  3. Daikin
  4. intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects

VRV BACnet gateway (iTM option) · BACnet points list

Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects BACnet points list

Updated 28 October 2026

Short answer

The DCM014A51 software option turns a Daikin intelligent Touch Manager into a BACnet IP server. The iTM acts as a BACnet virtual router: each indoor unit becomes its own virtual BACnet device carrying the same 37-object list, and a separate system control device holds schedule, auto-changeover, timed-override and forced-off objects. Objects can be enabled or disabled per unit during commissioning, so a site may expose fewer points than listed.

This page lists 41 BACnet objects for the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Daikin’s own free documentation, linked below.

Manufacturer
Daikin
Model
intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects
Equipment
VRV BACnet gateway (iTM option)
Equipment type
VRF & split air conditioners
BACnet objects
41 (24 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
DCM014A51, iTM BACnet, intelligent Touch Manager, DCM601A71, DCM601B71, iTM BACnet Server Gateway
Source document
intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 Design Guide · DG_DCM014A51_02-19 · rev. 2019-02
Download CSV 41 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects

Integration in brief

Enable the DCM014A51 option on the iTM, assign each indoor unit a unique device ID and a BACnet network number for the virtual network, then use Occupancy Mode and the setpoint objects per indoor unit device. System-wide schedule, auto-changeover and forced-off objects sit on the separate system control device.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 1Occupancy ModeOcc/Unocc/Standby; sends on/off to the indoor unitCommand
MV 4Operation ModeCool/Heat/Fan/DryCommand
AV 6Occ Cooling SetpointOccupied cooling setpointWrite
AV 7Occ Heating SetpointOccupied heating setpointWrite
MV 16Fan SpeedLow / medium / high / autoCommand
BI 2Unit On_Off StatusActual on/off statusRead
AI 5Room TemperatureIndoor unit room temperature, °F/°CRead
BI 3Alarm StatusAlarm; error code in the Description propertyRead
BI 26Communication StatusCommunication alarm for the unitRead

Enable & remote start

Writing Occupancy Mode (MO 1) is the start/stop: Occ sends On, Unocc sends Off, Standby sends On with energy saving (setpoint offset by 3.6 F / 2 C). The iTM sends the command even if the unit is already in that state, and Occupancy Mode is set to 1 (Unocc) at iTM start-up. The 'Enable iTM Schedule Operation' object on the system control device turns the iTM's own schedule on or off.

Heartbeat & communication loss

No BMS heartbeat is described. If a written value is not accepted by the indoor unit, the iTM reverts the BACnet present value to the previous value after a 10-minute timer.

