VRV BACnet gateway · BACnet points list

Daikin DMS502B71 Interface for use in BACnet BACnet points list

Updated 28 October 2026

Short answer

The DMS502B71 BACnet Interface (with the optional DAM411B51 expansion for DIII-Net ports 3 and 4) is a BACnet IP server that maps every VRV indoor unit group to the same 35-member object template. Integrators read on/off, mode, fan speed, room temperature, alarm and malfunction code, and can write start/stop, mode, setpoint, fan speed, airflow direction and remote-controller permit/prohibit per group. Object names end in the three-digit indoor unit number and instance numbers are built from that unit number.

This page lists 34 BACnet objects for the Daikin DMS502B71 Interface for use in BACnet — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.

Manufacturer
Daikin
Model
DMS502B71 Interface for use in BACnet
Equipment
VRV BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
34 (15 writable)
Transport
BACnet IP
Firmware
Ver. 6.20 or later
Also known as
DMS502B71, DAM411B51, D-BACS, Daikin VRV BACnet interface, BACnet Interface, EDUS72-749
Source document
Design Guide - Interface for use in BACnet (DMS502B71 / DAM411B51) · EDUS72-749C
Download CSV 34 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin DMS502B71 Interface for use in BACnet

Integration in brief

Commission the interface with the Daikin test-operation/setup tool, then address each indoor unit group by its object suffix (000-255). Typical integration writes start/stop, mode, setpoint and fan speed per group and reads on/off status, room temperature, alarm and malfunction code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1StartStopCommand_XXXStart/stop the indoor unit groupCommand
MO 5AirConModeCommand_XXXOperation mode commandCommand
AV 10TempAdjust_XXXSetpointWrite
MO 7AirFlowRateCommand_XXXFan speed commandCommand
BI 2StartStopStatus_XXXActual on/off statusRead
AI 9RoomTemp_XXXRoom temperature (reference value)Read
BI 3Alarm_XXXIndoor unit malfunction alarmRead
MI 4MalfunctionCode_XXXDaikin malfunction codeRead
BI 20CommunicationStatus_XXXCommunication error with the unitRead

Enable & remote start

There is no separate enable: the BMS writes the command objects directly. Remote-controller lockouts are available per group (RemoteControlStart, RemoteControlAirConModeSet, RemoteControlTempAdjust = Prohibit), and CL_Rejection (only on 000/064/128/192) disables Daikin centralized controllers on that DIII-Net line. SystemForcedOff stops all units on a DIII-Net line and blocks remote-controller starts; clearing it does not restart the units, so the BMS (or another controller) must start them again.

Network setup

Watch out for

Daikin DMS502B71 Interface for use in BACnet BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

