VRV BACnet gateway (iTM option) · BACnet points list

Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects BACnet points list

Updated 28 October 2026

Short answer

With the DCM014A51 option, each VRV outdoor unit appears behind the iTM's BACnet virtual router as its own virtual device. Common points report communication, mode, alarm, defrost, oil return, calculated power and current and outdoor air temperature, and up to three modules (main, sub-1, sub-2) add read-only refrigerant pressures, temperatures, compressor speeds, fan step and expansion valve positions.

This page lists 75 BACnet objects for the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.

Manufacturer
Daikin
Model
intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects
Equipment
VRV BACnet gateway (iTM option)
Equipment type
VRF & split air conditioners
BACnet objects
75 (0 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
DCM014A51, iTM BACnet outdoor unit, intelligent Touch Manager, DCM601A71, DCM601B71
Source document
intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 Design Guide · DG_DCM014A51_02-19 · rev. 2019-02
Download CSV 75 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects

Integration in brief

Outdoor units are read-only virtual devices behind the iTM; map communication, alarm, mode and defrost status plus the module data you need. Only modules that exist on the system (main, sub-1, sub-2) generate objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MI 2Operation ModeCool/Heat/Fan/Heat & CoolRead
BI 4Defrost ModeDefrost activeRead
AI 9Outdoor Air TemperatureAmbient temp sensed at the outdoor unitRead
AI 6Electric Power (calculated)Outdoor unit power draw, kW (calculated)Read
BI 1Communication StatusOutdoor unit communication alarmRead
BI 3Outdoor Unit Alarm StatusOutdoor unit alarm with error codeRead