Network setup

Watch out for

Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

41 of 41 shown
Type
Access
Show
Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects BACnet Points List
DescriptionStates
MOmin1Occupancy ModeOccupancy modeCommand1=Unocc, 2=Occ, 3=Standby
BImin2Unit On_Off StatusIndoor unit on/off statusReadInactive=Off, Active=On
BImin3Alarm StatusAlarm status; error code in Description propertyReadInactive=Normal, Active=Alarm
MVmin4Operation ModeOperation modeCommand1=Cool, 2=Heat, 3=Fan, 4=Dry
AImin5Room TemperatureRoom temperature°F/°CRead
AVmin6Occ Cooling SetpointOccupied cooling setpoint°F/°CWrite
AVmin7Occ Heating SetpointOccupied heating setpoint°F/°CWrite
AV8Unocc Cooling SetpointUnoccupied (setback) cooling setpoint°F/°CWrite
AV9Unocc Heating SetpointUnoccupied (setback) heating setpoint°F/°CWrite
AV10Max Cooling SetpointCooling setpoint upper limit°F/°CWrite
AV11Min Cooling SetpointCooling setpoint lower limit°F/°CWrite
AV12Max Heating SetpointHeating setpoint upper limit°F/°CWrite
AV13Min Heating SetpointHeating setpoint lower limit°F/°CWrite
AV14Min Setpoint Differential (Cooling & Heating)Minimum cool/heat setpoint differential°F/°CWrite
BV15Cooling & Heating Setpoint Tracking ModeCooling and heating setpoint tracking modeCommandInactive=Disable, Active=Enable
MVmin16Fan SpeedFan speedCommand1=Low, 2=Reserved, 3=Medium, 4=Reserved, 5=High, 6=Reserved, 7=Reserved, 8=Auto
MV17Airflow DirectionAirflow direction (louver position)Command1=P0, 2=P1, 3=P2, 4=P3, 5=P4, 6=Reserved, 7=Reserved, 8=P7
BV18Timed Override OperationTimed override operationCommandInactive=Disable, Active=Enable
MI19Current Unit OperationCurrent unit operationRead1=Off, 2=Normal, 3=Override, 4=Setback
MV20Remote Controller Prohibit (On_Off)Remote controller on/off permit/prohibitCommand1=Permit, 2=Prohibit, 3=Stop Only
BV21Remote Controller Prohibit (Operation Mode)Remote controller mode permit/prohibitCommandInactive=Permit, Active=Prohibit
BV22Remote Controller Prohibit (Setpoint)Remote controller setpoint permit/prohibitCommandInactive=Permit, Active=Prohibit
BI23Filter Sign StatusFilter sign statusReadInactive=Normal, Active=Alarm
BV24Filter Sign ResetFilter sign resetCommandInactive=Reset, Active=Alarm
BI25Indoor Fan StatusIndoor fan statusReadInactive=Off, Active=On
BImin26Communication StatusCommunication statusReadInactive=Normal, Active=Alarm
BI27Thermo-on StatusThermo-on statusReadInactive=Off, Active=On
MI28Compressor StatusCompressor statusRead1=Off, 2=On, 3=Defrost/Hot Start
BI29Aux Heater StatusAuxiliary heater statusReadInactive=Off, Active=On
BV30Forced Thermo-offForced thermo-offCommandInactive=Disable, Active=Enable
BI31Indoor Unit Changeover OptionChangeover option available on this unitReadInactive=Not Available, Active=Available
AI32Return Air TemperatureReturn air temperature°F/°CRead
AI33Discharge Air TemperatureDischarge air temperature°F/°CRead
AI34Liquid Pipe TemperatureLiquid pipe temperature°F/°CRead
AI35Gas Pipe TemperatureGas pipe temperature°F/°CRead
AI36EV PositionElectronic expansion valve positionRead
BI37Freeze ProtectionFreeze protection (select FXEQ/FXFQ/FXTQ/FXUQ/FXSQ/CXTQ models)ReadInactive=Off, Active=On
BO1Enable iTM Schedule OperationSystem control device: enable iTM scheduleCommandInactive=Disable, Active=Enable
BO2Enable iTM Auto-Changeover OperationSystem control device: enable auto-changeoverCommandInactive=Disable, Active=Enable
MV3Timed Override MinutesSystem control device: timed override durationminCommand1=30, 2=60, 3=90, 4=120, 5=150, 6=180
BO4System Forced OffSystem control device: forced shutdown of all groupsCommandInactive=Inactive, Active=Active

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects

How many BACnet points does the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects have?

This list has 41 BACnet objects: 6 analog inputs, 9 analog values, 9 binary inputs, 3 binary outputs, 6 binary values, 2 multi-state inputs, 1 multi-state output, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects BACnet points are writable?

24 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects BACnet documentation?

The source is intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 Design Guide (DG_DCM014A51_02-19), revision 2019-02, published free by Daikin at https://daikincomfort.com/docs/default-source/itm-bacnet-server-gateway-option/eg-itm_bacnetgatewayguide_v2-0.pdf.

What are the minimum BACnet points to integrate the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects?

Start with MO 1 Occupancy Mode (Occ/Unocc/Standby; sends on/off to the indoor unit); MV 4 Operation Mode (Cool/Heat/Fan/Dry); AV 6 Occ Cooling Setpoint (Occupied cooling setpoint); AV 7 Occ Heating Setpoint (Occupied heating setpoint); MV 16 Fan Speed (Low / medium / high / auto); BI 2 Unit On_Off Status (Actual on/off status); AI 5 Room Temperature (Indoor unit room temperature, °F/°C); BI 3 Alarm Status (Alarm; error code in the Description property); BI 26 Communication Status (Communication alarm for the unit).

How do I enable BMS control of the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects?

Writing Occupancy Mode (MO 1) is the start/stop: Occ sends On, Unocc sends Off, Standby sends On with energy saving (setpoint offset by 3.6 F / 2 C). The iTM sends the command even if the unit is already in that state, and Occupancy Mode is set to 1 (Unocc) at iTM start-up. The 'Enable iTM Schedule Operation' object on the system control device turns the iTM's own schedule on or off.

Does the Daikin intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects need a BACnet heartbeat or have a communication timeout?

No BMS heartbeat is described. If a written value is not accepted by the indoor unit, the iTM reverts the BACnet present value to the previous value after a 10-minute timer.

How do I check these points on the real intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 - Indoor Unit and System Objects?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Daikin BACnet points lists

Source: intelligent Touch Manager (iTM) BACnet Server Gateway DCM014A51 Design Guide · DG_DCM014A51_02-19 · rev. 2019-02. Object names, instances and units are reproduced as published; descriptions are our own.