34 of 34 shown
Type
Other
Access
Show
Daikin DMS502B71 Interface for use in BACnet BACnet Points List
DescriptionStates
BOmin1StartStopCommand_XXXOn/Off settingCommandInactive=Off, Active=On
BImin2StartStopStatus_XXXOn/Off statusReadInactive=Off, Active=On
BImin3Alarm_XXXAlarmReadInactive=Normal, Active=Malfunction
MImin4MalfunctionCode_XXXMalfunction codeRead1=Normal, other states=Daikin-specified malfunction code
MOmin5AirConModeCommand_XXXOperation mode settingCommand1=Cool, 2=Heat, 3=Fan, 4=Auto, 5=Dry
MI6AirConModeStatus_XXXOperation mode statusRead1=Cool, 2=Heat, 3=Fan, 4=not used, 5=Dry
MOmin7AirFlowRateCommand_XXXFan speed settingCommand1=Low, 2=High, 3=Middle, 4=Auto
MI8AirFlowRateStatus_XXXFan speed statusRead1=Low, 2=High, 3=Middle, 4=Auto
AImin9RoomTemp_XXXMeasured room temperature°C/°FRead
AVmin10TempAdjust_XXXSetpoint°C/°FWrite
BI11FilterSign_XXXFilter sign signalReadInactive=No, Active=Yes
BV12FilterSignReset_XXXFilter sign signal resetWriteReset
BV13RemoteControlStart_XXXRemote controller permit/prohibit (On/Off)WriteInactive=Permit, Active=Prohibit
BV14RemoteControlAirConModeSet_XXXRemote controller permit/prohibit (operation mode)WriteInactive=Permit, Active=Prohibit
BV16RemoteControlTempAdjust_XXXRemote controller permit/prohibit (setpoint)WriteInactive=Permit, Active=Prohibit
BV17CL_Rejection_XXXCentralized control (lower central control disable)WriteInactive=Enabled, Active=Disabled
ACC18GasTotalPower_XXXAccumulated gasm3Read
ACC19ElecTotalPower_XXXAccumulated powerkWhRead
BImin20CommunicationStatus_XXXCommunication statusReadInactive=Normal, Active=Communication error
BV21SystemForcedOff_XXXForced system stopWriteInactive=Inactive, Active=Active
AV22AirDirectionCommand_XXXAirflow direction settingWrite
AI23AirDirectionStatus_XXXAirflow direction statusRead
BO24ForcedThermoOFFCommand_XXXForced thermo-off settingCommandInactive=Inactive, Active=Active
BI25ForcedThermoOFFStatus_XXXForced thermo-off statusReadInactive=Inactive, Active=Active
BO26EnergyEfficiencyCommand_XXXEnergy saving settingCommandInactive=Inactive, Active=Active
BI27EnergyEfficiencyStatus_XXXEnergy saving statusReadInactive=Inactive, Active=Active
BI28ThermoStatus_XXXThermo-on statusReadInactive=Off, Active=On
BI29CompressorStatus_XXXCompressor statusReadInactive=Off, Active=On
BI30IndoorFanStatus_XXXIndoor fan statusReadInactive=Off, Active=On
BI31HeaterStatus_XXXHeater statusReadInactive=Off, Active=On
MO32VentilationModeCommand_XXXVentilation mode setting (ERV)Command1=Bypass, 2=ERV, 3=Auto
MI33VentilationModeStatus_XXXVentilation mode status (ERV)Read1=Bypass, 2=ERV, 3=Auto
MO34VentilationAmountCommand_XXXVentilation amount setting (ERV)Command1=Low, 2=High, 3=Auto, 4=Low (fresh up), 5=High (fresh up), 6=Auto (fresh up)
MI35VentilationAmountStatus_XXXVentilation amount status (ERV)Read1=Low, 2=High, 3=Auto, 4=Low (fresh up), 5=High (fresh up), 6=Auto (fresh up)

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DMS502B71 Interface for use in BACnet and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin DMS502B71 Interface for use in BACnet

How many BACnet points does the Daikin DMS502B71 Interface for use in BACnet have?

This list has 34 BACnet objects: 2 analog inputs, 2 analog values, 10 binary inputs, 3 binary outputs, 6 binary values, 5 multi-state inputs, 4 multi-state outputs, 2 accumulators. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin DMS502B71 Interface for use in BACnet BACnet points are writable?

15 of the 34 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin DMS502B71 Interface for use in BACnet BACnet documentation?

The source is Design Guide - Interface for use in BACnet (DMS502B71 / DAM411B51) (EDUS72-749C), published free by Daikin at https://daikincomfort.com/docs/default-source/interface-for-use-bacnet-/eg-dms502b71bacnet-guide.pdf.

What are the minimum BACnet points to integrate the Daikin DMS502B71 Interface for use in BACnet?

Start with BO 1 StartStopCommand_XXX (Start/stop the indoor unit group); MO 5 AirConModeCommand_XXX (Operation mode command); AV 10 TempAdjust_XXX (Setpoint); MO 7 AirFlowRateCommand_XXX (Fan speed command); BI 2 StartStopStatus_XXX (Actual on/off status); AI 9 RoomTemp_XXX (Room temperature (reference value)); BI 3 Alarm_XXX (Indoor unit malfunction alarm); MI 4 MalfunctionCode_XXX (Daikin malfunction code); BI 20 CommunicationStatus_XXX (Communication error with the unit).

How do I enable BMS control of the Daikin DMS502B71 Interface for use in BACnet?

There is no separate enable: the BMS writes the command objects directly. Remote-controller lockouts are available per group (RemoteControlStart, RemoteControlAirConModeSet, RemoteControlTempAdjust = Prohibit), and CL_Rejection (only on 000/064/128/192) disables Daikin centralized controllers on that DIII-Net line. SystemForcedOff stops all units on a DIII-Net line and blocks remote-controller starts; clearing it does not restart the units, so the BMS (or another controller) must start them again.

How do I check these points on the real DMS502B71 Interface for use in BACnet?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.