Network setup

Watch out for

Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

75 of 75 shown
Type
AnalogBinaryMulti-state
Show
Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects BACnet Points List
DescriptionStates
BImin1Communication StatusOutdoor unit communication statusReadInactive=Normal, Active=Alarm
MImin2Operation ModeOutdoor unit operation modeRead1=Cool, 2=Heat, 3=Fan, 4=Heat & Cool
BImin3Outdoor Unit Alarm StatusOutdoor unit alarm; error code in DescriptionReadInactive=Normal, Active=Alarm
BImin4Defrost ModeDefrost modeReadInactive=Off, Active=On
BI5Oil ReturnOil return operationReadInactive=Off, Active=On
AImin6Electric Power (calculated)Calculated electric powerRead
AI7Electric Current (calculated)Calculated electric currentRead
AI8System Capacity CodeSystem capacity codeRead
AImin9Outdoor Air TemperatureOutdoor air temperature°F/°CRead
AI100M_Condensing PressureMain outdoor unit: Condensing PressureRead
AI101M_Evaporating PressureMain outdoor unit: Evaporating PressureRead
AI102M_Condensing TemperatureMain outdoor unit: Condensing Temperature°F/°CRead
AI103M_Evaporating TemperatureMain outdoor unit: Evaporating Temperature°F/°CRead
AI104M_Inverter Compressor 1 SpeedMain outdoor unit: Inverter Compressor 1 SpeedRead
AI105M_Inverter Compressor 2 SpeedMain outdoor unit: Inverter Compressor 2 SpeedRead
AI106M_Fan StepMain outdoor unit: Fan StepRead
AI107M_EV Position 1Main outdoor unit: EV Position 1Read
AI108M_EV Position 2Main outdoor unit: EV Position 2Read
AI109M_Hot Gas Temperature (Compressor 1)Main outdoor unit: Hot Gas Temperature (Compressor 1)°F/°CRead
AI110M_Hot Gas Temperature (Compressor 2)Main outdoor unit: Hot Gas Temperature (Compressor 2)°F/°CRead
AI111M_Liquid Pipe TemperatureMain outdoor unit: Liquid Pipe Temperature°F/°CRead
AI112M_Liquid Pipe Temperature (HX Upper)Main outdoor unit: Liquid Pipe Temperature (HX Upper)°F/°CRead
AI113M_Liquid Pipe Temperature (HX Lower)Main outdoor unit: Liquid Pipe Temperature (HX Lower)°F/°CRead
AI114M_Liquid Pipe Temperature (Deicer)Main outdoor unit: Liquid Pipe Temperature (Deicer)°F/°CRead
AI115M_Gas Pipe Temperature (HX Upper)Main outdoor unit: Gas Pipe Temperature (HX Upper)°F/°CRead
AI116M_Gas Pipe Temperature (HX Lower)Main outdoor unit: Gas Pipe Temperature (HX Lower)°F/°CRead
AI117M_Suction TemperatureMain outdoor unit: Suction Temperature°F/°CRead
AI118M_Compressor Suction TemperatureMain outdoor unit: Compressor Suction Temperature°F/°CRead
AI119M_Subcool Inlet TemperatureMain outdoor unit: Subcool Inlet Temperature°F/°CRead
AI120M_Subcool Outlet TemperatureMain outdoor unit: Subcool Outlet Temperature°F/°CRead
AI121M_Subcool EV PositionMain outdoor unit: Subcool EV PositionRead
AI200S1_Condensing PressureSub-1 outdoor unit: Condensing PressureRead
AI201S1_Evaporating PressureSub-1 outdoor unit: Evaporating PressureRead
AI202S1_Condensing TemperatureSub-1 outdoor unit: Condensing Temperature°F/°CRead
AI203S1_Evaporating TemperatureSub-1 outdoor unit: Evaporating Temperature°F/°CRead
AI204S1_Inverter Compressor 1 SpeedSub-1 outdoor unit: Inverter Compressor 1 SpeedRead
AI205S1_Inverter Compressor 2 SpeedSub-1 outdoor unit: Inverter Compressor 2 SpeedRead
AI206S1_Fan StepSub-1 outdoor unit: Fan StepRead
AI207S1_EV Position 1Sub-1 outdoor unit: EV Position 1Read
AI208S1_EV Position 2Sub-1 outdoor unit: EV Position 2Read
AI209S1_Hot Gas Temperature (Compressor 1)Sub-1 outdoor unit: Hot Gas Temperature (Compressor 1)°F/°CRead
AI210S1_Hot Gas Temperature (Compressor 2)Sub-1 outdoor unit: Hot Gas Temperature (Compressor 2)°F/°CRead
AI211S1_Liquid Pipe TemperatureSub-1 outdoor unit: Liquid Pipe Temperature°F/°CRead
AI212S1_Liquid Pipe Temperature (HX Upper)Sub-1 outdoor unit: Liquid Pipe Temperature (HX Upper)°F/°CRead
AI213S1_Liquid Pipe Temperature (HX Lower)Sub-1 outdoor unit: Liquid Pipe Temperature (HX Lower)°F/°CRead
AI214S1_Liquid Pipe Temperature (Deicer)Sub-1 outdoor unit: Liquid Pipe Temperature (Deicer)°F/°CRead
