stg_2Heating Stage 2Read0=OFF, 1=ON
BV26Comp_LockoutCompressor Lockout, heat pump onlyWrite0=OFF, 1=ON
BV27OAT_SensorOutdoor Sensor PresentRead0=OFF, 1=ON
BV28Local_OvrdLocal Override ModeRead0=OFF, 1=ON
BV36Stpt_HoldHold Temperature SetpointRead0=Schedule, 1=Hold
MVmin1Occupied_ModeOccupied ModeCommand1=Occupied, 2=Standby, 3=Unoccupied
MVmin2System_ModeSystem Heat-Cool ModeCommand1=OFF, 2=Auto, 3=Cool, 4=Heat
MVmin3Fan_ModeFan Auto-Manual ModeCommand0=Auto, 1=ON
MV6Fan_IconFan IconRead1=ON, 2=Auto, 3=Fail, 4=Service, 5=Low, 6=Med, 7=High
MV7Occupied_IconOccupied Mode IconRead1=Occupied, 2=Overrid, 3=Unoccupied, 4=Occ Hold, 5=Standby
MV8Heat_Cool_IconHeat & Cool IconRead1=Cool, 2=Cool Auto, 3=Heat Auto, 4=Heat, 5=OFF, 6=Emg Heat, 7=EHeat Auto
LO1Cl LoopCooling LoopRead
LO2Ht LoopHeating LoopRead
LO3DAT LoopDischarge Air Temp LoopRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AppStat BACnet Thermostat (DAPPS) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin AppStat BACnet Thermostat (DAPPS)

How many BACnet points does the Daikin AppStat BACnet Thermostat (DAPPS) have?

This list has 72 BACnet objects: 4 analog inputs, 3 analog outputs, 27 analog values, 5 binary outputs, 24 binary values, 3 loops, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin AppStat BACnet Thermostat (DAPPS) BACnet points are writable?

36 of the 72 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin AppStat BACnet Thermostat (DAPPS) BACnet documentation?

The source is BACnet Design Guide - BACnet Thermostat Protocol Information (Table 5: BACnet Standard Objects) (DG-DAPPS), revision 10/19, published free by Daikin at https://daikincomfort.com/docs/default-source/appstat--bacnet-thermostat/dg-dapps.pdf.

What are the minimum BACnet points to integrate the Daikin AppStat BACnet Thermostat (DAPPS)?

Start with MV 1 Occupied_Mode (Occupancy command: occupied, standby, unoccupied); MV 2 System_Mode (System mode: off, auto, cool, heat); MV 3 Fan_Mode (Fan command: Auto or On); AV 5 Occ_Cl_Stpt (Occupied cooling setpoint); AV 6 Occ_Ht_Stpt (Occupied heating setpoint); BO 1 Fan (Fan start/stop output (1 = on)); BV 8 Mode (Current heat or cool mode); AV 1 Space_Temp (Space temperature used for control); AV 20 Discharge_Temp (Discharge air temperature); BV 14 Fan_Status (Fan proof alarm (0 = alarm)).

How do I enable BMS control of the Daikin AppStat BACnet Thermostat (DAPPS)?

There is no separate enable point. Occupied_Mode (MV 1), System_Mode (MV 2) and Fan_Mode (MV 3) are commandable and act directly; Occ_Schedule (BV 5) reflects the schedule. Local overrides from the keypad show in Local_Ovrd (BV 28) and Stpt_Hold (BV 36).

How do I check these points on the real AppStat BACnet Thermostat (DAPPS)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin BACnet points lists

Source: BACnet Design Guide - BACnet Thermostat Protocol Information (Table 5: BACnet Standard Objects) · DG-DAPPS · rev. 10/19. Object names, instances and units are reproduced as published; descriptions are our own.