AI215S1_Gas Pipe Temperature (HX Upper)Sub-1 outdoor unit: Gas Pipe Temperature (HX Upper)°F/°CRead
AI216S1_Gas Pipe Temperature (HX Lower)Sub-1 outdoor unit: Gas Pipe Temperature (HX Lower)°F/°CRead
AI217S1_Suction TemperatureSub-1 outdoor unit: Suction Temperature°F/°CRead
AI218S1_Compressor Suction TemperatureSub-1 outdoor unit: Compressor Suction Temperature°F/°CRead
AI219S1_Subcool Inlet TemperatureSub-1 outdoor unit: Subcool Inlet Temperature°F/°CRead
AI220S1_Subcool Outlet TemperatureSub-1 outdoor unit: Subcool Outlet Temperature°F/°CRead
AI221S1_Subcool EV PositionSub-1 outdoor unit: Subcool EV PositionRead
AI300S2_Condensing PressureSub-2 outdoor unit: Condensing PressureRead
AI301S2_Evaporating PressureSub-2 outdoor unit: Evaporating PressureRead
AI302S2_Condensing TemperatureSub-2 outdoor unit: Condensing Temperature°F/°CRead
AI303S2_Evaporating TemperatureSub-2 outdoor unit: Evaporating Temperature°F/°CRead
AI304S2_Inverter Compressor 1 SpeedSub-2 outdoor unit: Inverter Compressor 1 SpeedRead
AI305S2_Inverter Compressor 2 SpeedSub-2 outdoor unit: Inverter Compressor 2 SpeedRead
AI306S2_Fan StepSub-2 outdoor unit: Fan StepRead
AI307S2_EV Position 1Sub-2 outdoor unit: EV Position 1Read
AI308S2_EV Position 2Sub-2 outdoor unit: EV Position 2Read
AI309S2_Hot Gas Temperature (Compressor 1)Sub-2 outdoor unit: Hot Gas Temperature (Compressor 1)°F/°CRead
AI310S2_Hot Gas Temperature (Compressor 2)Sub-2 outdoor unit: Hot Gas Temperature (Compressor 2)°F/°CRead
AI311S2_Liquid Pipe TemperatureSub-2 outdoor unit: Liquid Pipe Temperature°F/°CRead
AI312S2_Liquid Pipe Temperature (HX Upper)Sub-2 outdoor unit: Liquid Pipe Temperature (HX Upper)°F/°CRead
AI313S2_Liquid Pipe Temperature (HX Lower)Sub-2 outdoor unit: Liquid Pipe Temperature (HX Lower)°F/°CRead
AI314S2_Liquid Pipe Temperature (Deicer)Sub-2 outdoor unit: Liquid Pipe Temperature (Deicer)°F/°CRead
AI315S2_Gas Pipe Temperature (HX Upper)Sub-2 outdoor unit: Gas Pipe Temperature (HX Upper)°F/°CRead
AI316S2_Gas Pipe Temperature (HX Lower)Sub-2 outdoor unit: Gas Pipe Temperature (HX Lower)°F/°CRead
AI317S2_Suction TemperatureSub-2 outdoor unit: Suction Temperature°F/°CRead
AI318S2_Compressor Suction TemperatureSub-2 outdoor unit: Compressor Suction Temperature°F/°CRead
AI319S2_Subcool Inlet TemperatureSub-2 outdoor unit: Subcool Inlet Temperature°F/°CRead
AI320S2_Subcool Outlet TemperatureSub-2 outdoor unit: Subcool Outlet Temperature°F/°CRead
AI321S2_Subcool EV PositionSub-2 outdoor unit: Subcool EV PositionRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects

How many BACnet points does the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects have?

This list has 75 BACnet objects: 70 analog inputs, 4 binary inputs, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects BACnet documentation?

The source is intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 Design Guide (DG_DCM014A51_02-19), revision 2019-02, published free by Daikin at https://daikincomfort.com/docs/default-source/itm-bacnet-server-gateway-option/eg-itm_bacnetgatewayguide_v2-0.pdf.

What are the minimum BACnet points to integrate the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects?

Start with MI 2 Operation Mode (Cool/Heat/Fan/Heat & Cool); BI 4 Defrost Mode (Defrost active); AI 9 Outdoor Air Temperature (Ambient temp sensed at the outdoor unit); AI 6 Electric Power (calculated) (Outdoor unit power draw, kW (calculated)); BI 1 Communication Status (Outdoor unit communication alarm); BI 3 Outdoor Unit Alarm Status (Outdoor unit alarm with error code).

How do I check these points on the real intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Outdoor Unit Objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin BACnet points lists

Source: intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 Design Guide · DG_DCM014A51_02-19 · rev. 2019-02. Object names, instances and units are reproduced as published; descriptions are our own.